thyssenkrupp Uhde India Pvt Ltd Vikhroli Mumbai India
ELECTRICAL WORKS FOR MS BLOCK UNIT AT NREP
2025_NRL_849552_1
TK-1P22A-MP-RFQ-0065
Open Tender
Electrical Works
450 days
Numaligarh Refinary Limited Assam
As per Tender
9 documents required · 9 mandatory
₹0
₹39.5 L
Yes
ONLINE
8 Jul 2025
18 Feb 2025
9 Apr 2025
18 Feb 2025
8 Apr 2025
11 Mar 2025
18 Feb 2025 - 3 Mar 2025
4 Mar 2025
Amount
GENERAL NOTES This document shall be read in conjunction with doc. "SCOPE OF SUPPLY-ELECTRICAL" DOC ID TK-1P22A-EL-SPE-0022. Technical Specification for the equipment / material to be supplied by CONTRACTOR is included therein. For 'Limit of Variation' in the rates / quantities / total value of work, please refer 'SPECIAL CONDITIONS OF CONTRACT'. Refer the document 'MASTER SUPPLIER LIST' for the makes of equipment / material to be supplied by CONTRACTOR. For all the equipment (suitable for Explosive Atmospheres) to be supplied by CONTRACTOR, relevant certification from applicable recognised approving authority shall be provided. For CONTRACTOR supplied items mentioned below, procurement / supply clearance for the items shall be given to CONTRACTOR, in lots as per Project requirement. Subsequent to the receipt of procurement / supply clearance, CONTRACTOR may initiate the required action in this regard. CONTRACTOR should read entire specification to understand in totality the scope of supply and Installation. Every line item for Supplies and Installation should be read along with the respective Installation standard / hook up drawings related to that specific line item to understand the scope of supply and Installation in totality. Any miss outs in supply scope in this regard by the CONTRACTOR shall not be entertained. Scope shall also include Packing, forwarding and transport to site, unloading and storage in Contractor's warehouse. All Required insturctions shall be followed as per manufacterer recommandation for long term storage. The qouted rates shall include charges for Routine and Type testing, TPI, Packing, forwarding, Insurance, Transportation to site, supply of Mandatory spares, commissioning spares and special tools and tackles.
EQUIPMENT
LV PANELS (WALL / CONCRETE / STEEL STRUCTURE MOUNTED)
LDB / ELDB / DCLDB/ PDB (Industrial type ) Supply of LDB / ELDB / DCLDB/ PDB Industrial type ) as per Technical specification for Industrial Equipment (Doc. no.TK-1P22A-EL-SPE-0074 )
LDB / ELDB Lighting Distribution Board / Emergency Sub Lighting Distribution Board
DCLDB ( Critical Lighting Distribution Board)
PDB (Short time current rating : 9 kA for 1 sec) Auxiliary Power Distribution Board
PDB (Short time current rating : 20 kA for 1 sec) Auxiliary Power Distribution Board
UPSDB (115 VAC) Auxiliary Power Distribution Board
24 Way with ATS
LDB / ELDB / DCLDB/ PDB (For Explosive Atmospheres) Supply of LDB / ELDB / DCLDB/ PDB ( For Explosive Atmospheres ) as per Technical Specification for Flameproof Equipment (Doc. no.TK-1P22A-EL-SPE-0019 )
LDB / ELDB (Gas Group : IIC) Lighting Distribution Board / Emergency Sub Lighting Distribution Board
DCLDB (Gas Group : IIC) Critical Lighting Distribution Board
PDB (Short time current rating : 9 kA for 1 sec) (Gas Group : IIC) Auxiliary Power Distribution Board
NON UPS PDB FOR INSTRUMENTS (125 A, Short time current rating : 20 kA for 1 sec) (Gas Group : IIC)
PDB for Hydro Jet area (400A) (Gas Group : IIC)
LOCAL CONTROL STATIONS (LCS)
Supply of Local Control Stations as per doc. no. TK-1P22A-EL-SPE-0018 (Technical Specification for Local Control Stations)
LCS Industrial type
Type H1 : Industrial type weatherproof : Stop PB (Red) Mushroom type, with stay put feature, with pad locking facility, with 2NO+2NC contacts + ON lamp
LCS for Explosive Atmospheres
Type A3 : Flameproof (Gas Group : IIC) : Start PB (Green); Stop PB (Red) with stay put feature, shrouded type, with pad locking facility & each PB shall have 2NO+2NC contacts
Type B3 : Flameproof (Gas Group : IIC) : Start PB (Green, shrouded type); Stop PB (Red) Mushroom type, with stay put feature, with pad locking facility & each PB shall have 2NO+2NC contacts & Ammeter (1A, MI type)
Type J3 : Flameproof (Gas Group : IIC) : Stop PB (Red), Mushroom type, with stay put feature, with pad locking facility & with 2NO+2NC contacts
Type L4 : Flameproof (Gas Group : IIC) :Trip-Neutral-Close (T-N-C) switch shall be spring return to neutral type from CLOSE position with two contacts each for time stamping & tripping signal. Switch shall be lockable in TRIP position. & Ammeter (1A, MI type) (Configuration: T-N-C SWITCH + AMMETER + RUN INDICATION + TRIP INDICATION)
Type P3 : Flameproof (Gas Group : IIC) :Trip-Neutral-Close (T-N-C) switch shall be spring return to neutral type from CLOSE position with two contacts each for time stamping & tripping signal. Switch shall be lockable in TRIP position & Ammeter (1A, MI type)
ELECTRICAL HEAT TRACING SYSTEM
Supply of Heat Tracing System comprising Power Distribution Board-cum-Control Panel, Heat Tracers and Accessories (Connector, Junction Box, fastening material, etc.), Temp. sensing elements, Thermostats, etc. as per Specification (Doc no. TK-1P22A-EL-SPE-0031) The scope includes design, engineering, manufacturing, inspection and testing at vendor’s works, packing, forwarding, supply to site.
Unit rates for addition/ deletion of following items during detailed engineering.
Self regulating heat tracer
Power Limiting heat tracer
Mineral insulated heat tracer
Power Junction Box
End Junction Box
Multiple entry power connection and tee
Small pipe adaptor
Insulation Entry Kit
Thermostat (with Kit)
CABLES AND WIRES, GLANDING, TERMINATIONS AND CABLE ROUTING SYSTEMS
CABLES AND WIRES Supply of armoured / unarmoured power / control / lighting / earthing . Communication cables of various sizes as per technical specifications attached with the Tender
Earthing cables Supply of MV / LV Cables as per the document attached elsewhere in the tender 650/1100V Al / Cu conductor, PVC insulated, unarmoured earthing cables
1 C x 6 sq.mm Cu Stranded, PVC insulated Green/Yellow cable
1 C x 16 sq.mm Cu Stranded, PVC insulated Green/Yellow cable
1 C x 25 sq.mm Cu Stranded, PVC insulated Green/Yellow cable
1 C x 50 sq.mm Cu Stranded, PVC insulated Green/Yellow cable
1 C x 95 sq.mm Cu Stranded, PVC insulated Green/Yellow cable
1 C x 25 sq.mm Al Stranded, PVC insulated Green/Yellow cable
1 C x 35 sq.mm Al Stranded, PVC insulated Green/Yellow cable
1 C x 50 sq.mm Al Stranded, PVC insulated Green/Yellow cable
1 C x 70 sq.mm Al Stranded, PVC insulated Green/Yellow cable
1 C x 120 sq.mm Al Stranded, PVC insulated Green/Yellow cable
GI Wire ropes
8 mm dia. GI wire rope
10 MM (3/8") DIA G.I WIRE ROPE
16 MM (5/8") DIA G.I WIRE ROPE
Supply of 650V / 1100V (Uo / U) voltage grade, Multistranded Cu conductor, PVC insulated, flexible cable, FRLS
3C x 2.5 sq.mm
Supply of single Core, Annealed Tinned Copper Conductor, cables with Fiber Glass, (Uninyvin, cable size : 1C x 109 sqmm)
Ehernet Cable (UTP CAT6e Cable)
CABLE GLANDING AND TERMINATION (HV)
HV Cable glands Industrial type
HV Cable gland suitable for 6.6 / 6.6 kV (UE) voltage grade, Al/Cu conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY (OD : 68 mm)
1C x 630 sq.mm A2XCEWaY (OD : 70 mm)
HV Cable gland suitable for 33 / 33 kV (UE) voltage grade, Al/Cu conductor, XLPE insulated, screened, armoured power cable
1C x 630 sq.mm A2XCEWaY (OD : 70 mm)
HV Cable glands for Explosive Atmospheres
HV Cable gland suitable for 6.6 / 6.6 kV (UE) voltage grade, Al/Cu conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY (OD : 68 mm)
HV Cable termination kit
HV Cable termination kit Heat shrinkable type (suitable for indoor installation) for 6.6 / 6.6 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY
1C x 630 sq.mm A2XCEFY
HV Cable termination kit Heat shrinkable type (suitable for indoor installation) for 33 / 33 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
1C x 630 sq.mm A2XCEWaY
CABLE GLANDING AND TERMINATION (MV)
MV Cable glands Industrial type
Cable glands suitable for 650 / 1100 V (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), XLPE insulated, screened, armoured power / control / lighting cables Cable Glands shall be of Nickel plated brass material, double compression type with PVC hood.
Cables with OD upto 20 mm.
Cables with OD above 20 mm but upto 30 mm.
Cables with OD above 30 mm but upto 40 mm.
Cables with OD above 40 mm but upto 50 mm
Cables with OD above 50 mm but upto 60 mm.
Cables with OD above 60 mm but upto 80 mm.
Cable glands suitable for 650 / 1100 V (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), XLPE insulated, unarmoured power cables (for battery banks) Cable Glands shall be of Nickel plated brass with PVC hood / Nylon , single compression type .
Cables with OD upto 20 mm.
Cables with OD above 20 mm but upto 30 mm.
MV Cable glands for Explosive Atmospheres
Cable glands suitable for 650 / 1100 V (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), XLPE insulated, screened, armoured power / control / lighting cables Cable Glands shall be of Nickel plated brass material, double compression type with PVC hood.
Cables with OD upto 20 mm.
Cables with OD above 20 mm but upto 30 mm.
Cables with OD above 30 mm but upto 40 mm.
Cables with OD above 40 mm but upto 50 mm
Cables with OD above 50 mm but upto 60 mm.
Cables with OD above 60 mm but upto 80 mm.
MV Cable gland reducers / expanders
MV Cable gland reducers - Industrial type
M20 x 1.5 (Male thread) to M16 x 1.5 (Female thread)
M25 x 1.5 (Male thread) to M20 x 1.5 (Female thread)
M32 x 1.5 (Male thread) to M25 x 1.5 (Female thread)
M50 x 1.5 (Male thread) to M32 x 1.5 (Female thread)
M63 x 1.5 (Male thread) to M50 x 1.5 (Female thread)
M80 x 1.5 (Male thread) to M63 x 1.5 (Female thread)
MV Cable gland expander Industrial type
M16 x 1.5 (Male thread) to M20 x 1.5 (Female thread)
M20 x 1.5 (Male thread) to M25 x 1.5 (Female thread)
M25 x 1.5 (Male thread) to M32 x 1.5 (Female thread)
M32 x 1.5 (Male thread) to M50 x 1.5 (Female thread)
M50 x 1.5 (Male thread) to M63 x 1.5 (Female thread)
M63 x 1.5 (Male thread) to M80 x 1.5 (Female thread)
MV Cable gland reducers for Explosive Atmospheres
M20 x 1.5 (Male thread) to M16 x 1.5 (Female thread)
M25 x 1.5 (Male thread) to M20 x 1.5 (Female thread)
M32 x 1.5 (Male thread) to M25 x 1.5 (Female thread)
M50 x 1.5 (Male thread) to M32 x 1.5 (Female thread)
M63 x 1.5 (Male thread) to M50 x 1.5 (Female thread)
M80 x 1.5 (Male thread) to M63 x 1.5 (Female thread)
LV Cable gland expander for Explosive Atmospheres
M16 x 1.5 (Male thread) to M20 x 1.5 (Female thread)
M20 x 1.5 (Male thread) to M25 x 1.5 (Female thread)
M25 x 1.5 (Male thread) to M32 x 1.5 (Female thread)
M32 x 1.5 (Male thread) to M50 x 1.5 (Female thread)
M50 x 1.5 (Male thread) to M63 x 1.5 (Female thread)
M63 x 1.5 (Male thread) to M80 x 1.5 (Female thread)
Cable entry blanking plugs
Cable entry blanking plugs Industrial type
Cable entry blanking plugs For Explosive Atmospheres
Cable Lugs: Supply of crimping type lugs for power / control / lighting / earthing cables of various sizes along with all the associated accessories including all labour and materials, as per approved drawings, specifications of this tender and directions of Engineer-in-Charge. Supply of lugs are included in Termination cost, this item shall be operated only in case of re-termination/ re-lugging due to Owner/ Consultant's instructions. This item shall not be operated due to fault of Contractor.
All sizes upto 16 sq. mm. (Lugs shall be heavy duty and long barrel crimping type)
All sizes from 25 to 35 sq. mm. (Lugs shall be heavy duty and long barrel crimping type)
All sizes from 50 to 185 sq. mm. (Lugs shall be heavy duty and long barrel crimping type)
All sizes from 240 to 400 sq. mm. (Lugs shall be heavy duty and long barrel crimping type)
All sizes from 500 to 630 sq. mm. (Lugs shall be heavy duty and long barrel crimping type)
All sizes from 25 to 35 sq. mm. (Lugs shall be heavy duty and long barrel crimping type)
All sizes from 50 to 185 sq. mm. (Lugs shall be heavy duty and long barrel crimping type)
All sizes from 240 to 400 sq. mm. (Lugs shall be heavy duty and long barrel crimping type)
1.5 sq. mm. (Lugs shall be insulated, Ring / Pin / Fork crimping type)
2.5 sq. mm. (Lugs shall be insulated, Ring / Pin / Fork crimping type)
All sizes from 4 sq.mm. to 10 sq. mm. (Lugs shall be insulated,Ring / Pin / Fork crimping type)
10 mm dia. GI wire rope
16 mm dia. GI wire rope
CABLE JOINTING
Cable straight through jointing kit
Supply of cable jointing kit along with all the associated accessories as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
HV Cable straight through jointing kit Heat shrinkable type (suitable for outdoor installation) for 6.6 / 6.6 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY (UE)
HV Cable straight through jointing kit Heat shrinkable type (suitable for outdoor installation) for 33 / 33 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
1C x 630 sq.mm A2XCEWaY (UE)
MV Cable straight through jointing kit (suitable for outdoor installation) for 650 / 1100 (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), XLPE insulated, screened, armoured power / control / lighting cables
Cables with OD upto 20 mm.
Cables with OD above 20 mm but upto 30 mm.
Cables with OD above 30 mm but upto 40 mm.
Cables with OD above 40 mm but upto 50 mm.
Cables with OD above 50 mm but upto 60 mm.
Cables with OD above 60 mm but upto 80 mm.
PREFABRICATED CABLE TRAYS
Prefabricated Cable Trays (GI) and accessories
Supply of prefabricated GI perforated and ladder type cable tray / covers, tray separators along with all the associated consumable material for assembly and appropriate installation of the same, as per doc. no. TK-1P22A-EL-SPE-0024 (Technical Specification for GI cable Trays)
Cable Trays Perforated (GI)
50 mm wide
100 mm wide
150 mm wide
Coupler plates along with SS304 fixing hardware
GI Coupler plates with 3 mm thick, along with necessary fixing hardware – stainless steel (SS304) nut, bolt, lock-nut) for 50/100/150 W perforated cable trays mentioned above. (Note : 1 no. set = 2 nos. coupler plates each)
GI Coupler plates with 2 mm thick, along with necessary fixing hardware – stainless steel (SS304) nut, bolt, lock-nut) for 50/100/150 W perforated cable trays mentioned above. (Note : 1 no. set = 2 nos. coupler plates each
Cable Ladders (GI) and Accessories
150 mm wide
300 mm wide
600 mm wide
Prefabricated Bends and Accessories Cable Ladders (GI)
Pre-Fabricated 90 degree horizontal bends (Bending Radius 300mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree horizontal bends (Bending Radius 600mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree horizontal bends (Bending Radius 900mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree horizontal bends (Bending Radius 1200mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree Inside Vertical bends (Bending Radius 300mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree Inside Vertical bends (Bending Radius 600mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree Inside Vertical bends (Bending Radius 900mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree Inside Vertical bends (Bending Radius 1200mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree Outside Vertical bends (Bending Radius 300mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree Outside Vertical bends (Bending Radius 600mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree Outside Vertical bends (Bending Radius 900mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree Outside Vertical bends (Bending Radius 1200mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree horizontal bends (Bending Radius 300mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree horizontal bends (Bending Radius 600mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree horizontal bends (Bending Radius 900mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree Inside Vertical bends (Bending Radius 300mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree Inside Vertical bends (Bending Radius 600mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree Inside Vertical bends (Bending Radius 900mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree Outside Vertical bends (Bending Radius 300mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree Outside Vertical bends (Bending Radius 600mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree Outside Vertical bends (Bending Radius 900mm)
300 mm wide
600 mm wide
Pre Fabricated Cable Tray Reducer
600 to 300 mm Reducer, Right Hand Side
600 to 300 mm Reducer, Left Hand Side
300 to 150 mm Reducer, Right Hand Side
300 to 150 mm Reducer, Left Hand Side
Pre Fabricated Equal Tee’s (Bending Radius-300 mm)
300 mm wide
600 mm wide
Pre Fabricated Equal Tee’s (Bending Radius-600 mm)
300 mm wide
600 mm wide
Pre Fabricated Equal Tee’s (Bending Radius-900 mm)
300 mm wide
600 mm wide
Pre Fabricated Unequal Tee’s (Bending Radius-300 mm)
300 x 150 x 300 mm wide
600 x 150 x 600 mm wide
600 x 300 x 600 mm wide
Pre Fabricated Unequal Tee’s (Bending Radius-600 mm)
300 x 150 x 300 mm wide
600 x 150 x 600 mm wide
600 x 300 x 600 mm wide
Coupler plates along with SS304 fixing hardware
GI Coupler plates with 3 mm thick, 4 holes on both the sides of size M10 hole & M8 hardware (along with necessary fixing hardware – stainless steel nut, bolt, lock-nut) for 150/300/450/600 W ladder type cable trays mentioned above. (Note : 1 no. set = 4 nos. coupler plates each)
Stainless Steel Coupler plates with 2 mm thick, 4 holes on both the sides of size M10 hole & M8 hardware (along with necessary fixing hardware – stainless steel nut, bolt, lock-nut) for 150/300/450/600 W ladder type cable trays mentioned above. (Note : 1 no. set = 4 nos. coupler plates each)
Hinges along with SS304 fixing hardware
Hinged GI plates 3 mm thick, 80 mm height along with necessary fixing hardware – stainless steel (SS304) nut, bolt, lock-nut) suitable for tray size 300/450/600 mm W (Note : 1 no. set = 4 nos. coupler plates each)
Hinged GI plates 2 mm thick, 80 mm height along with necessary fixing hardware – stainless steel (SS304) nut, bolt, lock-nut) suitable for tray size 300/450/600 mm W (Note : 1 no. set = 4 nos. coupler plates each)
Tray Covers with fixing clamps along with necessary SS304 hardware
100 mm wide
150 mm wide
300 mm wide
600 mm wide
Hold Down Clamps (HDGI)
Hold down Clamps (HDGI) for Horizontal Ladder Cable Tray with necessary SS 304 fixing hardware
Hold down Clamps (HDGI) for Vertical Ladder Cable Tray with necessary SS 304 fixing hardware
Separators for Cable Ladders (GI) with necessart SS 304 fixing hardware
CONDUITS FOR CABLE LAYING / PROTECTION AND PULL BOXES
Supply of heavy duty rigid GI / PVC conduits and all the associated accessories Supply of accessories such as GI clamps, joints, bends reducers / adaptors for the conduits and other consumable material such as edge protection grommet at either ends for GI conduits as per the site requirement is considered in running meter length of the conduits.
Rigid GI conduits
25 mm nominal dia
50 mm nominal dia
100 mm nominal dia
150 mm nominal dia
Rigid GI conduits RED coloured (For Fire Alarm System cables)
25 mm nominal dia
50 mm nominal dia
Heavy duty PVC conduits
25 mm nominal dia
50 mm nominal dia
Flexible PVC conduits
25 mm nominal dia
Pull boxes for cable pulling in conduits
Supply of pull boxes (GI enclosure) indicate below excludes pull boxes already covered in the section "Point Wiring for Office buildings / Control rooms / Other rooms with false ceiling"
4 way Pull boxes,100mm L x 100mm W x 75mm D, 1no. 25mm knockout on all four sides
LIGHTING, SMALL POWER, WELDING SOCKETS AND JUNCTION BOXES
LIGHTING
Lighting fixtures
Supply of lighting fixtures and associated components / accessories such as lamps, chokes, condensers, reflectors for integral fixtures including certified glands, PVC hood and lugs, entry plugs etc. including all labour and materials, as per approved drawings, specifications of this tender and directions of Engineer-in-Charge.
Lighting Fixtures Industrial type Refer specification TK-1P22A-EL-SPE-0017 for LED type Industrial Light Fittings
1x40W LED Tube Light Fixture
2x20W LED Tube Light Fixture
10W LED Bulkhead Light Fixture
11W LED Decorative Down Light fixture suitable for false ceiling
36W LED recessed mounted square (600 mm X 600 mm) fixture suitable for False Ceiling
18W LED (suitable for 110V DC) recessed mounted square (600 mm X 600 mm) fixture suitable for False Ceiling
1 X 45W LED, Well Glass Integral Luminaire
1X26W,(suitable for 110V DC) LED Tube Light Fixture
Lighting Fixtures for Explosive Atmospheres Refer specification TK-1P22A-EL-SPE-0020 for LED type Light Fittings for Explosive Atmospheres.
1 X 45W LED, Ex'd', IIC, T3 Well Glass Integral Luminaire
1 X 26W (suitable for 110V DC) LED, Ex'd', IIC, T3 Well Glass Integral Luminaire
1 X 100W LED, Ex'd', IIC, T3 Medium Bay / High Bay Integral Luminaire
1 X 150W LED, Ex'd', IIC, T3 Medium Bay / High Bay Integral Luminaire
1 X 250W LED, Ex'd', IIC, T3 Medium Bay / High Bay Integral Luminaire
1 X 150W LED, Ex'd', IIC, T3 Flood Light Luminaire
LED aviation light Ex d, IIC, T3 (15W) with control panel. Colour of lamp and type (steady/ falshing) will be informed during Detailed Engineering.
1X40W LED Tube light fixture , Ex'd', IIC, T3
Special Lighting fixtures
Supply of special lighting fixtures and all the associated accessories, as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
Emergency lighting fixture with built-in battery
1x18W, Fluorescent, Industrial
1x18W, Fluorescent, for Explosive Atmospheres
Emergency EXIT sign with built-in battery
Refer 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL' for the 'Type designations' (TYPE-1, TYPE-2 etc.) mentioned below.
Hand lamps
24V Industrial Hand lamps along with 20 m extension cable 3C x 2.5sq.mm, YY, 20m, along with the plug suitable for 24V, 5A Industrial switch socket
24V Hand lamps for Explosive Atmospheres (Zone1/Zone2, Ex-d, IIC, T3, ) alongwith 20 m extension cable 3c x 2.5sq.mm, YY long with the plug suitable for 24V, 5A Industrial switch socket
Supply of Lighting Poles Supply of GI lighting pole as per approved drawing along with supply of fixing hardware like U clamp & bolt, for platform mounted pole
Installation details : L04
Installation details : L05
Installation details : L11
Installation details : L14A
EXHAUST FANS AND CEILING FANS
Industrial type Exhaust fans
Supply of Industrial type Exhaust fans and associated accessories such as louvers and bird screen, as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
300mm dia.
450mm dia.
600mm dia.
Exhaust fans for Explosive Atmospheres
Supply of Exhaust fans for Explosive Atmospheres and associated accessories such as louvers and bird screen, as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
300mm dia.
450mm dia.
600mm dia.
SMALL POWER
Supply of various small power equipment and all associated accessories, as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
Switch socket outlets
Supply of Decorative type switch socket outlets Supply of Supply of Decorative type switch socket outlets as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 1 no. piano type switch
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 2 nos. piano type switches
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 3 nos. piano type switches
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 4 nos. piano type switches
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 5 nos. piano type switches
Decorative type switch socket box with 1 no. 5/15A switch socket unit
Decorative type switch in single module with 1 no. 5A piano type switches
Decorative type switch in double module with 2 no. 5A piano type switches
Decorative type switch in tripple module with 3 no. 5A piano type switches
Decorative type switch in quad module with 4 no. 5A piano type switches
Decorative type switch socket switchboard with 5/15A, 5 pin, socket outlet with 15A switch and 'ON' LED indication & fuse
Surface / Concealed mounting type ( 2-Module) RJ 11 / RJ 45 Connectors Female type complete with Moduler box, cover plate etc. for telephones
Industrial type switch socket outlets (for Indoor Installation) Supply of Industrial type switch socket outlets (for Indoor Installation) as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
20A, single phase switch socket outlet with 1no. 3 pin socket and 1 No. 20 A, 10 kA, SPMCB, in sheet steel enclosure
Convenience Switch socket outlets Supply of Convenience Switch socket outlets as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
Industrial Convenience sockets (single phase)
16A, 240 V 3 pin single phase socket outlet
Convenience sockets (single phase) for Explosive Atmospheres
16A, 3 pin,240V AC single phase socket outlet (Ex-d , IIC , T3)
Industrial switch socket unit (portable)
24V, 5A Industrial switch socket unit with built-in 100VA, 220V / 24V transformer
Switch socket unit for Explosive Atmospheres
240V,16A and 24V, 5A combination type switch socket unit for Explosive Atmospheres (Zone 1/2, Ex-d , IIC , T3), with built-in 100VA, 240V / 24V transformer
240V,16A and 24V, 5A combination type switch socket unit for Explosive Atmospheres (Zone 1/2, Ex-d , IIC , T3), with built-in 100VA, 240V / 24V transformer (Portable Handlamp Sockets supplied with trolleys)
JUNCTION BOXES (JB) / POWER JUNCTION BOXES (JB)
Supply of various types of junction boxes / power junction boxes suitable for the required cable entries and all associated accessories, as per doc. no.TK-1P22A-EL-SPE-0074 (Technical specification for Industrial Lighting & Small Power Panels, Junction Boxes & Welding Receptacles) and TK-1P22A-EL-SPE-0019 (Technical Specification for Flameproof Industrial Lighting & Small Power Panels, Junction Boxes & Welding Receptacles) Supply of junction boxes suitable for bottom entry of incoming and outgoing cables, inclusive of suitable terminals for undrilled gland plate, cable terminations, busbars for cable termination as required, facility for earthing cable termination inside and outside the termination, along with the associated accessories such plugs for cable openings, fixing hardware
Junction boxes Industrial type
Junction boxes (Indoor)
4 way Lighting JB, Indoor
5 way JB for small power sockets , Indoor
Junction boxes (Outdoor)
4 way Lighting JB, Outdoor
4 way Welding socket JB, Outdoor
Communication System Junction Boxes Supply of Industrial Weatherproof Junction boxes as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'. Supply of cable glands, cable blanking plugs suitable to cable OD, cable entry size is included in the scope
Indoor FA System JB For housing addressable module of 1 no. Exit Light Incoming : 2Px1.5 sq.mm(1 No.) - M25 + 1Px2.5 sq.mm(1 No.) - M20 Outgoing : 2Px1.5 sq.mm(1 No.) - M25 + 1Px2.5 sq.mm(1 No.) - M20
Indoor FA System JB Incoming : 2Px1.5 sq.mm(1 No.) - M25 Outgoing : 2Px1.5 sq.mm(1 No.) - M25
Indoor PA System JB for Speakers Incoming : up to 20Px2.5 sq.mm(1 No.) - M40 Outgoing : 2Px2.5 sq.mm(12 Nos.) - M25 (9 Nos. Gland + 3 Nos. Plug)
Outdoor PA System JB for Speakers Incoming : up to 12Px2.5 sq.mm(1 No.) - M40 Outgoing : 2Px2.5 sq.mm(12 Nos.) - M25 (9 Nos. Gland + 3 Nos. Plug)
Indoor PA System JB for FCS Incoming : up to 20Px2.5 sq.mm(1 No.) - M40 Outgoing : 2Px2.5 sq.mm(12 Nos.) - M25 (9 Nos. Gland + 3 Nos. Plug)
Indoor Telephone System JB (IDF) Industrial Weatherproof type telephone system junction box /IDF Krone/screw type terminals, including termination and connections of incoming and outgoing telephone cable JB / IDF with 1 nos 20 Pair incoming cable(s) and 20 nos 2 Pair outgoing cable(s)
Junction boxes for Explosive Atmospheres
4 way Lighting JB, (Ex-d, IIC , T3)
5 way JB for small power sockets, (Ex-d, IIC , T3)
4 way Welding socket JB, (Ex-d, IIC , T3)
Junction box (Ex-d, IIC , T3) suitable for 415 V system suitable for Incoming cable size 3R-3Cx240sq.mm and outgoing cable size 2R-3Cx240sq.mm
Junction boxes for Communication System Supply of Industrial Weatherproof Junction boxes as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'. Supply of cable glands, cable blanking plugs suitable to cable OD, cable entry size is included in the scope
Indoor FA System JB for housing addressable module of 1 no. Detector Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.), 1Px1.5 (1 Nos.) NPT thread glands : 3 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Indoor FA System JB Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.), 1Px1.5 (1 Nos.) NPT thread glands : 3 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Outdoor FA System JB for housing addressable module of 1 no. MCP Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.), 1Px1.5 (1 Nos.) NPT thread glands : 3 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Outdoor FA System JB for housing addressable module of 1 no. Hooter / Becon Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.), 1Px2.5 (1 Nos.) NPT thread glands : 3 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Outdoor FA System JB for housing addressable module of 1 no. Detector Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.), 1Px1.5 (1 Nos.) NPT thread glands : 3 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Outdoor FA System JB for Housing 2 addressable modules and 2 zener barrier Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.), 1Px1.5 (2 Nos.) NPT thread glands : 4 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Outdoor FA System JB for End of resistor / Fault Isolator in FA loop Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.) NPT thread glands : 2 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Indoor Telephone System JB (IDF) Flameproof type telephone system junction box /IDF 9Ex-d, IIC,T3) Krone/screw type terminals, including termination and connections of incoming and outgoing telephone cable JB / IDF with 1 nos 20 Pair incoming cable(s) and 20 nos 2 Pair outgoing cable(s)
Outdoor PA System JB for FCS Incoming : 12Px1.5 (1 No.) Outgoing : 2Px1.5 (6 Nos.) NPT thread glands : 7 Nos. Plugs : 2 Nos. (1 No. Plug for 12Px1.5 and 1 No. for 2Px1.5)
Outdoor PA System JB for Speakers Incoming : 12Px2.5 (1 No.) Outgoing : 2Px2.5 (12 Nos.) NPT thread glands : 13 Nos. Plugs : 3 Nos. (1 No. Plug for 12Px2.5 and 2 Nos. for 2Px2.5)
Indoor PA System JB for Speakers Incoming : 12Px2.5 (1 No.) Outgoing : 2Px2.5 (12 Nos.) NPT thread glands : 13 Nos. Plugs : 3 Nos. (1 No. Plug for 12Px2.5 and 2 Nos. for 2Px2.5)
POWER SOCKET OUTLETS
Supply of various types of power socket outlets and all associated accessories, as per doc. no.TK-1P22A-EL-SPE-0074 (Technical specification for Industrial Lighting & Small Power Panels, Junction Boxes & Welding Receptaclest) and TK-1P22A-EL-SPE-0019 (Technical Specification for Flameproof Lighting & Small Power Panels, Junction Boxes & Welding Receptacles)
Industrial Power Socket Outlets
Industrial type, 415V, 63A, TPN & E socket outlet, with die cast Al LM6 enclosure , Type WS1
Industrial type, 415V, 100A, TPN & E socket outlet, with die cast Al LM6 enclosure , Type WS2
Power Socket Outlets for Explosive Atmospheres
For Explosive Atmospheres, 415V, 63A, TPN & E socket outlet, with die cast Al LM6 enclosure, Type WS3 (Ex-d, IIC , T3)
EARTHING AND LIGHTNING PROTECTION
EARTHING MATERIAL
Earthing conductor
Supply of GI strip / bare copper conductor for earthing
25 x 6 mm GI strip
40 x 5 mm GI strip
50 x 6 mm GI strip
75 x 10 mm GI strip
Earth / lightning protection electrodes
Supply of Earth / lightning protection electrodes along with the associated accessories / material as per 'Installation Details - Earthing', including any additional hardware as per site requirement so as to ensure the completeness of installation work
Installation Type : E01A :100 mm Dia, 3 m length GI pipe earth electrode for Electrical Safety earth
Installation Type : E01B : 100 mm Dia, 6 m length GI pipe earth electrode for Instrument clean earth
Installation Type : E01A : 100 mm Dia, 3 m length GI pipe lightning protection electrode
Earth buses
Supply of Earth buses along with the associated accessories (excluding structural steel) as per 'Installation Details - Earthing' and applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work
Supply of steel support structure / supporting frames for above shall be considered separately in SECTION - F.
Installation Type : E02A GI earth bus for Electrical safety
Installation Type : E02B GI earth bus for Electrical safety
Installation Type : E02A - GI earth bus for instruments
Installation Type : E02B - GI earth bus for instruments
Installation Type : E20 - Mounted on cable tray for Electrical
Installation Type : E20 - Mounted on cable tray for Instrumentation
Installation Type : E22 - Cu insulated earth bus
Supply of following Earthing Materials as per Installation Type : E14 1. 9 DIA G.I. BAR 2. SHARP JAW TONG TYPE HEAVY DUTY SPRING CLAMP-100A
LIGHTNING PROTECTION MATERIAL
Lightning protection conductor
Supply of GI strip / bare copper conductor/aluminium/HDGI Round conductor for Lightning protection and associated accessories
Supply of accessories such as test links, cross connectors, parallel connectors for lightning protection down conductors, epoxy insulator supports and the associated accessories as per 'Installation Details - Lightning Protection' / as indicated in applicable construction documents / as per the site requirement, are considered in running meter length of lightning protection down conductors.
Installation Type: E16 Roof Conductor (Conductor Size- 25x6mm)
Installation Type: E16 Down Conductor (Conductor Size- 25x6mm)
Test Link : E16 : 50x6mm GI Link 150mm Long
Lightning protection rods / finials
Supply of Lightning protection rods / finials (lightning arrestors) along with the associated accessories (excluding structural steel) as per 'Installation Details - Lightning Protection' and applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work
Supply of steel support structure / supporting frames for above shall be considered separately in SECTION - F.
Installation Type : E24
Installation Type : E25
Installation Type : E26
Installation Type : E27
STRUCTURAL STEEL
Supply of structural steel Section wise requirement shall be estimated by CONTRACTOR, as per the applicable construction documents / various applicable 'Installation Details' mentioned in 'SECTIONS - A to E' in this document. Measurement of steel quantity for installation shall be based on actual quantities installed at site without wastage allowance.
Structural steel (MS)
Supply of coating material and paint as required for surface preparation and painting of steel shall be as per doc. TP-1ZZZA-PI-SPE-0003 (Technical Specification for Painting) is included in scope.
Structural steel (Hot deep galvanized GI)
MISCELLANEOUS ITEMS
CANOPIES
Supply of GI / FRP canopies for various equipment and all associated accessories, as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'. Site visit as required to confirm the actual dimensions / arrangement of various equipment installed at site, so as to fabricate canopy exactly suitable for the equipment is considered in the scope. Supply of all the Installation Material (including steel supporting frame as required) required as per site requirement is included in the scope.
Canopies for Motors
GI canopy complete with louvers backed up by wire mesh
Upto 3.0 kW
3.7 kW to 15 kW
18.5 kW to 37.0 kW
45.0 kW to 90 kW
110 kW to160 kW
GI canopy complete with louvers backed up by wire mesh - HV (6.6kV) Motors
Above kW to 280 kW
Above 280 kW to 500 kW
Above 500 kW to 750 kW
Above 750 kW to 1200 kW
Above 1200 kW to 2000 kW
Above 2000 kW to 5000 kW
Above 5000 kW to 8000 kW
GI Canopies omplete with louvers backed up by wire mesh for MV panels (wall / concrete / steel structure mounted) / LCS / Power Socket Outlets /Convenience Socket Outlets
LDB / ELDB / PDBs
Local Control Station (LCS)
20A / 32A Power Socket Outlets in sheet steel enclosure / die cast Al LM6 body
63A / 100A Power Socket Outlets in sheet steel enclosure / die cast Al LM6 body
CIVIL WORK
Anchor fasteners
Supply of aheavy duty Galvanised steel anchor fasteners for supporting various equipment in brick work / concrete work
Supply of anchor fasteners indicated below excludes those already considered in various 'Installation Details' mentioned in 'SECTIONS - A to E' in this document.
Anchor fasteners M8 type x 60mm
Anchor fasteners M10 type x 75 mm
Anchor fasteners M12 type x 100 mm
Supply of certified soft sand of known resistivity (Resistivity of sand shall be between 10,000 – 30,000 ohm.cm. )
Supply of approved second class bricks of 75 mm thickness in cable trenches for cable protection, as per approved drawings, specifications of this tender and directions of Engineer-in-Charge.
Supply approved Red coloured concrete tiles in cable trenches for cable protectionas per approved drawings, specifications of this tender and directions of Engineer-in-Charge.
SAFETY ITEMS
Supply of safety items as per applicable statutory requirements / HSE documents / as indicated in applicable construction documents
Enameled caution boards for 33 kV.
Enameled caution boards for 6.6 kV.
Enameled caution boards for 1.1 kV.
Enameled Danger plates to be installed in electrical rooms such as transformer bay, switchgear room etc.
3 ply Lamicoid tag plates of appropriate size for various equipment, with White letters on Black background, as per the site requirement
Epoxy insulating floor coating (Valency Compound Make - Valency-111 CLASS A or equivalent
33kV System
6.6 kV systems -
upto 1.1 kV systems
Supply of 1000mm wide Synthetic Insulating mat (as per IS 15652: 2006) including supply of necessary adhesive for following grades (thickness as per voltage withstand requirements) required for maintenance of electrical equipment in substation, including cutting to required shape in running length, including all labour and materials, as per applicable Indian or International standards and CEA Guidelines and as per directions of Engineer-in-Charge
33kV System
6.6 kV systems -
upto 1.1 kV systems
First aid information chart (for electrical hazards such as Shock treatment): Framed laminated shock treatment chart, conforming to IE rules, in English and local language "Assamese". Name, address and telephone number of nearest doctor shall be mentioned in it.
First aid boxes along with required medicines / medical equipment, containing ointments for treatment of electrical burns, conforming to IE rules.
Wall mounted, Electrical Single Line Diagrams-A0 size" for the unit including frame, glass, hardwares, etc.
Industrial electrical Rubber hand gloves, Class 1 of reputed make
Rubber hand gloves pairs (1.1 kV grade).
Rubber hand gloves pairs (6.6 grade).
Rubber hand gloves pairs (33 kVgrade).
Discharge rod with earthing facility (upto 6.6 kV grade) with voltage detection
Discharge rod with earthing facility (Above6.6 kV up to 33kV) with voltage detection
LOTO with multiple locks (HESP) of reputed make.
Locks with keys of reputed make
Supply of following items for Battery area
Chemical Resistant Apron
Chemical Resistant Boot Pairs
Chemical Resistant Hand Gloves Pairs
Goggles used for Chemical handling
Electrical Protection suit / ARC FLASH SUIT 12CAL with JACKET, PANT ,GLOVES and FACE SHIELD for 12 Calories
GENERAL ITEMS
Supply of following items and all the associated accessories as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
Office tables of reputed make
Office chairs of reputed make
Full size Cupboard of reputed make, sheet steel enclosure (for documentation)
Tool Cabinet, Wall Mounted
Key Cabinet, Wall Mounted
Tarpaulin (for weather protection of stored electrical equipment)
Insulated step ladder of reputed make (suitable for indoor work in switchgear rooms)
Supply of Fire proofing of cables up 3 m length at entry points of both endsincluding all labour and materials required. (Actual area of surface painted shall be measured) _ - (As perIEC 60331) Fire proof paint for cables for 1 hour Fire Rating (CABLE SURFACE AREA WISE) Fire retardant cable coating HILTI : CP679A / OBO BETTERMAN equivalent product
Supply of Fire Stop (Fire Sealing) material suitable to withstand for 240 mins including all labour and materials required for sealing the wall opening / conduits fire sealings.Refer annex EW4-6 for details of openings to be sealed
Supply of Fire Stop (Fire Sealing) material suitable to withstand for 90 mins including all labour and materials required for sealing the wall opening / conduits fire sealings.Refer annex EW4-6 for details of openings to be sealed
Supply of Weather proofing material HILTI make including all labour and materials required for sealing the wall opening / conduits fire sealings.
LV Switchgear Components
6A, 9 kA, DP MCB
10A, 9 kA, DP MCB
20 / 32 A, 9 kA, DP MCB
Terminal Blocks
up to 2.5 sqmm
Above 2.5 sq. mm up to 6 sqmm
Ethernet Switch
Unmanaged Ethernet switch - Dual Power Supply (110V DC / 230 V AC) No of Ports : 6 X RJ 45 Ethernet Ports + 2 XFO Ports (Multi Mode) Uplink Speed : 1000MBPS /1GBPS The scope includes supply of LIU / Patch Panel with MMFO Patch cords (Length : 5 meter)between Ethernet switch & LIU.
Unmanaged Ethernet switch - Dual Power Supply (110V DC / 230 V AC) No of Ports : 10 X RJ 45 Ethernet Ports + 2 XFO Ports (Multi Mode) Uplink Speed : 1000MBPS /1GBPS The scope includes supply of LIU / Patch Panel with MMFO Patch cords (Length : 5 meter)between Ethernet switch & LIU.
TOOLS & TACKLES OF REPUTED MAKE Make shall be approved by Owner / Consultant, all supplied material shall be industrial grade, ISI certified.
True RMS Digital Multimeter with Display of up to 3 digits of decimal. Make:-Megger,Fluke, Kyoritsu, Hyoki
Continuity Testers
Tong Testers Make:-Meco, Megger, Fluke, Kyoritsu, Hyoki
Phase Sequence Meter
Tachometers (Non-Contact type)
Lux Level Meters for illumination check
Insulation Resistance Testers (Meggers) of 500V, 1000V rating Make:-Megger,Fluke,kyoritsu, Hyoki
Insulation Resistance Testers (Meggers) of 2500V & 5000V rating, battery operated- Make:-Megger,Fluke,kyoritsu, Hyoki
Earth Resistance Testers with all accessories and clamps - Make: -Megger,Fluke,kyoritsu, Hyoki
Description of Work / Item(s)
Amount
GENERAL NOTES This document shall be read in conjunction with doc. "SCOPE OF WORK-ELECTRICAL" DOC ID TK-1P22A-EL-SPE-0022. For 'Limit of Variation' in the rates / quantities / total value of work, please refer 'SPECIAL CONDITIONS OF CONTRACT'. CONTRACTOR shall only use 'Released for Construction (RFC)' drawings / documents for execution of work during the Construction phase. Dismantling activities shall be paid at 30% of the unit rates of the respective installation work. Dismantling activities shall only be paid to CONTRACTOR if instructed by OWNER / CONSULTANT, and not for erroneous execution done by CONTRACTOR. All the fixing hardwares such as nuts, bolts, U-bolts, screws, washers & clamps shall be of Stainless Steel (SS304), unless otherwise specified in Installation details and applicable construction documents CONTRACTOR shall ensure that the rates quoted for execution of electrical works take into account all requirements, services, activities & responsibilities defined as forming part of CONTRACTOR’s scope in the Tender Document / Contract. Special attention shall be given to include the efforts necessary to implement & comply with the relevant safety practices to be followed for the electrical works at the Plant Site, as per the applicable HSE documents. CONTRACTOR should read entire specification to understand in totality the scope of supply and Installation. Every line item for Supplies and Installation should be read along with the respective Installation standard / hook up drawings related to that specific line item to understand the scope of supply and Installation in totality. Any missouts in supply scope in this regard by the CONTRACTOR shall not be entertained.
EQUIPMENT
TRANSFORMERS
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, installation of assemblies / sub-assemblies, assembling and installation of components / devices supplied separately/ loose - as recommended by MANUFACTURER / applicable construction documents, Testing of oil, first filling and first filtration of oil, touch up painting, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. Minor civil work such as chipping, grouting for fixing of associated equipment / assemblies and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. Supply of all fixing hardware as per the site requirement is included in the scope. Supply, Fabrication, surface preparation, painting and installation of steel support of steel support structure / supporting frames as per the site requirement for above shall be considered separately in SECTION - F
Power transformers (Oil filled)
TAG : 1U64-SS16-TR-210A & 1U64-SS16-TR-210B Rating : 25 / 31.5 MVA, 33 kV / 6.9 kV, ONAN / ONAF, Dyn11 WITH OCTC, 2 winding including PDMS, OMR System Approx. Dimensions (LxBxH) : 5730 x 3940 x 4330 mm Oil capacity : 7700 ltrs. (6380kg.) Approx. Weight : 36180 kg (including oil) The Transformer Tank may be partially filled with oil at the time of shipment. CONTRACTOR shall completely fill the Tank at site.
Distribution transformers (Oil filled)
TAG : 1U64-SS16-TR-331A/B, 332A/B, 333A/B, 334A/B Rating : 2000 kVA, 6.6 kV / 433 V, ONAN, Dyn11 WITH OCTC Approx. Dimensions (LxBxH) : 3300 x 2400 x 3500mm Oil capacity : 1850 ltrs. Approx. Weight : 7900 kg (including oil) The Transformer Tank may be partially filled with oil at the time of shipment. CONTRACTOR shall completely fill the Tank at site.
Dry type transformers (Lighting / Heat tracing / Isolation transformers etc.) with all accessories
TAG : 1U64-SS16-TR-335 Rating : 2200 kVA, 6600 V / 433 V, 2 winding, indoor installation Approx. Dimensions (LxBxH) : 3700 X 3100 X 3200 mm Approx. Weight : 6200 Kg Location : Indoor
TAG : 1U64-SS16-TR-503A/B Rating : 300 kVA, 415 V / 433 V, 2 winding Approx. Dimensions (LxBxH) : 1620 X 1675 X 1550 mm Approx. Weight : 1400 Kg Location : Indoor
TAG : 1U64-SS16-TR-504A/B Rating : 50 kVA, 415 V / 433 V, 2 winding Approx. Dimensions (LxBxH) : 1680X 1000 X 1000 mm Approx. Weight : 460 kg Location : Indoor
Filtration of transformer oil by filter machine provided by the contractor for improving the insulation strength of oil to the required strength, including all labour and materials, specifications of this tender and directions of Site Engineer-in-Charge. (Excluding the supply of oil). but including required BDV oil testing Cost of first filteration shall be included in installation cost of Transformer. This rate shall be applicable only in event of addtional filteration requirement due to site conditions after completion of first flteration
BUSDUCTS
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of shipping sections / assemblies / sub-assemblies, assembling and installation of components including bends and risers / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, alignment for appropriate termination of busbars at both the ends, Installation of bends, fixing of flexible joints, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work Testing, precommissioning and commissioning activities are included in the scope Minor civil work such as chipping and modifications in the wall cutout, as required, for making busduct wall opening suitable for busduct entry etc., replastering and making area good as per the site requirement (including the supply of consumable material for the same), sealing with fire proofing compound, is included in the scope. Supply of all fixing hardware as per the site requirement is included in the scope. Fabrication and installation of steel support structure / supporting frames (inside and outside the substation building) for equipment as per the site requirement, is considered separately in SECTION - F.
6.6 kV, 3150 A, 40kA for 1 sec, Aluminium busbar Construction : Sheet steel / Aluminium enclosure, Phase Segregated From : Transformer secondary to Switchgear Incomers Approx. Weight : 340 kg / m
415 V, 3200 A, 50kA for 1 sec, Aluminium busbar Construction : Sandwich type, Material of enclosure : Galvanized steel / Aluminium From : Transformer secondary to Switchgear Incomer Approx. Weight : 50 kg / m
NEUTRAL GROUNDING RESISTOR (NGR)
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of equipment and accessories, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. Testing, precommissioning and commissioning activities are included in the scope. Minor civil work such as chipping, grouting for fixing of equipment / assemblies and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. Supply of all fixing hardware as per the site requirement is included in the scope. Fabrication and installation of steel support structure / supporting frames for equipment as per the site requirement, is considered separately in SECTION - F.
TAG : 1U64-SS16-NGR-210A/B Rating : 3.8 kV, 400 A for 30 sec Approx. Dimensions (LxBxH) : 1450 x 890 x 950 mm Approx. Weight : 450 kgs
HV SWITCHBOARDS - 6.6kV Switchboards, HV PFIC Panels, HV VFD / Soft Starter panels etc Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of various shipping sections / assemblies, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, interpanel wiring, stenciling with paint on equipment enclosures as required, and other associated work so as to ensure the completeness of installation work. Installation of condition monitoring sensors, modules etc. as applicable is included in the scope. Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. Minor civil work such as chipping, grouting for fixing of equipment as per the site requirement and replastering the same (including the supply of consumable material for the same) is included in the scope. Fabrication and installation of steel support structure / supporting frames for equipment as per the site requirement, is considered separately in SECTION - F. Supply of all fixing hardware as per the site requirement is included in the scope.
TAG : 1U64-SS16-AIS-210 Rating : 6.6 kV, 3150 A, 40kA for 1 sec. Construction : Floor mounting, single front Nos. of vertical sections : 72 Approx. Dimensions (LxBxH)mm : 600/800/1000 x 1950/2250/2500 x 2500 mm (per vertical section) Approx. Weight : 800 / 1200 kg (per vertical section) Switchboard Arrangement : Double Line,front to front The scope includes installation of interconnecting busduct between 2 lines of switchboard & Arc duct / arc absorber with wall frame assembly as applicable.
Unit rate for additional / deletion of Vertical section for Item as per sr. no. A/4.1
TAG : 1U64-KAM-2781-VCB (6.6 kV Output VCB Panel) Rating : 6.6 kV, 800 A, 40kA for 1 sec. Nos. of vertical sections : 3 Approx. Dimensions (LxBxH)mm : 600 x 1570/1970 x 2500mm (per vertical section) Approx. Weight : 700 kg (per vertical section)
TAG : 1U64-KAM-2782A/B-VCB (6.6 kV Output VCB Panel) Rating : 6.6 kV, 1250 A, 40kA for 1 sec. Nos. of vertical sections : 2 Approx. Dimensions (LxBxH)mm : 600 x 1570 x 2200mm (per vertical section) Approx. Weight : 700 kg (per vertical section)
TAG : 1U64-SS16-CAP-210A/B (PFIC Panel, indoor type) Rating : 6.6 kV, 3750 kVAr Nos. of vertical sections : 6 Approx. Dimensions (LxBxH)mm : 1200/1400 x 2400 x 2475 mm (per vertical section) Approx. Dimensions (LxBxH)mm : 9400 x 2400 x 2475 mm (overall) Approx. Weight : 1800 kg (per vertical section)
TAG : 1P23-KAM-2781-VFD1 and 1P23-KAM-2781-VFD1 (HV VFD Panel) Rating : 6.6 kV, 2600 kW Approx. Dimensions (LxBxH) : 6000 x 1500/1200 x 2800 mm Approx. Weight : 8800 kgs Mounting : On floor Scope also includes installation of -common PLC Panel with approx. dimensions (L X B XH) : 2000 mm X 600 mm X 2315 mm, Approx. weight : 600 kgs Common CMS Panel with approx. dimensions (L X B XH) : 700 mm X 350 mm X 700 mm, Approx. weight : 70 kgs
TAG : 1P23-KAM-2782A/B-VFD (Soft Starter Panel) Rating : 6.6 kV, 2600 kW Approx. Dimensions (LxBxH) : 6300 x 1100 x 2750 mm Approx. Weight : 9900 kgs Mounting : On floor Approx. weight : 9900 kgs
LV / MV SWITCHBOARDS (FLOOR MOUNTED)
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of various shipping sections / assemblies, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, interpanel wiring, stenciling with paint on equipment enclosures as required, and other associated work so as to ensure the completeness of installation work. Installation of condition monitoring sensors, modules etc. as applicable is included in the scope. Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. Minor civil work such as chipping, grouting for fixing of equipment as per the site requirement and replastering the same (including the supply of consumable material for the same) is included in the scope. Fabrication and installation of steel support structure / supporting frames for equipment as per the site requirement, is considered separately in SECTION - F. Supply of all fixing hardware as per the site requirement is included in the scope.
TAG : 1U64-SS16-PMCC-331 Rating : 415 V, 3200 A, 50 kA for 1 sec. Construction : Floor mounting, single front Nos. of Shipping sections : ~ 10 Approx. Maximum Dimensions (LxBxH)mm : 1900 x 1750 x 2630mm (per shipping section) Approx. Dimensions (LxBxH)mm : 15000 x 950 / 1450 / 1750 x 2630 mm (overall) Approx. Maximum Weight : 2100 KGS.(per shipping section ) Approx. Weight : 16000 KGS.(overall )
TAG : 1U64-SS16-PMCC-332 Rating : 415 V, 3200 A, 50 kA for 1 sec. Construction : Floor mounting, single front Nos. of Shipping sections : ~ 10 Approx. Maximum Dimensions (LxBxH)mm : 1650 x 1750 x 2630mm (per shipping section) Approx. Dimensions (LxBxH)mm : 14000 x 950 / 1450 / 1750 x 2630 mm (overall) Approx. Maximum Weight : 1900 KGS.(per shipping section ) Approx. Weight : 14500 KGS.(overall )
TAG : 1U64-SS16-PMCC-333 Rating : 415 V, 3200 A, 50 kA for 1 sec. Construction : Floor mounting, single front Nos. of Shipping sections : ~ 9 Approx. Maximum Dimensions (LxBxH)mm : 1900 x 1750 x 2630mm (per shipping section) Approx. Dimensions (LxBxH)mm : 14500 x 950 / 1450 / 1750 x 2630 mm (overall) Approx. Maximum Weight : 2100 KGS.(per shipping section ) Approx. Weight : 17000 KGS.(overall )
TAG : 1U64-SS16-EPMCC-334 Rating : 415 V, 3200 A, 50 kA for 1 sec. Construction : Floor mounting, single front Nos. of Shipping sections : ~ 13 Approx. Maximum Dimensions (LxBxH)mm : 1650 x 1750 x 2630mm (per shipping section) Approx. Dimensions (LxBxH)mm : 19500 x 950 / 1450 / 1750 x 2630 mm (overall) Approx. Maximum Weight : 2100 KGS.(per shipping section ) Approx. Weight : 21500 KGS.(overall )
TAG : 1U64-SS16-MCC-446 Rating : 415 V, 800 A, 50 kA for 1 sec. Construction : Floor mounting, double front Nos. of Shipping sections : ~ 4 Approx. Maximum Dimensions (LxBxH)mm : 2450 x 1250 x 2600mm (per shipping section) Approx. Dimensions (LxBxH)mm : 7250 x 950 / 1250 x 2600 mm (overall) Approx. Maximum Weight : 2100 KGS.(per shipping section ) Approx. Weight : 6500 KGS.(overall )
TAG : 1U64-SS16-MCC-447 Rating : 415 V, 800 A, 50 kA for 1 sec. Construction : Floor mounting, double front Nos. of Shipping sections : ~ 7 Approx. Maximum Dimensions (LxBxH)mm : 2450 x 1250 x 2600mm (per shipping section) Approx. Dimensions (LxBxH)mm : 11100 x 950 / 1250 x 2600 mm (overall) Approx. Maximum Weight : 2100 KGS.(per shipping section ) Approx. Weight : 10000 KGS.(overall )
TAG : 1U64-SS16-MCC-448 Rating : 415 V, 800 A, 50 kA for 1 sec. Construction : Floor mounting, double front Nos. of Shipping sections : ~ 12 Approx. Maximum Dimensions (LxBxH)mm : 2450 x 1250 x 2600mm (per shipping section) Approx. Dimensions (LxBxH)mm : 22000 x 950 / 1250 x 2600 mm (overall) Approx. Maximum Weight : 2100 KGS.(per shipping section ) Approx. Weight : 19000 KGS.(overall )
TAG : 1U64-SS16-MCC-450 Rating : 415 V, 800 A, 50 kA for 1 sec. Construction : Floor mounting, double front Nos. of Shipping sections : ~ 4 Approx. Maximum Dimensions (LxBxH)mm : 2450 x 1250 x 2600mm (per shipping section) Approx. Dimensions (LxBxH)mm : 8000 x 950 / 1250 x 2600 mm (overall) Approx. Maximum Weight : 2100 KGS.(per shipping section ) Approx. Weight : 7200 KGS.(overall )
TAG : 1U64-SS16-MCC-451 Rating : 415 V, 800 A, 50 kA for 1 sec. Construction : Floor mounting, double front Nos. of Shipping sections : ~ 5 Approx. Maximum Dimensions (LxBxH)mm : 2450 x 1250 x 2600mm (per shipping section) Approx. Dimensions (LxBxH)mm : 8000 x 950 / 1250 x 2600 mm (overall) Approx. Maximum Weight : 2100 KGS.(per shipping section ) Approx. Weight : 7200 KGS.(overall )
TAG : 1U64-SS16-EMCC-452 Rating : 415 V, 800 A, 50 kA for 1 sec. Construction : Floor mounting, double front Nos. of Shipping sections : ~ 7 Approx. Maximum Dimensions (LxBxH)mm : 2450 x 1250 x 2600mm (per shipping section) Approx. Dimensions (LxBxH)mm : 9500 x 950 / 1250 x 2600 mm (overall) Approx. Maximum Weight : 2100 KGS.(per shipping section ) Approx. Weight : 8500 KGS.(overall )
TAG : 1U64-SS16-ASB-504 Rating : 415 V, 800 A, 50 kA for 1 sec. Construction : Floor mounting, double front Nos. of vertical sections : ~12 Approx. Dimensions (LxBxH)mm : 800/1050 x 1750/1450 x 2530 mm (per vertical section) Approx. Weight : 900 KGS.(per vertical section )
TAG : 1U64-SS16-MLDB-503 Rating : 415 V, 800 A, 20 kA for 1 sec. Construction : Floor mounting, single front Nos. of vertical sections : ~12 Approx. Dimensions (LxBxH)mm : 800/1050 x 1450/650 x 2430 mm (per vertical section) Approx. Weight : 900 KGS.(per vertical section )
TAG : 1U64-SS16-EMLDB-504 Rating : 415 V, 100 A, 10 kA for 1 sec. Construction : Floor mounting, single front Approx. Overall Dimensions (LxBxH)mm : 6000 x 650 x 2430 mm Approx. Weight : 500 kg
MISCELLANEOUS Panels / Items (WALL / CONCRETE / STEEL STRUCTURE MOUNTED) (Industrial / For Explosive Atmospheres)
Installation of industrial weather proof / flame proof Lighting, Power panels on steel structures/concrete coloumn/wall etc, including supply & making of concrete foundations if required for supports, minor civil works if any, and installation of canopies. This also includes supply of necessary hardware, cement, sand , touch up painting, stenciling , Including Lifting & Transportation from storage area to the place of installation with contractor's own lifting and transportation arrangement, unpacking, assembly, including all labour and materials complete as per approved drawings, Installation of LV panels (wall / concrete / steel structure mounted) shall be as per 'Installation Details - Power' and applicable construction documents Supply of Installation materials (excluding structure steel), including any additional material as per site requirement so as to ensure the completeness of installation work is included in the scope Testing, precommissioning and commissioning activities are included in the scope. Minor civil work such as chipping, grouting for fixing of equipment and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. Fabrication and installation of steel support structure / supporting frames for equipment as per the site requirement, is considered separately in SECTION - F. Supply of all fixing hardware as per the site requirement is included in the scope. Weights indicated below are euqipment/ item weights to be installed.
Lighting / Power Panels LDB / ELDB / DL LDB / PDB (6way / 9way / 12way / 15way / 18way/ 24 Way)
Local Control Panel / Local Starter Panel / Local Isolators / Hydro jetting PDB
Weight of the Unit up to 20 kg
Weight of the Unit above 20 up to 100 kg
Weight of the Unit above 100 upto 200 kg.
Weight of the Unit above 200 upto 300 kg.
BATTERY CHARGER (DC UPS) AND BATTERY
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of equipment / assemblies, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. Assembly of battery rack, placement of battery cells on the support rack, electrolyte filling and associated work as recommended by MANUFACTURER is included in the scope. Installation of battery MCCB with enclosure at the location indicated in the applicable layouts is included in the scope. Installation of Battery monitoring system as applicable is included in the scope. Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. First charge, Discharge and again charging of battery bank is included in scope. Minor civil work such as chipping, grouting for fixing of equipment / assemblies and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. Fabrication and installation of steel support structure / supporting frames for various equipment / assemblies as per the site requirement, is considered separately in SECTION - F. Supply of all fixing hardware as per the site requirement is included in the scope.
TAG : 1U64-SS16-ECH-503 (For Switchgear Control)
Battery charger (Dual redudant) Rating : 110 VDC, 160 A, Battery charger with seperate DCDB Construction : Non Compartmentalised, Single / Double front Approx. Dimensions (LxBxH) : 2200 x 800 x 2000 mm Approx. Weight : 600 kgs (Overall) Mounting : On Floor
Battery bank : 1U64-SS16-BAT-503A/B Battery type : Ni-Cd No, of cells : 95 Rating : 300 AH Mounting : floor mounted battery rack, multi-tier
DCDB : 1U64-SS16-DCDB-503-1 No. Rating : 110 VDC, 160 A Construction : Compartmentalised, Single front Approx. Dimensions (LxBxH) : 6500 x 450 x 2200 mm Approx. Weight : 850 kgs (Overall) Mounting : On Floor
Battery Isolator (MCCB) - 2 Nos. Enclosure : Flameproof Mounting : on wall
Cell Booster (Portable type) - 2 Nos. Approx. Dimensions (LxBxH) : 600 x 600 x 500 mm
TAG : 1U64-SS16-ECH-504 (For DC Critical Lighting)
Battery charger (Single) Rating : 110 VDC, 75 A, Battery charger with seperate DCDB Construction : Non Compartmentalised, Single / Double front Approx. Dimensions (LxBxH) : 600 x 600 x 1500 mm Approx. Weight : 200 kgs (Overall) Mounting : On Floor
Battery bank : 1U64-SS16-BAT-504 Battery type : Ni-Cd No, of cells : 95 Rating : 140 AH Mounting : floor mounted battery rack, Two-tier
DCDB : 1U64-SS16-DCDB-504- 1 No. Rating : 110 VDC, 75 A Construction : Compartmentalised, Single front Approx. Dimensions (LxBxH) : 1200 x 450 x 1600 mm Approx. Weight : 150 kgs (Overall) Mounting : On Floor
Battery Isolator (MCCB)-1 Nos Enclosure : Flameproof Mounting : on wall
Cell Booster (Portable type) - 2 Nos. Approx. Dimensions (LxBxH) : 600 x 600 x 500 mm
AC UPS AND BATTERY
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of equipment / assemblies, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work Assembly of battery rack, placement of battery cells on the support rack, electrolyte filling and associated work as recommended by MANUFACTURER is included in the scope. Installation of battery MCCB with enclosure at the location indicated in the applicable layouts is included in the scope. Installation of Battery monitoring system as applicable is included in the scope. Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. First charge, Discharge and again charging of battery bank is included in scope. Minor civil work such as chipping, grouting for fixing of equipment / assemblies and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. Fabrication and installation of steel support structure / supporting frames for various equipment / assemblies as per the site requirement, is considered separately in SECTION - F. Supply of all fixing hardware as per the site requirement is included in the scope.
TAG : 1U64-SRR6-UPS-501
UPS Rating : 115 VAC, 200 kVA, Parallel redudant UPS with common bypass and separate ACDB Construction : Non Compartmentalised, Single / Double front Approx. Dimensions (LxBxH) : 8000 x 1200/1000 x 2100 mm (Overall) Mounting : On False floor supported with structural steel base frame
Battery bank : 2 sets Battery type : Ni-Cd No, of cells (Per set) : ~ 375 Rating of cell : ~ 650 AH Mounting : floor mounted battery rack, multi-tier
ACDB : 1 No. Rating : 115 V AC, 2000 A Construction : Compartmentalised, Single / Double front Approx. Dimensions (LxBxH) : 13000 x 850 x 2200 mm Mounting : On False floor supported with structural steel base frame
Battery Isolator (MCCB)-2 Nos Enclosure : Flameproof Mounting : on wall / Floor
Cell Booster (Portable type) - 1 Nos. Approx. Dimensions (LxBxH) : 700 x 700 x 600 mm
MV (415V) VARIABLE FREQUENCY DRIVES, THYRISTORIZED HEATER CONTROL PANELS, EXCITATION CONTROL PANELS etc.
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of equipment and accessories, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. Minor civil work such as chipping, grouting for fixing of equipment / assemblies and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. Fabrication and installation of steel support structure / supporting frames for equipment / accessories as per the site requirement, is considered separately in SECTION - F. Supply of all fixing hardware as per the site requirement is included in the scope.
TAG : 1P24-EEH-0981 Rating : 415V, 1746 kW No of shipping sections : 6 Approx. Maximum Dimensions (LxBxH) : 2800 x 1200 x 2250 mm (per shipping section) Approx. Dimensions (LxBxH) : 12000 x 1000 / 1200 x 2250 mm (overall) Approx. Weight : 8000 kgs (overall) Mounting : On floor
TAG : 1P24-EEH-0882 Rating : 415V, 103 kW Approx. Dimensions (LxBxH) : 1300 x 600 x 2050 mm Approx. Weight : 1000 kgs (overall) Mounting : On floor
TAG : 1P23-EEH-6383 Rating : 415V, 40 kW Approx. Dimensions (LxBxH) : 900 x 500 x 2225 mm Approx. Weight : 700 kgs (overall) Mounting : On floor
TAG : 1P23-EEH-6382 Rating : 415V, 37 kW Approx. Dimensions (LxBxH) : 900 x 500 x 2225 mm Approx. Weight : 700 kgs (overall) Mounting : On floor
TAG : 1P23-EEH-6381 Rating : 415V, 425 kW Approx. Dimensions (LxBxH) : 2100 x 1000 x 2375 mm Approx. Weight : 1600 kgs (overall) Mounting : On floor
TAG : 1P23-EEH-0882 Rating : 415V, 302 kW Approx. Dimensions (LxBxH) : 1800 x 1000 x 2375 mm Approx. Weight : 1500 kgs (overall) Mounting : On floor
TAG : 1P23-EEH-6385 Rating : 415V, 302 kW Approx. Dimensions (LxBxH) : 1000 x 250 x 600 mm Approx. Weight : 250 kgs (overall) Mounting : On wall
TAG : 1P23-KAM-2782AB-SYNC.(Excitation Panels for H2 Rich Gas Compressor Motor) Construction : Floor mounting, single front Approx. Overall Dimensions (LxBxH)mm : 1650 x 750 x 2265 mm Approx. Weight : 1000 kg Mounting : On floor
TAG : 1P23-PM-8801A/B-VFD, 1P22-PM-3902A/B-VFD,1P22-PM-4001A/B-VFD Rating : 415V, up to 5.5 kW Approx. Dimensions (LxBxH) : 800 x 600 x 2000 mm Approx. Weight : 500 kgs (overall) Mounting : On floor
TAG : 1P24-EAM-0953A-VFD, 1P24-EAM-2451A/B-VFD , 1P23-EAM-2651A/B/C-VFD Rating : 415V, Above 5.5 kW, up to 15 kW Approx. Dimensions (LxBxH) : 1000 x 600 x 2000 mm Approx. Weight : 700 kgs (overall) Mounting : On floor
TAG : Various (VFD Panels) Rating : 415V, Above 15 kW, up to 30 kW Approx. Dimensions (LxBxH) : 1000 x 600 x 2000 mm Approx. Weight : 800 kgs (overall) Mounting : On floor
INDUCTION MOTORS AND CANOPIES Alignment as required for the accessories such as terminal box, assembling and installation of components / devices supplied separately as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. Checking of all interface connections, change of grease in bearings, wherever required, including supply of approved type of grease, no load/full load running of motor, including all labour and materials, as per specifications of this tender and directions of Site Engineer-in-Charge. Testing, precommissioning and commissioning activities are included in the scope.
MV (415V) Motors
Upto 3.0 kW
3.7 kW to 15 kW
18.5 kW to 37.0 kW
45.0 kW to 90 kW
110 kW to160 kW
Above 160 kW up to 315 kW
HV (6.6 kV) Motors
Above 160 kW up to 400 kW
Above 400 kW up to 800 kW
Above 800 kW up to 1200 kW
Above 1200 kW up to 1500 kW
Above 1500 kW up to 3000 kW
Above 3000 kW up to 7500 kW
Canopies
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of canopy for the motor - as per applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work, minor modifications (cutting, drilling etc.) in the canopy fitting arrangemet if required. Supply of all fixing hardware as per the site requirement is included in the scope.
MV (415V) Motors
Upto 3.0 kW
3.7 kW to 15 kW
18.5 kW to 37.0 kW
45.0 kW to 90 kW
110 kW to160 kW
Above 160 kW up to 315 kW
HV (6.6 kV) Motors
Above 160 kW up to 400 kW
Above 400 kW up to 800 kW
Above 800 kW up to 1200 kW
Above 1200 kW up to 1500 kW
Above 1500 kW up to 3000 kW
Above 3000 kW up to 7500 kW
MV (415V) Electric Heaters : Testing and commissioning of Electric Heaters of following ratings and checking of all interface connections including Electric Heater Junction box installation along with associated cables, terminations. Providing assistance for successful commissioning of heaters, laying and termination of braided cables to heater terminal box (as applicable), testing and commissioning works, including all labour and materials, as per approved drawings, specifications of this tender and directions of Site Engineer-in-Charge.
up to 5.5 kW
Above 5.5 kW but upto 22 kW.
Above 22 kW but upto 45 kW
Above 45 kW but upto 160 kW
Above 160 kW but upto 450 kW.
Above 1000 kW but upto 1750 kW.
LOCAL CONTROL STATIONS (LCS)
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of equipment, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. Testing, precommissioning and commissioning activities are included in the scope. Supply of installation materials (excluding structure steel) as per installation details-power and applicable construction documents are included in the scope. Fabrication and installation of steel support structure / supporting frames for equipment as per the site requirement, is considered separately in SECTION - F.
Industrial/ Explosive Atmospheres type LCS (wall / concrete / steel structure mounted)
INSTALLATION OF SWITCH-BOARDS, RELAY AND CONTROL PANELS, ANNUNCIATION PANELS, UPS SYSTEM, BATTERY CHARGERS, DISTRIBUTION BOARDS, CUBICLES WITH ELECTRICAL EQUIPMENT, VSD/ Softstarter PANELS, RTCC panles, MISC .ELECTRICAL PANELS, ETC Switchboards / panels indicated below excludes items already considered in sr. no. A/5 to A/9 above
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of various shipping sections / assemblies, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, interpanel wiring, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. Testing, precommissioning and commissioning activities are included in the scope. Minor civil work such as chipping, grouting for fixing of equipment and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. Supply of all fixing hardware as per the site requirement is included in the scope. Fabrication and installation of steel support structure / supporting frames for various equipment/ assmblies as per the site requirement, is considered separately in SECTION - F. Supply of all fixing hardware as per the site requirement is included in the scope.
Weight of the Unit above 100 upto 500 kg.
Weight of the Unit above 500 upto 1000 kg.
Weight of the Unit above 1000 upto 1500 kg.
Weight of the Unit above 1500 upto 3000 kg.
Weight of the Unit above 3000 upto 5000 kg.
ELECTRICAL HEAT TRACING SYSTEM
Installation of Heat Tracing System comprising Power Distribution Board-cum-Control Panel, Heat Tracers and Accessories (Connector, Junction Box, fastening material, etc.), Temp. sensing elements, Thermostats, etc. as per Specification (Doc no. TK-1P22A-EL-SPE-0031) Testing, precommissioning and commissioning activities are included in the scope. Supply of installation materials, fixing hardware etc as per Installation details and applicable construction documents are included in the scope
CABLE / WIRE LAYING, TERMINATION AND CABLE ROUTING SYSTEMS
CABLE LAYING
Handling, shifting of cable drums from site-store / yard to the installation location, unpacking, laying of cables / wires in cable trays (either located above ground or inside RCC cable trenches) / directly buried underground / in sand filled cable trenches (trench constructed by others) / in culverts, duct banks/ through above ground conduits (PVC / GI) clamped on wall or structure or through floor conduits (excluding lighting circuit cables, from LDB / ELDB onwards upto the lighting fixtures) - as recommended by MANUFACTURER / applicable construction documents and other associated work so as to ensure the completeness of installation work. Job also includes return of unused cable/drums to the Owner's store & removal of empty drum/ scrap cables to Owner's Scrap Yard. Testing, precommissioning and commissioning activities are included in the scope. Supply and installation of certified trefoil clamps of non-magnetic materia for 1 core cables, spacer bars and saddles, dressing of cables using Stainless Steel cable ties, cable tags(RFID tags) and ferrules (including all fixing hardware) as per the site requirement are included in the scope. The motorized winch required for cable pulling shall be arrange by contractor and no separate payment for the same will be made Minor civil work such as chipping / drilling of through-holes / cutouts in floor / walls, replastering and making area good after work done, providing sleeves during the cable laying as per the site requirement and replastering the same (including the supply of consumable material for the same) is included in the scope. Supply and Installation of cable route markers with warning tapes (as applicable) shall be as per 'Installation Details - Power' and applicable construction documents is included in the scope
HV CABLES
Cables with OD above 40 mm but upto 60 mm.
Cables with OD above 60 mm but upto 80 mm.
LV Power Cables Aluminium condutor cables
Cables with OD upto 20 mm.
Cables with OD above 20 mm but upto 30 mm.
Cables with OD above 30 mm but upto 40 mm.
Cables with OD above 40 mm but upto 50 mm.
Cables with OD above 50 mm but upto 60 mm.
Cables with OD above 60 mm but upto 80 mm.
Cables with OD above 80 mm but upto 100 mm.
Cables with OD above 100 mm but upto 120 mm.
LV Power/ Control/ Signal / Fire alram / Communication / Telephone etc - Copper condutor cables
Cables with OD upto 20 mm.
Cables with OD above 20 mm but upto 30 mm.
Cables with OD above 30 mm but upto 40 mm.
Cables with OD above 40 mm but upto 50 mm.
Cables with OD above 50 mm but upto 60 mm.
EARTHING CABLES (laid above ground/ Undergorund) 1100V Al / Cu conductor, PVC insulated, unarmoured earthing cables :- Laying and termination of earthing cables including supply of lug. laying,clamping and connecting individual equipment to the earthstrip or earth plate with following sizes of Cables including supply of required lugs, all hardware for connections, Including all labour and materails, as per approved drawings, specifications of this tender and directions of Engineer-in-charge
1 C x 6 sq.mm Cu Stranded, PVC insulated Green/Yellow cable
1 C x 16 sq.mm Cu Stranded, PVC insulated Green/Yellow cable
1 C x 25 sq.mm Cu Stranded, PVC insulated Green/Yellow cable
1 C x 50 sq.mm Cu Stranded, PVC insulated Green/Yellow cable
1 C x 95 sq.mm Cu Stranded, PVC insulated Green/Yellow cable
1 C x 25 sq.mm Al Stranded, PVC insulated Green/Yellow cable
1 C x 35 sq.mm Al Stranded, PVC insulated Green/Yellow cable
1 C x 50 sq.mm Al Stranded, PVC insulated Green/Yellow cable
1 C x 70 sq.mm Al Stranded, PVC insulated Green/Yellow cable
1 C x 120 sq.mm Al Stranded, PVC insulated Green/Yellow cable
GI Wire ropes
Laying,clamping and connecting individual equipment to the earthstrip or earth plate with following sizes of G.I wire / G.I wire rope, including supply of required lugs, conductors, all hardware for connections, Including all labour and materails, as per approved drawings, specifications of this tender and directions of Engineer-in-charge
8 SWG Solid GI wire
10 mm (3/8") Dia. flexible GI wire rope
16 mm (5/8") Dia. flexible GI wire rope
FIBRE OPTIC CABLES : "LAYING OF FIBRE OPTIC CABLE:The job includes collection and transportation of all required material from store to work site, laying of FO cable of various sizes along with HDPE conduits inclusive of supply of HDPE conduits, cutting of the cable as per actual measurement/ cableschedule, tagging at definite span length, dressing & clamping, providing identification tags at both ends, as required and complete the job in all respects as per specification, drawings and instructions of Engineer In-Charge HDPE conduit shall be as per IS-4984 or as per equivalent IEC code. The outer sheath colour of HDPE conduits shall be orange with black for the fittings throughout the fibre optic cable run.
Fibre Optic Cable - up to 8 Fibre
Fibre Optic Cable - 12 Fibre
Fibre Optic Cable - 24 Fibre
FLEXIBLE CONDUCTOR CABLES
650V / 1100V (Uo / U) voltage grade, Multistranded Cu conductor, PVC insulated, flexible cable
Cables with OD upto 20 mm.
Cables with OD above 20 mm but upto 30 mm.
Special cables
Silicon Insulated Flexible cable / Uninyvin cables
Cables with OD upto 20 mm.
Cables with OD above 20 mm up to 40 mm
CAT 6A Cable
MODBUS SERIAL RS485
CABLE GLANDING AND TERMINATION (HV) (Industrial / For Explosive Atmospheres)
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembly and installation of HV cable termination kit and cable glands with PVC hoods, installation of components supplied separately - as recommended by MANUFACTURER / applicable construction documents, installation of tinned copper lug, drilling and treading of gland plate, termination of cable at designated location and other associated work so as to ensure the completeness of installation work.
Cable termination shall be carried out by experienced, competent & certified personnel from the termination kit MANUFACTURER / installation CONTRACTOR.
Glanding and Termination of 6.6 / 6.6 kV (UE) voltage grade, Al / Cu conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY
1C x 630 sq.mm A2XCEFY
HV Cable termination kit Separable Connector type (suitable for indoor installation) 6.6kV (UE) HV cables grade, Al conductor, XLPE insulated, screened, armoured power cable. Motor cable TB is suitable for Elastimold Separable connector. The Separable connectors will be supplied by motor manufacturer and will be free issue to the contractor. Contractor to supply THREE CORE HEAT SHRINKABLE BREAKOUT KIT and carry out the complete installation of the separable connector kit.
3C x 240 sq.mm
Glanding and Termination of 33 / 33 kV (Uo / U)grade, Al conductor, XLPE insulated, screened, armoured power cable
1C x 630 sq.mm A2XCEWaY
CABLE GLANDING AND TERMINATION (MV) (Industrial / For Explosive Atmospheres)
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembly and installation of cable glands (industrial / For Explosive Atmospheres type) with PVC hoods, installation of components supplied separately - as recommended by MANUFACTURER / applicable construction documents, installation of lug, drilling and treading of gland plate, termination of cable (excluding lighting circuit cables, from SLDB / ESLDB onwards upto the lighting fixtures) at designated location and other associated work so as to ensure the completeness of installation work. Scope shall include drilling of holes, if not provided by manufacturer. Supply of Crimping type Lugs shall be included in the cost. Type of Lug shall be as per type of terminals provided in equipment. For CT circuits Ring type lug shall be used. For Control cables,Tinned copper lugs shall be insulated, Ring / Pin / Fork crimping type as per terminal requirments. For Power cables, lugs shall be tinned copper / Aluminium (Tinned Copper lugs for copper conductor cable and Aluminium Lugs for Aluminium conductor cables ) tubular type, heavy duty long barrel lugs for bolted connection Supply and installation of Bi-metallic washer if the material of bus bar and Lugs are dissimilar are included in Contractor scope.
MV POWER CABLES Glanding and Termination of 650 / 1100V (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), XLPE insulated, screened, armoured power / lighting cables
Cables with OD up to 20 mm
Cables with OD above 20 mm but up to 30 mm
Cables with OD above 30 mm but up to 40 mm
Cables with OD above 40 mm but up to 50 mm
Cables with OD above 50 mm but up to 60 mm
Cables with OD above 60 mm but up to 80 mm
MV CONTROL ,FIRE ALARM AND COMMUNICATION CABLES Glanding and Termination of 650 / 1100V (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), PVC/XLPE insulated, screened, armoured control, Fire Alarm and Communication Cables
All sizes from 2 to 7 cores and upto 2.5 sq. mm
All sizes from 8 to 16 cores and upto 2.5 sq. mm
All sizes from 17 to 24 cores and upto 2.5 sq. mm
All sizes from 1P to 4P and upto 2.5 sq. mm
All sizes from 5P to 10P and upto 2.5 sq. mm
All sizes from 11P to 15P and upto 2.5 sq. mm
All sizes from 16P to 30P and upto 2.5 sq. mm
All sizes from 30P to 50P and upto 2.5 sq. mm
All sizes from 50P to 100P and upto 2.5 sq. mm
All sizes from 1T to 8T and upto 2.5 sq. mm
Glanding and Termination of FIBRE OPTIC CABLES (Single Mode / Multi Mode) Scope includes Supply of kit, preparation of all fibres and splicing / patching, OTDR measurement, Supply of adequate consumables for the execution of the work (such as fibre optic connectors suitable for the application) testing, tools & tackles, manpower, etc. all complete as per direction of Engineer-in-Charge is included in scope.
Fibre Optic Cable - 6 / 8 Fibre
Fibre Optic Cable - 12 Fibre
Fibre Optic Cable - 24 Fibre
Termination of armoured Jelly filled cables and connection of leads excluding the supply of cable glands and lugs but including fixing of cable glands, supply and fixing of PVC shrouds for outdoor terminations, cutting, stripping of cable insulation, crimping the lug on to the conductor, clamping of the cable- cores, marking with wire number, ferrules etc., including all labour and materials, as per approved drawings, specifications of this tender and directions of Site Engineer-in-Charge
All sizes from upto 5 pair
All sizes above 5 pair upto 30pair
All sizes above 30 pair upto 50pair
All sizes above 50 pair upto 100pair
WIRES AND FLEXIBLE CONDUCTOR CABLES
Termination of 1100V, Multistranded Cu conductor, PVC insulated, flexible wires
Cables with OD upto 20 mm.
Cables with OD above 20 mm but upto 30 mm.
Glanding & Termination of Special cables
Silicon Insulated Flexible cable / Uninyvin cables
Cables with OD upto 20 mm.
Cables with OD above 20 mm up to 40 mm
CAT 6A Cable (The scope includes supply of RJ 45 plug)
Modbus RS 485
CABLE JOINTING
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembly and installation of straight through joint kits, installation of components supplied separately - as recommended by MANUFACTURER / applicable construction documents, and other associated work so as to ensure the completeness of installation work. Civil work such as construction of concrete chamber with cover (for cables directly buried underground) as per the site requirement (including the supply of consumable material for the same) is included in the scope.
HV CABLES
Straight through joint for 6.6 / 6.6 kV (UE) voltage grade, Al / Cu conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY (UE)
Straight through joint for 33 / 33 kV (Uo / U)grade, Al conductor, XLPE insulated, screened, armoured power cable
1C x 630 sq.mm A2XCEWaY
MV CABLES
650 / 1100V (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), XLPE insulated, screened, armoured power / control / lighting cables
Cables with OD upto 20 mm.
Cables with OD above 20 mm but upto 30 mm.
Cables with OD above 30 mm but upto 40 mm.
Cables with OD above 40 mm but upto 50 mm.
Cables with OD above 50 mm but upto 60 mm.
Cables with OD above 60 mm but upto 80 mm.
Installation of Jointing kits (for joints between Single/ MultiMode Fiber Optic armoured cables), Preparation of all fibres, splicing / patching, OTDR measurement, Supply of adequate consumables for the execution of the work (such as fibre optic connectors suitable for the application),testing, tools & tackles, manpower, etc. all complete as per direction of Engineer-in-Charge.
6/8 Fiber
24 Fiber
PREFABRICATED CABLE TRAYS
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembly and installation of prefabricated galvanized steel ladder type / perforated cable trays / FRP cable trays (above ground or inside concrete trenches) with all associated accessories such as bends, reducers, T-joints, fixing clamps, earthing continuity conductors etc. - as recommended by MANUFACTURER / applicable construction documents, fixing of cable trays / associated accessories to steel supports, stenciling with paint as required and other associated work so as to ensure the completeness of installation work. Site fabrication of cable tray accessories such as bends, reducers, T-joints etc. from cable tray straight runs as per the site requirement is included in the scope. For prefabricated cable trays accessories such as bends, reducers, T-joints etc. installtion of coupler plates is included in scope. For Ladder type Cable tray, the Bends/ Risers/ Tees are prefabricated/site fabricated. Cable tray bends/ riser/Tees etc on pipe rack are preferebally prefabricated. Rest of the bends can be site fabricated as per instructions given by Engineer-in-Charge. For perforated trays upto and including 150mm, the Bends/ Risers/ Tees/ Redcuers with covers shall be site fabricated as per instructions given by Engineer-in-Charge Fabrication and installation of steel support / bracket for cable trays / accessories as per the site requirement, is considered separately in this SOR. Supply of all fixing hardware as per the site requirement is included in the scope.
Cable Trays Perforated (GI) and Accessories
Installation of cable tray accessories such as bends, reducers, T-joints etc. is considered in cable tray running length.
50 mm wide
100 mm wide
150 mm wide
Cable Ladders (GI) and Accessories
Installation of cable tray accessories such as bends, reducers, T-joints etc. is considered in cable tray running length.
150 mm wide
300 mm wide
600 mm wide
Cable Tray Covers (Bottom / TOP) (GI) and Accessories
100 mm wide
150 mm wide
300 mm wide
600 mm wide
Separators for Cable Ladders (GI)
300 mm / 600 mm wide
CONDUITS FOR CABLE LAYING / PROTECTION
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembly and installation of heavy duty rigid GI / PVC conduits on wall / concrete / steel structure (with edge protection grommet at either ends for GI conduits), cutting, bending of conduits and other associated work so as to ensure the completeness of installation work. Installation of GI clamps, reducers / adaptors for the conduits, tees, pull boxes as per the site requirement and the associated work is included in the scope. Supply of waterproof compound (of reputed make) and sealing of conduit openings after laying of cable by applying the same is included in the scope. Civil work such as chipping / drilling of through-holes / cutouts in floor / walls (as per the site requirement) and replastering and making area good after installation of conduits as per the site requirement (including the supply of consumable material for the same) is included in the scope. Supply of all fixing hardware as per the site requirement is included in the scope. Installation of conduits and associated accessories for 'Point Wiring for Office buildings / Control rooms / Other rooms with false ceiling' is considered separately in SECTION - C
Rigid GI conduits
25 mm nominal dia
50 mm nominal dia
100 mm nominal dia
150 mm nominal dia
Rigid GI conduits RED coloured (For Fire Alarm System cables)
25 mm nominal dia
50 mm nominal dia
Heavy duty PVC conduits
25 mm nominal dia
50 mm nominal dia
Flexible PVC conduits
25 mm nominal dia
LIGHTING, SMALL POWER, WELDING SOCKETS AND JUNCTION BOXES
LIGHTING
Installation of Industrial / For Explosive Atmospheres type lighting fixtures Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of lighting fixtures, assembling and installation of components / accessories such as lamps, chokes, condensers, reflectors, control gear box for non-integral fixtures etc. supplied separately - as recommended by MANUFACTURER / applicable construction documents, checking of internal wiring, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work' The scope is inclusive of Installation of loop-in / loop-out junction box / connector &associated with each fixtures- as per applicable installation details with associated cabling, glanding, termination of cable from Junction box / connectors to Light fixture. Installation of lighting fixtures shall be as per 'Installation Details - Lighting' and applicable construction documents. Testing, precommissioning and commissioning activities are included in the scope. Installation of lighting fixtures shall be as per 'Installation Details - Lighting' and applicable construction documents. The supply of installation materials (except lighting poles and structure steel) as per "Installation Details-Lighting" and including any additional material as per site requirement so as to ensure the completeness of installation work is included in the scope.
Installation of Poles are considered separately. Fabrication, surface preparation, painting and installation of steel support of steel support structure / supporting frames as per the site requirement for above shall be considered separately in SECTION - F
Lighting Fixtures
Fluorescent lighting fixtures
Installation Type : L09A
Installation Type : L09B
Installation Type : L09C
Installation Type : L10
Well glass lighting fixtures
Installation Type : L07A
Installation Type : L07B
Installation Type : L07C
Installation Type : L07D
Installation Type : L07E
Installation Type : L07F
Installation Type : L04
Installation Type : L05
Installation Type : L06
Medium bay / high bay lighting fixtures
Installation Type : L13A
Installation Type : L13B
Installation Type : L13C
Flood lighting fixtures
Installation Type : L12
Installation Type : L02
Installation Type : L11
Emergency lighting fixture with built-in battery (Installation types same as listed under Section C1.1.1 to C1.1.5)
Insatallation Type : L09B
Emergency EXIT sign with built-in battery
Installation Type : L16
Installation Type : L17
Installation Type : L18
Installation Type : L19
Installation Type : L20
Installation Type : L21
Aviation light (flashing / steady burning) with controller
Installation Type : L14A
Installation Type : L14B
Installation Type : L14C
Vessel lamps
Installation Type : Flange Mounted on Sight Glasses
Installation of Lighting Poles Installation, alignment & earthing of single arm GI lighting pole as per approved drawing along with supply of fixing hardware like U clamp & bolt, for platform mounted pole. Including welding, structuralworks, paint and all sundry materials as required. For ground mounted poles it includes supply and fixing of G.I pipes, G.I flat for earthing purpose, steel, base plates, paint and all sundry materials as required. Including all labour and materials complete as per approved drawings, specification of this tender and directions of Engineer-in-charge. This shall include local transportation from storage area to actual place of installation by contractor's own lifting & transporting arrangement.The installation of Lighting pole will be carried out as per IFC drawing & suit to site conditions to avoid fouling with other Piping, Structure & access ways. Refer tender documentation, including Typical installation drawings, RFC construction drawings and as per direction of Engineer In-Charge
Installation details : L04
Installation details : L05
Installation details : L11
Installation details : L14A
Junction boxes for Lighting Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of junction boxesand associated accessories on wall / concrete / steel structure - as recommended by MANUFACTURER / applicable construction documents, checking of internal wiring, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. Testing, precommissioning and commissioning activities are included in the scope. Minor civil work such as chipping, grouting for fixing of various equipment, replastering and making area good etc.as per the site requirement (including the supply of consumable material for the same) is included in the scope. Installation of Junction Boxes shall be as per 'Installation Details - Lightingr' and applicable construction documents. The supply of installation materials (excludingstructure steel) as per "Installation Details-Lighting" and including any additional material as per site requirement so as to ensure the completeness of installation work is included in the scope. Supply of all fixing hardware as per the site requirement is included in the scope. Fabrication, surface preparation, painting and installation of steel support of steel support structure / supporting frames as per the site requirement for above shall be considered separately in SECTION - F Installation of loop-in / loop-out junction box / connector are covered in the installation of respective light fixture installation. The qty indicated below are lighting junction boxes required for lighting branch circuits/
Installation Type : L08B / L08C / L08D / L08E / L08F / L08G
Point Wiring for Office buildings / Control rooms / Other rooms with false ceiling
Installation of surface wiring / concealed wiring (in brick wall / decorative type aluminium partition in office rooms) using 2.5sq. mm flexible copper PVC wires, GI / PVC conduits, assembly and installation / embedding of heavy duty rigid GI / PVC conduits on / in wall / concrete structure (with edge protection grommet at either ends for GI conduits), cutting, bending of conduits - as per the applicable construction documents and other associated work so as to ensure the completeness of installation work. Installation of GI clamps, reducers / adaptors for the conduits, tees, pull boxes as per the site requirement and the associated work is included in the scope. Civil work such as chipping / drilling of through-holes / cutouts in walls (as per the site requirement) and replastering and making area good after embedding of conduits as per the site requirement (including the supply of consumable material for the same) is included in the scope. Testing, precommissioning and commissioning activities are included in the scope. Supply 2.5 sq.mm flexible copper PVC wires as requried, supply GI conduits for SURFACE CONDUIT WIRING / PVC conduits for CONCEALED CONDUIT WIRING and associated accessoreis such as GI clamps, reducers / adaptors for the conduits, tees, pull boxes, along with all fixing hardware as per the site requirement is included in the scope. For installation of wires above false ceiling / below false floor, conduits can be installed on surface of wall / concrete structure, after consultation with OWNER / CONSULTANT. Elsewhere, installation of wires shall be in concealed conduits.
Primary Circuit (From SLDB / ESLDB / Lighting Junction Box upto Switch Box for local control)
1 point (wire length approx. 20m)
1 point (wire length approx. 30m)
1 point (wire length approx. 40m)
1 point (wire length approx. 50m)
1 point (wire length approx. 60m)
Secondary Circuit (From Switch Box for local control upto the lighting fixture / 5A/15A switch socket outlet / fan etc.)
1 point (total wire length approx. 7m)
2 point (total wire length approx. 15m)
3 point (total wire length approx. 22m)
4 point (total wire length approx. 30m)
5 point (total wire length approx. 40m)
6 point (total wire length approx. 50m)
7 point (total wire length approx. 60m)
Laying, Glanding and Termination for lighting circuit cables (650 / 1100V (Uo / U) voltage grade, Cu conductor (stranded / solid), XLPE insulated, armoured) from SLDB / ESLDB onwards upto the lighting fixtures / associated control gear boxes / junction boxes (applicable for all Lighting Fixtures, excluding Street Lighting Fixtures and Lighting Fixtures for Office buildings / Control rooms / Other rooms with false ceiling) Handling, shifting of cable drums from site-store / yard to the installation location, unpacking, laying of lighting circuit cables / wires in cable trays / through above ground conduits (PVC / GI) clamped on wall or structure or through floor conduits / by cleating of cables to concrete / wall / steel structrues by saddles - as per applicable construction documents and other associated work so as to ensure the completeness of installation work. Handling, shifting of cable drums from site-store / yard to the installation location, unpacking, laying of lighting circuit cables / wires in cable trays / through above ground conduits (PVC / GI) clamped on wall or structure or through floor conduits / by cleating of cables to concrete / wall / steel structrues by saddles - as per applicable construction documents and other associated work so as to ensure the completeness of installation work. Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembly and installation of cable glands (industrial / For Explosive Atmospheres type) with PVC hoods, installation of components supplied separately - as recommended by MANUFACTURER / applicable construction documents, installation of lug, termination of cable at designated location and other associated work so as to ensure the completeness of installation work. Supply of all fixing hardware such as spacer bar, saddles, UV resistant PVC cable ties, Al cable tags, PVC hoods, etc. as as per the site requirement is included in the scope. Quantity of Lighting Fixtures, associated control gear boxes / junction boxes is defined in this document under the respective headings. The quantity of total looping cable length required for the work is mentioned below.
3 C X 2.5 sq.mm
3 C X 4 sq.mm
3 C X 6 sq.mm
3 C X 10 sq.mm
EXHAUST FANS AND CEILING FANS
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of exhaust / ceiling fans and associated accessories - as recommended by MANUFACTURER / applicable construction documents, checking of internal wiring other associated work so as to ensure the completeness of installation work Testing, precommissioning and commissioning activities are included in the scope. Minor civil work such as chipping, modifications in the wall cutout as required, grouting of frame, replastering and making area good etc.as per the site requirement (including the supply of consumable material for the same) is included in the scope. Supply of all fixing hardware as per the site requirement is included in the scope.
Industrial type Exhaust fans
300mm dia.
450mm dia.
600mm dia.
Exhaust fans For Explosive Atmospheres
300mm dia.
450mm dia.
600mm dia.
SMALL POWER
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of small power equipment and associated accessories such as control switches, socket outlets, modular box, face plate etc. - as recommended by MANUFACTURER / applicable construction documents, checking of internal wiring other associated work so as to ensure the completeness of installation work Testing, precommissioning and commissioning activities are included in the scope. Minor civil work such as chipping, grouting for fixing of various equipment, replastering and making area good etc.as per the site requirement (including the supply of consumable material for the same) is included in the scope. Supply of all fixing hardware as per the site requirement is included in the scope.
SWITCH SOCKET OUTLETS
Civil work such as chipping of walls (as per the site requirement) and replastering and making area good after embedding of modular boxes for switch boxes, as per the site requirement (including the supply of consumable material for the same) is included in the scope.
Decorative type switch socket outlets
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 1 no. piano type switch
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 2 nos. piano type switches
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 3 nos. piano type switches
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 4 nos. piano type switches
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 5 nos. piano type switches
Decorative type switch socket box with 1 no. 5/15A switch socket unit
Decorative type switch in single module with 1 no. 5A piano type switches
Decorative type switch in double module with 2 no. 5A piano type switches
Decorative type switch in tripple module with 3 no. 5A piano type switches
Decorative type switch in quad module with 4 no. 5A piano type switches
Decorative type switch socket switchboard with 5/15A, 5 pin, socket outlet with 15A switch and 'ON' LED indication & fuse
Surface / Concealed mounting type ( 2-Module) RJ 11 / RJ 45 Connectors Female type complete with Moduler box, cover plate etc. for telephones
Industrial type switch socket outlets (for Indoor Installation)
20A, single phase switch socket outlet with 1no. 3 pin socket and 1 No. 20 A, 10 kA, SPMCB, in sheet steel enclosure
CONVENIENCE SWITCH SOCKET OUTLETS (Wall/column/structure/Railing mounted)
Installation of Industrial / Explosive Atmospheres type Switch Socket Outlets shall be as per 'Installation Details - Lighting and applicable construction documents. Supply of Installation materials (excluding structure steel) as per 'Installation Details - lighting' is included in the scope. Fabrication and installation of steel support structure as per the site requirement, is considered separately in SECTION - F.
Convenience sockets (single phase) Installation Type : L15A / L15B / L15C / L15D
24V, 5A switch socket unit for Industrial / Explosive Atmospheres, with built-in 100VA, 220V / 24V transformer, Installation Type : L15A / L15B / L15C / L15D
JUNCTION BOXES (JB) AND POWER JUNCTION BOXES (PJB) FOR MOTORS / OTHER EQUIPMENT - - Industrial / Explosive Atmospheres type
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of junction boxes (except lighting JB) / power junction boxes and associated accessories on wall / concrete / steel structure - as recommended by MANUFACTURER / applicable construction documents, checking of internal wiring, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. Testing, precommissioning and commissioning activities are included in the scope. Supply of Installation materials (excluding structure steel) as per Installation details-Power is included in the scope. Fabrication and installation of steel support structure as per the site requirement, is considered separately in SECTION - F. Installation of Junction Boxes shall be as per 'Installation Details - Power' and applicable construction documents.
Weight of Unit up to 5 kg
Weight of Unit above 5 kg, but up to 20 kg
Weight of Unit above 20 kg, but up to 100 kg
Weight of Unit above 100 kg, but up to 200 kg
POWER SOCKET OUTLETS
Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of switch socket outlets and associated accessories such as control switches, socket outlets, junction box, front plate etc. on wall / concrete / steel structure - as recommended by MANUFACTURER / applicable construction documents, checking of internal wiring, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. Testing, precommissioning and commissioning activities are included in the scope. Installation of Industrial / Explosive Atmospheres type Power socket outlets shall be as per 'Installation Details - Power' and applicable construction documents. Supply of Installation materials (excluding structure steel) as per 'Installation Details - Power' is included in the scope. Fabrication and installation of steel support structure as per the site requirement, is considered separately in SECTION - F.
Industrial / Explosive Power Socket Outlets
Installation Type : P10A/B
Installation Type : P15
Installation Type : P17
FIRE ALARM AND COMMUNICATION SYSTEMS
FIRE ALARM (FA) SYSTEM
Handling, shifting from site-store / yard to the installation location, unpacking, assembling and installation of various components in FA system and associated accessories such as manual call points, plug-in devices, bases for devices etc. on wall / concrete / steel structure - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required andand other associated work so as to ensure the completeness of installation work. Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. Minor civil work such as chipping, grouting for fixing of various equipment and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. Supply of Installation materials (excluding structure steel) as per 'Installation Details - FA System' is included in the scope. Supply of all fixing hardware as per the site requirement is included in the scope. Installation shall be as per 'Installation Details - Fire Alarm System' and applicable construction documents. Fabrication and installation of steel support structure as per the site requirement, is considered separately in SECTION - F.
Central FA panel TAG : LATER Approx. Dimensions (LxBxH) : 600 x 600 x 2000 mm Approx. Weight : 200 kgs Mounting : Wall mounted / Column mounted / On False floor supported with structural steel base frame Location : SRR (Indoor)
FA system accessories Industrial type / Explosive Atmospheres
Installation Type: FAHC1
Installation Type: FAHS1
Installation Type: FAHZ1
Installation Type: FASC1
Installation Type: FASC2
Installation Type: FASS1
Installation Type: FCPC1
Installation Type: FCPC2
Installation Type: FCPP1
Installation Type: FCPP2
Installation Type: FCPR1
Installation Type: FCPS1
Installation Type: FMDC1
Installation Type: FMDF1
Installation Type: FMDF2
Installation Type: FMDF3
Installation Type: FMDS1
Installation Type: FRIC1
Installation Type: FRIF1
Installation Type: FCPS2
Installation Type: CFBC1
Installation Type: CFBS1
PUBLIC ADDRESS (PA) SYSTEM
Handling, shifting from site-store / yard to the installation location, unpacking, assembling and installation of various components in PA system and associated accessories such as field call stations, acoustic hoods etc. on desk / wall / concrete / steel structure - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. Minor civil work such as chipping, grouting for fixing of various equipment and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. Supply of Installation materials (excluding structure steel) as per 'Installation Details - Communication & PA System' is included in the scope. Supply of all fixing hardware as per the site requirement is included in the scope. Installation shall be as per 'Installation Details - Communication & PA System' and applicable construction documents. Fabrication and installation of steel support structure as per the site requirement, is considered separately in SECTION - F.
Central PA panel Approx. Dimensions (LxBxH) : 800 x 800 x 2000 mm Approx. Weight : 250 kgs Mounting : On False floor supported with structural steel base frame Location : SRR (Indoor)
Master Control Station Installation of Master Control Station (MCS) consisting of control key board, Loud speaker, goose-neck microphone, console mounted handset, headset and other accesories (Installation Type: CMCS1) Mounting : Desk stop
PA system accessories Industrial type / Explosive Atmospheres
Installation Type: CTFC1
Installation Type: CTFC2
Installation Type: CTFR1
Installation Type: CTFR2
Installation Type: CTFS2
Installation Type: CTFS3
Installation Type: CFBC1
Installation Type: CFBR1
Installation Type: CFBS1
Installation Type: CSPKC1
Installation Type: CSPKC2
Installation Type: CSPKC3
Installation Type: CSPKF1
Installation Type: CSPKP1
Installation Type: CSPKS1
Installation Type: CSPKR1
Installation Type: CMCS1
TELEPHONE SYSTEM Handling, shifting from site-store / yard to the installation location, unpacking, assembling and installation of various components in PA system and associated accessories such as field call stations, acoustic hoods etc. on desk / wall / concrete / steel structure - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. Minor civil work such as chipping, grouting for fixing of various equipment and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. Supply of Installation materials (excluding structure steel) as per 'Installation Details - Communication & PA System' is included in the scope. Supply of all fixing hardware as per the site requirement is included in the scope. Installation shall be as per 'Installation Details - Communication & PA System' and applicable construction documents. Fabrication and installation of steel support structure as per the site requirement, is considered separately in SECTION - F.
Installation of Telephine Ststem cabinet onsists of Access switch, Media gate wat etc
Installation shall be as per 'Installation Details - Communication & PA System' and applicable construction documents.
Telephone ( Industrial type / Explosive Atmospheres)
Installation Type: CTFC2
Installation Type: CTFS2
Installation Type: CTFZ1
Junction boxes
Telephone System Junction Box / IDF with 1 nos. 20 Pair incoming cable(s) and 20 nos 1 Pair outgoing cable(s)
CCTV SYSTEM Handling, shifting from site-store / yard to the installation location, unpacking, assembling and installation of various components in CCTV system and associated accessories such as cameras, JBs, plug-in devices, bases for devices etc. on wall / concrete / steel structure / Self standing - as recommended by MANUFACTURER / applicable construction documents, stencilling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. Supply of all the Installation Material and Installation shall be as per 'Installation Details - Communication & PA System' and applicable construction documents and applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work. and as per approved drawings, specifications of this tender and directions of Engineer-in-Charge.. Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. Minor civil work such as chipping, grouting for fixing of various equipment and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope.
CCTV Cabinet Approx. Dimensions (LxBxH) : 800 x 800 x 2000 mm Approx. Weight : 250 kgs Mounting : On False floor supported with structural steel base frame Location : SRR (Indoor)
Cameras
Installation of Cameras including wiper & washer system and mounting poles/ structures, with required civil foundations, supply and installations erection material etc. as applicable are included in scope
Installation Type: CTVC1
Installation Type: CTVC2
Installation Type: CTVR1
Installation Type: CTVS1
EARTHING AND LIGHTNING PROTECTION
Handling, shifting from site-store / yard to the installation location, unpacking, assembling and installation of earthing and lightning protection systems and accessories underground / wall / concrete / steel structure / cable trays - as recommended by MANUFACTURER / applicable construction documents and other associated work so as to ensure the completeness of installation work. Testing, precommissioning and commissioning activities are included in the scope.
EARTHING
Installation shall be as per 'Installation Details - Earthing' and applicable construction documents.
Installation of earth conductor laid underground
Installation and connection of GI earthing strip buried individually at a depth of 600 mm including welding at joints, providing anti-corrosive paint r bitumen and jute covering for welded portion, clamping and necessary hardware for connecting, excavation and refilling etc., including all labour and materials, as per approved drawings & specifications For GI earthing conductors, laying of conductor including bending, drilling, welding / jointing as required is included in the scope. For GI earthing conductors, supply and application of coal tar bituminous paint or cold galvanising paint on welded joints is included in the scope. Excavation of soil up to the required depth, installation of earth conductor (GI strip / bare copper conductor / insulated copper cable), back filling and compacting of soil and disposing the excess soil, termination as required is included in the scope
40 x 5 mm GI strip
25x 6 mm GI strip
50 x 6 mm HDGI strip
75 x 10 mm HDGI strip
Installation of earth conductor laid on wall / concrete / steel structure / cable trays Installation of earth conductor (GI strip) on wall / concrete / steel structure / cable trays by cleating at every 500mm, termination as requied. For GI earthing conductors, laying of conductor including bending, drilling, welding / jointing as required is included in the scope. For GI earthing conductors, supply and application of coal tar bituminous paint or cold galvanising paint on welded joints is included in the scope. Supply of all fixing hardware as per the site requirement is included in the scope.
50 x 6 mm HDGI strip
75 x 10 mm GI strip
Installation of earth conductor to be embedded in finished concrete floors Installation of earth conductor (GI strip) on concrete floors For GI earthing conductors, laying of conductor including bending, drilling, welding / jointing as required is included in the scope. For GI earthing conductors, supply and application of coal tar bituminous paint or cold galvanising paint on welded joints is included in the scope. Civil work such as chipping / drilling of through-holes / cutouts in floor and replastering and making area good after installation of conductor as per the site requirement (including the supply of consumable material for the same) is included in the scope.
40 x 5 mm GI strip
50 x 6 mm GI strip
75 x 10 mm GI strip
Installation of earthing / lightning protection electrodes
Excavation of soil upto the required depth, installation and testing of earth electrode, filling of the pit with the appropriate material as required, earthing connection of earth electrode with main earth grid, back filling, compacting of soil, disposing the excess soil. Civil work including construction of concrete chamber with cover for the earth pit as per the site requirement is included in the scope.
Installation Type : E01A
Installation Type : E01B
Installation of earth buses Installation and testing of earth buses on wall / concrete / steel structure / cable trays. Supply of all fixing hardware as per the site requirement is included in the scope. Fabrication and installation of steel support structure as per the site requirement, is considered separately in SECTION - F.
Installation Type : E02A
Installation Type : E02B
Installation Type : E20
Installation Type : E22
Install following Earthing Material as per Installation Type : E14 1. 9 DIA G.I. BAR 2. SHARP JAW TONG TYPE HEAVY DUTY SPRING CLAMP-100A
Installation of Pipe line Flange/ Pipe Earthing material as per Installation Standard E09/E10 (Doc. No.TK-1P22A-EL-STD-0003), .This shall include installation of 10 MM (3/8") DIA GI WIRE ROPE for the no. of Flange connections.The Termination scope also includes supply of lugs for GI wire rope and all hardware etc. Refer List For Pipe Line Bonding (Doc. No.TK-1P22A-EL-LST-0010 ) for details of Flange earthing
LIGHTNING PROTECTION
Installation shall be as per 'Installation Details - Lightning Protection' and applicable construction documents.
Installation of lightning protection conductor laid on wall / concrete / steel structure / roof Installation of lightning protection conductor (GI strip) on wall / concrete / steel structure including the installation of test links and accessories, insulator supports, termination as required. For GI earthing conductors, laying of conductor including bending, drilling, welding / jointing as required is included in the scope. Supply of Installation materials (excluding structure steel) as per installation details-Earthing" is included in the scope. Supply of all fixing hardware as per the site requirement is included in the scope.
25 x 6 mm HDGI strip
Installation of lightning protection rods / finials
Installation of of lightning arrestors, including the required supporting arrangement.
Supply of all fixing hardware as per the site requirement is included in the scope.
Installation Type : E24
Installation Type : E25
Installation Type : E26
Installation Type : E27
STRUCTURAL STEEL
Fabrication, erection (by welding / fixing by anchor fastners), surface preparation and painting of structural steel as per the applicable construction documents so as to ensure the completeness of installation work for all the electrical equipment / items mentioned in Section A to E above, and chequered plates as per the applicable construction documents. Supply of all consumables such as welding electrodes (Advani Oerlikon or equivalent), gas for cutting etc. are included in the scope. Measurement of steel quantity for installation shall be based on actual quantities installed at site without wastage allowance. Surface preparation and painting of steel shall be as per doc. TP-1ZZZA-PI-SPE-0003. (Technical Specification for Painting)
Structural steel (MS)
Galvanised Iron (GI)
MISCELLANEOUS ITEMS
CIVIL WORK
Excavation
Excavation in soil for the purpose of cable laying activity up to a depth of 2m (maximum) and width of trench 4m (maximum) considering all the relevant safety standards, backfilling the excavated area after cable laying activity, consolidation after backfilling and disposing the surplus earth at required location. Installation of soft sand of known resistivity, red coloured concrete tiles of appropriate voltage grade for cable protection, warning tapes, cable markers(including RFID tags) etc. (after cable laying activity is completed) is included in the scope.
Soft / medium soil (Excavation & Back-filling)
Miscellaneous civil work
Activities indicated below are already included in 'SECTIONS - A to E' of this document. Unit rates are requested in the event that additional work is required over and above that already identified in 'SECTIONS - A to E'. The below mentioned rates shall be applicable only if specifically agreed & approved by OWNER / CONSULTANT.
Chipping / drilling of through-holes / cutouts in concrete floor / beam, replastering and finishing the same
Chipping / drilling of through-holes / cutouts in brick walls and replastering the same.
Manual excavation of all types of soil and backfilling the excavated area, consolidation after backfilling and disposing the surplus earth at a point outside the site
Laying of RCC hume pipes of dia 150mm for road crossing including excavation of road upto a depth of 1500 mm back filling and consolidating the surface. Supply of RCC hume pipes of reputed make as required, and civil work such as excavation, installation of hume pipes (including the supply of consumable material for the same), backfilling is included in the scope.
filling/spreading of certified soft sand of known resistivity in the concrete trenches build by others after laying of cables, compacting the same. The scope includes removal of RCC trench covers/ slab, refixing of RCC trench Covers/Slabs after filling / spreading the sand, including all labour and materials complete as per approved drawings, specification of this tender and directions of Engineerin-in-charge
Installation of approved second class bricks of 75 mm thickness in cable trenches for cable protection, including all labour and materials, as per approved drawings, specifications of this tender and directions of Engineer-in-Charge. (Actual area of laid brick surfaces shall be measured).
Installation of approved Red coloured concrete tiles in cable trenches for cable protection, including all labour and materials, as per approved drawings, specifications of this tender and directions of Engineer-in-Charge. (Actual area of laid brick surfaces shall be measured). The scope includes supply and installation of warning tape as per Installation details
Anchor fasteners
Installation of heavy duty Galvanised steel anchor fasteners for supporting various equipment, in brick work / concrete work Installation of anchor fasteners indicated below excludes those already considered in various applicable 'Installation Details' mentioned in 'SECTIONS - A to E' in this document. Installation of anchor fasteners indicated below excludes those already considered in various applicable 'Installation Details' mentioned in 'SECTIONS - A to E' in this document
Anchor fasteners M8 type x 60mm
Anchor fasteners M10 type x 75 mm
Anchor fasteners M12 type x 100 mm
SAFETY ITEMS
Installation of safety items mentioned below, in all the electrical rooms / buildings / transformer yards, etc. as per applicable statutory requirements / HSE documents / as indicated in applicable construction documents.
Enameled caution boards for 33 kV.
Enameled caution boards for 6.6 kV.
Enameled caution boards for 1.1 kV.
Enameled Danger plates to be installed in electrical rooms such as transformer bay, switchgear room etc.
3 ply Lamicoid tag plates of appropriate size for various equipment, with White letters on Black background, as per the site requirement
Epoxy insulating floor coating (Valency Compound Make - Valency-111 CLASS A or equivalent
33kV System
6.6 kV systems -
upto 1.1 kV systems
Installation of Synthetic Insulating mat (as per IS 15652: 2006). The rate shall include cutting to required size and placing the mats in front of switchgear panels as directed by Site Engineer-in-charge. The mat shall be permanently pasted on the floor.
33kV System
6.6 kV systems -
upto 1.1 kV systems
First aid information chart (for electrical hazards such as Shock treatment) : Framed laminated shock treatment chart, conforming to IE rules, in English and local language. Name, address and telephone number of nearest doctor shall be mentioned in it.
First aid boxes along with required medicines / medical equipment, containing ointments for treatment of electrical burns, conforming to IE rules.
Wall mounted, Electrical Single Line Diagrams-A0 size" for the unit including frame, glass, hardwares, etc.
GENERAL ITEMS
Installation of general items mentioned below, as required.
Office tables of reputed make
Office chairs of reputed make
Full size Cupboard of reputed make, sheet steel enclosure (for documentation)
Tool Cabinet, Wall Mounted
Key Cabinet, Wall Mounted
Tarpaulin (for weather protection of stored electrical equipment)
Insulated step ladder of reputed make (suitable for indoor work in switchgear rooms)
Installation of Fire proofing of cables up 3 m length at entry points of both endsincluding all labour and materials required. (Actual area of surface painted shall be measured) _ - (As perIEC 60331) Fire proof paint for cables for 1 hour Fire Rating (CABLE SURFACE AREA WISE) Fire retardant cable coating HILTI : CP679A / OBO BETTERMAN equivalent product
Installation of Fire Stop (Fire sealing) material suitable to withstand for 240 min including all labour and materials required for sealing the wall / Floor opening / conduits fire sealings. Refer annex EW4-6 for details of openings to be sealed
Installation of Fire Stop (Fire sealing) material suitable to withstand for 90 min including all labour and materials required for sealing the wall / Floor opening / conduits fire sealings. Refer annex EW4-6 for details of openings to be sealed
Installation of Weather proofing material HILTI make including all labour and materials required for sealing the wall opening / conduits fire sealings.
ELECTRICAL STATUTORY APPROVAL
Obtaining approval on applicalbe Released for Construction (RFC) / Final drawings, commencement certificate from concerned authorities, approval of installations, liasoning with electrial inspector, organising inspector visits to site ( up to 3 visits) as required as per applicable statutory norms, etc. and all the associated work
MANPOWER SUPPLY RATES PER DAY
The below mentioned rates for Manpower Supply shall be applicable only for work performed over and above the electrical works already defined as forming part of CONTRACTOR’s scope in the Tender Document / Contract. Note: These rates for man power are applicable only after total completion of Electrical Installation & Commissioning activities. This shall also include the Implementation of LOTO system during precommissioning & commissioning stage . The below mentioned rates shall be applicable only if specifically agreed & approved by OWNER / CONSULTANT.
Electrical Job Superviser
HSE Supervisor
Electrician / Wireman with authorized certificate/ Technician
Fitter
Welder / Gas Cutter
Rigger
Mason
Helper / Semi-skilled
Testing Engineer
Cable Jointer
Qualified Electrical Engineer
LAXMI ENGINEERING PVT. LTD. (BID ID -3192573)
M/s SterlingElectro Enterprises.P.Ltd (BID ID -3196183)
Konstelec Engineers Limited (BID ID -3192858)
NORTH EASTERN ENGINEERS (BID ID -3187167)
Offshore Infrastructures Ltd (BID ID -3189050)
Konstelec Engineers Limited (BID ID -3192858)
NORTH EASTERN ENGINEERS (BID ID -3187167)
LAXMI ENGINEERING PVT. LTD. (BID ID -3192573)
M/s SterlingElectro Enterprises.P.Ltd (BID ID -3196183)
Offshore Infrastructures Ltd (BID ID -3189050)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid