| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.2 CrAccepted-AOC SCF 15 HUDA COMPLEX 184 NEW IDC 124001 | ROHTAK | HARYANA | 124001 | ₹2.2 Cr | L1 | Accepted-AOC L1 bidder rates are lowest hence accepted. |
| 2 | L2₹2.3 Cr+₹3.7 L (1.67%)Rejected-AOC GAUSHALA MARKET TEHSIL NARNAUL NARNAUL 123001 | NARNAUL | NARNAUL | HARYANA | 123001 | ₹2.3 Cr+₹3.7 L (1.67%) | L2 | Rejected-AOC L2 bidder hence rejected. |
| 3 | L3₹2.3 Cr+₹9.9 L (4.49%)Rejected-AOC VILLAGE DUMERKHA KALAN POST OFFICE DUMERKHA KALAN TEHSIL UCHANA DISTRICT JIND 126115 HARYANA | DUMERKHA KALAN | JIND | HARYANA | 126115 | ₹2.3 Cr+₹9.9 L (4.49%) | L3 | Rejected-AOC L3 bidder hence rejected. |
| 4 | L4₹2.7 Cr+₹44.5 L (20.1%)Rejected-AOC | ₹2.7 Cr+₹44.5 L (20.1%) | L4 | Rejected-AOC L4 bidder hence rejected. |
Tender Value
₹2.5 Cr
EMD Value
₹5.0 L
Closing Date
11 Jul 2024, 5:00 pmClosed
Radha Krishan Mittal
Division - Projects and Traffic
Development of Bus Depot for e-Buses at sector-48, Gurugram, Haryana (Electric Substation)
2024_HRY_385169_1
202467A7E16B EDA5 4A69 848A 400CF59F216B743001
Open Tender
Civil Works
Works
180 days
Gurugram
2 documents required · 2 mandatory
₹1,180
₹5.0 L
Yes
13 Aug 2024
2 Jul 2024
12 Jul 2024
2 Jul 2024
11 Jul 2024
2 Jul 2024
Amount
Supply and erection of copper strip 40mm x 5 mm for Earthing on surface and recess in ground including the cost of all required accessories i.e. nut bolts stapples etc complete in all respect upto the entire satisfaction of Engineer-in-charge.
Supply, installation, testing and commissioning of 11 KV Package type compact Sub Station as per IEC 62271-202. Outdoor type enclosure having modular construction Enclosure type-tested for IP2X and enclosure class k10, Water and air-tight joints, made of Galvanized sheet steel of 2mm. The Enclosure shall have IP54 degree of protection for HT and LT switch gear compartment and IP23 degree of Protection for Transformer compartment. Each compartment will be provided with the door and pad locking arrangement. The compartment illumination lamp with door operated switch shall be provided for each compartment. Interconnection between HT switchgear and Transformer using XLPE Single core cable and Interconnection between Transformer and LT switchgear using Busbars, Internal earthing connections. All metallic components shall be earthed to a common earthing point. Substation can be lifted with transformer installed: Enclosure painted with powder coating/polyurethane paint. (Make: ABB, Siemens, Schnieder) HT Switchgear- 11 KV 630 Amps. 21 KA/3 Sec NonExtensible Ring Main Unit 2 Way Compact Switchgear consisting 1 No. VCB feeder with SF6 Insulated in Stainless steel enclosure with series trip, Self-powered microprocessor based numerical over current and earth fault protection relay and 1 No. Cable feeder. Relay shall have communication port and SCADA Compatible. Transformer- 3 Phase, 50 HZ, 2000 KVA, Oil Type ,11 / 0.415 KV, DYn -11, Copper Wound, Class A insulation, Transformer as per IS 1180 Energy Efficiency Level 2, Off Circuit Tap Changer with winding temperature indicator /controller actuated by means of resistance temperature detector embedded in LV winding, outdoor type transformer with approximately 5 % impedance tapping for Off load tape changer operation on HV side in steps of 2.5% for plus 7.5% having cable end boxes on HV side suitable for 3 core x240 Sq.mm XLPE cable of 11 KV grade, Type of colling ONAN. L.T Side of Transformer shall have Bus Bars up to LV Switchgear. LV Enclosure- L.T Panel shall have 2MM CRCA Sheet Enclosure with Powder Coated as per IS. Incomer- 3200 Amp ACB 65 KA Fixed type Microprocessor Based having Trip Feature, Earth Fault Protection with metering and Indicators complete in all respect compatible with SCADA. Necessary Bus Bar arrangements for outgoing cable shall be made in LT Panel. LV Enclosure shall have continuous Earthing with suitable GI Strip. Note: - RCC foundation cost is inclusive with complete in all respect with all required accessories up to the entire satisfaction of engineer-in-charge. CSS Make : ABB, Siemens, Schnieder
Supply and Laying, jointing testing and connecting XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade, of size 300 sq mm, 3 core, IS 7098 marked, suitable for HT 11 KV (E) system, laid in trenches / ducts / encased in GI pipe / fixed to pole, including jointing and testing complete all as specified and directed. Makes:- National, Havells, KEI, Polycab
Providing and laying HDPE pipe 160 mm id PE-63PN-4 (For laying cables as mentioned and bring the site in its orignal position, upto the entire satisfaction of engineer-in-charge. Make:- Flexi-flow, Flow-well, finolex, Duraline
Material and labour for Cable jointing kit for 11 KV Earthed grade cable for Indoor termination heat shrink type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 300 sqmm, complete all as specified and directed.
Bidder Name
Amount
Highlight Associates and Contractors (GSTN-06AAKFH2063G1ZK) BID ID -1107009
DHEERAJ ENTERPRISES (GSTN-06AAKFD3784C1ZI) BID ID -1114860
Sh. Shyam Lal Contractor(GSTN-NA)--1115027
Shree Shyam Associates(GSTN-NA)--1113539
Shree Shyam Associates
DHEERAJ ENTERPRISES
Sh. Shyam Lal Contractor
Shree Shyam Associates
Highlight Associates and Contractors
Sh. Shyam Lal Contractor
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .