| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.5 LAccepted-Finance 49 1 ISWAR GUPTA ROAD KOLKATA 700 028 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700028 | L1 | Accepted-Finance That the bid is L1 therefore Provisional order issued | |
| 2 | L2₹2.7 L+₹22,000 (8.95%)Rejected-Finance 197 4 KANTADANGA ROAD P O FINGAPARA KANKINARA NORTH 24 PARGANAS PIN 743129 | KANKINARA | NORTH 24 PARGANAS | WEST BENGAL | 743129 | L2 | Rejected-Finance that the bid is not L1 | |
| 3 | L3₹2.7 L+₹25,634 (10.4%)Rejected-Finance 24A RABINDRA SARANI KOLKATA 700 073 | KOLKATA | KOLKATA | WEST BENGAL | 700073 | L3 | Rejected-Finance that the bid is not L1 | |
| 4 | L4₹2.8 L+₹30,617 (12.5%)Rejected-Finance 3 C DR JAGABANDHU LANE KOLKATA 700012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | L4 | Rejected-Finance that the bid is not L1 |
Tender Value
Refer Docs
EMD Value
₹6,564
Closing Date
17 Nov 2022, 1:00 pmClosed
EE KNHED PW Dte
KIT Building Annex, 4th Floor,P-16, India Exch. Place Extn., Kolkata -700073
SITC of covid specific infrastructure in proposal hybid CCU at Ground floor CB Building under RGKar MCH Electrical Sub-Division EI Work for Construction of single storied plant room for set up medical gas pipe line system MGPS
2022_WBPWD_420295_1
WBPWD/EE/KNHED/NIQ-53/22-23
Open Tender
ELECTRICAL WORKS ORG
Item Rate
21 days
Kolkata
Please refer Tender documents.
5 documents required · 5 mandatory
₹6,564
12 Dec 2022
7 Nov 2022
21 Nov 2022
9 Nov 2022
17 Nov 2022
9 Nov 2022
Amount
S & F 415 Volt, 315 Amp (Front operated) SDSFU with its HRC fuse Link -- L&Twith sheet steel enclosure on angel iron frame including Cabel entry box of 400 Amp. (Front operated) Make- L&T
Supply & drawing 1.1KV grade double run 2Rx 3.5C x 95 sq.mm.Al. Ar. PVC /XLPEcable & 2 x 10 SWGGI wire. Through MS clamp saddling of flat size 12mm x4 saddling(3' gapping) on wall, Under the Ground & surfacesurfaceFrom LT panel to PSA plant ( Make- Glostar/ KEI/ Havells)
Supply & Fixing of L shape MS angel 50x50x6 mm of length 10" x 6" Including making drilled hole,Fixing on wall with 2 set anchor bolt with 2 coat RO primer and Paint.
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables. [F4/7©] a) 3.5 core X 95 sq.mm.
Finishing of the XLPE/PVC insulated armoured cable ends by crimping method with cable sockets and insulated tapes etc., including supplying sockets, soldering materials, tapes etc. and making connection to switch, BDB and BBC etc. [F-5/8.(b)] a) 3.5 core X 95 sqmm
Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of powder coated colour. With 25x25x3mm angle iron suppor of following size: 300x50x1.25mm (18SWG)
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By TATA-Medium GI pipe [G1/2(a)]
Supply and laying 25mmx6mm hot dip GI flat earthing strip laying in ground as per EIC for DG and AMF panel body earthing including all necessery work like making hole, welding, connecting with GI bolt etc.
Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (Make- Legrand/L&T/ABB/Cabtree) 250A [ D-11 /15] i) 6 way Enclosure
Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection.(Make- Legrand/ABB/Cabtree)[D-8/ 10] A) 250 A
Supplying and fixing 240/415 V TP MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection. (Make- Legrand/ABB/Cabtree) [D-6/7] A) 63A
Supplying and fixing 240/415 V SP MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection. (Make- Legrand/ABB/Cabtree) [D-6/ 7] A) 16-25A
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required [E-14/ 1(a)] make Gloster/Finolex/polycab/KEI 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) ECC
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. [F-5/9] i) 2.5 sq mm
ii) 4 sq mm
Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) in 19 mm bore, 3 mm thick polythen pipe (for horizontal & vertical run in wall and celing portion through prelaid polythen pipe) complete with all accessories embedded in wall to light/fan/call bell points with Piano key type switch (Anchor make) fixed on sheet metal (16 SWG) switch board with bakelite/perspex (wall matching colour) top cover (3 mm thick) flushed in wall incl. mending good damages to original finish [E-10/ 3] i) Average run 6 mtr
do-do-on board 6A piano plug point [E-10/ 4]
Supply & delivery of 4ft T8 22W single LED fitting complete with 1×18W LED tube on ceiling with ceiling plate down rod etc. as required. (Philips- Cat No. TMC 501/ Crompton- LTT8-20 & IGP131LT8/Wipro/ Magik/ Panasonic/ Syska)
S & D of ceiling fans (make - Orient summer king/ Usha Striker) of following dimensions: 48''
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire. [ C-3/21.(a)]
Fixing only fluorescent light fitting suspended 25 cm bellow theceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports incl.S&F EI conduit, ball socket/socket type ceiling plate and connecting the length of PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm) flexible copper wire of 1.10 mt. length. [C-2/15]
S & F 30cm (12'') sweep A.C. exhaust fan (EPC-heavy duty) after cutting after cutting holes in the wall and making good the damages and smooth cement finsh etc. as practicble as possible and providing necy length of PVC insulated Cu wire and making connections incl.
Supply & Fixing louver shutter on wall with necy. bolts & nuts (6 mmdia x 62 mm long) Aluminium [D-14/32.(a)] 30 cm Exhaust fan (12")
Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/ perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex coverand making necessary connections as required
Terms and condition The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of Work/submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Special Terms and Conditions 1. It is stated that the above work place is existing COVID Hospital, In case of any mishap or accidental to any staff that deputed by the agency the whole responsibility is to be borne by the concern agency. 2. The Agency shall be responsible for provisioning of all COVID safety measures including regular sanitiziation of work places, vaccination of employees and compliance of stated directive and COVID appropriate norms. 3. All the issues related to the safety of the staffs should be taken care by the agency itself. (Rate should be quotated including all taxes and duties)
Defect Labilities period for 01 year from the date of completion of work. (Rate should be quotated including all taxes and duties)
M/S R. K. ENTERPRISE
STANDARD BUILDERS
S. A. ENTERPRISE
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .