Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹60.0 LAccepted-AOC A 76 SURENDRA NAGAR ISMAILGANJ FAIZABAD ROAD LUCKNOW UTTAR PRADESH 226016 UDYAM UP 50 0018139 | LUCKNOW | UTTAR PRADESH | 226016 | L1 | Accepted-AOC Lowest bidder accepted | |
| 2 | L2₹62.8 L+₹2.8 L (4.59%)Rejected-Finance 4 R G BARUAH ROAD SUNDARPUR GUWAHATI KAMRUP ASSAM 781005 | KAMRUP METRO | ASSAM | 781005 | L2 | Rejected-Finance Lowest bidder accepted | |
| 3 | L3₹63.3 L+₹3.3 L (5.56%)Rejected-Finance KARNATAKA | RAICHUR | KARNATAKA | 584123 | L3 | Rejected-Finance Lowest bidder accepted | |
| 4 | L4₹68.6 L+₹8.6 L (14.3%)Rejected-Finance 107 265 BRAHAMA NAGAR KANPUR UP 208012 | KANPUR NAGAR | UTTAR PRADESH | 208012 | L4 | Rejected-Finance Lowest bidder accepted | |
| 5 | L5₹79.0 L+₹19.0 L (31.7%)Rejected-Finance A 42 JAI AMBEY NAGAR TONK ROAD JAIPUR RAJASTHAN 302018 | JAIPUR | RAJASTHAN | 302018 | L5 | Rejected-Finance Lowest bidder accepted |
Tender Value
₹62.8 L
Closing Date
21 Jan 2022, 6:00 pmClosed
Asstt. GM (Engg.-Elect.)
Asstt. GM (Engg.-Elect.), Airports Authority of India, Operational Offices, M.P. Airport, Udaipur 313022 (Rajasthan)
Provision of online UPS for CCRs at Maharana Pratap Airport, Udaipur
2021_AAI_100002_1
AAI/UDR/ENGG(E)/UPS/2021-22
Open Tender
Electrical Works
Item Rate
120 days
M.P. Airport
As per WNIT
20 documents required · 20 mandatory
₹1,180
Exempted
5 Feb 2022
30 Dec 2021
24 Jan 2022
31 Dec 2021
21 Jan 2022
31 Dec 2021
31 Dec 2021 - 17 Jan 2022
Amount
Design, supply, installation, connection, testing and commissioning of 2x160 KVA capacity 3 phase input 3 phase output true online UPS system with PWM technology, double conversion parallel topology, isolating transformer, having mimic display, alarm and warning system, control and monitoring, protection, bypass facility etc. and with 12V SMF battery bank suitable to provide a minimum 30 minutes back up at the rated full load for individual UPS. The UPS system shall be capable to cater the 100% unbalance load of Airfiled lighting through constant current regulator(CCR). The work includes MS powder coated battery rack, connectors, batteries interconnection, cabling between battery bank and UPS with required size insulated copper conductor, termination as per site condition etc. complete as required and as per technical specifications.
Supply of 5 C x 120 sqmm XLPE insulated and PVC sheathed, 1.1 KV grade copper conductor unarmored cable conforming to IS: 7098 part 1 with upto date amendements and conforming to technical specifications.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of 5 core 120 sqmm size in the existing RCC/ HUME/ METAL pipe OR in the existing masonry open duct OR on wall surface OR on cable tray etc. as required as per site conditions.
Supplying and making end termination with gland and copper lugs for 5 core 120 sqmm size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 kV grade as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Repalcement of MCCB in existing LT panel with required modification in panel, provision of bus connection, wiring, testing and commissioning etc. complete as required as per actual site conditions and including supply and fixing of following accessories. 1 Nos. 400 A 4P MCCB (Ics=Icu=35 KA) 1 No. of breaker 'ON/OFF' indicating lamps.
Disconnection, shifting, end termination, testing and commissioning of following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade from one panel to another in CCR hall. The work includes supply of required aluminium lugs etc. complete as required.
3.5 Core 120 sqmm
3.5 Core 50 sqmm
All inclusive comprehensive maintenance from OEM / authorised service dealer of OEM for 2X160 KVA UPS system for five year after defect liability period of two year (excluding replacement of batteries) complete as required and as per special conditions of contract.
First year after DLP (3% SITC cost including frieght, insurance, transportation etc.)
Second year after DLP (3% commulative enhancement on first year cost)
Third year after DLP (4% commulative enhancement on second year cost)
Fourth year after DLP (4% commulative enhancement on third year cost)
Fifth year after DLP (4% commulative enhancement on forth year cost)
DS Systems Pvt Ltd
ECS ENGINEERING PVT LTD
Awasthi Electric Works
RS Power Systems Pvt. Ltd.
stage.html
html • 0.06 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .