Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹1.5 CrAdmitted-Finance | -12.11% | ₹1.5 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.5 Cr+₹1.7 L (1.14%)Admitted-Finance | -11.11% | ₹1.5 Cr+₹1.7 L (1.14%) | L2 | Admitted-Finance |
| 3 | Not Admitted-Fee/PreQual/Technical | - | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| 4 | Not Admitted-Fee/PreQual/Technical | - | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹1.7 Cr
EMD Value
₹3.4 L
Closing Date
17 Aug 2026, 6:00 pmClosed
GM RSRDC LTD JAIPUR
GM RSRDC LTD SETU BHAWAN, JHALANA DOONGARI JAIPUR
SITC of Fire Fighting work in construction of 300 Bedded Satellite Hospital(Phase-I for 150 Beds) at Sangpaner Jaipur
2026_RSRDC_585013_1
RSRDCC NIT 298/2026-27 Dated 07.08.2026 Sl No 04
Open Tender
Electrical Works
Percentage
365 days
Bedded Satellite Hospital(Phase-I for 150 Beds)
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,360
PD RSRDC Elect2 Jaipur through NEFT/RTGS/IMPS
₹3.4 L
20 Aug 2026
9 Aug 2026
18 Aug 2026
9 Aug 2026
17 Aug 2026
10 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | PUMP EQUIPMENT(Electrical BSR 2022) | 0 | Each | 0 | ₹0 |
| 2 | Supplying, Installation, Testing & Commissioning of Electrical Driven fire fighting duty pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given as A, B, C, D, E, F, G and H. | 0 | Each | 0 | ₹0 |
| 3 | (A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head | 0 | Each | 0 | ₹0 |
| 4 | (B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal | 0 | Each | 0 | ₹0 |
| 5 | (C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head | 0 | Each | 0 | ₹0 |
| 6 | (D) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed 2900 / 1500 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect . | 0 | Each | 0 | ₹0 |
| 7 | ( E) Common bed plate fabricated from mild steel channel for installation of pump and Motor including anti vibration pads. | 0 | Each | 0 | ₹0 |
| 8 | (F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Physical presence of Department’s representatives. | 0 | Each | 0 | ₹0 |
| 9 | (G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM | 0 | Each | 0 | ₹0 |
| 10 | (H)Suitable size Reinforced cement concrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | 0 | Each | 0 | ₹0 |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.33 MB
agrement.pdf
Tender Documents • 0.45 MB
AnnexureABCD_RTPPAct2012_AnnexureC.pdf
Tender Documents • 0.10 MB
PdBankAccountNumberDetails.pdf
Tender Documents • 0.30 MB
various_Circulars_orders.pdf
Tender Documents • 0.32 MB
EligibilitycriteriaofBiddersforqualifyinginTechnicalBid.pdf
Tender Documents • 0.59 MB
AnnxAPWDELECTBSR2022.pdf
Tender Documents • 0.44 MB
gentcalongwithdlptc-ff.pdf
Tender Documents • 0.44 MB
Engineering_Cost.pdf
Tender Documents • 0.69 MB
BOQ_1039200.xls
BOQ • 0.39 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .