EMD Value
₹59,880
Closing Date
29 Jun 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Cdr, HQ 138 WE
HQ 138 Works Engineers PIN-914138 C/O 56 APO
REPAIR/ MAINTENANCE TO HT OH LINES,TRANSFORMERS, VCBS AND CONNECTED WORKS AT KARU AND SHESHARTHANG AREA UNDER GE 860 EWS
2023_MES_598852_1
138WE/L-35/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE 860 EWS
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE 860 EWS
₹59,880
Yes
16 Sept 2023
27 May 2023
6 Jul 2023
27 May 2023
29 Jun 2023
10 Jun 2023
Amount
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5 m depth for laying of cable/ stay assy/HT poles and getting out in hard/dense soil complete all as specified and directed by Engr-in-Charge.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 3.0 m depth for foundation of poles and getting out in hard/dense soil complete all as specified and directed by Engr-in-Charge.
Returning filling incl spreading watering and well ramming in layers not exceeding 25cm in hard and dense soil complete all as specified and directed by Engr-in-Charge.
Removing excavated material not exceeding 50 mtrs and depositing where directed at a level n. exc 1.5mtr above the starting point complete all as specified and directed by Engr-in-Charge.
Material and labour for Plain cement concrete 1:4:8 type D-2 (using 40 mm graded crushed stone aggregate) as in foundation of poles/stay assy including use of necessary form works for rough finished surface complete all as specified and directed by Engr-in-Charge.
Material and labour for PCC 1:3:6 type C–2 (using 40 mm crushed graded stone aggregate/as in foundation for poles/ stay and necessary form work for rough finished surface complete all as specified and directed by Engr-in-Charge.
Material and labour for PCC 1:2:4 type B–2 (using 40 mm crushed graded stone aggregate/as in coping of poles/ stay assy including use of necessary form works for rough finished surface complete all as specified and directed by Engr-in-Charge.
Sand cushioning to underground cable complete all as specified and directed by Engr-in-Charge. in clause 19.75 of SSR Part - I.
M&L for un reinforced precast concrete cable cover class HV type I, flat size 300mm x 180 mm x 40 mm complete all as specified and directed by Engr-in-Charge.
M&L tubes galvanised in repair with all fittings and fixed complete to walls and ceilings or laid in floors/with pole/trenches "Light grade" 80 mm dia for the protection of the U/G cable complete all as specified and as directed by Engineer-in-Charge.
Dismantling & taking down insulator any type any size from HT pole complete all as specified and directed by Engr-in-Charge.
S&F polymer composite Pin Insulator, grey in color , dia of FRP rod 20 mm, lengrth of FRP rod (min) 165 mm, dia of weather sheds100mm as per IEC 61109 for 11000 volts grade complete all as specified and directed by Engr-in-Charge.
S&F polymer composite disc type , grey in colour working pressure 11000 voltscomplete all as specified and directed by Engr-in-Charge.
M&L for dehydration of transformer oil with mobile transformer filteration plant at site with all required accessories connected to transformer and carrying out filteration of transformer oil for the desired dielectric strength. ie not less than 30 KV at 2.5 mm gapcomplete all as specified and directed by Engr-in-Charge. Note : Test certificate shall be submitted before and after filteration for dielectric strength.
Supply and Filling Transformer Oil of good quality for Topping Up transformers 200 KVA to 630 KVA Capacity having dielectric strength not less than 50 KV , flash point not less than 135 degree C , having low viscosity for filling or replacing the old oil complete all as specified and directed by Engr in Charge.
M&L for shifting of outdoor type transformer upto 400 KVA from GE 860 to civil Work shop at leh and placed on the platform for repairing by the vendor complete all as specifed and directed by Engineer-in-charge
Dismantling of air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism for repair/ replacement of broken/worn out components and insulators etc complete all as specified and directed by Engr-in-Charge.
Dismantling burnt / defective Gang Operated Switch keeping away from site , Supply & install 11 KV 3 Phase Gang operated air break switch with drop out fuses set ( consisting 12 Nos Post Insulator ) 400 amp capacity, vertical mounting with fixed and moving contacts complete with locking arrangement and fixing the gang operated switch on existing two/four pole structure including making all jumper connections with insulated leads of suitable size with line tops etc, complete all as specified and directed by Engr-in-Charge.
Dismantling the Existing Damaged Danger Notice plate from the HT Poles keeping away from site and M & L Danger notice plate of 1.6mm mild steel sheet , vitreous enamelled white ,with letters, figures and conventional skull and bones in signal red colour and fixed with MS Clamps,bolts,nuts of approved size for HT, 25x20 mm size complete all as specified and directed by Engr-in-Charge.
M & L cable Jointing Kit for 11 KV (Earthed) grade cable for Outoor termination heat shrinkable joint complete with jointing material and accessories suitable for 3 core XLPE Armoured aluminium cable of size 95 Sqmm complete all as specified and directed by Engr-in-Charge.
M & L cable Jointing Kit for 11 KV (Earthed) grade cable for Outoor termination heat shrinkable joint complete with jointing material and accessories suitable for 3 core XLPE Armoured aluminium cable of size 185 Sqmm complete all as specified and directed by Engr-in-Charge.
M&L steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 (11.0 mtr long) complete all as specified and directed by Engr-in-Charge.
S&F stay assembly set comprising of 14mm long GI stay bow, 2150mm long stay rod 20mm dia with threaded end GI nut bolt and washers, thimble including 300x300x6mm MS stay plate and exposed surfaces shall be given two coat of aluminium paint over a coat of red oxide primer complete including dismantling of existing damaged assembly complete with all accessories as shown in electrical plate No 1 of MES schedule part-I complete all as specified and directed by Engr-in-Charge. (Excavation, earth work, PCC & insulator shall be measured and paid separately).
M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structrural steel sections including nuts, bolts, washers, welding, bending cold or size as indicated or directed nand inclusive of one primer coat, one under coat and one finishing coat of aluminium paint of approved make complete all as specified and directed by Engr-in-Charge.
Supply, laying, testing and commissioning of semi conducting compound conductor screened PVC bedded galvanized steel strip or wire armoured XLPE insulated heavy duty 11000 Volts grade with stranded aluminium conductor of size 185 Sqmm x 3 core confirming to IS 7098 Part-II, suitable for earthed system complete all as specified and directed by Engr-in-Charge. Note : 1. The end termination joint shall be measured and paid separately under respective items. 2. Excavation, earth work, sand cushioning and protection cover will be measured and paid for separately.
All as per item No 25.00 but of size 95 Sqmm 3 core complete all as specified and directed by Engr-in-Charge.
Supply and fixing aluminum conductor steel reinforced (ACSR) of any size, straining properly on insulators and binding on existing HT poles or new poles with and incl 02mm dia aluminium binding wire complete all as specified and directed by Engr-in-Charge. Note : The 3% for sag, joints & jumpers shall be added in measurements. (a) 1 of 6/1x3.00mm (Ferret)
Opening of the VCB , 11 KV 630/400 Amps of make Crompton greaves/ABB by removing of the Breaker from the existing position after disconnecting all the connections from the system, servicing, Overhauling of the same, checking of the same for proper operation, spring charge, charged control cables are fastened tightly to the terminals, any abnormality, VCB, cleaning the surface of the insulators, fasten the bolts, checking and correcting interrupting units, mechanism, linkages etc, fasten the hardwares of control wiring, check that the split pins, Circlips, dowell pins etc. have not come out and are intact, lubricate the mechanism, moving parts by castrol, all purpose grease or equivalent, check that the vaccum pots/chambers is within limit including opening of the shutters properly, replacing of the trip catch, roller, holding catch, stopper, close push button, closing cum reassembling, controll limit switches reconnecting of the breaker for smooth functioning complete all as specified and directed by Engr-in-Charge.
Decarbunizing/cleaning complete HT 11KV, 3 phase independent bus bar, bus bar chamber of HT panel electrification connection complete, HT VCB switch gear arrangement incoming and outgoing installed in sub-stations after removing the complete bus bar spout, circuit spout from the bus bar chamber, cleaning with CTC and ensure proper decarburizing, re-fixing the same after applying backtol (Red) solution to the spout, checking all the connections, tightening the nuts, bolts thimbles for incoming and outgoing system complete, replacement of damaeged space heater along with thermostats, door/position limit switches, controll fuses and servicing /greasing to manual charging/ spring charging mechanism line CTs. PTs and replacement of damaged PT Fusesall as specified and directed, rate quoted is inclusive of bactol red, CTC & cotton waste provided by contractor complete all as specified and directed by Engr-in-Charge.
Supply only closing coil assembly 110v DC for VCB complete all as specified and directed by Engr-in-Charge.
Supply only fix tripping coil 110V DC for VCB complete all as specified and directed by Engr-in-Charge.
Supply only 11 Kv PT HV Back up fuse cat no 12Kv ABCNA 3.15A 38/10 as per OEM Recommendation complete all as specified and directed by Engr-in-Charge.
M&L for replacing existing unservicable silica jel with new crystal clean silica jel for the breathers of transformers capacity 50 to 630 KVA complete all as specified and directed by Engr-in-Charge.
Supply and replace unservicable (broken / cracked) breathers assy complete of various transformers suitable for pipe entry of 20/25 mm dia complete all as specified and directed by Engr-in-Charge.
Supply and fix oil temperature guage complete all as specified and directed by Engr-in-Charge.
Disconnecting defective out door/indoor transformers,11KV/433 V of 63 to 400 KVA from HT/LT sides taking down transformer oil completely,storing oil in suitable container (to be provided by the conractor),lifting the top cover and core assembly carefully and checking the conditions,refilling the tranformer oil completely after necessary repairs like rewinding with copper wire, LT busing, HT bushing, breather assy, temperatute gauge, tap changer and fixing the top cover and painting to transformer complete all as specified and directed. Note : In case of major repaires/replacement in transformer,which can not be undertaken at site, the transformer shall be shifted to civil workshop deemed to be included in unit rate. After complete repair test report from auth agency will be submitted to Engr-in-Charge.
M & L Anti-Climbing device spike type fabricated out of MS bars ( round,square and flat) including nuts,bolts and washers and welding into two halves made to shape to suit the cross section of the pole complete all as specified and directed by Engr-in-Charge.
Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metres below normal ground level, connecting to the galvanised iron strip 32×6mm by means of bolts, nuts , check nuts and washers of galvanized iron and galvanised iron strip protected by provision of GI light grade pipe 40 mm bore including provision of concrete pit made from PCC ( 1:2:4) type B-1 (using 20 mm graded stone aggregate) with 40mm thick cover of RCC 1:2:4 reinforced with XPM (Weight not less than 4 Kg/Sqm) and frame of angle iron 40 x 40 x 6 mm and handle of 6 mm dia MS bar made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom, 1.50 metre long placed on top edge of earth plate, common salt & charcoal filling, with fixing arrangement , funnel, wire mesh and earth work in hard/dense soil , returning filling in and removal of surplus soil to a distance not exceeding 50 metres, all as per electrical plate No 5 of SSR 2009 Part-I and connecting to MCBDB’s earth test point all as specified or indicated including testing on completion complete all as specified and directed by Engr-in-Charge.
S&F MS chequared Plate cover 10 mm thickness for cable duct including 2 coats of synethic enamel paint over a coat of red oxide primer complete all as specified and directed by Engr-in-Charge.
M&L for preparation old (exposed) painted surfaces of existing HT/ LT steel tubular pole, struts including cross arms, clamps etc complete and applying two coats of aluminium paint over a coat of red oxide primer over the ground and making 30cm wide strip with black and yellow paint including numbering of HT/LT poles at a height of 1.5 mtr above ground level as per existing having 15mm width and 50mm bold letter complete all as specified and directed including Marking Red Stipn painting on HT Poles etc complete all as specified and directed by Engr-in-Charge.
Winding wire for transformer complete all as specified and as directed by Engr-in-Charge
HV Bush for transformer complete all as specified and as directed by Engr-in-Charge
LV Bush for transformer complete all as specified and as directed by Engr-in-Charge
HV Bush Rod for transformer complete all as specified and as directed by Engr-in-Charge
LV Bush Rod for transformer complete all as specified and as directed by Engr-in-Charge
Rubber gasket Set for transformer complete all as specified and as directed by Engr-in-Charge
EESSI
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .