Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.3 CrAdmitted-Finance | ₹4.3 Cr | L1 | Admitted-Finance |
| 2 | L2₹4.4 Cr+₹3.5 L (0.82%)Admitted-Finance A 41 HIRALAL NAGAR NEAR DIXIT SWEETS SAROJINI NAGAR KANPUR ROAD LUCKNOW UTTAR PRADESH 226008 | LUCKNOW | UTTAR PRADESH | 226008 | ₹4.4 Cr+₹3.5 L (0.82%) | L2 | Admitted-Finance |
| 3 | L3₹4.4 Cr+₹5.0 L (1.15%)Admitted-Finance | ₹4.4 Cr+₹5.0 L (1.15%) | L3 | Admitted-Finance |
| 4 | L4₹4.4 Cr+₹6.2 L (1.43%)Admitted-Finance | ₹4.4 Cr+₹6.2 L (1.43%) | L4 | Admitted-Finance |
| 5 | L5₹4.5 Cr+₹12.0 L (2.77%)Admitted-Finance | ₹4.5 Cr+₹12.0 L (2.77%) | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Alliance Transcon Pvt. Ltd. L2 | SNS TECHNOLOGIES L1 | AJAY KAPOOR L3 | M/s M. S. CONSTRUCTIONS L6 | N S ENTERPRISES L7 | CEEKAY EPC PROJECTS PRIVATE LIMITED L5 | INDUSTRIAL ELECTRICALS L4 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00Creation of 10 Nos 11/0.415KV, 100KVA, 3-phase Distribution Substation | ||||||||||
| 1.01 | Supply, Installation & commissioning of 11/0.433kV, 100KVA, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, "BIS Marked" (Aluminium Wound) (Aluminium wound) with LV Cable Box having detachable Aluminium Gland plate.(As per latest Amendments and IS) | 10 | No | 2,00,000 ₹20,00,000 | 1,95,000 ₹19,50,000 Lowest | 2,27,906 ₹22,79,060 | 2,50,000 ₹25,00,000 | 2,10,000 ₹21,00,000 | 3,50,000 ₹35,00,000 | 2,00,002 ₹20,00,020 |
| 1.02 | Supply, Transportation, Erection of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface. | 20 | No | 20,500 ₹4,10,000 | 17,900 ₹3,58,000 Lowest | 21,000 ₹4,20,000 | 24,000 ₹4,80,000 | 23,200 ₹4,64,000 | 20,500 ₹4,10,000 | 18,000 ₹3,60,000 |
| 1.03 | Supply, Transportation, Fabrication & Fixing of G.I Channel Iron, Cross arms, Angle Iron Braces, Clamps etc. duly fabricated including all necessary G.I Nut & Bolts & Washers etc. ( All the Items are Galvanized) | 3,080 | Kg | 170 ₹5,23,600 | 125 ₹3,85,000 | 150 ₹4,62,000 | 150 ₹4,62,000 | 137.5 ₹4,23,500 | 102 ₹3,14,160 Lowest | 150 ₹4,62,000 |
| 1.04 | Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type | 10 | Set | 6,500 ₹65,000 Lowest | 10,000 ₹1,00,000 | 8,500 ₹85,000 | 10,000 ₹1,00,000 | 13,500 ₹1,35,000 | 7,500 ₹75,000 | 14,000 ₹1,40,000 |
| 1.05 | Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A | 10 | Set | 3,000 ₹30,000 Lowest | 3,500 ₹35,000 | 5,000 ₹50,000 | 4,000 ₹40,000 | 8,250 ₹82,500 | 3,500 ₹35,000 | 5,000 ₹50,000 |
| 1.06 | Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA, LA with polymer housing, Stn. Type | 10 | Set | 5,000 ₹50,000 | 4,500 ₹45,000 | 5,000 ₹50,000 | 4,000 ₹40,000 Lowest | 6,000 ₹60,000 | 6,500 ₹65,000 | 8,000 ₹80,000 |
| 1.07 | Providing & fixing of PVC Cable 185 mm² along with 12 Nos Al. Thimble of 185 mm² | 440 | Mtr | 300 ₹1,32,000 | 370 ₹1,62,800 | 200 ₹88,000 | 400 ₹1,76,000 | 378 ₹1,66,320 | 150 ₹66,000 Lowest | 310 ₹1,36,400 |
| 1.08 | Providing & Fixing of LT Distribution Box for 100kVA DTR with 160A MCCB for incomer & SFU’s for Outgoing Circuits including Busbar arrangements for Phases & Neutral of EC Grade Aluminium, PVC Insulated Sleeved Busbar of required load handling capacity with colour code for Phases and Neutral differentiation, including Aluminium thimbles of required sizes for proper termination etc. | 10 | No | 7,500 ₹75,000 Lowest | 28,000 ₹2,80,000 | 20,000 ₹2,00,000 | 35,000 ₹3,50,000 | 37,000 ₹3,70,000 | 75,000 ₹7,50,000 | 25,000 ₹2,50,000 |
| 1.09 | Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 Mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. | 30 | No | 4,000 ₹1,20,000 | 4,000 ₹1,20,000 | 3,000 ₹90,000 | 2,500 ₹75,000 | 5,700 ₹1,71,000 | 3,500 ₹1,05,000 | 2,000 ₹60,000 Lowest |
Tender Value
₹5.2 Cr
EMD Value
₹10.4 L
Closing Date
20 Oct 2023, 4:00 pmClosed
Office of Executive Engineer ED-II JPDCL
Office of Executive Engineer ED-II JPDCL
Supply Installation, Testing, Commissioning of 11 KV Dedicated Feeders to B.S.F BOP in Suchetgarh and Mandal Block under ED-II JPDCL
2023_PDD_231696_1
ENIT 50A of 2023 Dated 30-09-2023
Open Tender
Electrical Works
Turn-key
90 days
Miran Sahib
As per ENIT and SBD
9 documents required · 9 mandatory
₹5,000
Executive Engineer ED-II JPDCL
₹10.4 L
16 Dec 2023
30 Sept 2023
21 Oct 2023
30 Sept 2023
20 Oct 2023
30 Sept 2023
Amount
Creation of 10 Nos 11/0.415KV, 100KVA, 3-phase Distribution Substation
Supply, Installation & commissioning of 11/0.433kV, 100KVA, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, "BIS Marked" (Aluminium Wound) (Aluminium wound) with LV Cable Box having detachable Aluminium Gland plate.(As per latest Amendments and IS)
Supply, Transportation, Erection of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface.
Supply, Transportation, Fabrication & Fixing of G.I Channel Iron, Cross arms, Angle Iron Braces, Clamps etc. duly fabricated including all necessary G.I Nut & Bolts & Washers etc. ( All the Items are Galvanized)
Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A
Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA, LA with polymer housing, Stn. Type
Providing & fixing of PVC Cable 185 mm² along with 12 Nos Al. Thimble of 185 mm²
Providing & Fixing of LT Distribution Box for 100kVA DTR with 160A MCCB for incomer & SFU’s for Outgoing Circuits including Busbar arrangements for Phases & Neutral of EC Grade Aluminium, PVC Insulated Sleeved Busbar of required load handling capacity with colour code for Phases and Neutral differentiation, including Aluminium thimbles of required sizes for proper termination etc.
Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 Mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing of Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
Providing & fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & fixing of 11kV Polymeric composite Disc Insulator 12kV with Fitting, min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Wedge Connectors / PG Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete
Supply ,Erection ,Testing and Commissioning of 38.20 km 11KV line with ACSR Weasel Conductor on 9 Mtrs Steel Tubular poles
Supply, Transportation, Erection of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface.
Supply, Transportation, Fabrication & Fixing of GI Channel Iron, GI Cross arms, GI Angle Iron Braces, GI Clamps etc duly fabricated including all necessary GI Nut & Bolts & Washers etc.
Supply, Laying & Stringing of ACSR Weasel Conductor on Cross arms through insulators including proper binding & twisting with soft Aluminium Wire
Providing & Fixing of PG Clamps for 30mm² ACSR Conductor.
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 10kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm.
Providing & Fixing of 11kV Polymeric composite Disc Insulator with fitting 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti-Climbing Device with Clamps
Providing of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Providing & Fixing of Stone Pad (300 mm x 300 mm x 75 mm)
Providing & Fixing of Aluminium Jointing Sleeves
Providing & installation of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GI stay rod & 7/3.15 mm dia GI stranded wire complete
Supply Erection ,Testing and Commissioning of 5.20 Kms 11KV line with 120 mm2 XLPE Cable on 9 Mtrs Steel Tubular poles
Supply Erection, Testing and Commissioning of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface.
Supply Erection, Testing and Commissioning of 11kV, Three core 120 mm2 Aluminium round wire Armoured XLPE Cable , FRLS, XLPE(11 kV, 3C ) ( compatible with latest IS standard )
Supply Erection, Testing and Commissioning of Heat Shrinkable Outdoor Cable Termination Kit
Providing and fixing of G.I Clamps including all necessary arrangements G.I Wire,Nut Bolts etc. for XLPE Cable ( Complete in all respects)
Providing and Fixing of Danger Plates
Providing and Fixing of Anti-Climbing Device with Clamps
Providing of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI strip
Providing of Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
Supply Erection, Testing and Commissioning of Mid Span Straight Throgh Jointing Kit for 11 kV XLPE Cable
Supply Erection, Testing and Commissioning of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Supply ,Erection ,Testing and Commissioning of Erection & Commissioning of Isolation point ( 18 Nos)
Supply Erection, Testing and Commissioning of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface.
Supply ,Fabrication & Fixing of GI Channel Iron, GI Cross arms, GI Angle Iron Braces, GI Clamps etc duly fabricated including all necessary GI Nut & Bolts & Washers etc.
Supply, Laying & Stringing of ACSR Weasel Conductor on Cross arms through insulators including proper binding & twisting with soft Aluminium Wire
Providing & Fixing of PG Clamps for 30mm² ACSR Conductor
Supply, Installation, Testing & Commissioning of 11 KV GO AB Switch, 3-phase, 3-pole, 400 Amp.
Supply, Installation, Testing & Commissioning of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 10kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supply & Fixing of Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete
Supply & Fixing of Danger Plates with Clamps
Supply & Fixing of Anti Climbing device with Clamps
Providing of Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm, 2.5 Mtr Long through GI Strip(2 nos for PCC poles & ino. For G O Switch/LA)
Providing of Stone Pad 300 mmx300mmx75mm
Supply ,Erection ,Testing and Commissioning of Augmentation of Substation from 100 KVA to 250 KVA
Supply, Installation & commissioning of 11/0.433 KV, 250 KVA 3-Phase Distribution Transformer with Bi-metallic terminal Connectors, Energy Level: 2, "BIS Marked" (Copper Wound) alongwith LV Cable Box having detachable Alumnium Gland plate including Transportation Note: Dismantling and Write Back of dismantled 100 KVA Distribution Transformer and allied material to Divisional store at Miran Sahib which includes labour and mechanical carriage charges involved .
Supply, Transportation, Erection of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface.
Supply, Transportation, Fabrication & Fixing of GI Channel Iron, GI Cross arms, GI Angle Iron Braces, GI Clamps etc duly fabricated including all necessary Nut & Bolts & Washers etc.
Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A
Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
Providing & Fixing of Single Phase PVC Cable 240 mm² ,1.1K V Grade, PVC Insulated Stranded Un-Armoured FRLS type alongwith Al. Thimbles for 240 mm² Cable termination with four colored PVC Tapings to distinguish the LT Phases and the Neutral. (2 Ckt)
Providing & Fixing of Pole mounted LT Distribution Box for 250 KVA DTR with 2 No. Triple Pole MCCB of 300 Amp with adjustable overload release of (80-100%) for incomer & & switch fuse unit for Out Going 2No Ckts. including Busbar arrangements for Phases & Neutral of EC Grade Aluminium,PVC Insulated Sleeved Busbar of required load handling capacity with colour code for Phases and Neutral differentiation, including Aluminium thimbles of required sizes for proper termination etc.
Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing of Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of 11kV Polymeric composite Disc Insulator 12kV with Fitting ,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of Wedge Connectors / PG Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Galvanized Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete
Alliance Transcon Pvt. Ltd.
AJAY KAPOOR
INDUSTRIAL ELECTRICALS
CEEKAY EPC PROJECTS PRIVATE LIMITED
M/s M. S. CONSTRUCTIONS
N S ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.81 MB
SBD50A.pdf
Tender Documents • 1.28 MB
BOQ_675369.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .