XEN MECHANICAL AND HOSPITAL DIVISION JAMMU
XEN MECHANICAL AND HOSPITAL DIVISION JAMMU
DESIGN, SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF G4 CATEGORYA PASSENGER LIFT01 NO, POWER CABLE, SERVO VOLTAGE STABLIZER, EARTING AND ALLIED WORKS TO BE INSTALLED AT NEWLY CONSTRUCTED CAPF BUILDING AT PCR, JAMMU
2026_PWDJK_301805_1
MHDJ/e-NIT 341 of 2025-26
Open Tender
Machineries/ Mechanical Engg Items
Turn-key
90 days
PCR
as per e nit
2 documents required · 2 mandatory
₹1,000
XEN MECHANICAL AND HOSPITAL DIVISION JAMMU
₹44,000
12 Feb 2026
30 Jan 2026
19 Feb 2026
30 Jan 2026
18 Feb 2026
6 Feb 2026
30 Jan 2026 - 11 Feb 2026
Power Cable: Providing, Laying, Clamping and Thimbling of new minimum 50sq mmx4 Core, PVC inner-sheathed, XLPE insulated aluminium armoured cable of Havells/Gloster/KEI/Polycab make from main electric panel to Servo and from servo to panel of 01No lift. Job includes proper laying and MS clamping of the cable along the walls & cable tray, thimbling the end terminals of the cable with thimbles and crimping them properly with the crimping tool and proper insulation. Complete job in all respects including cost of material, carriage, Skilled/unskilled labour charges, taxes etc.
Servo: Supply, installation, testing and commissioning of minimum 25KVA Servo Motor controlled oil cooled digital microcontrolled Automatic Voltage Stabilizer to operate on un balanced 3 Phase load (Transformer oil to be cooling medium and shall be ISI marked IS-335 with latest amendments) and suitable to operate on unbalanced input phase voltage of 120 to 280 volts(phase to neutral), input voltage range 210-480V(phase to phase) and delivering voltage of 415 ± 1 %, 3 Phase, 50 Hz ± 3 % AC power supply. The stabilizer shall be copper wound in sheet steel case, duly painted and filled with transformer oil. The voltage stabilizer should have safety of single phase preventer and phase reversal. The voltage stabilizer should be provided with 3 phase Aluminium bus bar for connection of lifts, MCCB of minimum rating 100A-4P-50kA and on load change over switch of minimum 100A, 4P required to by-pass the voltage stabilizer. Complete job in all respects including cost of material, carriage, Skilled/unskilled labour charges, taxes etc.
Earthing:- Suitable chemical earthing to the lift motor, panel & servo by way of excavation of pit of proper size upto a depth of 03 meter, copper electrode in hard and soft soil followed by filling of required quantity of earthing chemical for each electrode and connection with GI strips. Job includes filling of pit with excavated soil and fitment of copper electrode with copper strips. Complete job in all respects including cost of material, carriage, Skilled/unskilled labour charges, taxes etc.
Lighting & Electric work: Providing and fitting of 15W LED bulb with 6amp socket and 2.5sqmm wire for connection through pvc pipe/batten at every 10 ft throughout the shaft of one lifts. Complete job in all respects including cost of material, carriage, Skilled/unskilled labour charges, taxes etc.
Providing and fitting of 4pole ELCB & MCB of suitable capacity as per recommendation of Lift OEM, with box. Complete job in all respects, wiring, thimbling including cost of material, carriage, Skilled/unskilled labour charges, taxes etc. Complete job in all respects including cost of material, carriage, Skilled/unskilled labour charges, taxes etc.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.91 MB
BOQ_979286.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .