Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 8TH FLOOR BRIGADE OPUS 70 401 KODIGEHALLI MAIN ROAD BENGALURU 560092 | BENGALURU | BENGALURU | KARNATAKA | 560092 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
₹29.6 L
EMD Value
₹45,000
Closing Date
27 Dec 2021, 4:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Superintending Engineer
Office of S.E. MMC-II, ATP Anpara
Supply, erection, testing and commissioning of Event Logger for the switchyard of 2X500 MW, BTPS, Anpara.
2021_RVUNL_611579_1
320/PD-III/BTPS/2021-22/CF-967
Open Tender
Electrical Work/ Equipment
Fixed-rate
365 days
ANPARA B THERMAL POWER PROJECT
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
DEPUTY CAO CFA AND BO BTPS ANPARA
₹45,000
4 Mar 2022
16 Aug 2021
28 Dec 2021
16 Aug 2021
27 Dec 2021
16 Aug 2021
120 days
Supply erection testing & commissioning of event logger compatible to IEC- 61850 suitable for 1000 Digital Events in 400 Kv/ 132 Kv switchyard, 2X500 MW, BTPS, Anpara per set comprises of 5X C264 in 80 TE case suitable for 1000 events (4U, 19” rack (80 TE), 110/ 220 V DC Base Rack. with plain front face, function keys, indicators, power supply, CPU with access to legacy link RS 485 towards substation level
Supply of Engineering workstation, 24” TFT monitor windows 10 OS + Software CMT for Engineering Workstation + A4 Laser Printer= Inverter 1KVA (ALAN make) + Along with 1X Unmanaged Ethernet Switch and necessary CAT 5 Cable
Erection, Testing & commissioning of the above offered event loggers
Supply of simplex type panel for mounting of event logger
Control Cable for status from control and relay panel to event logger per bay distance from existing panel to event logger panel is 40 meter (control panel and relay panel* 24 bays of 400 KV bays + control panel and relay panel* 17 bays of 132 KV bays) Considering control panel to event logger is 20 meters Considering relay panel to event logger is 20 meters Total distance from control panel and relay panel to event logger is 40 meters.
K2S Corporation
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .