Loading…
Loading…
Tender Value
₹2.5 Cr
EMD Value
₹5.0 L
Closing Date
18 May 2026, 3:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
SRDSTECSIG
14 conditions · 2 needing a document upload
Financial Eligibility Criteria: The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Form-2, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
Technical Eligibility Criteria: The Tenderer must have successfully completed or substantially completed any one of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: (i)Three similar works costing not less than the amount equal to 30% of advertised value of the tender, or (ii)Two similar works costing not less than the amount equal to 40% of advertised value of the tender, or (iii)One similar work costing not less than the amount equal to 60% of advertised value of the tender.
Defination of Similar Work :- Any work of Provision or maintenance of Automatic Fire Detection & Alarm/Automatic Fire suppression system. OR Any Signaling work which includes provision of Automatic Fire Detection & Alarm/Automatic Fire suppression system. Note 1: Tenderer may be required to submit the schedule of those works, Completion/Performance Certificates of which have been submitted by him/her in support of 30% / 40% / 60% (as the case may be) criterion of similar nature of work.
14 conditions · 9 needing a document upload
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
PAN Number to be attached.
Registered Office Address with contact no.
Detail of Bid Security paid, through only payment modes available on IREPS portal like net banking, debit card, credit card etc.
Mandatory undertaking regarding Employment/Partnership of Retired Railway Employees as per Clause No. 12 of Chapter-I as per Annexure- E.
Mandatory certificate to be submitted by tenderer along with tender documents as per Annexure- A.
GST Number to be attached.
Mandatory Power of Attorney to be submitted by tenderer along with tender documents as per Annexure- B.
MOA & AOA, Resolution of Board and POA, Sole Proprietorship, Notarized partnership deed with POA and latest certificate of registration with Registrar of the firms must be attached. Year of Formation / Incorporation. (As per Clause-10 of Tender Document
Upload duly filled and signed Cover Letter (Tender Form 1)
Mandatory Document Tenderer uploaded Annexure-A (1) {This certificate is to be given by attorney/authorized signatory/each member of Partnership firm/Joint Venture (JV)/Hindu Undivided Family (HUF)/Limited Liability Partnership (LLP) etc.)}of tender documents.
An undertaking by the tenderer shall be provide at the time of tender submission that the equipment shall be procured from RDSO/TEC/OEM covering supply, installation, testing, commissioning of system including after sales support required during the warranty period.
Augmentation of Automatic Fire Alarm System over Delhi Division.
558-Sig-16-M-Tender-1473
558-Sig-16-M-Tender-1473
Open
Works - General
12 Months
Delhi, Delhi
₹0
₹5.0 L
18 May 2026
24 Apr 2026
4 May 2026
29 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 2,48,06,187.09 | ||
| — | 320.00 | — | — | ||
| Supply, installation, commissioning Heat and Smoke Multi sensor detector with automatically adjusts sensitivity levels without the need for operator intervention or programming sensitivity increase with heat varying and floating sensitivity from 0.5 to 4%/Ft and shall be plug in type facility and address through switch. The base should also be supplied as per RDSO/SPN/217/. Inspection: RDSO for supply portion. | — | — | — | 18,43,724.8 | |
| — | 20.00 | — | — | ||
| Supply, Installation, commissioning of analogue addressable UL listed Fire alarm Control Panel with 80-character display with battery charger and battery, backup for 24 Hr. normal operation and 15 Min alarm operation addressable power supply and alphanumeric keypad for installation for the FAS panel and 1000 event recording facility without GSM interface module as per RDSO/SPN/217/2016. Ver. 1.0 or latest. Inspection: RDSO for supply portion. | — | — | — | 1,06,96,867.8 | |
| — | 1500.00 | — | — | ||
| Supply, installation, commissioning of analogue type Linear Heat Sensing (LHS) cable which is self-restorable after the fire event as long as its temperature does not exceed specified resettable temperature limit of 120 degree Celsius it shall have an activation temperature of 70 degree Celsius as per RDSO/SPN/217/2018. ver 2.0 or latest. Inspection: RDSO for supply portion. | — | — | — | 25,53,285 | |
| — | 1.00 | — | — | ||
| Supply, installation, commissioning of GUI software to monitor health of detector and other devices along with control panel. The software shall be accessible over TCP/IP. It shall also be able to indicate in the device whenever the detector or the device would require to be serviced as per RDSO/SPN/217/2018. ver 2.0 or latest. Inspection: RDSO for supply portion. | — | — | — | 1,69,602.69 | |
| — | 40.00 | — | — | ||
| Supply, installation, commissioning of UL listed glass break manual call point as per RDSO/SPN/217/2018. ver 2.0 or latest. Inspection: RDSO for supply portion. | — | — | — | 2,21,138 | |
| — | 40.00 | — | — | ||
| Supply, installation, commissioning of audio-visual RDSO/SPN/217/2018. ver 2.0 or latest. Inspection: RDSO for supply portion. | — | — | — | 4,37,335.2 | |
| — | — | — | alarm | ||
| — | — | — | unit | ||
| — | 20.00 | — | — | ||
| Supply, installation, commissioning of Linear Heat Sensing interface module as per RDSO/SPN/217/2018. ver 2.0 or latest. Inspection: RDSO for supply portion. | — | — | — | 28,34,184.8 | |
| — | 4000.00 | — | — | ||
| Supply, installation, commissioning of circuit integrity cable 2 core 1.5 Sq.mm as per RDSO/SPN/217/2018. ver 2.0 or latest. Inspection: RDSO (Armoured/Unarmoured to be mentioned). Inspection: RDSO for supply portion. | — | — | — | 11,07,440 | |
| — | 40.00 | — | — | ||
| Supply, Installation, testing and commissioning of Control module with backbox and all other accessories as per RDSO/SPN/217/2018 ver-2 or latest. Inspection: RDSO for supply portion. | — | — | — | 3,60,786.4 | |
| — | 100.00 | — | — | ||
| Supply, Installation, testing and commissioning of Monitor module with back box and all other Monitor accessories as per RDSO/SPN/217/2021 ver-3 or latest. Spares cost is also included & to be supplied as per RDSO para no. 4.15. Inspection: RDSO for supply portion. | — | — | — | 9,01,966 | |
| — | 20.00 | — | — | ||
| Supply, installation and testing and commissioning of Aspiration Type smoke Detection System complete. (As per RDSO Specification no. RDSO/SPN/217/2021 ver 3.0 or latest). Inspection: RDSO for supply portion. | — | — | — | 30,83,653.4 | |
| — | 1000.00 | — | — | ||
| Supply, Installation, Testing & Commissioning of UL/LPCB/VDS listed CPVC Pipe 25 mm Dia & Pipe Accessories for the Aspiration detection. Approval-ULand shall comply to RDSO/SPN/217/2018 Ver 2 or latest. Inspection: RDSO for supply portion. | — | — | — | 5,51,380 | |
| — | 150.00 | — | — | ||
| Additional input wiring to data logger From Potential Free Contact of Main unit of Automatic Fire Detection and Alarm System. Supply portion INSPECTED BY CONSIGNEE | — | — | — | 44,823 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
splinstruction.pdf
ATTACHMENT
Tender-Doc-1473.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .