GE 867 EWS
GE 867 EWS C/O 99 APO PIN-913867
REPAIR AND MAINT OF JOINERIES SANITARY FITTING, INTERNAL WIRING, SECURITY STREET LIGHT, LT PANEL, LT UG CABLE, WATER SUPPLY AND CONNECTING MISC ALLIED WORKS AT SHERWANI UNDER GE 867 EWS
2023_MES_600168_1
GE/867/TOKEN/17 OF 2023-2024
Open Tender
Civil Works
Item Wise
270 days
KALIMPONG
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE 867 EWS
₹47,000
23 Aug 2023
1 Jun 2023
30 Jun 2023
1 Jun 2023
28 Jun 2023
14 Jun 2023
1 Jun 2023 - 12 Jun 2023
Amount
Dismantling of plain or corrugated steel sheeting, any gauge and thickness including Nainital or similar pattern roof coverings complete all as specified and as directed.
S&F Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50 mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and as directed.
S&F Pre-painted galvalume aluminum zinc coating GI based Plain steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and as directed.
S&F 0.63 mm thick galvanised, corrugated mild steel sheeting with two corrugations side lap, fixed with coach screws and washers, in roofs, walls etc. with grade of zinc coating 275 complete all as specified and as directed.
Dismantling timber scantlings 40 Sqcm and over in section, in unframed work position complete all as specified and as directed.
M&L for second class hard-wood in scantling fixed in clean swan complete all as specified and as directed.
Dismantling timber fillets, rails, posts rafters purlins etc under 40 Sqcm in section fixed in unframed work position complete all as specified and as directed.
M&L for second class hard-wood plain fillets sectional area exc 13 but n. exc 25 sqcm square ,rectangular or triangular in section, clean sawn, secured with nails or brads complete all as specified and as directed.
Dismantling wall and ceiling boards (fiber, pulp, insulation etc) or insulation boards/slabs/ blankets, any thickness including cover fillet complete all as specified and as directed.
S&F GI frame work of size 605 x 605 mm, for seamless celing comprising of GI perimeter chanel 0.55mm thick with two unequal flanges of 20 and 30 mm and web of 27mm fixed to surrounding wall using nylon sleeves and screws at 450mm centre to centre/ intermediate channel 0.9mm thick having two equal flanges of 15mm each and web of 45mm suspended from soffit at approx 900mm centre to centre with GI cleat and steel expansion fasteners with and including ceiling section (not exc 1.2m length) of 0.55mm thickness having kurled web of 50mm and flange of 26mm each with lips of 10.5mm fixed to the intermediate channel with connecting clips across the intermediate channel at 457 mm centre to centre complete all as specified and as directed.
S&F hangers 6mm dia GI (upto 1200mm length) adjusting level fixed to roof slabs by means of ceiling cleats made out of GI flat 40 x 3mm size 60mm long and expansion hold fasterners 12.5mm dia 40mm long complete all as specified and as directed.
M&L 4 mm thick E Board (Everest) non combustible moisture resistant plain building boards, fixed to timber/GI aluminium frame work with screws as in ceiling complete all as specified and directed.
M&L preparing new surfaces,plastered or unplastered and applying three coats of white wash on undecorated surface of ceiling for AC boards.
Dismantling floor, hearth or wall tiling including cement mortar bedding but not backing, removing rubbish off the complete all as specified and directed.
M&L for non - skid Ceramic tiles 7 to 8 mm thick (square/ rectangular) area of each tile exceeding 0.11 sqm but not exceeding 0.18 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match the surfaces of tile over and including 15 mm thick screed bed in cement mortar (1:6) complete all as specified and directed.
M&L for non - skid Ceramic tiles 7 to 8 mm thick (square/ rectangular) area of each tile exceeding 0.11 sqm but not exceeding 0.18 sqm, on vertical surfaces such as dado/skirting set and jointed in neat cement slurry and pointed in white or coloured cement to match the surfaces of tile over and including 10 mm thick backing coat in cement mortar (1:4) complete all as specified and directed.
Demolition of cement concrete (unreinforced) in ground floor and pavings not exc 15 cm thickness (below or above ground level) complete all as specified and directed.
M&L for 75mm thick cement concrete (1:3:6) type C-2 (using 40 mm graded crushed stone aggregate) as in plinth protection, path/steps etc complete all as specified and directed.
M&L for 40 mm thick cement concrete (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) as in floors finished even and smooth using extra cement complete all as specified and directed.
Taking down chowkhats or frame exc 1.50 sqm but n. exc 4 sqm each with shutter (without taking off shutters from the frame) complete all as specified and directed.
Taking down chowkhats or frame not exc 1.50 sqm each with shutter (without taking off shutters from the frame) complete all as specified and directed.
S&F for second class hard-wood plain, solid, straight chowkats and frames wrough framed rebated on the solid, rounded or chamfered put together with glue pinned at joints, complete all as specified and directed.
S&F 30mm thick second class hard wood, plain, framed panelled shutters (any number of panels), with panels of timber flat on both sides (feather edged), or of veneered particle board medium density wood particle board with commercial face veneers complete all as specified and directed.
S&F 30 mm thick second class hard wood, glazed and skeleton shutters for door, open rebated and prepared to receive glass, gauze, etc, edges of framing plain, chamfered or rounded. fitted with cut and mitred beads for securing glass, etc. sizes of members of shutters as specified in SSR Part-I, Section 8, clause 8.24 (a) complete all as specified and directed.
S&F 30 mm thick second class hard wood, glazed and skeleton shutters for window, ventilator etc, open rebated and prepared to receive glass, gauze, etc, edges of framing plain, chamfered or rounded. fitted with cut and mitred beads for securing glass, etc. sizes of members of shutters as specified in SSR Part-I, Section 8, clause 8.24 (b) complete all as specified and directed.
Solid PVC door frame of size 50mm x 47mm made out of 5mm plain colour PVC sheet reinforced with MS square tube, suppling & fixing in openings complete all as specified and directed.
S&F for factory made solid panel PVC door shutter 30 mm thick (style) consisting of frame made out of M.S. tubes for top & bottom rails. M.S. frame shall be covered with heat moulded plain colour PVC ‘C’ channel having a PVC sheet strip of 20mm width stuck inside with solvent cement for stiles and plain colour PVC sheets for top rail, lock rail & bottom rail on either side & as gap insert for top rail & bottom rail; Panelling of plain colour PVC sheet to be fitted in the M.S. frame welded / sealed to the stiles & rails with suitable PVC sheet beading, and joined together with solvent cement, suppling & fixing in the frame at site as per specification complete all as specified and directed.
S&F galvanised mild steel wire cloth 0.63 mm nominal dia of wire and average width of aperture 1.40 mm and fixed with tinned tacks or galvanised wire staples complete all as specified and directed.
S&F 3mm thick sheet glass, ordinary quality and glazing with oil putty in square n exc 0.5 sqm in each pane complete all as specified.
M&L Preparation new wooden surfaces of any description, over 10cm width or girth and applying two coat of synthetic enamel paint over one coat of pink primer complete all as specified and directed
M&L Preparation new steel surfaces, of any description, over 10cm width or girth and applying two coat of synthetic enamel paint over one coat of red oxide primer complete all as specified and directed
S&F 75mm size butt hinges, medium weight , cold rolled, mild steel and fixed complete all as specified and directed
S&F 100mm size butt hinges, medium weight , cold rolled, mild steel and fixed complete all as specified and directed
S&F of 150mm long aluminium, anodised, barrel tower bolt, of extruded section and fixed complete all as specified and directed
S&F of 200mm long aluminium, anodised, barrel tower bolt, of extruded section and fixed complete all as specified and directed
S&F 125mm size aluminium handles, cast type, anodised and fixed complete all as specified and directed
S&F 150mm size aluminium handles, cast type, anodised and fixed complete all as specified and directed
S&F 300mm long aluminium alloy, anodised sliding door bolts with haps staple (bolt type), and fixing clips of sheet, cast or extruted sections and fixing bolt and sliding bolts of extruted sections or cast aluminium alloy and fixed complete all as specified and directed.
S&F 15mm bore tubes medium grade galvanised with all fittings and fixed complete to walls and ceiling or laid in floors including for re fixing or removal to store, complete all as specified and as directed.
S & F in repair bib taps 15mm bore cast copper alloy chromonium plated with crutch or butterfly, handle, screwed down, screwed for iron pipe, complete all as specified and as directed.
S & F in repairs pillar taps cast copper alloy chrominium plated with capstan heads, chromium plated, screwed down high pressure with or without lettered "Hot or Cold" with long screwed shanks and fly nuts screwed for iron pipe, complete all as specified and as directed.
S & F in repair 15mm stop cock/Angle valve cast copper alloy chromonium plated screwed down high pressure, with crutch or butterfly handle screwed both ends for iron pipe or for unions, complete all as specified and as directed.
S & F in repair PVC connection pipe 15mm size with PTMT nuts of 600 length, complete all as specified and as directed.
S & F in repair vitreous china squatting pan, Orissa pattern, size 580 x 440 mm white, with integral foot rests (excluding flushing cistern and flush pipe), complete all as specified and as directed.
S & F in repair vitreous china, wash down water closet pedestal pattern complet all as specified.
S & F in repair PVC valveless syphonic action type flushing cistern,10 ltr capacity, low level, white with inlet, ball valve float and handle including brackets and connection to pipes, complete all as specified and as directed.
S & F in repair Vitreous china WHB 550 x 400 mm white flat back including bracked complete all as specified and as directed.
M&L for 75mm dia PVC (SWR) pipes single socketed, in any length with rubber ring joints, laid in trenches or in floors, complete all as specified and as directed.
M&L for 110mm dia PVC (SWR) pipes single socketed, in any length with rubber ring joints, laid in trenches or in floors complete all as specified and as directed.
M&L 75mm PVC (SWR) bends
M&L 110mm PVC (SWR) bends
S&F in repair Health faucet (ABS Body) mild steel chromium plated suitable for 15 mm dia pipe with 1.25 metre long flexible tube and ABS wall hook including making connections and fixed in position complete in all respect as specified.
Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 mtr in depth; for foundation etc. and getting out in Soft/loose soil complete all as specified and as directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in Soft/loose soil complete all as specified and as directed.
Removing excavated material n.exc 50 mtr and depositing where directed at level n.exc 1.5 mtr above the starting point, complete all as specified and as directed.
Excavation in post holes (or simillar holes) each not exceeding 0.5 cum , getting out, retaining, filling in and ramming earth or broken rubble mixed with earth around, in layesrs not excedding 25 cm, watering and removing surplus soil to a distance not exceeding 50 mtr and making good surfaces complete all as specified and as directed.
M & L for Providing precast cement concrete solid building block over 10cm in width and setting in mortar 1:6 using pre cast cement concrete Block 1:3:6 type C1 using 20mm graded stone agg complete all as specified and as directed.
M & L for cement concrete (1:3:6) type C-2 (using 40 mm graded crushed stone aggregate ) as in foundation , filling and mass concrete complete all as specified and as directed.
M & L PCC (1:3:6) type C-1 (using 20 mm graded crushed stone aggregate ) as in coping including weathering, slightly rounded or chamfered angles and throating , as directed and necessary from work complete all as specified and as directed.
M/L for Point wiring complete with 1.5 sqmm single core PVC insulated and PVC unsheathed FRLS multistranded copper conductor cable 1100 volt grade enclosed in and including PVC casing and capping with accessories fixed on surface on walls/ceiling by means of PVC sleeves, Dash fastners and cadmium plated screws including sunken junction box not less than 3.0 mm thick concealed in wall, mounting accessories like switches, sockets fan regulators with 3.0 mm thick Laminated sheet top covers etc including 1.5 Sqmm single core multi stranded copper conductor PVC insulated and unsheathed cable as earth continuity conductor to common earth dolly. for the One light/fan/bell point controlled by one switch 6 Amp one way
All as per item Number 61 but One 3 pin socket outlet on same board with other switches.
All as per item Number 61 but One 3 pin switch socket combination 6 amp on the independent board.
All as described as per item No 61 above but point wiring with 2.5 sqmm single core multi stranded copper conductor PVC insulated & unsheathed FRLS cable 1100 volt grade and 2.5 sqmm PVC insulated and unsheathed FRLS cable 1100 volt grade with multi stranded copper conductor for earth wire for 15/16 amp multi purpose socket combination point on independent board.
S & F in replacement under repair switch piano flush type single pole, one way 6amp, complete all as specified and as directed. Make: Anchor/SSK/Cona
S & F in replacement under repair switch socket combination 5 pin 6 amp, complete all as specified and as directed. Make: Anchor/SSK/Cona
S & F in replacement under repair Switch socket combination 2 in 1, 3 pin, 5 and 15 Amp flush typecomplete all as specified and as directed.
S & F in replacement under repair ceiling rose surface bakelite three terminal 65 x 50 mm three terminal 230 volts ISI marked, complete all as specified and as directed.
S & F in replacement under repair lamp holder,PVC/Polycarbonate type and back plate suitable for batten fitting, complete all as specified and as directed.
S & F in replacement under repair flush type bell push 6 amp duly marked for bell complete all as specified and as directed. Make : Anchor/SSK/CONA
S & F in replacement under repair Electronic ding dong bell AC 230V single pole make Anchor/ Bajaj
S & F in replacement under repair fan regulator electronic type 100Watt 20V-50Hz complete all as specified and as directed. Make: Ancho cat No 38660 or equivalent
S & F in replacement under repair ceiling fan capacitor 2.5 mfd complete all as specified and as directed.
S & F Energy efficient LED tube light fitting 4", 1x18 watt, with bipin holders, connector block, CCT - 6500K, system output lumen not less than 1800lm, aluminium housing, surge protection range 3KV including connecting up with PVC insulated 3 core sheathed 0.5 sqmm copper conductor two numbers PVC mounting blocks for fixing of fitting, Make : Batten : Cat part No- TMC 501 of Philips or LUMILINE+BS18WLED865SPCSS of Havells or equivalent. Tube rod :- Philips, Cat part No- MAS LED tube 18W 1800lm 865 T8 or PHOTONULTRAE2.01213T8SSTL18WLED865SPC of Havells equivalent.
S&F Endura LED Bulkhead fitting 10 watt, system lumen output not less than 950lm, Operating temperature: -10° C to +45° C, Operating voltage range: 140-270 V, CRI ≥ 80, system efficacy ≥95, including connecting up with 3.0 core, 0.5 sqmm copper conductor PVC sheathed from connector to ceiling rose including taking down old u/s light fitting complete all as specified and as directed. Make : Crompton Cat part No "LBH-10-CDL" or equivalent in Philips/Havells.
S & F in replacement under repair 9W LED Bulb suitable for B22 holder . System Efficacy should be > 85 lm/ W. PF > 0.9, The Lamp Should have Cool Daylight Color temp of 6500K, lumen output >800 lm, complete all as specified and as directed. Make: Philips/Wipro/Crompton
Dismantling and taking out submain wiring 2/3/4/6 wire of any size, segregating for material for reuse, making good disturbed surface of walls/floors to match with existing surface and taking out from site complete all as specified and as directed.
S & F in replacement under repair MCB DB factory made IP 42 of SPN 8 way protection class metal double door with 200 Amp rating bus bar 240/430V for fixing of MCBs/Isolators/RCCBs etc complete all as specified and as directed. Make : Legrand/Schneider/L&T
All as per item number 78 but SPN 4 way
Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB Complete with connection testing and commissioning complete including taking down old unserviceable MCB complete all as specified and as directed. Make : Legrand/Seimen/Schneider
All as per item No 80 but SPN 40 to 63 Amps 'C' curve. Make : Legrand/Seimen/Schneider
M&L for Sub main wiring with FRLS two single core PVC insulated and unsheathed fire retardant multi stranded copper conductor cable 1100 volt grade IS-694, marked of 4.0 Sqmm size drawn through and including not less than 25 mm dia PVC conduit medium grade ISI marked and conduit junction boxes, terminal boxes and accessories such as tees, bends, elbows, reducers, bell mouth tube ends fixed to the surface of wall/ceiling including one run of 4.0 sqmm PVC insulated and unsheathed FRLS multi stranded copper conductor cable for earth wire continuity conductor, complete all as specified and as directed. (NOTE : Two runs of single core 4.0 sqmm and one run of 4.0 sqmm copper FRLS cable as earth continuity conductor and suitable size conduit with accessories shall be measured as one length.)
Supply and fixed on surface Rigid non metallic PVC casing caping of size 25mm including of all tee, bends, elbows and fixing accessories such as couplers, lock nuts,saddles, pipe hooks including taking down old broken PVC casing caping and making good surface complete all as specified and directed.
Supply and fixed on surface Rigid non metallic PVC casing caping of size 20mmincluding of all tee, bends, elbows and fixing accessories such as couplers, lock nuts,saddles, pipe hooks including taking down old broken PVC casing caping and making good surface complete all as specified and as directed.
M&L earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15cm on all side and connected to and including galvanized earth lead wire 4.0 mm dia upto 7.5 mtrs long by means of nuts and bolts, check nuts and washers of GI and connected to earhing test point and earth dolly all as shown in electrical plate No 3 of MES schedule Part-I, and testing on completion including necessary excavation and earth work in any type of soil, PCC(1:3:6) type C1 chamber, CI Cover with cast iron frame, funnel with watering pipe 20mm dia medium grade, wire mesh and lugs, GI protection pipe15mm dia, light grade 7.5 mtr long for protection of earth lead upto test point etc incl taking down old u/s earthing complete all as specified and as directed.
Refixing of old serviceable light fitting of any description including clamps etc as required complete all as specified and as directed.
S&F of Exhaust fan 200 mm sweep 1300 RPM with minimum airflow/air delivery 450 Cmh, light weight, rust proof body & blades, self opening louvers for protection from birds & rain water, IP-55, 200-240 Volt AC supply, rated power input not more that 30watt, connecting up including provison of cable from ceiling rose to fan incl taking down existing fan from same location. Make : Crompton Greaves, Model : BRISK AIR , or equivalent in USHA/Bajaj. Note: Old UNSV ceiling fans will be deposited to MES Store at Rhenock
Taking down existing unserviceable service cable of any size and S&F 1100 volts grade heavy duty PVC insulated stranded aluminium conductor cable of cross-sectional area 10 Sqmm size (one twin core cable flat or circular, served with inner sheathing of PVC tape and overall PVC sheathed) in service connections, suspended by insulating hangers not more than 1 mtr apart including 4 mm suspension wire and testing on completion complete all as specified and as directed. MAKE : FINOLEX/PLAZA/ HAVELLS/ POLYCAB/KEI.
Taking down carefully electric storage type water heater (Geysers) of any make and any capacity from its mounting place opening for inspection compete Including back plate heating element inner copper tank etc. De-scaling back plate and heating element by cleaning with Sulfuric acid/ de-scaling compound and re-assembling of Geysers after repairs carrying out and re-fixing in same position (Replaced items such as spares measured and paid separately)in relevent item including making good to walls with CM (1:3) or PCC (1:2:4) and plastering the wall surfaces with CM 1:6 and replacement of old nuts, bolts and rubber gasket etc complete all as specified and as directed. (Note :- Any type of rubber gasket , rubber washer, screws , insulator tape required in work deem to be included in the rate).
M&L for 1.5 KW capacity Heating Element, triangular type including making electrical connection incl taking down old u/s heating element complete all as specified and as directed.
All as per item Srl No 90 but of capacity 2.0 KW complete all as specified and as directed.
Supply & fixing PVC connection heavy duty with brass/PTMT nuts of reqd length not exceeding 300 mm with rubber & PVC washer suitable for 15 mm bore GI pipe complete for cold water incl taking down old u/s connection complete all as specified and as directed.
Supply & fixing hot water outlet connection made of brass chromium plated with Union rubber washer suitable for 15 mm bore GI pipefor hot water incl taking down old u/s item complete all as specified and as directed.
Supply & fix in replacement of thermostat (automatic cut of) of existing type & make, 15 Amps, 230/250 volts AC ISI marked complete all as specified and as directed.
Supply & fix in replacement safety valve as per existing make and type, ISI marked complete all as specified and as directed.
S&F in replacement plug top 15 Amps 240 Volts complete all as specified and as directed.
M&L in repairs PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 200 x 150 x 50 mm deep complete all as specified and as directed.
All as per item No 97 here-in-before but of size 175 x 100 x 50 mm complete all as specified and as directed.
Taking down of exhaust fan upto 450/300mm sweep, opening, replacement of unserviceable accessories, servicing, oiling, greasing, complete overhauling of fan and re-assembling and testing complete for efficient functioning after fixing / hanging in position from ceiling rose to fan complete all as specified and as directed. (Note : Gun metal bush, bearing will be measured and paid under relavant item here-in-after).
Supply only gun metal bush of sizes suitable for exhaust fan upto 450 mm sweep complete all as specified and as directed.
Supply only ball bearing No 6203 suitable for fan of existing make type & sweep complete all as specified and as directed. Make:- NBC/SKF/TATA
Checking of exhaust fan (of any sweep) by replacing unserviceable capacitor/ tightening the loose connections if any including testing complete all as specified and as directed. (Note: Capacitor of required capacity will be measured & paid under relavent item here-in-after)
Supply only 2.5/4.0 MFD capacitor suitable for exhaust fan of existing type & sweep complete of 300/250/150mm capacity complete all as specified and as directed.
Dismantling / Taking out Unserviceable LT cables of size 50 sqmm to 120 sqmm from any position i.e ground / walls / poles / culverts etc complete with protection pipe complete all as specified and as directed.
Supply and Laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor on wall/in trench with the help of shadel of Size of 70 Sqmm 3.5 core as required at site, complete all as specified and as directed. Make : MESCAB/HAVELLS/POLYCAB/KEI/GLOSTER or equivalent as approved by GE
All as per item Number 105 but Size of 50 Sqmm 3.5 core
Dismantling / Taking out Unserviceable LT cables of size upto 35 sqmm any core from any position i.e ground / walls / poles / culverts etc complete with protection pipe complete all as specified and as directed.
Supply and Laying cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor on wall/in trench with the help of shadel of Size of 35 Sqmm 3.5 core as required at site, complete all as specified and as directed. Make : MESCAB/HAVELLS/POLYCAB/KEI/GLOSTER or equivalent as approved by GE
All as per item Number 108 but Size of 25 Sqmm 3.5/4 core
M&L for sand cushioning to U/G cable in layers in trenches complete all as specified and as directed. Note :- Only compacted thickness shall be measured for payment
M&L for well burnt bricks, sub class 'B' bricks of size 250mmx125mmx75mm, best quality locally available laid flat dry in trenches for cable protection complete all as specified and as directed.
Dismantling / Taking out Unserviceable GI pipe of any size removing material from site complete all as specified and as directed.
M & L GI tube light grade for passing through cables under the floor, along the wall or along the pole of 40 mm bore dia and fixed to the poles/walls with suitable size of MS clamps and nut and botls/washers etc including taking down old GI tubing complete all as specified and as directed.
All as per item Number 113 but 25 mm bore
Dismantiling/taking out old unserviceable LT insulator any size, any type from poles complete all as specified and as directed.
S & F for pin type insulator porcelain vitreous white/ brown or green including one galvanised mild steel spindle two GI washer and one GI nut 100mm height, 65mm dia for 1100 Volt grade complete all as specified and as directed.
Material and labour for spray painting to outdoor/Indoor type double door LT panels/Fedder pillar box incl angle iron stand with synthetic enamel paint after cleaning the surface thouroughly with scrapper including protecting/cleaning of cables, wiring and other non painted parts complete all as specified and as directed.
Supply and fix cable jointing kit in repairs of existing LT 1.1 KV grade cable disconnecting from site (by means of disconnecting from panel/trench by excavation) against item Ser No 7.01 to 7.02 above, for outdoor termination Straight through tubular sleeve version type joint complete with jointing materials and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 sqmm to 120 Sqmm, complete all as specified and as directed.
Supply and fix cable jointing kit in repairs of existing LT 1.1 KV grade cable disconnecting from site (by means of disconnecting from panel/trench by excavation) against item Ser No 9.01 & 9.02 above, for outdoor termination Straight through tubular sleeve version type joint complete with jointing materials and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 sqmm to 50 Sqmm, complete all as specified and as directed.
Supply and fix cable jointing kit in repairs of existing LT 1.1 KV grade cable disconnecting from site (by means of disconnecting from panel/trench by excavation) against item Ser No 9.40 & 9.50 above, for outdoor termination Straight through tubular sleeve version type joint complete with jointing materials and accessories suitable for 2.0 core XLPE armoured aluminium conductor cable of size upto 25 Sqmm, complete all as specified and as directed.
S & F for Sackle type insulator porcelain vitreous white/ brown or green including one galvanised mild steel straps of size 31 x 5 mm, washers insulator bolt of 14 mm dia and nuts complete of size 100 mm hight and 115mm dia of working pressure 1100 volts grade complete all as specified and as directed.
S&F in repair cable route marker of size 100 mm x 100 mm x 5mm thick with GI plate with inspection threon bolted / welded to 35 mm x 35mm x6 mm angle iron 60 cm long and fixing the same in ground as required for LT cable complete all as specified and as directed.
S&F in repairs Busbar Chambers 8 way 100 Amps outdoor type (IP 65/66) pole mounted including provision of fixing on pole by means of suitable size of clamps with nut and bolts OR provision of fixing on 50 x 50 x 6mm thick angle iron frame work upto height of 0.9mtr above ground level including necessary connection complete all as specified and as directed. Make Havells cat part No IHBC010004 or equivalent make of SMC/Hencel.
Trimming of tree branches which touches the LT OH lines and 2.5 Mtr away from centre line of LT OH lines span not exceeding 60 Mtr distance between poles by using neccessory T&P items and depositing the tree branches/leaves at 30 Mtrs away from the site, complete all as specified and as directed. (Note -Any number of tree branches cut in one span will be measured as one lenght of payment.)
Supply and fixing of earth continuity conductor or main earthing lead fixed to wall or batten or recess or chases or burried on ground or drawn in conduit pipe or fixed to poles in repairs or any other indicated situation for the loop earthing etc. as required of size 32 x 6 mm galvanized iron strip complete all as specified and as directed.
M&L earthing complete with galvanized steel earth plate electrode 600mmX600mmX6.3mm buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15cm on all side and connected to and including using 32 x 6 mm galvanized MS strip wire upto 7.5 mtrs long by means of nuts and bolts, check nuts and washers of GI and connected to earhing test point and earth dolly all as shown in electrical plate No 3 of MES schedule Part-I, and testing on completion including necessary excavation and earth work in any type of soil, PCC(1:3:6) type C1 chamber, pre-cast RCC slab 50mm thick in cement concrete (1:2:4), type B1, reinforced with welded steel wire fabric or XPM, (weight not less than 4 Kg per Sqm) with cast iron frame, funnel with watering pipe 20mm dia medium grade, wire mesh and lugs, GI protection pipe 40 mm dia, light grade 7.5 mtr long for protection of earth lead upto test point etc complete all as specified and as directed. Note : (a) Length of earthig connection incl GI strip and protection pipe more than 7.5 Mtr will be measured separately. (b) Contractor should conduct necessary test such as Earth continuity, earth resistance test in presence of JE (E/M)/Engr-incharge.
Description all as per item No 126.00 above but with GI conductor 4 mm dia as earth electrode and 15mm dia protection pipe complete all as specified and as directed.
Dismantling / Taking down of cross arms of channel or sections etc complete setting aside for reuse (serviceable one) or removing from site of work complete all as specified and as directed.
M & L cross arms, bracings, supports clamps, stay clamps etc fabricated from structural steel sections including nuts, bolts, washers welding bending cold or hot drilling holes for bolts any size of shape and including hooks & clamps for aerial bunch cable as indicated and directed and inclusive of 2 coats of aluminium painting over a coat of red oxide primer complete all as specified and as directed.
Dismantling / Taking down old unsv stay assembly complete all as specified and as directed.
M & L stay assembly with accessories as shown in Elect plate No- 01 of MES schedule Part-I complete with diameter of rod 16 mm, complete all as specified and as directed. (Note - Loop type insulator , stay clamps , excavation and concrete will be measured and paid separately.)
Supply & Fixing in replacement loop type insulator vitreous porcelain white, brown, or green of size 65 X 90 mm clearance of hole 16 mm.
M&L for painting of steel tubular pole of any size , vertical complete with cross arms with one coat of aluminium paint after cleaning and preparation of surfaces of poles, cross arms, painting 30 cm wide Yellow and black strip on poles up to 1.5 mtr high above coping level and numbering of size 70mmx40mm by using stencil to the pole with black synthetic enemal paint (1st grade ) complete all as specified and as directed.
Restringing of existing LT overhead line including removing the existing binding wire and rebinding with new binding wire after tightning of overhead lines including disconnecting existing jumpher and connections and reconnecting after tightning of conductor incl replacement of all jumpers complete all as specified and as directed. (Note - (a) Any run of conductor in between two span in LT lines shall be measured as one lenght for payment purpose. (b) ACSR conductor will be measured and paid separately).
M&L for Repairing of LT panel by means of replace the hinge and locking arrangement of the existing panel, tightening the cable with bus bar by means of suitable lugs, replacement of suitable indicator with colour complete all as specified and as directed.
S & F in repairs MCCB 4 pole 160 Amps, with thermal release range 70-100% and magnetic setting adjustable, breaking capacity 36 KA complete all as specified and as directed.
S & F in replacement of existing type MCCBs of 100 Amps, 415Volt, breaking capacity 25 KA, 4 Pole, complete all as specified and as directed.
M & L Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size, including taking out old unserviceable rusted out danger plate, complete all as specified and as directed.
M & L for DK Thermoplastic cable junction boxes in repairs of make Sintex, product code GSJB-3126, IP 65 of size 270 x 225 x 135mm of metric knockouts for cable entry, weather proof for indoor/outdoor installation with and including glands/insulators and with 4 terminals for terminating one incoming and outgoing UG cable of size 10/16 sqmm 2/4 core and fixed to wall/Steel Poles by means of suitable size of clamps with nut and bolts complete including taking down existing existing junction box complete all as specified and as directed. (NOTE: Make of Junction box shall be Sintex/Hensel or equivalent as approved by GE)
S&F in repairs LED street light fittings, IP-66, 72 watt including bracket made out of 40 mm dia light grade GI pipe not less than 1.2 mtr long bend to shape duly fixed with MS clamps of 3mm thick, nut, bolts etc complete fixed to steel tabular poles including electrical connection complete with 3 core 1.5 Sqmm PVC sheathed stranded copper wire ISI marked from junction box to fitting complete all as specified and as directed. Make : Crompton, Cat part No "LSTP-72-CDL" or equivalent model of Philips/Bajaj.
Supply and Laying in replacement u/s cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables of Size of 16 Sqmm 4 core (heavy duty) 1100 Volts grade with stranded aluminium conductor on wall/in Trench with the help of shadel of following size as required at site, complete all as specified and as directed. Make : MESCAB/HAVELLS/POLYCAB/GLOSTER/KEI
Taking down unserviceable fitting of any type or any wattage i.e. 100/90/80/72/60/45/30/25 Watt energy efficient street light fitting, identifying the fault, repair / replacement of old unserviceable accessories with new accessories, reassembling and make the street light fitting functional and refixing in existing location including three core copper PVC insulated conductor of 1 sqmm size (nominal area) of suitable length to connect the lumaniries to overhead conductor / existing lines complete all as specified and as directed . (Note : Spares part/material required for repair to street light fitting shall be measued and paid separtely under relevent items as supply only).
Supply only 1100 volts grade heavy duty cable PVC insulated and FR PVC rounded sheathed, copper conductor (flexible) industrial cable, conforming IS: 694 of size 1.5 sqmm 3 core laid along pole from junction box to light fitting complete all as specified and as directed.
Supply only in replacement of street light driver of 25 watt to 50 watt, 230V,50Hz suitable for operation over voltage range of 140V to 270V by emoving from existing position complete all as specified and as direcred.
Supply only in replacement of street light driver of 55 watt to 100 watt, 230V,50Hz suitable for operation over voltage range of 140V to 270V by emoving from existing position complete all as specified and as directed.
M & L in for DK Thermoplastic cable junction boxes IP 65 with of size 185 x 165 x 60 of metric knockouts for cable entry, weather proof for outdoor installation and including glands and with 4 terminals for terminating one incoming and outgoing UG cable of size 10/16 sqmm 2/4 core and fixed to the PSC/Steel Poles by means of suitable size of clamps with nut and bolts and incl provn for fixing 01 No. of single pole MCBs 6-32 amps,10KA and MCB TP 6-32 amps, 10 KA, ‘C’ series 01 No inside the box incl taking down old u/s junction box complete all as specified and as directed. Make : Sintex/Hensal or equivalent approved by GE.
S&F Busbar Chambers 4 way 100 Amps outdoor type (IP 65/66) pole mounted including provision of fixing on pole by means of suitable size of clamps with nut and bolts including necessary connection including taking down of old u/s bus bar complete all as specified and as directed. Make: Havells cat part No IHBC010004 or equivalent make of SMC/Hensel
M&L for painting of steel tubular pole of any size , vertical complete with cross arms with one coat of aluminium paint after cleaning and preparation of surfaces of poles, cross arms, painting 30 cm wide Yellow and black strip on poles up to 1.5 mtr high above coping level and numbering of size 70mmx40mm by using stencil to the pole with black synthetic enemal paint (1st grade ) complete all as specified and as directed.
M&L for Cleaning of semi under ground water sumps of 10,000 Glns capacity by removing residual/balance water, taking out solid residual loose dirt, scales, mud, fungus, vegetation growth, scrubbing the complete inner surface of wall and floor with wire brushes and cleaning with water and again cleaning and washing completely using bleaching powder and fresh water, drying the entire surface and applying two coats of lime wash internally and writing the date of cleaning on external surfaces with thick synthetic enamel paint in bold Capital letters (not exceeding 15 cm high) once in six month complete all as specified and as directed.
All as per item No 149 but 5,000 Gln capacity
M&L for disconnecting existing PVC water tanks of capacity 2000 ltrs, setting aside (or lowering if requried) cleaning and removing all scale & dirt etc., from tanks and mouths of circulating pipes etc., by using bleaching powder and writing/marking MES Number and date of cleaning on external surfaces with thick synthetic enamel paint in bold Capital letters (not exceeding 15 cm high) and hoisting if requried, re-connecting and re-fixing in position complete all as specified and as directed.
All as per Item No 151 but 1000 Ltrs
All as per Item No 151 but 500 Ltrs
M&L for construction of Valve chamber of internal dimension/size 600 x 600 x 600 mm, with 200mm thick pre-cast PCC solid block masonry (made of PCC (1:3:6) type C-1 : using 20mm graded crushed stone aggregate) wall in cement mortar (1:6), with 1.6 mm thick MS sheet cover, fixed with 25x25x6 mm stiffner welded around, welded over angle iron frame of size 65 x 65 x 6 mm with locking arrangements including applying two coats of first grade synthetic enamel paint (of approved tint) over a coat of red oxide primer on steel surfaces, necessary earth work in soft/loose soil with and including 100 mm thick PCC (1:3:6) Type C-2 (using 40mm graded stone aggregete) as in foundation, 50 mm thick PCC (1:2:4),Type B-1 (using 20mm graded stone agregate) as in coping on top including rendering 10mm thick in cement mortar 1:6, finished even and fair and applying three coats of white wash on exposed surfaces, complete including demolition of existing unserviceable valve chamer complete all as specified and as directed. (The chamber shall be 150 mm above the ground level).
S&F gun metal, globe or gate valves of 50 mm bore dia, with iron wheel head, screwed both ends for iron pipes and fixed including taking down old unserviceable one.
All as per Item No 155 but 40 mm bore dia
All as per Item No 155 but 25 mm bore dia
All as per Item No 155 but 20 mm bore dia
All as per Item No 155 but 15 mm bore dia
Supply only Aquafit brand Calcium Hypo Chlorite 65% to 70% Chlorine content in grangular and tablet form complete all as specified and as directed. Make : Purichlor or equivalent makes as approved.
Dismantling of old unserviceable tank of any make existing PVC water tanks 2000 Ltrs all as specified and as directed.
All as per item No 161 but 1000 Ltrs
All as per item No 161 but 500 Ltrs
S&F Rotational moulded polythene water storage tank ( cylindrical vertical with closed tops ) hoisted and fixed in position of 2000 Ltrs capacity, all as specified and as directed.
All as per item No 164 but 1000 Ltrs
All as per item No 164 but 500 Ltrs
Taking up or down existing galvanized iron water tubing and connections, carefully without any damage from the trenches, ground or walls of the 50 mm bore sizes, including cleaning for re-fixing, complete all as specified and as directed.(Excavation and earth work measured and paid separately)
All as per item No 167 but 40 mm bore
All as per item No 167 but 25 mm bore
All as per item No 167 but 20 mm bore
S&F in replacement steel water tubing of the 50 mm bore sizes, ‘Medium grade’, galvanized, with all fittings; laid in trenches or on ground, complete all as specified and as directed.(Excavation and earth work measured and paid separately)
All as per item No 171 but 40 mm bore
All as per item No 171 but 25 mm bore
All as per item No 171 but 20 mm bore
Re-fixing the old steel tubing and connections in new or old position in trenches, ground, of 50 mm bore sizes
All as per item No 175 but 40 mm bore
All as per item No 175 but 25 mm bore
All as per item No 175 but 20 mm bore
M & L for painting on old surfaces with two coats of synthetic enamelled paint on a coat of red oxide primer complete all as specified and as directed.
S&F PVC cover for polythene water storage tanks of 2000 Ltrs capacity of different make like sintex/polycon or eqvli etc, with suitable nuts, bolts and locking arrangement incl removing the broken unserviceable one complete all as specified and as directed.
All as per item No 180 but 1000 Ltrs
All as per item No 180 but 500 Ltrs
M&L for cutting existing steel tubing for alterations or additions (Each cut measured) and inserting new Tee, bend, elbow etc for Upto 40 to 50 mm dia GI tubing complete all as specified and as directed.
All as per item No 183 but Upto 25mm dia
S&F PVC float valve, high pressure with polythene float and fly nut complete screwed for PVC pipe and fixed in25 mm dia bore pipe incl taking down old u/s one, complete all as specified and as directed. Make : PRAYAG or equivalent.
All as per item No 185 but 20 mm dia
All as per item No 185 but 15 mm dia
M&L for construction of angle iron stage made out of MS equal angle of suitable size of thick complete including fabricated work complete all as specified and as directed.
M & L for painting on new surfaces with two coats of synthetic enamelled paint on a coat of red oxide primer complete all as specified and as directed.
Cutting of PCC making holes inserting GI pipe and making good disturbed surface, complete all as specified and as directed.
S&F Butter Fly Valve lever operated conforming to IS 13095 of size upto 40/50 mm dia PN 1.6, connected with two end flanges suitable for connecting with GI Pipe medium grade, nut-bolts etc including taking down old unserviceable one complete with flanges nut - bolts etc complete all as specified and as directed.
M&L for Collect sample of raw water from any location at Sherwani mil stn, Chemical laboratory testing of water from local PHE department and submit the report to concerned JE (E/M) complete all as specified and as directed.
Repair to u/s sluive valve 80mm bore by dimantling all the parts after removing from site and replacement of all parts like spindle, GM lock, nuts, gasket, nuts both and washer etc to make fully serviceable and refixing the same in original position including connection complete all as specified and as directed. (Note :Brass spindle will be measured and paid separatley)
All as per item No 193 but for 50mm bore complete all as specified and as directed.
Supply only brass spindle suitable for 80mm bore sluice valve complete all as specified and as directed.
All as per item No 195 but for 50mm bore complete all as specified and as directed.
Painting of GI pipes of any size with two coats of synthetic enamel paint after scratching the existing paint properly and cleaning the surface properly complete all as specified and as directed.
Note: In case doubling/duplicancy of BOQ items , the lowest quoted rate shall be applicable for payment.
DEDUCTED AMOUNT OF SCHEDULE OF CREDIT
MS BRAHMA CONSTRUCTION
DEEP CHANDRA JOSHI
M/S JAYSHREE CONCERN
HEM RAJ GURUNG
G K SUTHAR
ANTHONY PRADHAN
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .