Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹2.4 CrAdmitted-Finance | -4.00% | ₹2.4 Cr | L1 | Admitted-Finance |
| 2 | L2₹2.5 Cr+₹8.8 L (3.59%)Admitted-Finance BONAGUND VERINAG ANANTNAG J K 192212 | -0.55% | ₹2.5 Cr+₹8.8 L (3.59%) | L2 | Admitted-Finance |
| 3 | L3₹2.5 Cr+₹9.9 L (4.05%)Admitted-Finance | -0.11% | ₹2.5 Cr+₹9.9 L (4.05%) | L3 | Admitted-Finance |
| 4 | L4₹2.6 Cr+₹11.8 L (4.85%)Admitted-Finance | +0.66% | ₹2.6 Cr+₹11.8 L (4.85%) | L4 | Admitted-Finance |
Tender Value
₹3.0 Cr
EMD Value
₹6.0 L
Closing Date
17 Apr 2026, 1:30 pmClosed
Executive Engineer RandB Mech Div South
Office of Executive Engineer RandB Mech Div South
Design, Supply, Installation, Testing and Commissioning of Customized 15 No (Gplus3)06 Passsenger MRL Lifts at Transit Accommodation at Allowpora Shopian Phase II.
2026_PWDJK_306823_1
e-NIT No 49 of RandB/MDSK/2025-26 Dated 27 / 03 /2026
Open Tender
Machineries/ Mechanical Engg Items
Percentage
90 days
Allowpora Shopain
Please refer Tender documents.
5 documents required · 5 mandatory
₹5,500
Executive Engineer RandB Mech Div South
₹6.0 L
Office of SE PW(RandB) Circle Pulwama Shopain
27 Aug 2026
27 Mar 2026
18 Apr 2026
27 Mar 2026
17 Apr 2026
27 Mar 2026
4 Apr 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Lift - MRL type
Supply,Installation Testing & Commissioning of Customised 06 Passenger (G+3) MRL lift at Transit accommodation Allowpora Shopian Phase II (excluding all the civil works). The lift shall be suitable for 06 passengers, of standard design having speed 1m/s serving from Ground, 1st, 2nd & 3rd floor i.e. 04 stops and 04 landings. The elevator shall be of state of art technology, energy efficient drive and all its components/ accessories shall conform to relevant IS standards.
• (The Defect Liability Period (DLP) of the equipment shall be 02 years.• Machine – Gearless machine located in the shaft on the top of guiderails• Power Supply – 400/415 V (3 Phase AC)
• Control – Simple Collective Selective Control (VF regenerative drive)• Available Hoist way dimensions - to be constructed by civil authorities.
• Landing door – Centre door opening in stainless steel hairline.
• Door opening :Ground, Ist, 2nd & 3rd floor on same side• Car design - Stainless steel in hairline finish.
• Handrail - Round handrail in stainless steel finish provided on rear wall of car.
• Alarm button in car operating panel with battery back-up.• Automatic operation for car fan.
• Anti-nuisance (empty car)• Anti-nuisance (car call cancellation at direction reversal)
• Blower fan in car for ventilation• Braille on push buttons
• Door open and door close buttons in car operating panel.• Door closing retries• Door nudging• Emergency light• Full load by-pass
• Infra–red screen for car door• Intercom Provision With Instrument
• Motor overheat protection.• Overload function with audio-visuals indication in car operating panel.• Phase failure and phase reversal protection.
• Automatic rescue device in case of power failure.• Attendant control.Car arrival chime on car top/voice synthesizer.
• LCD dot matrix scrolling display in car operating panel.• LCD matrix scrolling display in landing operating panel on all floors.
• Fireman control.• Fireman emergency return
The rates are inclusive of all minor adjustments that may be required in hoistway/pit for completion of the job
Providing & Laying integral Cement based water proofing (Injected type) treatment including preperation of surface and then applying and grouting a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with proprietary water proofing compound confirming to IS: 2645. After proper curing apply a second coat of cement slurry admixed with proprietry water proofing compound. The job includes finishing the surface with 20mm thick jointless cement morter of mix 1:4 | - | C.Job | 0.03 | - |
| 2 | Electric Works
Supply, installation, testing & commissioning of 3 Phase-30 KVA Servo-Stabilizer including oil and all allied electrical acessories with earthing.
The stabiliser should have following specifications:
a) Capacity: 30 KVA, 3-phase unbalanced type
b) Input: (100-265) V AC P-N; (180 - 460) V AC P-P
c) Output: 415 V ± 1% - phase to phase
d) Supply: 3 phase, 4 wires, 50Hz
e) Operation: Automatic
f) Duty cycle: Continuous
g) Transformer windings: Copper wound on CRGO laminations as per IS specifications
h) Cooling: Oil cooled
i) Efficiency: Better than 98% at full load
j) Overload capacity: 15% for continuous 4 hours
k) Waveform distortions: Nil
l) High speed voltage correction: up to 8V to 20V per second
m) Protections: Under voltage, Over voltage and Overload with time delay
n) Other features: LED indicators, Digital AC ammeter, AC voltmeter, Frequency meters, Phase Sequence meters, Single phase preventer, Stabilizer by-pass arrangement. | - | Job | 0.29 | - |
| 3 | Supply, installation, testing & commissioning of 3 Phase- 10 KVA Servo-Stabilizer including oil and all allied electrical acessories with earthing.
The stabiliser should have following specifications:
a) Capacity:10 KVA, 3-phase unbalanced type
b) Input: (100-265) V AC P-N; (180 - 460) V AC P-P
c) Output: 415 V ± 1% - phase to phase
d) Supply: 3 phase, 4 wires, 50Hz
e) Operation: Automatic
f) Duty cycle: Continuous
g) Transformer windings: Copper wound on CRGO laminations as per IS specifications
h) Cooling: Oil cooled
i) Efficiency: Better than 98% at full load
j) Overload capacity: 15% for continuous 4 hours
k) Waveform distortions: Nil
l) High speed voltage correction: up to 8V to 20V per second
m) Protections: Under voltage, Over voltage and Overload with time delay
n) Other features: LED indicators, Digital AC ammeter, AC voltmeter, Frequency meters, Phase Sequence meters, Single phase preventer, Stabilizer by-pass arrangement. | - | Job | 1 | - |
| 4Supply, Installation and Testing & Commissioning of Control Panel enclosed in suitable sized CRC/weather proof Enclosure(SWG16, powder coated) with IP-Rating to prevent ingress of water and comprising of Bus bar MCCBs, contactors, relays, single phase preventers, earth fault relays, changeover switches, for lifts with following specifications with Earthing. Incomer: 1. MCCB 125 4P 01 No (30kA breaking capacity) of reputed make preferably L&T/ABB/Schneider. 2. Front Operated Manual Change Over (125A) 01 No. (4P) 3. MCCB 100A TPN (18kA breaking capacity) of reputed make preferably L&T/ABB/Schneider. 4. 125A Aluminum 4 Pole Bus Bar –01 set 5. Digital Voltmeter with Selector Switch 6. Digital Ammeter with Selector Switch & CT’s 7. Phase Indicator Set Outgoing feeders: a) 40A Four Pole MCBs C curve (10kA breaking Capacity)- 03 No's of reputed make preferably L&T/ABB/Schneider. The job is inclusive of the cost on account of concrete foundation/footing for resting of the Control Panel. | |||||
| 5 | Supply, Installation and Testing & Commissioning of Control Panel enclosed in suitable sized CRC/weather proof Enclosure(SWG16, powder coated) with IP-Rating to prevent ingress of water and comprising of Bus bar MCCBs, contactors, relays, single phase preventers, earth fault relays, changeover switches, for lifts with following specifications with Earthing.
Incomer:
1. MCCB 100A 4P 01 No (30kA breaking capacity) of reputed make preferably L&T/ABB/Schneider.
2. Front Operated Manual Change Over (100A ) 01 No. (4P)
3. MCCB 80A TPN (18kA breaking capacity) of reputed make preferably L&T/ABB/Schneider.
4. 100A Aluminum 4 Pole Bus Bar –01 set
5. Digital Voltmeter with Selector Switch
6. Digital Ammeter with Selector Switch & CT’s
7. Phase Indicator Set
Outgoing feeders:
a) 40A Four Pole MCBs C curve (10 kA breaking Capacity)- 02 No's of reputed make preferably L&T/ABB/Schneider. The job is inclusive of the cost on account of concrete foundation/footing for resting of the Control Panel. | - | Job | 1 | - |
| 6Supply, Installation and Testing & Commissioning of Control Panel enclosed in suitable sized CRC/weather proof Enclosure(SWG16, powder coated) with IP-Rating to prevent ingress of water and comprising of Bus bar MCCBs, contactors, relays, single phase preventers, earth fault relays, changeover switches, for lifts with following specifications with Earthing. Incomer: 1. MCCB 80A 4P 01 No (18kA) of reputed make preferably L&T/ABB/Schneider. 2. Front Operated Manual Change Over 100A ) 01 No. (4P) 3. MCCB 63A TPN (18kA breaking capacity) of reputed make preferably L&T/ABB/Schneider. 4. 100A Aluminum 4 Pole Bus Bar –01 set 5. Digital Voltmeter with Selector Switch 6. Digital Ammeter with Selector Switch & CT’s 7. Phase Indicator Set Outgoing feeders: a) 40A Four Pole MCBs (10 kA breaking Capacity)- 01No's of reputed make preferably L&T/ABB/Schneider. The job is inclusive of the cost on account of concrete foundation/footing for resting of the Control Panel. | |||||
| 7Providing / Fitting of 3.5 core, 70 sqmm XLPE, PVC sheathed, armoured Al cable from Distribution Transformer to Servo Stabilizer with other required accessories cable glades,clamps,saddles for proper connections and fixings of suitable ratingto be laid underground as per requirement. (to be paid as per actual) | |||||
| 8Providing / Fitting of 3.5 core, 50 sqmm XLPE, PVC sheathed, armoured Al cable from Servo Stabilizer to Control Panel with other required accessories cable glades,clamps,saddles for proper connections and fixings of suitable rating for proper laying/connections as per relevant standards, to be laid as per requirement. (To be Paid as per actual) | |||||
| 9 | Providing / Fitting of 3.5 core, 35 sqmm XLPE, PVC sheathed, armoured Al cable from Servo Stabilizer to Control Panel with other required accessories cable glades,clamps,saddles for proper connections and fixings of suitable rating for proper laying/connections as per relevant standards, to be laid as per requirement. (To be Paid as per actual) | - | Rm | 1 | - |
| 10 | Providing / Fitting of 3.5 core, 25 sqmm XLPE, PVC Sheathed, Al cable from Control Panel to individual lifts with other required accessories cable glades,clamps,saddles for proper connections and fixings of suitable ratingfor proper laying/connections as per relevant standards, to be as per requirement. (To be Paid as per actual) | - | Rm | 1 | - |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.95 MB
Tendernotice_2.pdf
PDF • 2.84 MB
BOQ_995983.xls
BOQ • 0.35 MB
CorrigendumAllowpora2.pdf
PDF • 0.48 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .