Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹29.7 LAccepted-Finance | ₹29.7 L | L1 | Accepted-Finance valid to be received. |
| 2 | L2₹31.6 L+₹1.8 L (6.19%)Accepted-Finance | ₹31.6 L+₹1.8 L (6.19%) | L2 | Accepted-Finance valid to be received. |
| 3 | L3₹33.3 L+₹3.6 L (12.0%)Accepted-Finance | ₹33.3 L+₹3.6 L (12.0%) | L3 | Accepted-Finance valid to be received. |
| 4 | L4₹38.0 L+₹8.3 L (27.8%)Accepted-Finance | ₹38.0 L+₹8.3 L (27.8%) | L4 | Accepted-Finance valid to be received. |
Tender Value
₹33.5 L
EMD Value
₹66,949
Closing Date
15 Apr 2025, 2:00 pmClosed
The Exe. Engg., PWD, WD-I, Daman.
The Multi Office Complex, PWD, 2nd Floor, Near Moti Daman Market, Moti Daman.
Regarding Supply and Installation of New Electrical Panel Wiring and LED Street Light Work at Collectorate Building Dholar, Moti Daman.
2025_DAMAN_4153_1
Tender Notice No.155/2024-255
Open Tender
Civil Works - Others
Works
180 days
Daman Disrict.
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
The Exe. Engg., PWD, WD-I, Daman.
₹66,949
2 May 2025
27 Mar 2025
15 Apr 2025
27 Mar 2025
15 Apr 2025
27 Mar 2025
Items :
Supplying & erecting approved make Four Pole 415V change over switch interior for panel mounting with operating mechanism A.C.23 duty confirming to IS for (F)400A
Supplying and erecting triple pole & neutral 440V/ 500V panel mounting Aluminium Busbars with four equal Nos. of bus having current density not more than 0.8 Amp. / sq.mm (Rated current / cross section area) duly wrapped with colour insulating tape for phase sequence of following current carrying capacity, erected with necessary bus bar supports /insulators, main cable socket to each busbar,erected in existing cubical panel with necessary connections. (D) Suitable for 400 Amp. Capacity
Supplying and erecting triple pole & neutral 440V / 500V panel mounting Copper Busbars with four equal Nos. of electrolyte bus having current density not more than 1.6 Amp. / sq.mm (Rated current / cross section area) duly wrapped with colour insulating tape for phase sequence of following current carrying capacity, erected with necessary bus bar supports /insulators, main cable socket to each bar, erected in existing cubical panel with necessary connections. (B) Suitable for 200 Amp. capacity
providing and erecting Approved make Three Phase & Neutral LT Heavy Duty Switch Disconnector Fuse Unit Cubical type for panel mounting complete with operating mechanism suitable to operate on 415V A.C. , 23A duty With HRC fuses of suitable load confirming to IS. 13947 (Part I & III). of following capacities. (e) 250 Amp
Providing & erecting weather proof, dust & vermin proof, floor mounted front operated indoor type cubical panel board necessary IP-42 and above protection as per approval from engineer incharge made from 14 SWG thick CRC M.S. sheet for outer body & doors, 16 SWG thick CRC M.S.sheet for internal partitions with necessary accesories , supporting angles/ flats channel including cutting, bending, drilling, welding, riveting with internal partitions & cable alley as per requirements & instruction of engineer-in-charge with erection of supplied switch gears, BUSBARS, suitable size of inter connecting PVC copper wire / copper-aluminium strips, rubber grommets, rib, bakelite control fuses/MCB for measuring instruments, earth bus & earth bolts, foundation flange - bolts-base Plates, sufficient nos. of hinged doors, handles with locking arrangement and rubber gasket,heavy duty end terminal connection,danger notice board,necessary ventilation,earthing strip complete. The Panel shall be painted with epoxy powder coating. (The rates excludes the cost of switchgears, bus bars, inter connecting mains & Copper Aluminium strips, meters, Fuses etc. The dimension shall be measured excluding base beams) The panel shall be supplied with following approved manufacturers with following size. (C) The standard companies switch gear shall be used and only manufacturers as per IEC 61439 for beneficial use. (ii) with 550 mm. Depth
Providing and erecting Approved make Three pole moulded case circuit breaker having breaking capacity ICU of 25 K.A. at 415 V having normal current rating up to 25 A to 100A. with Fixed thermal & magnetic release suitable to work on A.C. supply 50 c/s. with all internal connections, spreader tinned copper & complete erected in existing 16 G.M.S. housing. ICS=100% of ICU only
providing and erecting Mains with ISI marked, 1.5KV grade electrolyte multi stranded, annealed copper conductor with heat resistant PVC insulated conforms to IS 694, IEC - 227 erected in existing pipe of following size (Specifically for control panel, relays, power switchgears, motor starters & control wiring) with required size of copper lugs, nuts and bolts if required. (h) One wire 25.00 sq. mm
(i) One wire 35.00 sq. mm
Solder less crimping type Copper lugs conforming to IS suitable for cable of following size evenly crimped with high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner. (E) 35/50 Sq.mm.
Supplying and erecting approved make suitable panel indicator LED type lamp, lens cover, complete erected with necessary connections.
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (I) 3 1/2 core 240 Sq. mm( 120 Sq. mm 1/2 core)
Making trench in soft soil of suitable width of 90 cm deep for laying cable or locating the fault all over the run and back filling the same and making the surface as normal ground.
Making trench in Hard Murrum / Tar Road of suitable width of 90 cm or required depth for laying any size of cable or locating the fault all over the run and back filling the same and making the surface as normal ground.
(B) If additional machinery like hammer driller or JCB use [Add]
Supplying following size of Light duty “A” Class G.I . Pipe & erecting as directed by Engineer-in-charge. (D) 100 mm dia.
Solder less crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner. (G) 120 Sq.mm.
(J) 225 Sq.mm.
Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The DBs should be used of same company of MCB to be used) suitable for (B) three phase incoming and single phase horizontal type outgoing Per phase isolation type (PPI) (b) sheet steel double door (iv)12 way
Providing and erecting busbar chamber confirming to IS-375 fabricated from 16 G.M.S. sheet, dust & vermin proof having hinged door with rubber gasket and necessary busbar supports with Aluminium busbar having current density not more than 0.8 Amp. / sq.mm (Rated current / cross section area) duly wrapped with colour insulation tape for phase sequence, three phase & neutral each Suitable for following current capacity with necessary painting mounted on wall or pedestal frame of required size with necessary connections. (A) Suitable for 63/ 100 Amp. Capacity
Providing and erecting Three pole Miniature isolator A.C. 22 duty confirms to IS 13947-3 in existing box. (b) for 63 Amp.
providing and erecting Miniature circuit breaker single pole 6A to 25A suitable to operate on 240 V A.C. system and having breaking capacity 10 KA to be erected in existing box. confirming to IS 8828/1996 with ISI Mark
Providing & erecting approved make street light / wall mounting junction box compression moulded from SMC (thermoset plastic) vertical sliding cover having locking with square head stud loop in / loop out in built terminal suitable for four core cable, waterproof of I.P. 54 protected with clamp or bolt nut & earth bolt of following size. (A) 200mm x 127mm x 83 mm
Providing and, fixing heavy duty flange type brass cable gland with rubber ring for PVC insulated armoured cable complete with out going tails, insulating tape etc for following size of cables. (B) 2 to 4 core 6 Sq. mm
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand / Solid Copper conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe at road crossing or floor of following size of cables. (C) 4 core 25 Sq. mm
Supplying & erecting in earthpit of minimum bore dia. 225mm size approved make Safe Earthing Electrode consisting Pipe-in-Pipe Technology as per IS 3043-1987 made of corrosion free hot dipped G.I.Pipes having Outer pipe dia of 80 mm having 80-200 Micron galvanising, Inner pipe dia of 40 mm having 200-250 Micron galvanising, connection terminal dia of 14 mm with constant ohmic value surrounded by highly conductive compound with high charge dissipation suitable for following type of applications with chamber and heavy duty cover.(approved make OEM has to submit test certificate including value of earth resistane of installation. [B] For Electrical installation up to 11 KV located in other than normal soil i.e.Soft Rock, Marshy Soil etc. -Length of Pipe : 2 mtr -Back filling Compound :1 no. Bag of 25 Kg
Providing and erecting Annealed bare Copper wire 8 to 16 SWG.
Providing and erecting required size HOT deep Galvanised iron strip for earthing of H.T. , OCB/ ACB/ Transformer LT panel board, Motors etc. using proper clamp.
Providing and erecting metallic vitrified danger notice board as per language suggested by engineer incharge for MEDIUM VOLTAGE installation to be erected as per IS-2551.
Providing & laying approved make Double walled corrugated pipes (DWC) of polyethylene(conforming to IS 14930 II )with necessary connecting accessories of same material at required depth in existing trench for laying of cable. below ground / road surface for enclosing cable (B)63mm outer dia
Supplying and erecting B class Galvanized iron pipe having smooth finished bore of the pipe on both ends erected nuts and bolts along the pole / wall shaping the pipe as per site requirement. Pipe dia as following.
Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) With oval conduit /PVC casing capping double lock type (b) 2 wire 2.5 sq. mm
providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (a) 2 wire 4 sq. mm
Providing and erecting required size Copper strip for earthing of H.T. OCB / ACB/ Transformer, LT panel board, Motors etc. using copper clamp.
providing and erecting Mains with ISI marked, 1.5KV grade electrolyte multi stranded, annealed copper conductor with heat resistant PVC insulated conforms to IS 694, IEC - 227 erected in existing pipe of following size (Specifically for control panel, relays, power switchgears, motor starters & control wiring) with required size of copper lugs, nuts and bolts if required. (f) One wire 10.00 sq. mm
Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kv grade ISI marked copper wires of following size to be erected as directed. (h) 2.50 Sq.mm 3 core round PVC sheathed
Neutral Link for (i) 32 / 63 / 125 Amps.
Providing and erecting Approved make Three pole moulded case circuit breaker having breaking capacity ICU of 25 K.A. at 415 V having normal current rating up to 25 A to 100A. with Fixed thermal & magnetic release suitable to work on A.C. supply 50 c/s. with all internal connections, spreader tinned copper & complete erected in existing 16 G.M.S. housing. ICS = 100% of ICU only
providing and erecting Miniature circuit breaker single pole 6A to 25A suitable to operate on 240 V A.C. system and having breaking capacity 10 KA to be erected in existing box. confirming to IS 8828/1996 with ISI Mark
Providing and erecting required size HOT deep Galvanised iron strip for earthing of H.T. , OCB/ ACB/ Transformer LT panel board, Motors etc. using proper clamp.
Supplying & erecting earth pit of minimum bore dia.150mm size approved make Earthing Electrode consisting Pipe-in-Pipe Technology as per IS 3043-1987 made of corrosion free hot dipped G.I.Pipes having Outer pipe dia of 50mm having 80-200 Micron galvanising, Inner pipe dia of 25 mm having 200-250 Micron galvanising, connection terminal dia of 12mm with constant ohmic value surrounded by highly conductive compound with high charge dissipation suitable for following type of applications with chamber and heavy duty cover.(approved make OEM has to submit test certificate) & having back filling compound of (B) Inner chemical (CCM Compound)- Resistivity:- 0.2 / meter testing as per IEC 62561-2017, Voltage drop:- < 1 volt at no load & dry form, Sulphar content:- <2%(C) Back fill Compound :- Earthing compound should be capable to retain moisture for long time Necessary test report must be submitted. [C] For Electrical Installation covering Transformer Neutrals, Lightning arrester Earthing, A.C.Plant & Sensitive Computer System(like Automation, SCADA)i.e. independent Earthing located in other than normal soil i.e. Soft Rock, Marshy Soil etc.. -Length of Pipe : 3 Mtrs. -Back filling Compound :2 nos Bags of 25 Kg. Length of Pipe : 2.00 mtrs
providing and erecting Cast iron earth plate size 30 X 30 X 0.35 cms. buried in specially prepared 2.5 Mtr. deep earth pit complete with necessary G.I. strip in G.I. pipe 2 Mtr. long with coupling and G.I. plug for earthing of switch gear, conduit run or power plug etc.
Providing and erecting XLPE (IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (A) 4 core 16 Sq. mm
(B) 4 core 25 Sq. mm
Making trench in soft soil of suitable width of 90 cm deep for laying cable or locating the fault all over the run and back filling the same and making the surface as normal ground.
Making trench in Hard Murrum / Tar Road of suitable width of 90 cm or required depth for laying any size of cable or locating the fault all over the run and back filling the same and making the surface as normal ground.
Add if additional machineries like hammer driller or JCB use (Add)
Providing & laying approved make Double walled corrugated pipes (DWC) of polyethylene(conforming to IS 14930 II )with necessary connecting accessories of same material at required depth in existing trench for laying of cable. below ground / road surface for enclosing cable (a) 50 mm. dia.
Providing and, fixing heavy duty flange type brass cable gland with rubber ring for PVC insulated armoured cable complete with out going tails, insulating tape etc for following size of cables. (E) 2 to 4 core 25 Sq. mm.
Solder less crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner. (C) 16/25 Sq.mm.
Providing and fixing Terminal board of size 5.0 x 127 x 152.4 mm.bakelite sheet with suitable brass studs with nuts, washers and clamps of size 25mm x 3mm suitable for pole painted with one coat of red lead paint.
Providing 1:2:4 cement concrete foundation & 70 % PCC from bottom including excavation for the pole of size 60 x 60 x 120 cm. Deep in below ground level with plinth of 45 cm x 45 cm(or 45 cm dia x 45 cm) high upper ground level with necessary curing and finishing in approved manner. ( for 7.5 & 8/8.5 mtr pole)
Supplying & erecting IP 55 grade following size section pillar fabricated from joint less M.S. Sheet with angle iron legs made from jointless M.S. Angle with cable clamps to be buried in ground to have appropriate erection to work uniform until erected with cement concrete foundation and 45 cm high bricks work finishing with plaster etc. hinged double door internally supported on both side, with internal and outside looking arrangement with look and keys in duplicate 35 x 35 x 5 mm M.S. Angle of Two Nos. one is welded and other with nut and bolt for erecting Bakelite sheet. Painting the Section Pillar inside and out side with three tank powder coated paint. section pillar roof should be without joint with water leakage proof & tested as per IP 55 test & followed by IS 2147 of 1962 (A) 150 X 90 X 75 cm section pillar fabricated from 14 Gauge MS Sheet with angle iron legs 95 cm long made from 40 X 40 X 6 mm thick MS angle..
Supplying and erecting bakelite sheet 12mm thick HYLAM make on existing angle iron frame.
Supplying and erecting B class Galvanized iron pipe having smooth finished bore of the pipe on both ends erected nuts and bolts along the pole / wall shaping the pipe as per site requirement. Pipe dia as following. (C) 40 mm dia.
Supplying & erecting approved make Digital time switch having lithium cell 6 years operative and operate battery backup 1 channel day clock with 14 memory programme , suitable to operate on 240V + 5%, 16A with, floating contacts Minimum switching setup time 1 minimum & LCD display also comprised permanent ON/OFF switching Programming switches & housed in fire proof thermoplastic enclosure & transparent cover erected as required with necessary connection erected as directed.
Supplying & erecting power contactor for time switch complete erected as per direction Cat. III. (D) 4 Pole 440V 40 Amp.
Supplying and erecting approved make Octagonal pole made from HR sheet steel. The pole should be made as per IS. and shall be coated with hot dip galvanizing as per IS 2629/2633/4759, suitable suspend local wind speed with integral Junction box consist of terminal plate of min 6mm Hylam sheet, standard profile 35mmX7.5mm Din-Rail for MCB Mounting, stud type terminal and arrangement for cable termination to be erected With Suitable foundation (Included) as per details given by manufacturer considering site requirement. (G) 8 Mtr. Long 70 mm Top X 155 mm bottom dia, 3 mm thickness with 260mmX260mmX16mm base plate, 4-M20 Bolts and 600mm long J-Bolt.Approx Pole weight 84 kg
Providing and erecting street light pole bracket comprising main B Class GI pipe of 4.2 cm/require outside dia. complete with suitable B Class G.I sleeve tubing of approx. 45cms.length and suitable for 76.5 mm / 80mm. / require size pole top having sufficient fasteners for fixing the brackets and having spread of 1 mtr. length with suitable rise as per site condition & suitable welded stiffener reducer and nipple with check nut complete painted with one coat of Red oxide / PU base primer and two coats of Aluminium / PU paint. paint with following nos of arms. [A] Single Arm bracket 1 Mtr
Solder less crimping type Copper lugs conforming to IS suitable for cable of following size evenly crimped with high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner. (B) 10 Sq.mm
Providing and fixing Pre-Cast Rubber Dye / Steel Dye inter locking concrete block 60mm thick with grade of concrete M300 pnumatic compressed/ vibrated mechanically and as per approved design Confirming to IS 15658 : 2006 including 35mm Sand Layer for levelling and filling the joint with sand in proper line and level as per guidlines of IRC : Sp 63-2018 erc. Complete
Supply & Fixing of EN-grade Foundation bolt M20 x 600mm long ( 4 nos )
DIPAL ELECTRICALS (BID ID -9158)
Maverick Electricals (BID ID -9159)
TECHNO ELECTRICALS (BID ID -9100)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .