| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹45.7 LAccepted-AOC | ₹45.7 L Quoted ₹46.7 L | L1 | Accepted-AOC Being Lowest |
| 2 | L2₹49.8 LRejected-Finance | ₹49.8 L | L2 | Rejected-Finance Not Being Lowest |
| 3 | L3₹55.7 LRejected-Finance | ₹55.7 L | L3 | Rejected-Finance Not Being Lowest |
| 4 | L4₹56.3 LRejected-Finance NEAR CENTRAL SCHOOL BALASORE DIST BALASORE ORISSA 756 001 | BALASORE | BALASORE | ORISSA | 756001 | ₹56.3 L | L4 | Rejected-Finance Not Being Lowest |
| 5 | L5₹56.7 LRejected-Finance HOUSE NO 37 AT VINAYAK URAN DIST RAIGAD NAVI MUMBAI MAHARASHTRA 400702 | RAIGAD | MAHARASHTRA | 400702 | ₹56.7 L | L5 | Rejected-Finance Not Being Lowest |
| Sl No | Description | Qty | Unit | MS SHIVA DURGA ENTERPRISES L1 | M/SNeelachal Enterprises L6 | Sagar Electricals L7 | ARIN AND COMPANY L2 | LAXMI ENTERPRISES L3 | S.P.TRADERS L5 | M/S T.N.CONSTRUCTION L4 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply, install, testing & commissioning of LT control panel board "out-door type" of suitable size with sufficient spacing for fixing of breakers and cable termination, factory fabricated CPRI approved (type-tested) of Make as per List of makes as enclosed with the tender,with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-54 & general construction confirming standards, double door, front & back openable with locking arrangement. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & tinned copper bus-bar wrapped with coloured PVC tape/sleeves of rating in conformity to the Incoming ACB/MCCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.0 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Ph, 4 wire system 415/440 volts grade incl complete internal wiring with not less than 2.5 sqmm FRLSH copper wire incl cable glands of suitable sizes including foundation with necessary earthwork as per manufacturers instruction complete with provision of the following accessories and as directed : (Location Proof Bhawan) | 1 | Each | 3,47,000 ₹3.5 L | 4,15,280 ₹4.2 L | 4,35,680 ₹4.4 L | 3,07,927 ₹3.1 L | 4,11,255 ₹4.1 L | 4,15,680 ₹4.2 L | 4,48,000 ₹4.5 L |
| 1.01BUSBAR :- 800 Amps rated copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance. INCOMING:- (i) MCCB of capacity 630 Amps, 4P, breaking capacity 36 KA with thermal magnetic release complete with rotary handle -02 Nos (ii) Change Over capacity 630Amps, 415 Volts, 4P with necessary handle -01 Nos (iii) Digital Voltmeter (0-500 Volts) with selector switch (iv) Digital Ampere meter (0-600 Ams) with selector switch (v) Indicator lamp with integral circuit (230/240 volt) and cluster LED (RED, ORANGE, BLUE) -01 set | ||||||||||
| 1.02(vi) Protection MCB 6-32 Amp SP - 02Nos (vii) CT (630/5A) -03 Nos (viii) Danger Plate - 01 No OUTGOING:- (i) MCCB 200 Amp,4P,25 KA with thermal magnetic release fixed type - 05 Nos. (ii) MCCB 100 Amp, 4P,25 KA with thermal magnetic release fixed type - 05 Nos. (iii) MCCB 63 Amp, 4P,18 KA with thermal magnetic release fixed type - 02 Nos. | ||||||||||
| 2.00 | All as per item No 1 above, Outdoor type, but housing with following switch gears :-
(Location : NAD SECTION PXE) | 1 | Each | 2,17,436 ₹2.2 L | 3,82,700 ₹3.8 L | 3,15,480 ₹3.2 L | 3,07,777 ₹3.1 L | 3,09,278 ₹3.1 L | 3,15,480 ₹3.2 L | 3,65,000 ₹3.6 L |
| 2.01BUSBAR :- 400 Amps rated copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance. INCOMING:- (i) 4 pole MCCB of capacity 320 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 36 KA with thermal magnetic release complete with rotary handle -01 No (ii) Digital Voltmeter (0-500 Volts) with selector switch (iii) Digital Ampere meter (0-600 Ams) with selector switch (iv) Indicator lamp with integral circuit (230/240 volt) and cluster LED (RED, ORANGE, BLUE) -01 set (v) Protection MCB 6-32 Amp - 02 Nos | ||||||||||
| 2.02(vi) CT (400/5A) -03 Nos (vii) Danger Plate OUTGOING:- (i) MCCB 160 Amp, 4P, 25 KA with thermal magnetic release - 02 Nos. (ii) MCCB 100 Amp, 4P, 25 KA with thermal magnetic release - 03 Nos. (iii) MCCB 63 Amp,4P, 18 KA with thermal magnetic release - 09 Nos. (iv) Analog timer with suitable contractor for street light purpose - 01 No. | ||||||||||
| 3.00 | All as per item No 1 above, Outdoor type, but housing with following switch gears :-
(Location : Fire fighting section PXE, Director office PXE, Married Accn near P/336, P/789, P/769 & P/766) | 4 | Each | 2,94,000 ₹11.8 L | 3,36,000 ₹13.4 L | 3,57,800 ₹14.3 L | 2,95,277 ₹11.8 L | 3,33,272 ₹13.3 L | 3,47,690 ₹13.9 L | 3,24,900 ₹13.0 L |
| 3.01BUSBAR :- 600 Amps rated copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance. INCOMING:- (i) MCCB 400 Amps, 4P, 36 KA with thermal magnetic release with rotary handle -01 No (i) Digital Voltmeter (0-500 Volts) with selector switch (ii) Digital Ampere meter (0-600 Ams) with selector switch (iii) Indicator lamp with integral circuit (230/240 volt) and cluster LED (RED, ORANGE, BLUE) -01 set (iv) Protection MCB 6-32 Amp SP - 02Nos (iv) CT (400/5A) -03 Nos (v) Danger Plate | ||||||||||
| 3.02OUTGOING:- (i) MCCB 160 Amp, 4P, 25 KA with thermal magnetic release - 04 Nos. (ii) MCCB 100 Amp, 4P, 25 KA with thermal magnetic release - 06 Nos. (iii) MCCB 63 Amp, 4P, 16 KA with thermal magnetic release - 06 Nos. (iv) MCB TPN 63 Amp, 10kA - 03 Nos (iv) Analog timer with suitable contractor for street light purpose - 01 No. | ||||||||||
| 4.00 | All as per item No 1 above, Outdoor type, but housing with following switch gears :-
Location : Firing Point-I PXE | 1 | Each | 2,59,224 ₹2.6 L | 3,21,555 ₹3.2 L | 3,35,690 ₹3.4 L | 2,87,107 ₹2.9 L | 3,18,567 ₹3.2 L | 3,27,590 ₹3.3 L | 3,18,000 ₹3.2 L |
Tender Value
Refer Docs
EMD Value
₹96,700
Closing Date
12 Jan 2026, 6:00 pmClosed
Garrison Engineer
GE (I) R and D Chandipur, Post-Chandipur, PIN-756025
SPECIAL REPAIR REPLACEMENT OF LT FEEDER PANEL AND CAPTIVE DG AT TECHNICAL AREA, PXE, CHANDIPUR
2025_MES_745669_1
8236/A/E8
Open Tender
Civil Works
180 days
GE (I) R AND D CHANDIPUR
As per Tender Documents
8 documents required · 8 mandatory
₹500
GE (I) R AND D CHANDIPUR
₹96,700
Yes
18 Feb 2026
22 Dec 2025
19 Jan 2026
22 Dec 2025
12 Jan 2026
5 Jan 2026
Supply, install, testing & commissioning of LT control panel board "out-door type" of suitable size with sufficient spacing for fixing of breakers and cable termination, factory fabricated CPRI approved (type-tested) of Make as per List of makes as enclosed with the tender,with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-54 & general construction confirming standards, double door, front & back openable with locking arrangement. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & tinned copper bus-bar wrapped with coloured PVC tape/sleeves of rating in conformity to the Incoming ACB/MCCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.0 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Ph, 4 wire system 415/440 volts grade incl complete internal wiring with not less than 2.5 sqmm FRLSH copper wire incl cable glands of suitable sizes including foundation with necessary earthwork as per manufacturers instruction complete with provision of the following accessories and as directed : (Location Proof Bhawan)
(vi) Protection MCB 6-32 Amp SP - 02Nos (vii) CT (630/5A) -03 Nos (viii) Danger Plate - 01 No OUTGOING:- (i) MCCB 200 Amp,4P,25 KA with thermal magnetic release fixed type - 05 Nos. (ii) MCCB 100 Amp, 4P,25 KA with thermal magnetic release fixed type - 05 Nos. (iii) MCCB 63 Amp, 4P,18 KA with thermal magnetic release fixed type - 02 Nos.
All as per item No 1 above, Outdoor type, but housing with following switch gears :- (Location : NAD SECTION PXE)
(vi) CT (400/5A) -03 Nos (vii) Danger Plate OUTGOING:- (i) MCCB 160 Amp, 4P, 25 KA with thermal magnetic release - 02 Nos. (ii) MCCB 100 Amp, 4P, 25 KA with thermal magnetic release - 03 Nos. (iii) MCCB 63 Amp,4P, 18 KA with thermal magnetic release - 09 Nos. (iv) Analog timer with suitable contractor for street light purpose - 01 No.
All as per item No 1 above, Outdoor type, but housing with following switch gears :- (Location : Fire fighting section PXE, Director office PXE, Married Accn near P/336, P/789, P/769 & P/766)
OUTGOING:- (i) MCCB 160 Amp, 4P, 25 KA with thermal magnetic release - 04 Nos. (ii) MCCB 100 Amp, 4P, 25 KA with thermal magnetic release - 06 Nos. (iii) MCCB 63 Amp, 4P, 16 KA with thermal magnetic release - 06 Nos. (iv) MCB TPN 63 Amp, 10kA - 03 Nos (iv) Analog timer with suitable contractor for street light purpose - 01 No.
All as per item No 1 above, Outdoor type, but housing with following switch gears :- Location : Firing Point-I PXE
OUTGOING:- (i) MCCB 250 Amp, 4P, 25 KA with thermal magnetic release - 02 Nos. (ii) MCCB 125 Amp,4P, 25 KA with thermal magnetic release - 05 Nos. (iii) MCCB 63 Amp,4P, 18 KA with thermal magnetic release - 04 Nos. (iv) MCB TPN 63 Amp, 16kA - 03 Nos
All as per item No 1 above, Outdoor type, but housing with following switch gears :- (Location Tank Shed PXE, Range Wing, OC Office, Sagardeep )
OUTGOING:- (i) MCCB 200 Amp, 4P, 25 KA with thermal magnetic release - 04 Nos. (ii) MCCB125 Amp,4P, 25 KA with thermal magnetic release - 04 Nos. (iii) MCCB 100 Amp, 4P, 25 KA with thermal magnetic release - 04 Nos. (iv) MCCB 63 Amp,3P, 18kA - 03 Nos
All as per item No 1 above, indoor type, but housing with following switch gears :- (Location Weapon Wing PXE)
OUTGOING:- (i) MCCB 250 Amp, 4P, 25 KA with thermal magnetic release - 02 Nos. (ii) MCCB 160 Amp,4P, 25 KA with thermal magnetic release - 03 Nos. (iii) MCCB 100 Amp,4P, 25 KA with thermal magnetic release - 04 Nos. (iv) MCCB 63 Amp, 4P, 18 KA - 04 Nos. (v) MCB 40-63 Amp, TP, 10 kA - 04 Nos.
All as per item No 1 above, indoor type, but housing with following switch gears :- (Location Weapon Wing (Sub-panel) PXE)
OUTGOING:- (i) MCCB 125 Amp, 4P, 25 KA with thermal magnetic release - 04 Nos. (ii) MCCB 63 Amp, 4P, 18 KA with thermal magnetic release - 04 Nos. (iii) MCB 40-63 Amp, TP, 10 kA - 04 Nos.
Supply and fix ETP grade copper busbar chamber of capacity 200A, 6 way complete inside metallic enclosure and all connected accessories
Supply, laying and testing of LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following sizes complete all as specified and directed. Note: Earth work ( Excavation, Returning & refilling and removal), sand cushining , cable protection cover, GI protection pipe shall be measured and paid for seperately under respective item of Sch 'A'.
150sqmm, 3.5core
120sqmm, 3.5core
95sqmm, 3.5core
70sqmm, 3.5core
50sqmm, 3.5core
Excavation in trenches in soft/loose soil n.exc 1.5m wide and n. exc 1.5m depth for laying of cable, errection of poles, stay and pipe line,and getting out complete all as specified and as directed by Engineer-in-Charge.
Returning & filling including spreading, leveling watering and well ramming in layers n. exc 25 cm thick in any type of soil complete all as specified.
Removal of excavated soil to a distance n. exc 50 m above the starting point complete all as specified and directed
M&L for laying of bricks locally available sub class 'B' bricks (old size) for cable protection cover laid flat and dry in trenches over the cable prependicular to the direction of cable all as directed.
M&L for local sand coushioning with dry and clean over and under the cable for protection of cable , 80 mm sand laid before laying the cable 150 mm sand after laying the cable and filling the sand in cable duct of inside the sub station building complete all as directed
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Aluminium conductor cable of size 70 to 95 sqmm,Indoor/Outdoor type
All as per item above but for cable of size 120 to 150 sq mm.
M& L for Earthing complete with galvanised steel earth plate eletcrode of size 60x60cm x 6.0 mm thick electrode as buried directly in ground (earth pit not less than 3mtr below normal ground level connected to GI earth strip 32mm x 6mm thick by means of bolts nuts,check nuts and washers at complete etc all as shown in electrical plate No-3 of SSR part-1 connected to earthing test point all as specified or indicated including PCC pit in PCC(1:3:6) type CI cast iron frame 50mm thick pre cast RCC (1:1½ :3) nominal mix cover slab reinforced with 8mm dia mild steel bar including necessary excavation earth work in soft/loose soil and disposal of spoil to a distance n.exc 50mtr and funnel with watering pipe wire mesh GI protection pipe 40mm bore including testing complete including taking out old us earthing material all as specified and directed by Engineer-in-Charge. (Note - Earthing lead and GI protection pipe beyond 7.5 mtr shall be measured and paid deparately)
Material and labour for replacement of radiator of 500 KVA DG set TBD 12D4V complete with new radiator of same size and specification complete with raddiator water tank and hose pipe set etc complete all as specified and as directed by Engr in charge.
Please Enable Macros to View BoQ information
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.55 MB
Tender8236A.pdf
Tender Documents • 1.07 MB
BOQ_834963.xls
BOQ • 0.25 MB
Download all tender documents and submit your bid