Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹19.6 LAccepted-AOC | L-1 | Accepted-AOC L-1 | |
| 2 | L-2₹20.8 L+₹1.2 L (5.87%)Rejected-Finance 438 NO 438 LIG 7TH B MAIN ROAD YELAHANKA NEW TOWN BANGALORE 560064 | BENGALURU | BENGALURU | KARNATAKA | 560064 | L-2 | Rejected-Finance L-2 | |
| 3 | L-3₹21.7 L+₹2.1 L (10.7%)Rejected-Finance | L-3 | Rejected-Finance L-3 |
Tender Value
₹21.1 L
EMD Value
₹42,265
Closing Date
13 Jul 2020, 10:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Director
CSIR -National Aerospace Laboratories, HAL airport road, Kodihalli, Bengaluru - 560017
Electrification of ECS-Ground test facility in Propulsion Division at CSIR NAL, Belur, Bengaluru - 560037
2020_CSIR_51733_1
ESD-NAL/01/E of 2020-2021
Open Tender
Electrical Works
Item Rate
90 days
CSIR -National Aerospace Laboratories, Bengaluru
Please refer tender document.
11 documents required · 11 mandatory
₹500
The Director
₹42,265
24 Sept 2020
1 Jul 2020
14 Jul 2020
1 Jul 2020
13 Jul 2020
1 Jul 2020
90 days
Amount
Supply, installation, testing & commissioning of LT Power control center (PCC) made of 2mm thick CRCA sheet steel dust, vermin proof, compartmentalized front access, welded construction for operation on 415V, 3 phase, 4 wire AC supply having the following as per IS standard : INCOMER: a)1000 A, 4Pole, 50 kA MCCB with built-in Thermo magnetic based O/L, S/C releases, one c/o Aux contact, one c/o Trip contact ,230 V shunt release, Spreader terminals, having rotary handle with door interlock, Emergency Push Button ---- 1 set b) Suitable rated Multi-function meter along with necessary moulded CT's class-1 with short link connected TB,s and RS 485 feature and wired terminals. ….. 1 set c) RYB Indication Lamps, MCCB ON, Off and trip lamp Indication ….. 1 set d)300 mA to 1200 mA rated Earth leakage relay with CBCT….. 1 set Control circuit wiring: with 1.5 sq. mm. PVC insulated copper conductor wires. e) Bus bar:1000A Rated TPN , Electrolytic grade tinned copper bus bar with current density of 1A per sq.mm with heat shrinkable, colored sleeves with DMC/SMC bus bar supports. f) Earthing:25 X 6 mm Copper earth bus throughout the length of the panel with double earth terminal provided on both side of the panel. OUTGOING: TP&N MCCB with built-in Thermo magnetic based O/L, S/C releases, Spreader terminals, having rotary handle with door interlock and lock for Each feeders of following rating and Braking capacity: 1) 800 A, 50KA - 1 No. 2) 400A, 36KA - 1 No. 3) 250A , 25KA - 1 No. 4) 125A, 25 KA - 1No. Note: Drawing to be got approved before fabrication.
Supply ,Installation, testing and commissioning of 2 TR/24000 BTU/Hr and 5 star Rated wall mounted inverter type cooling hi wall split air conditioner having noise level less than 55db, with wireless remote controller, hermetically sealed/scroll/rotary compressor and Eco friendly refrigerant,Condensor and Evaporator coils of copper with auto swing, air filter, self diagnosing with digital display facility, auto restart etc., suitable for operation on 230V, single phase, 50Hz, AC power supply. Indoor & outdoor units including inter connected with refrigerant lines, first charging of refrigerant gas if required. The indoor and outdoor unit shall be fixed rigidly on wall using necessary MS angles frame / Mounting frame, clamps, bolts, nuts,vibrating Dampers, drain pipe, including supply of copper control cabling of suitable core as per standard between indoor and outdoor etc all complete. the refrigerant pipe shall be provided with necessary insulation. Also making holes in the wall for running cu.refrigerant pipes, drain pipe and making good the same after completing the works as per site requirement.
Supplying and Fixing of Cu refrigerant tube with Thermal Foam of suitable size for 2 TR Hi Wall Split Air Conditioner, interconnection of both suction and liquid lines between indoor and outdoor unit as per standard.(Beyond the standard length available in the standard packing of AC unit)
Supply and fixing of 25 mm PVC drain pipe along with accessories,
supplying and fixing of 50mm PVC cover pipe with its accessories for covering Refrigerent Line.
Supply, installation, testing & commissioning of 5 KVA UPS With 30 Min backup single phase to single phase operating with input MCB,L+N+E, 230V,50HZ,power factor 0.8 lag. output Parameters: Power:5000VA/4000W,Voltage -230V(±1%),Double Conversion Type, Pure sine wave,Frequency Regulation - 50HZ(±1%),Transfer Time-Mains to Battery is Zero Millisec, Transfer Time – Inverter to Bypass -Synchronisation Mode is 4msec, Voltage THD <=2% Linear Load, <=4% Non Linear Load,Output Efficiency >90.00% at Full Load,Overload capacity 110% for 10minute, 120% for 15Sec.Crest Factor 3:1 Output Power Factor >=0.8 lag Battery: Battery Type SMF Battery ,Voltage 12V Backup Support Time 30 Minute with Full Load ,Total VAH Minimum of 4992 Required.DC Links and Battery Rack Required Communication & Management: Interface Ports DB-9, RS232,smart slot, usb.Control Panel Multifunction LCD status and Control Console having Automatic Bypass and Forced Air cooling . Indications: LCD Display Input Voltage/Output voltage/load level/Battery Level/Battery Mode/AC Mode/Bypass/Fault,Alarm Audible and Visible Alarms for Battery mode, Battery low, Overload and fault occurrence.Manual Bypass Should have a Manual Bypass Switch to be used at time of UPS Problem/Maintenance. Protection: Mains Input Under voltage and Overvoltage Cut-off Inverter Output Overvoltage/Shortcircuit/Output Undervoltage/Battery LowNoise Level <=42.00dBA around 1 meter from surface of Unit.
Supply of 3CX185sq.mm size Aluminium conductor of 11kV(E) grade XLPE insulated PVC sheathed armoured UG cable in one length as required.
Supply of following size Aluminium conductor of 1.1kV grade XLPE insulated PVC sheathed armoured UG cable in one length as required.
3½ C X 300 sq. mm
3½ C X 240 sq. mm
Supply of following size copper conductor of 1.1kV grade XLPE insulated PVC sheathed armoured UG cable in one length as required.
4C X 50 sq. mm
4C X10 sq. mm
3C x 4 sq.mm
3C x 2.5 sq.mm
4C X1.5 sq.mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11KV(E) grade of 185sq.mm size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV(E) grade of 185sq.mm size in the existing masonry open duct as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV(E) grade of 185 sq. mm size in the existing RCC/ HUME/ METAL pipe as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.
Upto 35 sq. mm
Above 35 sq. mm and upto 95 sq. mm
Above 185 sq. mm and upto 400 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching(75 cm deep)and re-filling etc as required
50 mm dia
80 mm dia
150 mm dia
Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3½ X 240 sq. mm
3½ X 300 sq. mm
Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for 185sq.mmsize of 3 core, XLPE aluminium conductor cable of 11 KV grade as required.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3½ X 240 sq. mm
3½ X 300 sq. mm
Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed armoured UG cable / XLPE copper conductor cable of 1.1 kV grade as required.
4C X 50 sq. mm
4C X10 sq. mm
3C x 4 sq.mm
3C x 2.5 sq.mm
4C x 1.5 sq.mm
Disconnecting,Dismantling of 3CX95sqmm size of 11KV XLPE armoured UG cable connected from the existing OCB and Transformer Terminals.
Disconnecting,Dismantling of following size of armoured UG cable connected from the existing Panels
3½cX300sqmm
3½cX240sqmm
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
4 way (4 + 12), Double door
8 way (4 + 24), Double door
Providing and fixing 125 A rating and 16KA breaking capacity and TP MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
Supplying and fixing 8 way, single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole 6 A
Single pole 10A
Single pole 20A
Double Pole 20A
Triple pole 32A
Triple pole and neutral 32 A
Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 A "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25A,240 V "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate as required.
15/16 A switch
3 pin 5/6 A socket outlet
6 pin 15/16 A socket outlet
Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required
1 or 2 Module (75mmX75mm)
3 Module (100mmX75mm)
6 Module (200mmX75mm)
8 Module (125mmX125mm)
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
3 x 2.5 sq. mm
3 x 4 sq. mm
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.(group c)
Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required.
Supplying and installing 100 mm width X 50 mm depth X 1.6 mm thickness size of perforated HotDipped Galvanised Iron cable tray (Galvanisation thickness notless than 50 microns) with perforation not more than 17.5%, inconvenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
Supply, fixing and making connection 36W to 40W, 240 V, natural white,Recess type LED fitting complete set with suitable driver with inbuilt protection in powder coated CRCA housing, Square shaped of minimum 600mm long,suitable for false ceiling and protected from dust and insects.
Supply ,fixing and making connection 60W,240 V,natural white,outdoor type street light LED fitting with suitable driver with inbuilt protection in Aluminum die–cast housing,with Dust penetration-protected, jet-proof(IP66) Protection,.
Supply ,fixing and making connection 120W ,240 V,natural white,high bay LED fitting with suitable driver with inbuilt protection in Aluminum die–cast housing, and protected from dust and insects and suitable support to install the fitting on the metal frame.
supply and fixing of 400 mm sweep metal body wall mounted fan with speed regulator suitable for operation on 230 V,50hz single phase supply.
Supply of 450 mm sweep,exaust fan of metal body to operate on single phase 230 V,50 Hz supply including suitable louvers with frame complete set as required.
Installation of exhaust fan upto 450 mm sweep in the existing opening, including making hole to suit the size of the above fan making good the damage,connection, testing, commissioning etc.as required.
Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes.
Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe(medium class) bracket for mounting of fluorescent / HPMV /HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts,bolts and washer, painting the flat iron with primer and finish paint etc. as required.
Supply and make Earth pit of advanced chemical gel and dual pipe technology consisting of dual pipe G.I pipe of 3000mm long 80mm dia as outer pipe with 50 mm dia of inner pipe of 80-100 microns galvanized, filled with highly conducting metallic compounds with the permanent sealing at both the ends and lead terminal of 50 X 10 mm size at the top the length of the electrode shall be 3000 mm excluding the lead terminal and the length of the lead terminal at the top shall be 100 mm. To ensure the moisture content and electrical conductivity, resistance lowering grounding minerals shall be filled around the electrode (min 50kgs). Heavy duty weather proof plastic earth pit chamber with cover and locking facility of dimension 254mm dia (top), 330mm dia(bottom) and 260mm (height) shall be used as earth pit chamber, Numbering of pit shall be made by painting.
Supply and make Earth pit of advanced chemical gel and single pipe technology consisting copper pipe of 3000mm long 80mm dia pipe with thickness of 1.6 to 1.8mm, filled with highly conducting metallic compounds with the permanent sealing at both the ends and lead terminal of 50 X 10 mm size at the top the length of the electrode shall be 3000 mm excluding the lead terminal and the length of the lead terminal at the top shall be 100 mm. To ensure the moisture content and electrical conductivity, resistance lowering grounding minerals shall be filled around the electrode (min 50kgs). Heavy duty weather proof plastic earth pit chamber with cover and locking facility of dimension 254mm dia (top), 330mm dia(bottom) and 260mm (height) shall be used as earth pit chamber, Numbering of pit shall be made by painting.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Supply ,fixing and making connection for Warning tower light with necessary support structure to fix on surface with three layer colours operating with 240 V,50 Hz Ac supply.
Supplying, installation, testing & commissioning of conventional automatic fire alarm system(4 Zones) with inbuilt battery, charge circuit complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required.
Supplying, installation, testing & commissioning of photo electronic smoke detector with builtin LED and mounting base plate suitable for operation on 12V / 24V complete with all connections etc. as required.
Supplying, installation, testing & commissioning of manual call point(MCP) of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required.
Supplying, installation, testing & commissioning of response indicator on surface/recess MS box having two LEDs metallic cover complete with all connections etc. as required.
Supplying, installation, testing & commissioning of electronic hooter with 5W/6W speaker and accessories enclosed in a suitable enclosure complete as required.
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
Supply, Fixing and configuration of Speech Dialer SD 2000 with 20 sec recording time, message, 15 telephone numbers to Fire Alarm system
Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required.
75 mm X 75 mm X 60 mm deep
100 mm X 100 mm X 60 mm deep
150 mm X 150 mm X 60 mm deep
Supplying and fixing of FRP Box 100mmX100mmX50mm size (nominal size) on surface with hinged door etc. as required.
Supply and fixing of 4mm thick M.S plate by welding on existing structures for mounting fixtures including painting as required.
Supply of Safety Insulation Mats as per IS:15652 ,Made of Dielectric “Elastomer” which possess elastic properties and may be natural or synthetic in nature. Typically a combination of rubber & Synthetic Polymer of thickness 2mm voltage grade of 3.3kV(MV class).
Legend writing by paint on each feeders with bold letter including current rating and connected load specification as directed by site engineer.
Supply and fixing of as built Single Line drawing(SLD)of the executed work in the photoframe size (1000mm*750mm) .
Supply and Fixing of Cable Marking Tags of Aluminium material with description engraved for Cable size ranging from 1.5sqmm to 300sqmm Tags should be tide with SS twisting wire of suitable size.
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
Supply and fixing of laminated type,wall mountable,Electrical Resuscitation Safety chart.
Classic Electricals
SUPRABHA ELECTRICALS
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .