SE EUDC-VI
33/11 KV S/S PURANIYA, ALIGANJ, LUCKNOW (U.P.)
For Maintenance and repairing of various capacity LT Transformer in the area of Substation University Bheekhampur and Ekka stand under Executive Engineer EUDD University Transgomti LESA Lucknow
2023_MVVNL_790070_6
74/EUDC(VI)/2022-23
Open Tender
Electrical Works
Item Rate
EUDD University
As per document
2 documents required · 2 mandatory
₹1,180
EE EUDD Mahanagar
₹6,000
Yes
3 Jul 2023
17 Jun 2023
24 Jun 2023
17 Jun 2023
23 Jun 2023
17 Jun 2023
Amount
Load measurement of Distribution Transformers & arresting of oil leakage where ever required. Opening of top cover & draining of transformer oil below LV bushing rod and replacement of following damage parts as on site & refilling of transformer oil after work completion tighting of top cover. Providing photograph before work and after work completion.(Only T/F oil shall be provided by department and all other Repairing Material arranged by the Contractor.)
240 KVA / 400 KVA
LV bushing rod 20 mm brass
LV bushing M+F
Gasket set
LV Oil seal 20 mm
LV bushing rod 30 mm brass
LV bushing M+F
Gasket set
LV Oil seal 30 mm
160 KVA – 630 KVA HV Porcelain bushing
160 KVA – 630 KVA HV bushing rod 12 mm brass
160 KVA – 630 KVA HV oil seal 12 mm
Replacement of moist silica gel breather
Installation of silica gel breather wherever required for
250 KVA/400KVA-250 gm
630 KVA-500 gm
Replacement of gasket top cover cork sheet 900x600x6mm packing wherever required.
Checking of transformer oil level and oil top up in distribution transformer conservator tank wherever required.
Provision of 70 fit deep pipe earthing of transformer body and neutral separately with 1.5 inch dia 60 fit pipe. Contractor to ensure that earth connection properly should be tight and earth resistance should be less the 01 ohm. ( All Material Provide by contactor)
M/S AARADHYA AND ADHYATM ASSOCIATES
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .