Superintending Engineer
Office of the Superintending Engineer, Western Electrical Circle , PWD, Purta Bhavan, 1st floor, Burdwan-713103
Construction 100 bedded critical care block(CCB) at hooghly district hospital under PM-ABHIM ----- SITC of Intelligent Fire detection System.
2025_WBPWD_836627_1
WBPWD/SEWEC /HED /NIQ-02/2025-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
45 days
Hooghly
Please refer Tender documents.
5 documents required · 5 mandatory
₹90,000
Office of the Superintending Engineer, Western Ele
8 Sept 2025
17 Apr 2025
7 May 2025
17 Apr 2025
5 May 2025
22 Apr 2025
17 Apr 2025 - 21 Apr 2025
21 Apr 2025
Amount
Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable multisensor detector IP 42 (VDS / EN / UL / FM / ULC approved) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. (Approved Make : Siemens Cerberus Pro/Honeywell / Johnson Controls)
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point (VDS /EN / UL / FM / ULC approved) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required.(Approved Make : Siemens Cerberus Pro/Honeywell / Johnson Controls)
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP65 (VDS / EN/ UL / FM / ULC approved).(Approved Make : Siemens Cerberus Pro/Honeywell / Johnson Controls)
Supply, Installation,Testing & Commisioning of Micropresssor controlled IP Addressable Heat detector 42 ( VDS / EN /UL / FM / ULC approved) with combination of fixed type & Rate of Rise of Temperature feature. Detector shall have minimum triggering temperature programmable from 60 deg. C to 80 deg. C., having high level of immunity to electromagnetic influances and show alarm signal limit temperature is reached. Detector shall have inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. (Approved Make : Siemens Cerberus Pro/Honeywell / Johnson Controls)
Supply, Installation, Testing & Commissioning of Addressable Input/Output Modules ( VDS / EN/ UL / FM / ULC approved ) for monitoring/controlling Flow switches / Fire exit doors / AHU/ Lift etc. with inbuilt short circuit fault isolator and minimum (04) four potential free contact with adjustable setting parameter likes of Input or output, complete in single or multiple housing with degree of protection IP 42 with flash LED indicator that conforms module is operational and integrated buzzer signaling maintenance alarm, complete as required. (Approved Make : Siemens Cerberus Pro/Honeywell / Johnson Controls)
Supplying, installation, testing and commissioning of LED type Response Indicator ( VDS / EN/ UL / FM / ULC approved) having 2 Nos. red coloured LED lamps including connections etc. ((Approved Make : Siemens Cerberus Pro/Honeywell / Johnson Controls)
Supply & Laying of 2 Core sheathed 1.5 sq.mm FRLSH flexible copper Cable (For Loop) (Make. Finolex/RR Kabel/Polycab/Gloster) through 20mm dia PVC "FR" type Rigid Conduit pipe(Precision/Polycab/AKG make color -RED or as approved by EIC ) with necessary arrangement as per GS.
SITC of Repeater Panel (VDS / EN / UL / FM / ULC approved) which will act as an add-on device for remote display of FACP status information of the FDA operating front related to the detectors and decetors zones.Event messages are displayed via LED collective indicators and on the 2-Line LCD display with the associated detecors zone number and a programmable additional text. Each message is signalled via the built-in buzzer. The buzzer can be acknowledged by pressing a button. The requisite LCD indicator panel can be operated on as RS 485 bus. (Approved Make: Siemens Cerberus Pro/Honeywell / Johnson Controls)
SITC of Power supply 230 V AC to 24V DC with all other accessories. (Make: Reputed)
Supply, Installation,Testing & Commisioning of Microprocessor based addressable fully networkable fire alarm control panel ( VDS /EN/ UL / FM / ULC approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel should have extra loop card slot for expansion of capcity twice.There should be LAN port(RJ 45 ) for communication with laptop for configuration the fire alarm system.
The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 60 minutes during Emergency condition, with integral battery charger complete in all respect as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software. (Approved Make : Siemens Cerberus Pro/Honeywell / Johnson Controls)
NOTE :- 1) The Fire Alarm system shall comply with latest requirements of -- (i) National Fire Protection Association (NFPA) Standards, (ii) IS 2189 , (iii) NFPA 70 National Electric Code, (iv) NFPA 72 National Fire Alarm & Signaling Code , (v) Local Statutory Regulations , (vi) Manufacturer Recommendation. vii) System should be integrated with the components like FACP, Detectors, MCP, Hooter, Monitor Module, Relay Module etc. and all these components should be of same brand.
TESTS :- 1) The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2) Before energizing the cables and wires, inspection and check for correct connections, and test for short circuits, ground faults, continuity, and insulation and other tests as per applicable Indian/International standards must be done.
TERMS & CONDITIONS :-
The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer /Certificate of authorisation from the original equipment manufacturer including responsibility of OEM shall be uploaded with the tender document folder/ OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
D.L.P. - 3 years.
Creative Projects (BID ID -6359474)
PERFECT IMAGE SOLUTIONS (BID ID -6346753)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .