Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹94.0 LAccepted-AOC H NO 959 SECTOR 3 ROHTAK | L1 | Accepted-AOC accepted | |
| 2 | L2₹95.8 L+₹1.8 L (1.96%)Rejected-AOC H NO 787 22 JHANG COLONY ROHTAK 124001 | ROHTAK | HARYANA | 124001 | L2 | Rejected-AOC rejected |
Tender Value
₹97.4 L
EMD Value
₹1.9 L
Closing Date
22 Jul 2024, 5:00 pmClosed
VISHWNATH KHICHI
ED - Rohtak
Pdg. DG Set and substation for lifts and LT connection for community Centre
2024_HRY_390021_1
20243A8D23C0 E170 4E67 9F89 9E7D57AF0339667BAR
Open Tender
Electrical Works
Works
120 days
Rohtak
Technical documents as per approved DNIT conditions.
3 documents required · 3 mandatory
₹5,000
₹1.9 L
Yes
21 Feb 2025
12 Jul 2024
23 Jul 2024
12 Jul 2024
22 Jul 2024
12 Jul 2024
Amount
HSR Items
[23.22.1.12]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.12. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. 4 pole MCCB 300 to 400 amp , 50 KA
[23.22.1.13]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.13. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. 4 pole MCCB 600 to 800 Amp , 50 KA
[23.22.1.3]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.3. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. TRIPLE POLE MCCB 16 to 100 Amp, 25 KA
[23.22.1.5]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.5. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. TRIPLE POLE MCCB 200 to 250 Amp, 25 KA
[23.22.2.1]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 2.1. MCCB Enclosure made of Sheet Steel suitable for mounting MCCB of following ratings MCCB up to 125 A FP
[23.23.7.1]MISCELLANEOUS 7.1. Supply and erection of cable tray cover made of 1.25 mm thick GI sheet as required including erection of the same on existing cable tray with necessary fixture and other material required to complete the job in all respect up to the entire satisfaction of Engineer-in Charge of the work. GI cable tray Cover , suitable for cable tray of 100 X 50 X 2 mm
[23.23.7.3]MISCELLANEOUS 7.3. Supply and erection of cable tray cover made of 1.25 mm thick GI sheet as required including erection of the same on existing cable tray with necessary fixture and other material required to complete the job in all respect up to the entire satisfaction of Engineer-in Charge of the work. GI cable tray Cover , suitable for cable tray of 375 X 50 X 2 mm metre
[24.1.1]EARTHING AND LIGHTENING ARRESTOR 1. Earthing with GL earth pipe 4.5 m long and 40 mm dia with masonry enclosures on the top etc. (but without charcoal or coke and salt) as required.
[24.1.10]EARTHING AND LIGHTENING ARRESTOR 10. Providing and fixing 25 mm x 5mm copper strip on surface or in recess for connections etc. as required with all labour and material.
[24.1.2]EARTHING AND LIGHTENING ARRESTOR 2. Extra for using salt and char coal/coke for pipe earth electrode as required.
[24.1.4]EARTHING AND LIGHTENING ARRESTOR 4. Earthing with tinned copper earth plate 600mmx600mmx3mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) etc. complete as required.
[24.1.5]EARTHING AND LIGHTENING ARRESTOR 5. Extra for charcoal or coke and salt for G.I. plate or copper plate earth electrode.
[24.1.7]EARTHING AND LIGHTENING ARRESTOR 7. Supplying and laying 25mm x 3 mm G.I. strip in 40 mm dia,GI pipe as/from earth electrode including soldering etc. as required.
[24.1.9]EARTHING AND LIGHTENING ARRESTOR 9. Providing and fixing 25 mm x5 mm copper strip in 40 mm dia G.I. pipe from earth electrode as required.
[24.2.10]LT CABLE 10. Supply and erection of cable route marker made of 50 cm long 10 mm dia M.S. Rod welded/riveted at the top with 10 cm dia 3 mm thick MS plate inscribed with cable word on it, having a cross arm 30 cm long of the same dia welded at the bottom, in exiting trench 45 cm below ground level.
[24.2.7.4]LT CABLE 7.4. Supply and erection of suitable compression type brass cable glands for underground Cable :- 70 sqmm to 95 sqmm Cable 3 to 3½ Core
[24.2.7.5]LT CABLE 7.5. Supply and erection of suitable compression type brass cable glands for underground Cable :- 120 sqmm to 185 sqmm Cable 3 to 32 Core
[24.2.7.6]LT CABLE 7.6. Supply and erection of suitable compression type brass cable glands for underground Cable :- 240 sqmm to Cable 3 to 32 Core
[24.2.8.10]LT CABLE 8.10. Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work. 120 sqmm
[24.2.8.11]LT CABLE 8.11. Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work. 150 sqmm
[24.2.8.13]LT CABLE 8.13. Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work. 240 sqmm
[24.2.8.6]LT CABLE 8.6. Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work. 35 sqmm
[24.2.8.8]LT CABLE 8.8. Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work. 70 sqmm
[24.3.1.1]HT CABLE 1.1. Laying and erection of XLPE (E)II kv HT aluminium conductor armoured cable 1 metre below ground level with sand & bricks with all labour and material including digging and refilling of trench as required up to 120 sqmm 3 core XLPE Cable
[24.3.3.1]HT CABLE 3.1. Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :70 to 120 sqmm
[24.3.4.1]HT CABLE 4.1. Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :70 to 120 sqmm
[24.5.2.3]MISCELLANEOUS ITEMS 2.3. S/E mark double walled corrugated (DWC) HDPE, pipe 10 Kg/Cm2 ,laid 0.75 Metre below ground level including digging and refilling of earth including cost of suitable size socket/coupler for HDPE pipe including the cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in charge of the work. DWC/HDPE pipe 63/50 mm outer dia/inner dia
[24.5.2.7]MISCELLANEOUS ITEMS 2.7. S/E mark double walled corrugated (DWC) HDPE, pipe 10 Kg/Cm2 ,laid 0.75 Metre below ground level including digging and refilling of earth including cost of suitable size socket/coupler for HDPE pipe including the cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in charge of the work. DWC/HDPE pipe 180/150 mm outer dia/ inner dia
[24.7.5]RCC FOUNDATIONS FOR DG SET 5. 250 KVA DG Set
NS Items
Supply of 250 kVA, Prime Duty CPCB4 plus (as per ISO3046),415 Volt, Radiator Cooled, Silent Type with acoustic enclosure, Diesel generating set having having 6 cylinders in line arrangement and 310 BHP@1500 rpm along with base frame, Alternator (capable of delivering 200kW output @ 0.8 power factor, 50 Hz, 415 V, Class H with temp rise limited to class H at 40 deg C ambient), Static Excitation System, Lub Oil System, Electronic Governor (Class G3 Governing) including Microprocessor based Gen set Controller, AVM pads, 02 Nos 12 volt Lead Acid type Battery with Copper leads suitable for 3 consecutive starts, Silencer, inbuilt Day oil tank of 400 litres app. capacity, terminal arrangements including cable termination box suitable for terminating of recommended size Al cable with all other associated items/accessories complete in all respect. Make: Kirloskar/Ruston/Cumins
SETC of 11 KV indoor HT metering panel complete with CTs PTs cubical and electronics meter with accuracy class 0.5 as per requirement /approved by HVPN department complete in all respect.
SandE of fire extinguisher ISI mark CO2 type of 4.5 Kg capacity as per IS 7285 duly erected/hung on wall with hooks with all labour and petty material required to complete the job in all respect upto the entire satisfaction of Engineer-in-charge of the work.
Supply and Erection of mild steel bucket stand suitable for 6 Nos. fire buckets, with buckets including the cost of welding and painting of complete stand will one coat of red oxide and 2 coats of approved paint of red colour with all labour and material required to complete the job in all respect up to the entire Satisfaction engineer in charge of the work (size 6`x4` made of GI pipe 32mm dia).
SandE of rubber mat of size 1Mx2M212mm thick suitable for 11 KV ISI marked complete in all respect upto the entire satisfaction of Engineer-in-charge of the work.
SETC of AMF panel suitable for 250 KVA DG set with ATS 400 amp Four pole, volt meter, Amp meter, CTs 400/5 amp, Phase indicator, battery charger 24 VDC 10 amp. And all types of LED indicators complete in all respect upto the entire satisfaction of Engineer-in-charge of the work.
Supply, installation, testing and commissioning of 11kV compact secondary substation outdoor type designed for natural cooling (K-10 class), having type tested equipments comprising of dry type CRT transformer and SF-6 insulated compact switchgear enclosed in robotically sealed stainless steel tank, low-voltage switchboard, interconnection between HT switchgear to transformer using Aluminium conductor Cables and transformer to LT-switchgear using Copper busbars, factory built ready for connection type, internal GI earthing provided complete with other associated equipments etc. complete as required conforming to IEC 62271-202 only and relevant IS specifications, as regards to design, manufacturing, type-testing, routine-testing and general operator safety precautions (IAC AB 20kA/1-sec). The enclosure shall have modular construction using G.I. Sheet steel and shall be powder-coated from exterior, with all major equipment inside common enclosure. The Transformer compartment will have IP-23D ingress protection, whereas the transformer used shall be Cast Resin Type specially designed for low losses as per losses defined. RMU, LT panel as well as LT switchgear, Vacuum Interrupter shall be of same make as PSS OEM to ensure life cycle optimization . Also, System Integrator/Licencse partner make CSS shall not be acceptable . ( Make: ABB/Schneider/Siemens) The compact substation shall primarily consist of : `A) HT SWITCHGEAR having 01 no FIxed-Type Load break Switches and 02 nos. Fixed-Type VCB (feeding into Transformer), enclosed in common tank( 2.5 mm thick ), made of robotically welded non-magnetic/non-ferritic Stainless Steel sheets, filled with SF6 gas acting as an excellent insulating medium, IP-67 tank design having leakage rate less than 0.1% per-annum, whereas it shall be Arc-Proof design with Internal Arc criteria of 20kA/1-sec individually. The Compact Switchgear shall be a front-flushed design with integrated spring-charging handle and associated Capacitive Voltage LED Indicators for arc-proof cable box, with associated Terminal Protector boots for mounting on site-replaceable cable bushings and front-facia semaphore mechanical indication for breaker ON/OFF/EARTH and associated Fault Passage Indicator for incoming Load break switch. The breaker will be provided with integrated Self-Powered 3OC plus 1EF relay with Low and High set for Over current and Earth Fault. Relay should have facility to display the maximum loaded phase current also.Relay shall record minimum 5 fault records with time stamping, and shall be operated via Resin cast RingCore Protection CTs of suitable ratio an burden.( Make: ABB/Schneider/Siemens)
11kV 630Amps 21KA/3 sec. Non-Extensible Ring Main Unit Compact switchgear (CVV)consisting of one Number Fixed manual Load break Switches and Two numbers Fixed Manual Vacuum Circuit Breaker in SF6 insulated stainless steel enclosure with series trip, self powered microprocessor based numerical over current and earth fault relay protection. Interconnection between HT Switchgear and primary of transformer shall be done through 1C x 3R x 95 sq.mm Aluminium Unarmoured XLPE cable (Make: ABB India Limited) 1 No. Each VCB consists of Relay of Ashida make of Model No: ADR 241S with communication port 1 No. Each VCB consists of Protection CT of 40/1A 2.5VA 5P10. 1 set Manometer 1 No. Fault passage indicator for incoming Load break switch only 1 No. Incoming and Outgoing Load break Switches suitable for Termination of 3C x 300 sq.mm AL cable only, Incoming Cable termination kits shall be in purchaser scope of supply only. Note : RMU, LT panel, Vacuum Interrupter shall be of same make as PSS OEM to ensure life cycle optimization . Also, System Integrator/Licencse partner make CSS shall not be acceptable . B TRANSFORMER 400KVA 11KV/433V Dyn11 Copper Wounded Cast Resin Dry Type Transformer with Off load tap links of plus 5% to -5% @2.5% with WTI scanner. Class of Insulation: H, Temperature rise limits 115 deg.C over an ambient of 50 degrees. Losses (Subject to IS Tol.) - NLL/LL - 1450/4750Watts and Impedance of 4.5%(Subject to IS Tol.) with WTI scanner.(Make-ABB India Limited)Hitachi)) 1 No. Winding Temperature Indicator with 1 alarm and trip contact 1 No. Surge arrestor in the HV side 1 set C LVS PANEL 630AMPS Copper BUSBAR (100% FOR PHASES AND 50% FOR NEUTRAL) - CURRENT DENSITY OF Copper 1.4 A/sq.mm, LT panel made up of 1.5/2 mm thick CRCA sheet INCOMER FROM TRANSFORMER 630 Amps 433V 4P 50Hz 50 KA Fixed Manual Type Moulded Case Circuit Breaker (MCCB) with Thermal Magnetic (TMA) based release for Overload , Shortcircuit Fault protection (Make: ABB India Ltd) 1 No. RYB, ON/OFF Trip Indication 1 Set
Multifunction meter of class 1 accuracy (Make: Rishabh/Conserve/EL measure) 1 No. 250 Amps 433V 4P 50Hz 50 KA Fixed Manual Type Moulded Case Circuit Breaker (MCCB) with Microprocessor based release for Overload , Shortcircuit and Earth Fault protection (Make: ABB India Ltd) 1 No 200 Amps 433V 4P 50Hz 35 KA Fixed Manual Type Moulded Case Circuit Breaker (MCCB) with Microprocessor based release for Overload , Shortcircuit and Earth Fault protection (Make: ABB India Ltd) 2 Nos APFC PANEL (135KVAR) 135KVAR Automatic power factor correction panel in 8 steps (25 KVAR x 4 plus 10kVAR x 3 plus 5kVAR x 1) consisting of following 400Amps 433V 3P 36KA Manual Fixed Type Moulded Case Circuit Breaker (MCCB) with Thermal mangetic based release for over current and magnetic short circuit as incomer to APFC Panel (with TMA release) (Make: ABB India Ltd.) 1 No. APFC RVC Relay for 8 steps (Make: ABB India Ltd.) 1 No. 25 KVAR metallized polypropylene capacitor bank (Make: ABB India Ltd.) 4 Nos Capacitor duty contactor for switching on and switching off 25 KVAR bank (Make: ABB India Ltd.) 4 Nos 63Amps 433V 3P 10KA Miniature Circuit Breaker for 25kVAR capacitor protection (Make: ABB India Ltd/HPL.) 4 Nos 10 KVAR metallized polypropylene capacitor bank (Make: ABB India Ltd.) 3 Nos Capacitor duty contactor for switching on and switching off 10 KVAR bank (Make: ABB India Ltd.) 3 Nos 32Amps 433V 3P 10KA Miniature Circuit Breaker for 10kVAR capacitor protection (Make: ABB India Ltd/HPL.) 3 Nos 5 KVAR metallized polypropylene capacitor bank (Make: ABB India Ltd.) 1 Nos Capacitor duty contactor for switching on and switching off 5 KVAR bank (Make: ABB India Ltd.) 1 Nos 16 Amps 433V 3P 10KA Miniature Circuit Breaker for 5kVAR capacitor protection (Make: ABB India Ltd/HPL.)
Supply and erection of 70 sqmm 3.5 core underground Aluminium Conductor armoured cable on surface/cable tray complete in all respect upto the entire satisfaction of Engineer-in-charge of the work. Make: Havells/Polycab/RR
Supply and erection of 150 sqmm 3.5 core underground Aluminium Conductor armoured cable on surface/cable tray complete in all respect upto the entire satisfaction of Engineer-in-charge of the work. Make: Havells/Polycab/RR
Supply and erection of 240 sqmm 3.5 core underground Aluminium Conductor armoured cable on surface/cable tray complete in all respect upto the entire satisfaction of Engineer-in-charge of the work. Make: Havells/Polycab/RR
Janta Electric Store
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .