| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹41.7 CrAccepted-AOC BLDG NO 22 2079 COAST GUARD ROAD NEAR COAST GUARD FAMILY ACCOMMODATION MUNDAMVELI PO PALLURUTHY VII ERNAKULAM 682 507 | ERNAKULAM | ERNAKULAM | KERALA | 682507 | ₹41.7 Cr | L1 | Accepted-AOC BEING LOWEST |
| 2 | L2₹42.9 CrRejected-Finance 216 C SIVA COLONY MAYO LINK ROAD AJMER RAJASTHAN 305007 | AJMER | RAJASTHAN | 305007 | ₹42.9 Cr | L2 | Rejected-Finance Not being L1 |
| 3 | L3₹43.5 CrRejected-Finance GP KIZHAKKAMBALAM KOLENCHERY | THRISSUR | KERALA | 680667 | ₹43.5 Cr | L3 | Rejected-Finance Not being L1 |
| 4 | L4₹44.5 CrRejected-Finance | ₹44.5 Cr | L4 | Rejected-Finance Not being L1 |
| 5 | L5₹48.0 CrRejected-Finance | ₹48.0 Cr | L5 | Rejected-Finance Not being L1 |
Tender Value
₹49.8 Cr
EMD Value
₹15 L
Closing Date
3 May 2025, 6:00 pmClosed
CHIEF ENGINEER CG GOA
CHIEF ENGINEER CG GOA 403806
PROVISION OF SINGLE LIVING ACCOMODATION FOR ICG TRAINEES (EPs) AND OTHER OTM INFRASTRUCTURE AT WILLINGDON ISLAND, KOCHI
2025_MES_702442_1
83084/E8
Open Tender
Civil Works
912 days
GE (I) (CG) KOCHI
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹3,000
GE (I) (CG) KOCHI
₹15 L
23 Jun 2025
24 Mar 2025
10 May 2025
24 Mar 2025
3 May 2025
26 Apr 2025
Amount
SCHEDULE "A" Part - I (BUILDING & STRUCTURE WORKS) Details of prepriced schedule is given in tender documents.
SCHEDULE "A" PART-II (SITE CLEARANCE AND EARTH WORK) Details of prepriced schedule is given in tender documents.
SCHEDULE "A" PART-III (INTERNAL WATER SUPPLY) Details of prepriced schedule is given in tender documents.
SCHEDULE "A" PART-IV (INTERNAL ELECTRIFICATION) Details of prepriced schedule is given in tender documents.
SCHEDULE "A" PART-V (LIFTS) Details of prepriced schedule is given in tender documents.
SCHEDULE "A" Part - VI (FIRE FIGHTING) Details of prepriced schedule is given in tender documents.
SCHEDULE "A" Part - VII (ROAD/PATH/ HARDSTANDING/CULVERT) Details of prepriced schedule is given in tender documents.
SCHEDULE "A" Part - VIII (BASKET BALL & VOLLEY BALL COURT) Details of prepriced schedule is given in tender documents.
SCHEDULE "A" Part - IX (EXTERNAL WATER SUPPLY) Details of prepriced schedule is given in tender documents.
SCHEDULE "A" Part - X (EXTERNAL ELECTRIFICATION) Details of prepriced schedule is given in tender documents.
SCHEDULE "A" PART-XI (SEWAGE DISPOSAL) Details of prepriced schedule is given in tender documents.
SCHEDULE "A" PART-XII (AREA DRAINAGE) Details of prepriced schedule is given in tender documents.
SCHEDULE "A" PART -XIII (FENCING/GATE/COMPOUND WALL) Details of prepriced schedule is given in tender documents.
SCHEDULE "A" PART -XIV (ORGANIC WASTE CONVERTER AND SMART ENERGY METER) Details of prepriced schedule is given in tender documents.
SCHEDULE "A" PART -XIV (MISCELLANIOUS ITEMS) Note:- This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col.' E ' signifies this fact only.
COOLING APPLIANCES Supply and install testing and commissioning of split type air conditioner 2 TR capacity of inverter technology 5 star rating with cordless remote control, single phase, 240 volts complete with all accessories such as indoor and outdoor units and refrigerant tubing of adequate length as required at site, indoor mounting plate, duly powder coated fixing with anchor bolts at any height, drain pipe of suitable size brought to ground level from any height, initial filling of refrigerant gas including making round hole on existing wall for taking up refrigerant tubing, drain pipe, cables etc and making good the disturbed surface to match with existing adjoining surface complete all as specified and directed
Supply and fix factory fabricated mild steel stand suitable for installation of out door unit of split type air conditioner fixing arrangement with anchoring bolts on wall surface at suitable height as per site condition.
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type, Wall mounted type & designed for input variation between 150 V to 280 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and suitable for 2 Ton AC.
Supply and install refrigerators, electric driven (single phase), Ac 230 V, capacity 190 Ltrs, Digital Inverter technology having smart inverter compressor, 5 star rated, single door, direct cool complete all as specified & directed.
Supply and install refrigerators, electric driven (single phase), Ac 230 V, capacity 300/310 Ltrs, Digital Inverter technology, having smart inverter compressor, 3 star rated, Double door, direct cool complete all as specified & directed.
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type, Wall mounted type & designed for input variation between 170 V to 280 V with output voltage stabilized at 230 V with accuracy of ± 2.5%
INTERNAL ELECTRIFICATION Supply and Fixing surface mounted LED batten 10W with extruded aluminum housing heavy duty integrated electronic driver, surge protection more than 2 KA and THD<10% Make: Havells Cat Part No: ENDURALINEAR0BS10W LED865SPCSS / WIPRO / PHILLIPS / BAJAJ
S & F BEE energy efficient and 5 star rated BLDC high-speed ceiling fan having 1200 mm blade sweep, air-flow not less than 210 CMM, operating voltage 220-240 V and frequency 50 Hz, including a down road of suitable size and electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fan complete all as specified and directed.
S & F energy efficient BEE star labelled with minium 3 star rating non-metallic fresh air fan having blade sweep 250 mm, air delivery not less than 860 CMH, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and directed. Make: Havells or BAJAJ
S & F Vertical triple pole & neutral (VTPN), double door, 8-way metallic modular distribution board conforming to IEC 61439-3, suitable for flush / surface mounting with provision for Suitable for 160 Amp FP MCCB as incomer and TP/SP MCBs as outgoing, reversible metal door, 200 A copper busbar for each phase, fully insulated & shrouded neutral bar, earth bar, wiriest & cable ties for cable management, profited masking sheet, etc. having IK 09 & IP 43 protection complete all as specified and directed.
S & F Vertical triple pole & neutral(VTPN), double door, 6-way metallic modular distribution board conforming to IEC 61439-3, suitable for flush / surface mounting with provision for Suitable for Up to 125 Amp FP MCCB as incomer and TP/SP MCBs as outgoing, reversible metal door, 200 A copper busbar for each phase, fully insulated & shrouded neutral bar, earth bar, wiriest & cable ties for cable management, profited masking sheet, etc. having IK 09 & IP 43 protection complete all as specified and directed.
MISC TV & TELEPHONE M & L for TV socket module metal flushed including flushed Box cover plate Box for 2 module complete all as specified.
M & L for telephone jack with module metal flushed including flushed Box cover plate Box for 2 module complete all as specified.
FIRE FIGHTING Supply & fixing of cast iron Air Release valve with two air outlets,100mm dia bore and fixing up in cast iron water supply mains.
M & L for coating and wrapping of under ground steel pipe buried in soil shall have protection against corrosion as per IS-10221. The coating and wrapping shall be carried out in systematic manner to get uniform thickness of coating as per IS specification
M & L for low smoke zero halogen flame retardant fire alarm cable 2 core, 1.5 sqmm copper conductor confirming to BS7629-1, BS6387 & rated for 500 V grade having plain stranded copper conductor with priming insulation of glass mica fire resistance tape & secondary insulation high performance silicon rubber with electrostatic screen of aluminum fire barrier type LT 53 outer sheath confirming to BS 7655, red in colour drawn through & including concealed steel conduit including laying, fixing, connecting complete all as specified and directed.
Staircase signage down of make Bajaj cat part no. 111499 model no. DSDWBB 3W double side display for staircase downwards (with 2 hours built in battery backup) complete all as specified and directed at site complete all as specified and directed.
S & F wall mounted LED emergency Exit signage luminaire Lit up using regular mains supply comes with a unique rechargeable Ni-Cd battery capable of emergency back up upto 05 hours (Cat No 220211 Make Bajaj or equivalent to CG/Havells.
Fire Extinguisher Dry Chemical powder[ABC] type 6 Kg capacity with mono Ammonium phosphate powder 50, stored pressure type, pressure Gauge, applicable on class A, B, C & electrically started fire A rating 13 A, B rating 34B, can construction deep down & CO2 Mig welded, Valve construction: Forging & Machining internal coating of can: Epoxy powder coating external coating of Can: Epoxy polyester powder coating, Sheet metal thickness: 1.80MM, ISI and EN approved, 5 years warranty.
Fire Extinguisher Carbon Dioxide type of 4.5Kg capacity. Ceasefire 4.5kg CO2 Gas type fire Extinguisher, Trolley mounted, Easy weight management Used Unused Mechanism Squeeze Grip, Gross weight 9.1kg empty weight 14.6kg, Can height 857MM, Diameter 140MM, Discharge time less than 10secs controllable discharge mechanism Applicable on class B & C fire, B rating 21B, Can Construction: Hot Spinning/ Forging, Valve Construction: Forging & Machining, Internal coating of Can: Not Applicable, External Coating of Can: Spray painting sheet metal thickness 4.5MM, ISI Approved 1 year
BASKET BALL & VOLLEY BALL COURT Supply and aplication of "SUNFLEX" Grand Prix acrylic synthetic cushioned surfacing system consisting of the following, complete all as specified and directed. 1) Cleaning the base surface 2) Application of bonding coat 3) One layer of black base (Resurfacer) 4) Three layer of cushion flex 5) One layer of seal coat 6) One layer of acrylic Grand Prix base coat colour 7) One layer of acrylic non-texured Grand Prix top coat finish colour 8) Game line marking with approved colour All complete as per international standard and quality.
S & F side net Garware brand black colour braided net with 2.5 mm thickness HDPE twine and 50 mm mesh size, heat treated machine made knotting, weather resistant and non degradable due to exposure to environmental conditions complete all as specified and as directed.
S & F for fibre board of 12mm thick to basket ball posts
EXTERNAL WATER SUPPLY M & L for CI foot Valve of 80 mm, flanged type including fixing with GI pipe of 80 mm dia by using nut bolts, washers, flanges etc complete all as specified and as directed.
Supply and fix Cast iron air release valve with 50 mm bore and two outlets as per IS:14845 complete all as specified and directed.
Supply install test and commission of centrifugal pump set, electric driven complete with all accessories suitable for pumping water 417 LPM discharge at 50 m head coupled with suitable size of electric motor AC 3 phase, 50Hz including connection from starter to motor terminal using proper size of copper cable including, connection of suction pipe from pump to foot valve, delivery pipe connected to the raising mains of the over head reservoir by means of suitable joints painting the suction and delivery pipe with super enamel paint over a coat of primer as per standard code of colour including MS base plate complete all as specified and directed. Note: Suction and delivery pipes shall be measured and paid under appropriate items (main water supply pump for building)
M & L Valve chamber of internal size 0.90m X 0.90m X 0.90m (internal dimensions) including excavation of earth work in any type of soil, 150mm thick PCC in 1:4:8 type D2 foundation, brick work in CM 1:6, 15 mm thick rendering in CM 1:4 to both internal and external surfaces upto 150mm depth below GL, PCC 1:3:6 type C1 as in coping, 4mm thick MS plate cover with two Nos. of hinges and one No. handle made out of MS round bar 10mm dia with necessary locking arrangement including painting to the steel surfaces with two coats of synthetic enamel paint over a coat of red oxide primer complete all as shown on drg and as specified. Note:- The estimated cost includes all earthwork and connected items. (External water supply-1, Treated water supply-1)
EXTERNAL ELECTRIC SUPPLY Cutting of bituminous road, PCC surface/floor by using mechanical method or any type carefully without damaging to adjacent area complete all as specified and directed.
Supply, fix, testing and commissioning of HT 11 KV, 3 phase 50 Hz, indoor type, totally enclosed metal clad switchgear complete with Vacuum Circuit Breaker having rupturing capacity 250 MVA, overload and earth fault protection, ammeter, voltmeter and of rating upto 400 Amp. VCB shall comply with IS: 13947 Part I to Part 5 (circuit breaker) IS: 3156 (Voltage transformer) & IS: 2705 (Current transsformer) complete all as specified and as directed by the Engr-in-Charge
Supply and fixing of cable tray made out of galvanised perforated sheet in 14 gauge, 50mm height including accessories like coupler, wall brackets up/down elbows, bend, tees etc., and fixing with FRP saddles in equal distances on wall crossing and making good to the surfaces as per direction.
Supply and fix cable route indicator made of round CI discembossed HT cable, of size 20cm dia 6mm thick duly riveted with GI angle of size 50x50x4mm and 60cm long including PCC 1:2:4 type B1 using 20mm aggregate 15cmx15cmx15cm for grouting the indicator complete all as specified.
Supply and fix cable route indicator made of round CI disc embossed LT Cable, of size 16cm dia 6mm thick duly riveted with angle of size 50x50x4mm and 60cm long including PCC 1:2:4 B2 using 20mm aggregate 15cm x 15cm x 15cm for grouting the same complete all as specified.
S & F PVC cable looping boxes of size 300 mm x 200 mm x 105 mm with TPN aluminium busbar and MCB SP 6 Amp- 01 No, 10 KA breaking capacity, C curve series, factory made with PVC sheet including heavy duty connector for connection of 3 core Copper cable 2.5 Sqmm & fixed to pole with suitable size flat iron clamp, nuts & bolts complete all as specified and directed by Engr-in-Charge. Make: Sintex or as approved by GE
AVIATION OBSTRUCTION LIGHT Supply and fix aviation obstruction light LED type comprising of aluminium housing with polycarbonate enclosure (Make: Bajaj Cat No. BGAV 302 LED)
DG SET Supplying, installing, testing and commissioning, factory assembled silent Diesel Engine driven generator set, fully wired alternator AC to give an output of 82.5 KVA continuously rating at a power factor 0.8 lagging, 3 phase 4 wire, 415 volts 50 Hz supply, 1500RPM, directly coupled with diesel engine liquid cooled mounted on common base frame complete with floor mounting fuel tank (service tank) of adequate capacity with fuel line & accessories, PCC foundation work as per manufacturer's instructions, vibration damper pads, control panel & other accessories etc and comprising of following. (A) Diesel Engine: Liquid cooled turbo charged with after cooler to deliver suitable BHP at 1500 RPM under NTP conditions of BS 5514 and conforming to IS 10001/ 10002, DIN 6271 & ISO 3046 with an overload capacity of 10% for one hour in any 12 hours continuous operation with the following accessories: Diesel engine of rated speed at full load electric start developing with system with radiator and including electronic governor control of class A1, engine control panel, lubricant oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for electric start with batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/flexible coupling and coupling guard complete (a) Radiator with blower fan or heat exchanger with guard. (b) Pipe coupling for engine cooling system piping. (c) Corrosion inhibitor coolant (d) Paper element filters (i) Fuel filter (ii) Lube oil filter (iii) By pass (e) Fly wheel housing and fly wheel to suit alternator. (f) Engine bearing mechanism in fly wheel housing. (g) Shut off coil with safeties for LLOP/HWT/over speed. (h) Dry type air cleaners and vacuum indicators. (j) Residential silencers.
(k) Stainless steel exhaust flexible bellows. (l) Motor driven priming pump. (m) Battery charging alternator. (n) Exhaust piping made out of STIC C class, MS pipe inclusive of all accessories and hardware, necessary supports scaffolding as per manufacturer's recommendations to sustain back pressure with rain cap. (o) Mineral wool insulation 2 inch thick suitable for 400 degree Celsius temperature cladded with aluminium sheet of 30 gauge for the entire length of exhaust pipe. (p) First fill of oil, coolant and diesel during commissioning and 12 hours testing. (q) Interconnecting copper cabling of adequate capacity batteries control. (r ) Fuel pipe class STIC 1" /1.5" /2" dia - 01 lot (s) Self starter 12 volts DC. (t) Electric operated electronic governor. (u) Fuel injection pump. (v) No of cylinders - as per manufacturer Design (w) Electronic instrument panel, complete with all accessories as per manufacturer's specifications displaying the following:- (i) 12V Battery. (ii) Water temperature. (iii) lubricating oil pressure. (iv) Engine speed -1500Rpm (v) Engine hours (vi) Frequency. (vii) Voltage. (w) Safety control (Trip and indication). (i) High water temperature (ii) Low lube oil temperature (iii) Over speed stop
(x) Base frame: Sturdy, fabricated welded construction, channel iron base frame (duly painted) for mounting engine and alternator as per manufacturer's design along with AVM pads. (y) Battery:-12 volts(1x12v Battery) DC, 180AH, maintenance free battery conforming to IS:14257 with leads & terminals (Make- Excide/Amaron). (z) Fuel tank: 12 hrs. full load diesel storage capacity fuel tank with mounting brackets factory made of 5mm thick HR/MS sheet with level indicator fuel inlet, fuel outlet, air vent, drain plug, in let arrangement for diesel filling fro exterior canopy (without opening its panel) etc complete all as specified and directed. (aa) Isolator panel with 160 amp MCCB (ab) Auto logic panel for automatic stat (B) Alternator: Alternator suitable rated for 100 KVA, 0.8 pf, 415 volts, 3 phase, 4 wire, 50 Hz at 1500 RPM, self excited and self regulated with AVR brushless, screen protected, drip proof , insulation class-H, IP -23, voltage regulation grade - VG 3 self ventilated and conforming to BS: 5000 / IS: 4722 suitable for engine as mentioned here-in before, conforming to IS: 13364(part-1)Make: KOEL GREEN / stampford / Crompton / kirloskar / Greaves (c) Acoustic Enclosure:- M & L for acoustic enclosure for the above 100 KVA DG set to reduce noise level to 75 dB measured at 1.0 meter distance for audible frequencies as per guide of Central Pollution Control Board and manufacturer's specification and comprising of following from authorized GOEMs of Gen Set manufacturer's specified:- (i) Sound insulation: 100mm thick Rock wool (Density 64 Kg/Cum) (ii) Outer body: 1.6mm thick CRCA (iii) Door: 1.6mm thick CRCA (iv) Base frame: ISMC 300 (v) Inside illumination: 1 No.- 1 x 18 watt LED fitting of make Phillips/ Bajaj/ Crompton.
(d) AMF Control panel:- Factory fabricated cubicle type, free standing, floor mounted, indoor type, IP-43, AMF control panel, provided with removable rear panels & hinged front panel for easy accessibility, fabricated out of not less than 2.0mm thick CRCA sheet including two coats of powder coated paint over a coat of red oxide primer etc and comprising of following: (e) AMF control circuit with 4 pole MCCB 160 Amps- 2 nos, with ultimate breaking capacity Icu-25 KA at 415 volts and microprocessor release conforming to IEC 60947 Part-I with breaking capacity Ics=Icu at 415 volts, thermal overload setting 70% to 100%, short circuit setting 5 to 10 times-02 Nos. for main supply & DG set supply with HRC back up fuse complete with all DC control relays/ Line voltage monitor (LVM) as per OEM specifications incorporating motorized stored energy operating Engine start, stop, three attempt starting facility and failure to start etc. (f) Digital load manager: Three phase 4 wire indicating V, I, PF, KVA, KW, F of Enercon make with serial communication port model No. EM6400 with class 1.0 accuracy meter or equivalent make suitable rating of CT per phase- one No. (iii) Indication lamp R, Y, B with 3 Nos. of 2A HRC fuses- 10 sets. (iv) Bottom gland plate for incoming and outgoing cables. (v) Circuit diagram plate. Note:- DG set should be suitable as per CPCB - 4 latest norm wef 01 July 2023 of National Clean Air programme (NACP) Act 1981.
SOLAR POWER PLANT Supplying, erecting, installing, testing and commissioning of grid connected Solar PV Plant 60 KW consisting of following: a) Ongrid solar three phase Inverter having BIS certification and IEC certification. The Inverter shall have online monitoring system. The inverter shall have inbuilt surge suppressor. The Inverter shall have manufacturer’s guarantee of 7 years. b) Photovoltic panels used shall be from ALMM list approved by MNRE confirming to DCR. The panels shall be of 540 Wp capacity. Total number of panel shall be 112 nos. The panel shall come with manufacturers performance guarantee of 25 years. c) The Panels shall be installed on roof with mounting structure of Pre-galvanized steel of various section and aluminium clamps and stainless steel bolts. d) Separate Earthing shall be provided for Inverter, solar panels. The chemical earthing shal be done using copper bonded rod of one meter length. With copper earthing strip of 20x3.15 mm e) Lightening arrestor with hollow copper rod of one meter length with aluminum down conductor of 20Sqmm connected to copper bonded rod of one meter length with pit filled with chemical. f) The DC cable of size 4 sqmm shall be used for interconnecting panels and the inverter. The wire shall be having ISI marking. The wiring shall be done using ISI make conduit pipe. g) The AC wiring shall be done using cables of proper size with ISI marking. h) The system shall consist of DC DB of proper rating having surge suppressor type 2 and DC fuse protection. i) The system shall consist of AC DB of proper rating having MCB of proper rating with ISI marking also surge suppressor type 2. j) The Bus bar box of proper rating will be used. The Busbar box shall have ISI mark.
Supply and laying DWC (Double wall Corrugated) duct pipe outer dia 63 mm and inner dia 50 mm conforming IS 16205 (Part 24) for protection of electric cable complete all as specified and directed.
SEWAGE DISPOSAL M & L DWC pipes ID 150mm / OD 175mm (SN-4 Grade) including couplers and fixtures complete all as specified and directed.
M & L DWC pipes ID 200mm / OD 225mm (SN-4 Grade) including couplers and fixtures complete all as specified and directed.
(i) 25sqmm 4 core XLPE UG cable including necessary excavation, returning, filling, sand cushioning and precast PCC factory made cable covers shalll also be provided for power connection from pump house to proposed STP (k) SS 304 Pipe clamps Clamps and fittings for wall mounting in SS 304 - As per requirement at the site. (l) Components for assembling and fixing solenoid valve set (m) Solenoid valve for pumping arrangement as per requirement/design at the site (n) Valve stand for valves (SS 304, 2mm thickness) - As per requirement (o) Tertiary treatment - Automatic filtration system having starter panel (automatic multiport valve), PSF, ACF, Filter feed pump(1w +1s) with a flow rate of 4-5 cum/h with cholrine dis-infection (p) Operation Manual & Maintenance manual (q) Construction of RCC Tanks for various components of 15 KLD STP with permanent specification(scope of STP covers all civil, electrical and mechanical components after end of sewage line till end of tertiary treatment and including treated storage water tank) with RCC M-30 design mix including excavation in any type of strata, foundation concrete, footing, pile/pile cap, plinth beam, column, lintel, roof beam, roof slab, internal and external plastering, finishing, roof treatment, plinth protection and including refilling of earth and dispersal of surplus earth within 500m lead etc complete all as specified and directed. (r) Construction of RCC Machine Room for 15 KLD STP with permanent specification of 20 sqm plinth area with RCC M-30 design mix including excavation in any type of strata, foundation concrete, footing, pile/pile cap, plinth beam, column, lintel, roof beam, roof slab, block walling, internal and external plastering, finishing, roof treatment, ATT, aluminium doors and windows, plinth protection and including refilling of earth and dispersal of surplus earth within 500m lead etc complete all as specified and directed. (s) The effluent(treated) sewage parameters are as follows: (i) pH: 6.5-8.3 (ii) COD < 50 mg/l
TREATED WATER SUPPLY Supply, installing, testing and commissioning of electrically driven horizontal Centrifugal Pump set as per specification, motor TEFC type, 2880 rpm, 415 V, 50 Hz, 3 phase, class 'F' insulation, IP 55 protection, 2 HP, starting on suitable DOL/Star Delta starter. The pump shall be horizontal, end suction, top discharge. The pump shall have cast iron casing, cast iron/bronze impeller(as per manufacturer), carbon steel shaft with common base frame (fabricated mild steel channel frame or cast iron type) placed on RCC (1:2:4) including foundation bolts, nuts etc. PVC insulated copper cable connection from starter to the motor terminals all as specified and directed by the Engineer-in-charge (01 No. Working + 01 No Stand By)
Supply and fix foot valve confirming to IS 4038, 25 mm dia
Supply and fix Non return valve of 25 mm dia.
PILE FOUNDATION Boring for cast in situ piles 900mm dia to any depth through any type of soil/ strata by DMC method using bentonite slurry including removal of spoil and depositing at a place outside MD land, using DMC method (Direct Mud Circulation) complete all as specified and as directed by the Engg-In-Charge
Boring for bored cast in situ pile 600 mm dia through any depth of any type of soil/ strata by DMC method using bentonite slurry including removal of spoil and depositing at a place outside MD land, using DMC method (Direct Mud Circulation) complete all as specified and as directed by the Engg-In-Charge
Boring for bored cast in situ pile 450 mm dia through any depth of any type of soil/ strata by DMC method using bentonite slurry including removal of spoil and depositing at a place outside MD land, using DMC method (Direct Mud Circulation) complete all as specified and as directed by the Engg-In-Charge
Reinforced cement concrete of grade M-35 design mix (RMC) as per IS-456 with using 20 mm graded stone aggregate in cast in situ DMC bored pile/under reamed bored pile of any length/any sections as shown on drg etc complete all as specified and directed.
Reinforced cement concrete of grade M-35 design mix (RMC) as per IS-456 with using 20 mm graded stone aggregate in pile caps / grade beams complete all as specified and as shown on drg (Note:- Reinforcement will be measured and paid for seperately under relavent items of this schedule)
Providing TMT bars (CRS/HCRM/CRM) in reinforcement 10 mm dia and over for bored piles of any length and any dia all as shown on drgs including cut to length, bend to required shape, cranking/hooking ends if necessary and binding with 0.9mm dia MS wire annealed or welding so as to secure the bar firmly in position/ required shape complete all as specified and shown on drgs.
Providing TMT bars (CRS/HCRM/CRM) in reinforcement 5 mm dia and over up to and including 10mm dia and conforming to IS-1786 as Helical/stirrups for piles cut to length, bent to shape required, and binding with 0.9mm dia MS wire annealed or welding so as to secure the bar firmly in position/ required shape complete all as specified and shown on drgs (Fe-500D).
All as per item No 15.062 here-in-before but for pile caps /grade beam complete all as specified and directed.
M & L for providing PCC (1:4:8) type D-2 using 40 mm graded stone aggregate for concrete layer below pile caps/ grade beam foundation complete all as specified and directed.
Formwork to sides of pile caps/ grade beams rough finished surface of concrete flat all as specified and as directed.
M & L for carrying out Initial Load test (vertical load test) cast in situ piles of 900 mm dia as per IS 2911 (Part 4) 2013 including mobilising and removing the testing equipments from site after testing is completed all as specified and directed. (Note:- Providing and installing test piles shall measured and paid separately)
M & L for carrying out Initial Load test (vertical load test) cast in situ piles of 600 mm dia as per IS 2911 (Part 4) 2013 including mobilising and removing the testing equipments from site after testing is completed all as specified and directed. (Note:- Providing and installing test piles shall measured and paid separately)
M & L for carrying out Initial Load test (vertical load test) cast in situ piles of 450 mm dia as per IS 2911 (Part 4) 2013 including mobilising and removing the testing equipments from site after testing is completed all as specified and directed. (Note:- Providing and installing test piles shall measured and paid separately)
M & L for carrying out Initial (lateral load test) cast in situ piles of 900 mm dia as per IS 2911 (Part 4) 2013 including mobilising and removing the testing equipments from site after testing is completed all as specified and directed. (Note:- Providing and installing test piles shall measured and paid separately)
M & L for carrying out Initial (lateral load test) cast in situ piles of 600 mm dia as per IS 2911 (Part 4) 2013 including mobilising and removing the testing equipments from site after testing is completed all as specified and directed. (Note:- Providing and installing test piles shall measured and paid separately)
M & L for carrying out Initial (lateral load test) cast in situ piles of 450 mm dia as per IS 2911 (Part 4) 2013 including mobilising and removing the testing equipments from site after testing is completed all as specified and directed. (Note:- Providing and installing test piles shall measured and paid separately)
M & L for carrying out Initial load test (pull out test) of cast in situ piles of 900 mm dia as per IS 2911 (Part 4) 2013 including mobilising and removing the testing equipments from site after testing is completed all as specified and directed. (Note:- Providing and installing test piles shall measured and paid separately)
M & L for carrying out Initial load test (pull out test) of cast in situ piles of 600 mm dia as per IS 2911 (Part 4) 2013 including mobilising and removing the testing equipments from site after testing is completed all as specified and directed. (Note:- Providing and installing test piles shall measured and paid separately)
M & L for carrying out Initial load test (pull out test) of cast in situ piles of 450 mm dia as per IS 2911 (Part 4) 2013 including mobilising and removing the testing equipments from site after testing is completed all as specified and directed. (Note:- Providing and installing test piles shall measured and paid separately)
M & L for carrying out Routine load Test (Vertical load Tests) all as per IS 2911 (Part 4) 2013 for 900 mm dia cast in situ piles including mobilising and removing the testing equipments from site after testing is completed
M & L for carrying out Routine load Test (Vertical load) all as per IS 2911 (Part 4) 2013 for 600 mm dia cast in situ piles including mobilising and removing the testing equipments from site after testing is completed
M & L for carrying out Routine load Test (Vertical load, Lateral load & Pull out Tests) all as per IS 2911 (Part 4) 2013 for 450 mm dia cast in situ piles including mobilising and removing the testing equipments from site after testing is completed
M & L for carrying out non destructive integrity test all as per IS 2911 (Part 4) 2013 for 900 mm dia cast in situ piles including mobilising and removing the testing equipments from site after testing is completed all as specified and directed.
M & L for carrying out non destructive integrity test all as per IS 2911 (Part 4) 2013 for 600 mm dia cast in situ piles including mobilising and removing the testing equipments from site after testing is completed all as specified and directed.
M & L for carrying out non destructive integrity test all as per IS 2911 (Part 4) 2013 for 450 mm dia cast in situ piles including mobilising and removing the testing equipments from site after testing is completed all as specified and directed.
ARBORICULTURE M & L for excavation of pits size 30cm x 30cm x 30cm in loose soil and filling the pit with mixture of river sand and approved top soil in the proportion of 1:3 mixed with 30% of cow dung powder, 100gms of bone meal and 100gm of neem cake powder
All as per item No 15.082 above but pit size 60cm x 60cm x 60cm with 30% cow dung and 250 gm bone meal and 250gm neem cake powder
Supplying and planting red palm or royal palm healthy sapling having 45cm height and shall have a minimum height of 65cm after 6 months
Supplying and planting coconut tree healthy sapling having 75cm height and shall have a minimum 95cm after 6 months.
Supplying and planting flower plants(Champa/ hybrid hibiscus/ Hybrid west Indian Jasmine/ Hybrid Plumeria white plant/ Panama yellow plant/ Oleander) healthy sapling having 10cm minimum height and shall have a minimum 25cm to 30cm height after 6 months.
Supplying and planting phylanthus healthy sapling having 15cm to 30cm height and shall have a minimum 45cm height after 6 months.
Supplying and planting bougainvillea colour flower plants healthy sapling having 15cm to 30cm height and shall have a minimum 45cm height after 6 months.
Supplying and planting song of India flower plants healthy sapling having 15cm to 30cm height and shall have a minimum 45cm height after 6 months.
Supplying and planting dracaena flower plants healthy sapling having 15cm to 30 cm height and shall have a minimum 60cm height after 6 months.
Supply and planting Mexican grass including providing manure as directed.
COMPOUND WALL & GATE S & F for Barbed Tape Concertina Coils of 600 mm outer dia madeout of 2.60 mm dia High Tensile Spring Steel wire dipped in corrosion preventive fluid (rusilo 901) of castrol make each coil having min 50 turns (circles) covering 6 m and an average weight not less than 8.5 Kg (plus or minus 5 %), medium blade including handle and spike at both ends of coil errected in position on top of mild steel angle by fixing with 1.70 mm GI wire for securing including necessary welding to MS Sections etc all as specified and directed.
M & L for PVC coated Galvanised steel 2 strand barbed wire 2.24 mm dia barbed with 2 mm dia barbs at 75 mm spacing and straining and fixing to any type of standard rail straining bolts, including securing or tying at crossing with and provision of galvanised mild steel wire, staples or steel pins complete all as specified and directed.
GREEN BUILDING NORMS Supply and Install Organic Waste Converter fully automatic having capacity 100Kg/day, having internal tank made of high quality stainless steel while external panels are powder coated for enhanced product life with necessary electric control panel, cabling necessary civil works for installing machine etc with following requirements:- Type of machine: Fully automatic in-vessel composter Composting method: Micro-organism base organic composting Type of micro-organism used: Heat resistant thermophilic bacteria Final Output: Organic soil additive Cycle time: 24Hrs Volume reduction in 24Hrs: 85-90% Internal tank: Stainless steel type Main agitator Shaft: Stainless steel type Input voltage: 415V Special features: VFD as standard across all models, Touchscreen standards Daily waste processing: 100Kgs
Supply,installation,testing and commissioning Three phase energy meter with the following specifications: Microprocessor based three phase tamper proof electronic static pre paid cum postpaid energy meter rating 415 Volts, 50 HZ of range 10-60 Amps, complying to IS16444 :2015 (reaffrimed 2020) with LED display and parameters like Voltage, Current, Frequency, Power, Power factor, KWH/KVA, default /in built dual source, inbuilt long range (LORAWAN) Communication suitable for outdoor LoRa data accumulator and also compatible for Prepaid and Postpaid online energy monitoring billing system with disconnection /reconnection through remote software / data export to ERP complete with 5 Years warranty. Make: Elmeasure Model: PE5121 or equivalent in Secure, L&T, Schneider, HPL, etc. Note: (a) The Energy Meter to be capable of running in both prepaid and postpaid mode. (b) The complete system to carry 5 year warranty.
Supplying, Fixing, testing and commissioning of configuration of cloud Hosted multi user web based software with following modules: (a) Meter Data Management Module The meter data management module would be responsible for collecting the data from the data concentrator and make the data available to the billing system. The system would support offline meter data entry. The meter data management system would capture and provide the following data: (i) 30 min instantaneous data from all the meters for seven parameters – Cumulative Energy, Cumulative Apparent Energy (as applicable), Power, Current, Voltage, Power Factor and Frequency (ii) Monthly billing survey data for cumulative energy and max demand (b) Billing Module: The billing module would collect the data from the meter data management module, calculate the energy consumption, calculate billing determinant and make energy data / billing data available to admin and end users. The billing module would include functionalities for tariff setup, bill format setup, bill adjustment, occupation billing and vacation billing. It would allow postpaid and prepaid functionality as required. (c) Occupation and Vacation Module: The system would support occupation / vacation based on the unit catagories. The system would support automatic data capture on occupation and vacation events.
(d) Customer Module: The system would include a customer portal for the resident /occupant to log in and view their own energy / billing data. (e) Energy Accounting Module: The system would include features of energy accounting. The system would be able to account for total energy block wise, facility wise and would also allow calculations of unaccounted energy in case total energy meter is also available. (f) Communication Module: The system would provide communication of energy data and bills via print, email and sms methods. (g) Meter Master Data: The system would support meter master data repository. The system would support meter replacement process. (h) Excel Export: The system would support export of metering and billing data in excel format. Make: Elmeasure or equivalent of Secure, L&T, HPL, etc.
Supply, install, test and commissioning of DCUs/Gateways and the arrangement of sim cards or internet to enable reliable medium for two way communication between smart meter and HES. The date acquisition (Push/Pull) frequency shall be configurable. It shall push events such as tamper, power off etc to HSE immediatly on occurrence /receipt from meter. It shall have provision for the cellular, WiFi and Ethernet communication for the backhaul to HES. It shall be capable of handling data of minimum 1000 numbers of any type of smart meter (1Ph/3Ph). It shall be able to communicate with the nearest meters at a distance of at least 500m, depending on topographical features. Communication of the nearest meters with other meters shall be establish through appropriate mesh formation. RF mesh shall support self forming and self healing features. The equipment shall be weather proof and dust proof (minimum rating IP54 for indoor and IP65 for outdoor installation). It shall have rechargable battery with backup for 01 (One) hour for normal meter reading, to push tamper event, carry out on demand reading etc complete all as specified and as directed.
Hosting GPRS (4G) charges for two Gateways for five years warranty from the date of completion (for the entire warrenty period) Maintenance after warranty) Make:-Airtel/Jio/Vodafone
Supply and installation of Ultrasonic smart digital Water meter 25mm (32mm thread size) suitable for domestic and commercial applications, make sustainico or equivqlent
PHASE-II (Item No. 15.101 to 15.106) COMPREHENSIVE MAINTENANCE OF LIFT Comprehensive maintenance comprising of routine, preventive & breakdown maintenance of 02 numbers of electrically operated Passenger Lift of capacity 544 kgs, 08 Passengers, speed 1.5 m/s with single speed motor, 415 V, 3 phase AC 50Hz supply suitable to serve G+5 upper floors with AC variable voltage and variable frequency drive(VVVF drive) complete with all standard accessories including ARD and batteries, simplex automatic & manual dual controlled operation with/without attendant, including repairs/ replacement of all defective and unserviceable parts during contact period, attending breakdown as and when intimated including necessary periodical safety checking and testing of lifts as mentioned in relevant code of practice/IE for the safe and efficient performance of lifts installed in relevant schedule here in before through out 12 months on all days including sundays & holidays for first year during defect liability period all as specified and directed
All as per item 15.101 above but for 2nd year during defect liability period.
All as per item 15.101 above but during 1st year after expiry of defect liability period.
All as per item 15.101 above but during 2nd year after expiry of defect liability period.
All as per item 15.101 above but during 3rd year after expiry of defect liability period.
ARBORICULTURE Maintenance of grass bed, trees and plants provided vide BOQ item 15.082 to 15.091 for 2 years from completion of entire work. Maintenance shall be carried out by regular watering, weeding, providing manure as recommended for healthy and lushy growth of plants/grass/trees, spraying insecticides as and when required, regular trimming/pruning to maintain proper growth and shape, regular mowing of grass bed to maintain the height of grass at not more than 2.5 inch, replacing dead/ non-growing plants complete all as given in PS Clause 41.00 and as directed by Engr-in-charge.
PHASE-III: (Item No. 15.108 to 15.121) COMPREHENSIVE MAINTENANCE AND OPERATION OF STP (Item No. 15.050 to 15.053) (For the period of 120 months after completion of Phase-I) Comprehensive Maintenance and operation of STP of capacity 15 KLD through out 12 months on all days including sundays & holidays for first year during defect liability period all as specified and directed
All as per item 15.108 above but for 2nd year during defect liability period.
All as per item 15.108 above but during 1st year after expiry of defect liability period.
All as per item 15.108 above but during 2nd year after expiry of defect liability period.
All as per item 15.108 above but during 3rd year after expiry of defect liability period.
All as per item 15.108 above but during 4th year after expiry of defect liability period.
All as per item 15.108 above but during 5th year after expiry of defect liability period.
All as per item 15.108 above but during 6th year after expiry of defect liability period.
All as per item 15.108 above but during 7th year after expiry of defect liability period.
All as per item 15.108 above but during 8th year after expiry of defect liability period.
NOTE: (A) Comprehensive Maintenance: The scope of comprehensive maintenance includes maintenance of complete infrastructure including RCC tank and machine room under this work and replacing all defective components and restoring any defect/ deformity/wear and tear during defect liability period of two years and comprehensive maintenance of all STP components under this job, Sl. Item No 15.050 to 15.053 of Schedule 'A' Part-XV and all pumps in the scope of STP work for further period of eight years after completion defect liability period. The scope shall also include comprehensive maintenance of all electrical & Sewage Pumps items such as main switch, starter, change over switch, MCCB, voltmeter, ammeter, panel board etc, Sewage water pump, valve system, controlling system, daily checking, leakage, checking noise, cleaning of plant and its surrounding area etc, as per manuafactures instructions and as specified and directed by Engr-in-charge. (a) Comprehensive maintenance includes replacement of all defective/ worn out/damaged parts with new parts and nothing extra shall be paid on this account except the payment specified in this item. (b) The contractor shall be responsible for periodic maintenance, as per maintenance schedule and specified including renewal / replacement of parts, lubricants, fittings/ fixtures, filling of bacteria, etc required for smooth functioning of the plant as per manufactures instructions. (c) The rate quoted shall be deemed to be inclusive of safety gear & required tools for maintenance. (d) The cosumable chemicals like sodium hypoclorite and chlorine shall only be supplied by GE for treatment of sewage and all other spares/ consumable are to be provided by the contractor without any extra cost. (e) Electricity for running of plant will be provided by GE.
(f) The Contractor shall maintain proper records of all kinds of daily, weekly, monthly, quarterly, half yearly and yearly or whatsover maintenance is carried out during contract period in a binded book / register and shall obtain the signature of Engineer-in-Charge every fortnightly. (g) The contractor shall provide display board at proper location near each installations duly writing the name of all concerned who are maintaining and running the plant. (h) In case of non functioning of STP plant, penal recovery @ Rs. 5000/- per day shall be effected starting 24hrs after the start of period on non functioning. (j) The installations shall remain in posession of the contractor for complete period of comprehensive maintenance and he shall be resposible for keeping the plant in running. (k) Any penalty imposed by regulating authorities related with upkeep of STP and quality of effluent shall be borne by contractor during the period and nothing shall be paid on this account. (l) The sludge produced from any component of STP shall become contractors property and shall be removed from site as early as possible. The rate shall be quoted accordingly. (B) OPERATION OF THE PLANT Operating and keeping the STP of 15 KLD capacity in running/ operational condition by deploying required technical staff to produce the treated effluent of specified quality including Sundays and holidays including all connected electrical & Sewage Pumps items such as main switch, starter, change over switch, MCCB, voltmeter, ammeter, panel board etc, Sewage water pump, valve system, controlling system, daily checking, leakage, checking noise, cleaning of plant and its sorrounding area etc by one FGM(skilled) per shift for 2 shifts in a day all per manufacturers instruction and as specified and directed by Engr-in-charge.
JAIN BUILDER (BID ID -3290807)
VIJAY CONSTRUCTIONS (BID ID -3290815)
Ashish Enterprises (BID ID -3291409)
S.N. Constructions (BID ID -3290276)
PUSHKARRAJ CONSTRUCTION PRIVATE LIMITED (BID ID -3289716)
AADHAR STUMBH TOWNSHIP PRIVATE LIMITED (BID ID -3290892)
Kurian And Varghese (BID ID -3291244)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid