Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.7 LAccepted-AOC | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹17.8 L+₹4.0 L (28.6%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 3 | L3₹19.8 L+₹6.0 L (43.1%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER |
Tender Value
₹28 L
EMD Value
₹56,000
Closing Date
5 Jul 2024, 6:00 pmClosed
GE 881 EWS C/o 56 APO
GE 881 EWS C/o 56 APO
REPAIR/ MAINTENANCE AND SERVICE OF DG SETS AND REPLACEMENT OF ALLIED ACCESSORIES IN THE AOR OF AGE B/R-I AND REPAIR/ REPLACEMENT TO E/M INTERNAL FITTINGS/ FIXTURES AND WIRING IN VARIOUS UNITS AT BALNOI AND SURANKOTE IN THE AOR OF STN HQ KG UNDER GE 8
2024_MES_658430_1
GE/PNH-23/2024-25
Open Tender
Civil Works
Item Rate
180 days
GE 881 EWS C/o 56 APO
AS PER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
GE 881 EWS
₹56,000
Yes
15 Jul 2024
7 Jun 2024
12 Jul 2024
7 Jun 2024
5 Jul 2024
21 Jun 2024
Amount
Opening of air/water cooled DG sets up to 40 KVA capacity by unscrewing, nuts, bolts and servicing of DG set, complete servicing, checking of oil, coolant, v-belts, greasing and oiling pf parts and toping up, cleaning the inner and outer body, tank and radiator etc by removing sludge etc and reassembling the DG set after comprehensive maintenance of DG sets as per B check, with providing qualified staff at the site which will be adequate to perform routine maint, observed and rectified minor fault if any, without extra cost complete all as specified and directed by Engr-in-charge. NOTES:- (i) Engine oil, oil filter, coolant replacement will be measured and paid separately under relevant items. (ii) 'B' check shall be carried out by the authorized dealer of Kirloskar/Crompton greaves. (iii) Testing equipment's requried for 'B' check shall be of contractor's responsibility. (iv) Make of existing DG Sets are kiriloskar, CG, cummines & Mahindra.
All as per srl item No. 1 above but for capacity 62.5/63 KVA DG set complete all as specified and directed.
All as per srl item No. 1 above but for capacity 100/125 KVA DG set complete all as specified and directed.
All as per srl item No. 1 above but for capacity upto 40 BHP DG set complete all as specified and directed.
Dismantling and taking out of Diesel Engine Generator Sets of 40 KVA capacity air/water cooled, situated at various pump houses/power houses and shifting to authorised work shop at Jammu for major overhauling by replacing the spare parts as required such as piston with pin & clips, piston ring set, cylinder liner, 'O' rings, cylinder head with bolts, belts, nozzle with holder all type of bush & bearings, connecting rod assy, valves with guide, rocker arm with cover, oil seals, slip rings, FIP assy, carbon bush incl any other parts reqd to repair the engine etc and re-installation at the original location including all necessary connections, connecting to alternator including commissioning and testing complete all as specified and directed. NOTES:- (i) Spare parts will be measured and paid separately under relevant items. (ii) Unit rate shall deemed to include Transport from site to Jammu workshop & back to site including neccessary T&P complete. (iii) The quoted rates shall also include labour element required for fixing of new spare parts under relevant item.
All as per srl item No. 2 above but for capacity 62.5/63 KVA DG set complete all as specified and directed.
All as per srl item No. 2 above but for capacity 100/125 KVA DG set complete all as specified and directed.
All as per srl item No. 2 above but for capacity upto 40 BHP DG set complete all as specified and directed.
Supply only following spare parts as per existing make & model suitable for DG set upto 40 KVA
Lubricant oil filter assembly
Lubricant oil filter element
Fuel filter suitable for engine
Fuel filter housing suitable for engine
Over flow pipe assembly suitable for engine
Fan Belt 1158 4 PK/1160 4 PK suitable for engine
Hose pipe for air cleaner including hose clips suitable for engine
Fuel pipe including clips suitable for engine
Turbo charger center assembly complete impeller and turbine
Lubricant oil pump assembly complete impeller and turbine
AVR card suitable for engine
Water separator for engine
Radiator assembly suitable for engine
PLC unit as per approved sample
LLOP switches per approved sample
Injector as per approved sample
Supply only following spare parts as per existing make & model suitable for DG set of capacity 62.5/63 KVA
Lubricant oil filter assembly
Lubricant oil filter element
Fuel filter suitable for engine
Fuel filter housing suitable for engine
Over flow pipe assembly suitable for engine
Fan Belt 1158 4 PK/1160 4 PK suitable for engine
Hose pipe for air cleaner including hose clips suitable for engine
Fuel pipe including clips suitable for engine
Turbo charger center assembly complete impeller and turbine
Lubricant oil pump assembly complete impeller and turbine
AVR card suitable for engine
Water separator for engine
Radiator assembly suitable for engine
PLC unit as per approved sample
LLOP switches per approved sample
Injector as per approved sample
Supply only following spare parts as per existing make & model suitable for DG set of capacity 100/125 KVA
Lubricant oil filter assembly
Lubricant oil filter element
Fuel filter suitable for engine
Fuel filter housing suitable for engine
Over flow pipe assembly suitable for engine
Fan Belt 1158 4 PK/1160 4 PK suitable for engine
Hose pipe for air cleaner including hose clips suitable for engine
Fuel pipe including clips suitable for engine
Turbo charger center assembly complete impeller and turbine
Lubricant oil pump assembly complete impeller and turbine
AVR card suitable for engine
Water separator for engine
Radiator assembly suitable for engine
PLC unit as per approved sample
Injector as per approved sample
Taking out radiator assembly of upto 125 KVA capacity DG sets of any make for repair by flushing out of coolant, cleaning, brazing/soldering or welding etc to stop the leakage of coolant and refixing the same after repair for smooth and efficient functioning, complete all as specified and directed by Engr-in-Charge.
Taking out alternator of 40 KVA DG set of any make and rewinding of rotor coil with super enamelled copper wire of suitable gauge, varnishing, changing insulating material, assembling, testing and connecting to DG set complete all as specified and directed by Engr-in-Charge. Note:- Rates quoted by contractor deemed to be included the rates for tranportation of alternator from site to workshop & back.
All as per srl item No. 7 above but for capacity 62.5/63 KVA DG set complete all as specified and directed.
All as per srl item No. 7 above but for capacity 100/125 KVA DG set complete all as specified and directed.
Taking out alternator of 40 KVA DG set of any make and rewinding of starter/field coil with super enamelled copper wire of suitable gauge, varnishing, changing insulating material, assembling, testing and connecting to DG set complete all as specified and directed by Engr-in-Charge. Note:- Rates quoted by contractor deemed to be included the rates for tranportation of alternator from site to workshop & back.
All as per srl item No. 8 above but for capacity 62.5/63 KVA DG set complete all as specified and directed.
All as per srl item No. 8 above but for capacity 100/125 KVA DG set complete all as specified and directed.
Taking out cylinder head, grinding of valve sheets and polishing with abrasive parts to valve sheets of 15 to 140 KVA DG set of any type complete all as specified and directed by Engineer-in-Charge.
Taking down FIP for overhauling by replacing all internal worn out parts & calibration of FIP complete of up to 140 KVA DG set of any type by authorised dealer complete all as specified and directed.
M&L for replacement of Old battery 12 volt, 90 AH, maintenance free complete all as specified and directed. Make: Exide/ Amaron
M&L for replacement of Old battery 12 volt, 150 AH, maintenance free complete all as specified and directed. Make: Exide/ Amaron
M&L for replacement of Old battery 12 volt, 180 AH, maintenance free complete all as specified and directed. Make: Exide/ Amaron
Special engine oil 20 W, 40 grade all as recommended by manufacturer for first filling in the new /repaired DG sets complete all as specified and directed Make : Kirloskar/ Castrol
M&L for Coolant concentrate for filling in radiator of DG set complete all as specified and directed. Make: Castrol or equivalent approved make as approved by GE.
Taking out self starter from Gen set for repair and rewinding with super enamelled copper wire of suitable gauge, varnishing, carbon bushes, bearing, gears etc as per existing incl replacement of all necessary parts as reqd for repair of self of capacity of DG set upto 125 KVA complete all as specified and directed by Engr-in-Charge.
All as per srl item No. 16 above but for alternator, 12 volt dinamo for charging of battery upto 125 KVA DG set complete all as specified and directed.
Supply and laying in trenches or passing through pipe/walls 1100 volts grade armoured, heavy duty XLPE electric cable with aluminium conductor of size 185 Sqmm 3.5 core including taking down old/ unsv cable any type complete all as specified and directed.
All as per srl item No. 18 above but for cable of size 120 sqmm, 3.5 core complete all as specified and directed.
All as per srl item No. 18 above but for cable of size 95 sqmm, 3.5 core complete all as specified and directed.
All as per srl item No. 18 above but for cable of size 70 sqmm, 3.5 core complete all as specified and directed.
All as per srl item No. 18 above but for cable of size 50 sqmm, 3.5 core complete all as specified and directed.
All as per srl item No. 18 above but for cable of size 35 sqmm, 3.5 core complete all as specified and directed.
All as per srl item No. 18 above but for cable of size 25 sqmm, 4 core complete all as specified and directed.
All as per srl item No. 18 above but for cable of size 16 sqmm, 4 core complete all as specified and directed.
S&F in repair Earthing in replacement for poles and other machinery/eqpt using GI strip as earth lead and MS galvanized steel earth plate electrode 600x600x 6.3mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate is not less than 1.5 mtr below normal ground level connected to galvanized iron strips 32x6mm with GI pipe, nuts, bolts and washers complete upto and PCC pit of required size in PCC 1:2:4 type B1 and RCC cover with frame, charcoal, common salt15cm at round the earth plate watering pipe 20mm med grade/galvanized and 40mm dia GI pipe light grade for GI strip protected steel with funnel complete all as specified and directed as shown in electrical plate No 3 of SSR Part-I 2009.
M&L for replacement of AMF panel/LT panels incl wiring, contracor, relays, MCBs, welding of doors, fixing of hinges brazing complete all as specified and directed
M&L for replacement of off-load change over switch 63 amps, 415 V, 4 pole front handle type as per site requirement, complete all as specified and directed
M&L for replacement of off-load change over switch 100 amps, 415 V, 4 pole front handle type as per site requirement, complete all as specified and directed
M&L for replacement of off-load change over switch 200 amps, 415 V, 4 pole front handle type as per site requirement, complete all as specified and directed
M&L for painting to DG set of any make/size incl base frame complete by spraying with two coats of synthetic enamel paint of first quality paint over a coat of red oxide primer after and incl complete removal of old paint and primer by scratching, rubbing and marking SM No., complete all as specified and directed by Engr-in-Charge.
Taking down carefully copper/ aluminium unserviceable/ perished point wiring (light, fan, socket or power complete including fixture and fittings such as switches, ceiling roses, pandents, regulators, sockets, light fittings,removing material from site for taking credit etc and making good disturbed surfaces of wall, floors, complete all as specifiecd and directed.
M&L for point wiring with two single core 1.5 Sqmm (nominal cross section area) FRLS PVC insulated unsheathed multistranded copper conductor cable and one single core 1.5 Sqmm (nominal cross section area) FRLS PVC insulated unsheathed multistranded copper conductor cable as earth continuity to common earth and connecting to earth dolly running in and including PVC casing & caping (ISI marked) of suitable size with PVC boards of appropriate sizes and all requisite accessories such as PVC elbow, Tee, collars, bends etc. with PVC terminals box & cover for mounting swtches, sockets, fan regulator etc for mounting switches, sockets, fan regulators etc complete all as specified and as directed for the following :-
One light/fan point controlled by one way switch 6 Amp complete all as specified and directed.
One ligh point controlled by two, two way switch 6 Amp complete all as specified and directed.
One 3/5 pin socket outlet 6 amp on same board complete all as specified and directed.
One 3/5 pin socket outlet 6 amp independent board complete all as specified and directed.
One bell point controlled by one way switch 6 Amp complete all as specified and directed.
All as per srl item No 33 here in before but for one 3 pin socket outlet 16/20 Amp independent with two single core 2.5 Sqmm size cable as phase & neutral and one single core 2.5 Sqmm as in continuous earth wire complete all as specified and directed.
S&F in repair ceiling rose, 3 terminal, surface bakelite 65 mm x 50mm, PVC/poly carbonate, insulated body, complete all as specified and directed.
S&F in repair switch piano flush type 6 Amp single pole one way, (ISI marked), complete all as specified and directed.
S&F in repair switch piano flush type 6 Amp two way, (ISI marked), complete all as specified and directed.
S&F in repair switch piano bell push flush type 5 Amp single pole one way (ISI marked) complete all as specified and directed.
S&F in repair socket outlet 2 in 1, 3 pin, 5 Amp flush type universal, complete all as specified and directed.
S&F in repair Switch socket multipurpose combination 2 in 1, 5 pin, 6 Amp flush type universal, complete all as specified and directed.
S&F in repair Switch socket outlet multipurpose combination 2 in 1, 6 pin, 5 and 15 Amp flush type universal, complete all as specified and directed.
S&F in repair Lamp holder PVC/Polycarbonate type with back plate suitable for batten fittings, complete all as specified and directed.
S&F in repair stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc. for 1200 / 1400mm sweep, complete all as specified and directed.
S&F in repair electric bell ding dong type 230 volts AC supply 50 Hz complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repair inverter LED batten 1x 20W, with square profile and polycarbonate channel, lithium iron battery with charging time of 8 to 10 hours and backup tile upto 04 hours with driver, holder incl LED tube light connecting up with with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed.
Supply and fixing in repair LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete. all as specified and directed.
S & F LED in repair light fitting 1x9W/1X10W bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.
S & F in repair surface mounted square/round type decorative LED light fittings 15 watt connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.
Supply and fixing in repair LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed.
Supply and fixing in repair LED building security light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed.
Supply and fixing in repair inverter LED bulb 9 watt including all connected items, complete all as specified and directed. Make : Havells cat part No. LED 9 W INVERTER BULB B22 CDL or equivalent make as specified in PS
S&F in repair LED driver suitable for 34 watt LED ceiiling light fittings and making connection to fitting complete all as specified and directed. Make:-Havells cat part No-LEDDRIVER36V36WS or Equivalent cat part of make as specified in Appx 'A' to P.S.
S&F in repair single pole and neutral enclosure with a two pin and metal earth plug and socket complete with & incl one single pole MCB of 20 Amps complete all as specified and directed.
S&F in repair sheet metal enclosure for DBs, TPN double door (IP43), 4 ways built in bus bars suitable for 415 volts, AC, 50 Hz and suitable for FP MCCB as incommer and out going SP/TP MCBs complete all as specified and directed. Note:- MCBs shall be measured and paid separately.
S&F in repair sheet metal enclosure for DBs, SPN double door (IP43), 4 ways built in bus bars suitable for 240 volts, AC, 50 Hz , including connecting both incoming and outgoing cable termination with proper taping, lagging testing and commissioning complete all as specified and directed.
S&F in repair sheet metal enclosure for DBs, SPN double door (IP43), 8 ways with 200 amps rated bus bar suitable for 240 volts, AC, 50 Hz, including connecting both incoming and outgoing cable termination with proper taping, lagging testing and commissioning complete all as specified and directed.
S&F in repair sheet metal enclosure for DBs, SPN double door (IP43), 12 ways with 200 amps rated bus bar suitable for 240 volts, AC, 50 Hz, including connecting both incoming and outgoing cable termination with proper taping, lagging testing and commissioning complete all as specified and directed.
S&F in repair MCB TPN 40-63 amps 415 volts 10 KA 'C' series, complete all as specified and directed. Make:-Havells cat part No- DHMGCTNF040 - DHMGCTNF063 or Equivalent cat part of make as specified in P.S.
S&F in repair MCB SPN 40-63 amps 415 volts 10 KA 'C' series, complete all as specified and directed. Make:-Havells cat part No- DHMGCSNF040 - DHMGCSNF063 or Equivalent cat part of make as specified in P.S.
S&F in repair MCB single pole 6 to 32 amps 240 volts 10 KA 'C' series complete all as specified and directed. Make:-Havells cat part No-DHMGCSPF006-032 or Equivalent cat part of make as specified in P.S.
Taking out old unsv exhaust fan from site and Supply and fix exhaust fan, steel body AC single Phase. 230V of size 300mm sweep, 1200 RPM with, blades, and frame and louvers complete all as specified and directed by Engineer-in-charge.
Taking out old unsv exhaust fan from site and replacement of exhaust fan made up of sturdy engineering plastic complete with louvers shutter, voltage 230 V, 50 Hz, 1200 RPM, copper winding of sweep 300mm incl all connecting accessories complete all as specified and directed by Engineer-in-charge.
S&F in repair PVC conduit non metallic rigid of size 25 mm dia (external) incl all accessories for fixing of conduit on wall and ceiling etc complete all as specified and directed.
S&F in repair PVC casing caping of size 25 mm incl all fixing accessories complete all as specified and directed.
S&F Earthing complete with galvanized steel earth plate electrode 60cmx 60cmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to galvanized iron wire 4.0mm dia by means of bolts, nuts and washers of galvanized iron or steel, protected by GI light grade pipe 15mm bore including GI light grade water pipe 20mm dia with funnel all as shown in electric plate No. 3 of 2009 SSR Pt-I and testing complete including earth work in any type of soil, PCC 1:2:4 type B-1 as in earthing pit and cover 50mm thick reinforced with 6mm dia MS round bar @ 10cm C/C both way and MS frame, common salt, charcoal and testing on completion including dismantling unsv earthing, complete all as specified and directed.
S&F in repair Sub main wiring with single core cable 2x 4 Sqmm FRLS insulated unsheathed stranded copper conductor cable 1100 Volts grade including surface PVC casing caping medium grade alongwith 1x 4 Sqmm FRLS insulated unsheathed copper conductor cable as earth wire connected with main earth dolly, complete all as specified and directed. Note:-Three wire of 4 sqmm and one run of PVC conduit/casing caping shall be measured as one unit.
S&F in repair Sub main wiring with single core cable 2x 6 Sqmm FRLS insulated unsheathed stranded copper conductor cable 1100 Volts grade including surface PVC casing caping medium grade alongwith 1x 6 Sqmm FRLS insulated unsheathed copper conductor cable as earth wire connected with main earth dolly, complete all as specified and directed. Note:-Three wire of 6 Sqmm and one run of pvc conduit/casing caping shall be measured as one unit.
S&F 1100 volts grade heavy duty cable PVC insulated solid aluminium conductor served with PVC tape and over all PVC sheathed in service connections suspended by insulating hangers not more than 1 m apart including 4mm dia GI suspension wire, one twin core cable flat or circular of size 6 Sqmm 2 core & including taking down old old unsv service cable connection, complete all as specified and directed.
S&F 1100 volts grade heavy duty cable PVC insulated solid aluminium conductor served with PVC tape and over all PVC sheathed in service connections suspended by insulating hangers not more than 1 m apart including 4mm dia GI suspension wire, one twin core cable flat of circular of size 10 Sqmm 2 core including taking down existing old service connection, complete all as specified and directed.
Repair and maintenance of unserviceable ceiling fan of 1200mm/1400mm sweep at contractor's work shop, incl dismantling complete the ceiling fan parts, inspecting serviceability of all the parts, refixing of serviceable parts after cleaning and replacement of unserviceable parts with company's genuine parts i.e. capacitor, bearing, bushes, shaft, bracket, rubber bush, connecting wire, PVC connector, aluminium clamp for rod, bracket, bush rod, greasing/oiling etc assembling, cleaning and testing of ceiling fan complete all as specified and directed. Note: (i) Unserviceable parts as above shall be measured and paid separately under relevant items of Sch 'A' item No 78 to 83 as supply only. (ii) Rewinding of stator will be measured & paid for separately under relevant item of Sch 'A'. (iii) Cost of minor part i.e. Cotter pin, screws shall be deemed to included in the cost of quoted rate.
Supply only bearing good quality for ceiling fan 1200mm/1400mm sweep ISI marked complete all as specified and directed.
Supply only Gun metal bush for ceiling fan 1200mm/1400mm sweep complete all as specified and directed.
Supply only capacitor 2.5 mfd ISI marked complete all as specified and directed.
Supply only brass bracket assy for hanging the ceiling fan 1200mm/1400mm sweep complete all as specified and directed.
Supply only 3 core flexible wire 40/.0076, white colour from ceiling rose to fan connector complete all as specified and directed.
Supply only stator shaft for ceiling fan complete all as specified and directed.
Supply and fixing in repair ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200/1400 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) complete all as specified and directed.
M&L for removing of old burnt winding of any size , type and rewinding of stator winding with superior quality copper wire with insulation complete all as specified and directed.
M&L for painting to ceiling fans completely in situ with one coat of synthetic enamel paint by spraying incl filling cavities with filler after preparation of painted surfaces, complete all as specified and directed.
M&L for replacement of down rod of ceiling fan 15 mm bore medium grade GI pipe 0.45 metre long with clamps, bolts, nuts, split pins washers of suitable size of approved quality, complete all as specified and directed.
M&L for replacement of down rod of ceiling fan 15 mm bore medium grade GI pipe 0.60 metre long with clamps, bolts, nuts, split pins washers of suitable size of approved quality, complete all as specified and directed.
Repair and maintenance of unserviceable exhaust fan of any cap and sweep by dismantling the exhaust fan parts, inspecting the serviceability of parts, refixing of serviceable parts after cleaning, replacement of unerviceable parts i.e. beaing, bush, capacitor, connecting wires, fan blade, locknut, rubber pad etc, oiling/greasing, cleaning and testing of exhaust fan complete all as specified and directed. Note: (i) Unserviceable parts replaced shall be measured and paid separately under relevant items of Sch 'A' item No 90 & 91 as supply only. (ii) Rewinding of stator winding shall be measured & paid for separately under relevant item of Sch 'A'. (iii) Cost of minor part i.e. screws shall be deemed to included in the cost of quoted rate.
Supply only double ball bearing (ISI marked) for exhaust fan of 200 mm sweep to 450 mm sweep fan complete all as specified and directed.
Supply only gun metal bush for Exhaust fan of any capacity. complete all as specified and directed.
M&L for rewinding of 450mm sweep exhaust fan motor with superior quality copper winding wire with insulation complete all as specified and directed.
M&L for rewinding of 300mm sweep exhaust fan motor with superior quality copper winding wire with insulation complete all as specified and directed.
Supply only blade of exhuast fan of 200 mm sweep to 450 mm sweep as per existing make complete all as specified and directed.
M&L for painting to exhaust fans completely in situ with one coat of synthetic enamel paint by spraying incl filling cavities with filler after preparation of painted surfaces, complete all as specified and directed.
VIKAS ENTERPRISES
KRISHNA ENGINEERING ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .