Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.1 LAccepted-AOC | ₹27.1 L | L1 | Accepted-AOC LOWEST BIDDER |
| 2 | L2₹28.1 L+₹95,711.70 (3.53%)Rejected-Finance | ₹28.1 L+₹95,711.70 (3.53%) | L2 | Rejected-Finance Not Lowest |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
26 Oct 2024, 6:00 pmClosed
GARRISON ENGINEER ABOHAR
GARRISON ENGINEER ABOHAR PIN 152116
REPAIR / MAINT LT OH LINE / UG CABLE, LT PANELS AND REPAIRS OF STREET LIGHTS AT MIL STN FAZILKA.
2024_MES_677221_1
TOKEN NO GE ABH-54/24-25
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
FAZILKA MIL STN
AS PER NIT
7 documents required · 7 mandatory
₹500
GE ABOHAR
₹60,000
Yes
1 Jan 2025
28 Sept 2024
28 Oct 2024
28 Sept 2024
26 Oct 2024
12 Oct 2024
Amount
Taking down defective LED street light or Flood light or High mask light or Post top lantern LED Light of any capacity viz 10W/20W/25W/30W/60/W/ 200W, fitting of any type from their existing position i.e. poles or bldg or pillers or gardens and re-fixing the same after carried out repairs i.e. replacement of LED driver,SPD , PVC wire and any other necessary connecting item and making suitable for lightning purpose, all as specified and directed by Engineer-in-Charge. Note : (i) LED driver, and SPD , 3 core cable will be measured and paid separately under respective items .(ii) Cost of nut, bolts & washers for fixing new items is deemed to be included in quoted rate.
Supply only surge protection device (SPD) of capacity 10 KV with phase, neutral and earth wire in incoming and out going both sides suitable for120/ 200 Watt LED Flood Light fitting complete all as specified and directed by Engineer-in-Charge. Make : Bajaj / Havells/Crompton
Supply only surge protection device (SPD) of capacity 8 KV with phase, neutral and earth wire in incoming and out going both sides suitable for 60 Watt LED Street Light fitting complete all as specified and directed by Engineer-in-Charge. Make : Bajaj / Havells/Crompton
Supply only surge protection device (SPD) of capacity 5 KV with phase, neutral and earth wire in incoming and out going both sides suitable for 25/30 Watt LED Light Street fitting complete all as specified and directed by Engineer-in-Charge. Make : Bajaj / Havells/Crompton
Supply only LED driver 25/30 W LED Street light fitting of type make/model as per sample complete all as specified and directed by Engineer-in-Charge.
Supply only LED driver 60 W LED Street light fitting of type make/model as per sample complete all as specified and directed by Engineer-in-Charge.
Supply only LED driver 120/200 W LED Street light fitting of type make/model as per sample complete all as specified and directed by Engineer-in-Charge.
Supply and fixing post top lantern LED type 25 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete. Make : Havells CAT PART NO. CORALPT25WLED757PSYMTOPC and equivalent make of Bajaj/Crompton
Supply and fixing LED Bollard Light(TULIP)/ Garden Light with optical acrylic diffuser of 9/10 watt , 5700 K and IP 66 Protection Complete all as specified and directed by Engineer -in-Charge. Make :Bajaj -CAT PART NO.BGBOM605 9 W LED WH, Crompton CAT PART NO - LBLSR-10-WW or equivalent in Havells
M&L for safely dismentling of existing high mast light 21 mtr long including flood lights, plinth area & complete operating mechanism, and safely shifting to other place within cantt area not more than 5 KM distance including transportation with necessary T&P . Re-assembling, errection, installation fixing and made functional complete in all repect including necessary foundation work all as specified & directed by Engr-In Charge.
Repair/ maint of High Mast including replacement of taking up and taking down mechanism including replacement of gear & pulley assembly for proper functing and greasing of high light fitting all as directed by Engineer in Charge.
Supply and fix in replacement Hot moulded (FRP) junction box of size 280mm x 200mm for street light pole with locking arrangement with 32 Amps, 4 way heavy duty terminal block suitable connection for three phase incoming cable three phase outgoing cable and single phase connection for light fittings with control MCB SP 10 Amps 01 Nos enclosed in thermoplastic box in closed shock proof safe IP 65, weather, vermin proof, dust and water proof complete with two number cable entry gland of standard size with suitable size mild steel clamps to fix on pole complete all as specified and directed by Engineer-in-Charge. Make : Neptune/ Hensel/ Sintex or equivalent as approved by GE
Supply & fixing in replacement of LED Flood light fitting of 120 Watt IP 66 made up of pressure die cast aluminium housing with toughened glass and high power LEDs and secondary lenses System efficacy >110/120 LPW, with 10 KV SPD Complete all as specified and directed by Engineer-in-Charge. MAKE : Crompton catpart No -TFS-504-120-57-60D-SL-GL-NSG or equivalent in Bajaj/Philips
Supply & fixing in replacement of LED of 60 Watt IP 66 Street lights fittings aerodynamically designed for all weather conditions with excellent thermal management, made up of pressure die cast housing with toughened glass and high power LED's with secondary and IP66 protection. 10 KV SPD included,Efficacy ≥110/120 LPW complete all as specified and directed by Engineer-in-Charge. MAKE - Crompton cat part no-CRP-409-60-57-SL-GL-NSG or equivalent in Bajaj/Philips
Excavation in trenches, not exc 1.5 m wide and n. exc 1.5 m depth for foundations of poles, struts, stays etc. or laying underground cable etc. in soft/loose soil, & getting out complete all as specified and directed by Engineer-in-Charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified and directed by Engineer-in-Charge
M & L for sand cushioning with dry coarse sand to under ground cable 23 cm thick, 8 cm thick below the cable and 15 cm thick after laying the cable complete all as specified and directed by Engineer-in-Charge. Note : Thickness after punning shall be considered for payment.
M & L for brick protection with old size sub class 'B' bricks laid flat , length of bricks across the route of underground cable all as specified and directed by Engineer-in-Charge.
M & L for boring hole across the Road/plinth/hard standing by trench less technology method suitable for 100mm bore pipe for 0.4 mpa working pressure for cable passing without damaging Road / Plinth /Floor complete all as specified and directed.
Disconnecting and taking out old unserviceable underground LT Cable of 2/3.5/4 core, 10 sqmm upto 240 Sqmm from trenches/ floor/ road /pipe /along poles including taking out old bricks complete all as specified and directed by Engineer-in-Charge. Note :Excavation, earth work required for item shall be measured and paid separately under respective items of BOQ.
Relaying of LT cable from 10 sqmm to 400 sqmm 2/3.5/4 core in same or other trenches/wall surfaces/flooring/road and testing on completion including good all disturbed surfaces to match with existing complete all as specified and directed. Note : Earth work viz excavation, sand cushioning will be measured and paid seprately.
Supply, laying in trenches or fixing to wall/pole or passing through pipe and and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 6 Sqmm 2 Core including making good to all disturbed surfaces/flooring/tiling/road to match with existing specifications complete all as specified and directed.Make:- HAVELLS/KEI/POLYCAB
All as per Srl item No 22 here-in-before but cable of cross sectional area 6 Sqmm, 4 core complete all as specified and directed by Engineer-in-Charge.Make:-HAVELLS/KEI/POLYCAB
All as per Srl item No 22 here-in-before but cable of cross sectional area 10 Sqmm, 4 core complete all as specified and directed by Engineer-in-Charge.Make:-HAVELLS/KEI/POLYCAB
All as per Srl item No 22 here-in-before but cable of cross sectional area 16 Sqmm, 4 core complete all as specified and directed by Engineer-in-Charge.Make:-HAVELLS/KEI/POLYCAB
All as per Srl item No. 22 here-in-before but cable of cross sectional area 25 Sqmm, 4 core complete all as specified and directed by Engineer-in-Charge.Make:-HAVELLS/KEI/POLYCAB
All as per Srl item No. 22 here-in-before but cable of cross sectional area 35 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge.Make:-HAVELLS/KEI/POLYCAB
All as per Srl item No.22 here-in-before but cable of cross sectional area 50 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge.Make:-HAVELLS/KEI/POLYCAB
All as per Srl item No.22 here-in-before but cable of cross sectional area 70 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge.Make:-HAVELLS/KEI/POLYCAB
All as per Srl item No.22 here-in-before but cable of cross sectional area 95 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge.Make:-HAVELLS/KEI/POLYCAB
All as per Srl item No.22 here-in-before but cable of cross sectional area 120 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge.Make:-HAVELLS/KEI/POLYCAB
All as per Srl item No.22 here-in-before but cable of cross sectional area 150 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge.Make:-HAVELLS/KEI/POLYCAB
All as per Srl item No.22 here-in-before but cable of cross sectional area 240 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge.Make:-HAVELLS/KEI/POLYCAB
Supply and fix in replacement of MCCB 4 pole 63A , 415 V, 50Hz having breaking capacity 16 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engg.in.Charge. Make: ABB/L&T/Schneider
Supply and fix in replacement of MCCB 4 pole 100 A , 415 V, 50Hz having breaking capacity 25 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engg.in.Charge Make: ABB/L&T/Schneider
Supply and fix in replacement of MCCB 4 pole 160 A , 415 V, 50Hz having breaking capacity 35 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engg.in.ChargeMake: ABB/L&T/Schneider
Supply and fix in replacement of MCCB 4 pole 250 A , 415 V, 50Hz having breaking capacity 35 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engg.in.Charge.Make: ABB/L&T/Schneider
Supply and fix in replacement of MCCB 3 pole 350 A/400 A , 415 V, 50Hz having breaking capacity 36 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engg.in.Charge.Make: ABB/L&T/Schneider
Supply only MCCB 3 pole 630 A , 415 V, 50Hz having breaking capacity 50 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engg.in.Charge.Make: ABB/L&T/Schneider
Supply only aluminium lugs suitable for cable of size 25/35 Sqmm complete all as specified and directed by Engineer-in-Charge.
Supply only aluminium lugs suitable for cable of size 50/70 Sqmm complete all as specified and directed by Engineer-in-Charge.
Supply only aluminium lugs suitable for cable of size 95/120 Sqmm complete all as specified and directed by Engineer-in-Charge.
Supply only aluminium lugs suitable for cable of size 150/240 Sqmm complete all as specified and directed by Engineer-in-Charge.
Supply only aluminium lugs suitable for cable of size 300/400 Sqmm complete all as specified and directed by Engineer-in-Charge.
S&F cable jointing kit for 1100 V (Earthed) grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 sqmm to 95 sqmm complete all as specified. Make: M-Seal/Birla 3M/Denson.
S&F cable jointing kit for 1100 V (Earthed) grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 120 sqmm to 150 sqmm complete all as specified. Make: M-Seal/Birla 3M/Denson.
S&F cable jointing kit for 1100 V (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 35 sqmm to 50 sqmm complete all as specified. Make: M-Seal/Birla 3M/Denson.
S&F cable jointing kit for 1100 V (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 sqmm to 95 sqmm complete all as specified. Make:Denson,M-Seal/Birla 3M/CCI
S&F cable jointing kit for 1100 V (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 120 sqmm to 300 sqmm complete all as specified. Make: M-Seal/Birla 3M/Denson.
M&L for cutting, trimming of branches along 2 pole/4 pole structure , OH Conductor of LT/HT line within 2 mts distance along both sides of structure /line complete all as directed by Engr-in-Charge.
Removal of bushes/plants/shrubs around the water supply or electric supply installation or near LT Panels , inside valve pits and surface excavation not exceeding 15 cm depth levelling the ground, removing excavated material outside the army cantt area complete all as specified and directed by Engr-in-Charge.
M&L for preparation old painted surfaces with synthetic enemel paint to LT steel tubbular pole 8.5/9 mtr long including clamps,brackets,chanel,cross arms,bracing support pipe for cable and swan neck etc, including zebra painting at bottom up to 1.5 mtr above from the PCC couping and writing pole No with white paint complete etc complete all as specified and as directed by Engr-In-Charge .Note: Pole number shall be marked with white enamel paint over a base of size 20cmx20cm on prepared with two coats of black enamel paint on pole surfaces.
Supply and fix GI pipe 50/80 mm bore light grade for protection of cable including provision of MS clamps, nuts, bolts etc required for fixing pipe along pole / wall / laid under the road / laid under the floor or in trenches complete all as specified and directred by Engineer-in-Charge.
M & L for preparation of old painted surfaces of LT panel size (up to 2.0x1.5mx0.8m) and applying spray painting with two coats of synethetic enamel paint over a coat of red oxide primer of existing color for outdoor/indoor panel board, outer & inner side and scraping out the old paint surfaces of existing panel boards including white wash to panel foundation/PCC base complete all as specified and directed by Engr-In-Charge .
Supply and fix in replacement of digital Ammeter 0 - 100 Amps & digital Voltmeter 0 - 500 Volts
Material and Labour MS work as in doors or gates or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering in doors or gates etc. to be prepared for hanging or sliding with and including hooks and hinges or steel hanging door fittings and hanging , fastening and fixing complete as in compound guards of transformers, four pole/two pole structures in sub stations or doors and gates of Panles or DB's incuding painting of two coats of enamel paint over one coat of zinc coating primer complete all as specified and directed. Note :- Disconnection of cables/wires, repair of broken doors/gates of panels and DB's by necessary welding with painting deemed to be included in rate quoted by contractor.
Earthing complete with galvanised steel earth plate electroe 60 cmx60cm6mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connectedto and including galvanized earth lead GI Strip of size 32x6mm by means of GI bolt/snuts/washers, protected by 40mm bore GI light grade pipe from earth plate & upto 3m long pole fixed with 2 clamp made from mild steel flat iron 32x6mm bolts, nuts, washer etc. earth plate shall be surrounded by alternate layer of charcoal or coke and common salt 15cm thick all around buttom and top of earth plate 20mm dia GI Medium grade pipe for watering and including funnel, wire mesh, RCC cover & frame PCC 1:3:6 type C1 using 20mm graded stone aggregate as in earthing pit including necessary excavation & earth work all as specified & shown on electrical plate No. 3 of SSR Part-I, (Note: (i) PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner (ii) earthing for Lightning protection is also included in the above item)
M&L for shifting of transformer of 100 to 400 KVA capacity from one place to another place of 2.0 KM, including providing of suitable vehicle for shifting complete all as specified and directed by Engineer-in-Charge.
Installation only Transformer step-down, 11/0.433 KVA complete, outdoor/indoor, copper wound, capacity 200 KVA all as specified and directed by Engineer-in-Charge.
M&L for shifting of pole of any type(steel/PCC) from one place to another place of 2.0 KM, including providing of suitable vehicle for shifting complete all as specified and directed by Engineer-in-Charge.
Fixing only prestressed concrete pole, 11.0 metres long. 152mm x 152mm at top and 152mm x 260mm at bottom, class 9 complete all as specified and directed by Engineer-in-Charge.
Supply, fabricating , fixing structural mild steel channel angle iron, flat iron and brackets etc for fabrications of cross arms, bracings, supports, D-clamps, stiffeners, eye hooks, bolts, pole clamps and back plates including nuts, bolts and washers, welding banding cold , or hot drilling holes for insulators bolts in any shape or size as indicated or directed and inclusive of one red oxide primer coat ,one under coat and one finishing coat of aluminium paint complete.(Insulators to be measured and paid for separately)
Excavation in trenches in any type of soil exceeding 1.5 mtr deep and not exceeding 3.0 mtr deep and not exceeding 1.5 mtr wide for laying of cables, RCC/Steel tubular poles/stays and struts etc getting out including trimming sides and forming bottom surface all as specified and directed at site.
M&L for plain cement concrete 1:4:8 type D-2 using 40mm graded stone aggregate in foundation of PCC poles/struts as specified including necessary form work all as specified and directed.
M&L for plain cement concrete 1:3:6 type C-2 using 40mm graded stone aggregate in foundation of stay assembly etc including necessary form work, all as specified and directed.
M&L for plain cement concrete 1:2:4 type B-1 using 20mm graded stone aggregate for coping around poles , including necessary form work finishing even and smooth without using extra cement , all as specified and directed.
HARSH CONSTRUCTION CO. (BID ID -3144202)
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .