| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.6 LAccepted-AOC 29 MODEL TOWN BEHIND GURUDWARA PATHANKOT | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L1 | Accepted-AOC Lowest | |
| 2 | L2₹30.2 L+₹2.6 L (9.27%)Rejected-Finance KRISHNA SOCIETY OPP TODI XRAY AND DIAG CENTRE MAKUM ROAD TINSUKIA ASSAM 786125 | TINSUKIA | ASSAM | 786125 | L2 | Rejected-Finance Being other than L1 | |
| 3 | L3₹31.2 L+₹3.6 L (13.0%)Rejected-Finance | L3 | Rejected-Finance Being other than L1 | |
| 4 | L4₹31.8 L+₹4.2 L (15.4%)Rejected-Finance | L4 | Rejected-Finance Being other than L1 | |
| 5 | L5₹32.0 L+₹4.4 L (15.8%)Rejected-Finance | L5 | Rejected-Finance Being other than L1 |
Tender Value
₹44 L
EMD Value
₹88,000
Closing Date
20 Aug 2022, 6:00 pmClosed
GE NAMS
GE NAMS AMRITSAR
REPAIR/MAINT AND DAY TO DAY COMPLAINTS OF STREET LIGHTS AND ALLIED WORKS AT INF BDE AREA AT NAMS
2022_MES_540307_1
GE NAMS-32/2022-23
Open Tender
Civil Works
Item Rate
270 days
GE NAMS AMRITSAR
CLASS D CATEGORY b(i)
7 documents required · 7 mandatory
₹500
GE NAMS
₹88,000
Yes
1 Sept 2022
23 Jul 2022
23 Aug 2022
23 Jul 2022
20 Aug 2022
6 Aug 2022
Amount
Repair of existing street light of any type or description, fixed in vertical position with poles/wall including disconnecting the electric connection, removing from pole/wall if required, carrying out minor repairs like disconection of wire/cable,cleaning of carbon on OH line and replacing starter, fuses, drivers,lens plate,choke, bulb,etc as required at site to make the items functional and refixing the same at same location or any other location, connecting with electric feeder and testing for functioning engaging sufficient man power and tool and plant etc to ensure safety of light/pole as well as working persons complete all as specified and directed. Note : (i) The un-serviceable items shall be replaced under respective items of relevent schedule as below. (ii) The complaint register, complaint slip in duplicate shall also be arranged by the contractor without any extra cost for recording/monitoring of electric supply /street light complaints .
(iii) T&P viz tools , ladder any type are provided by the contractor to the electrician party. (iv) Complaint slip will be delivered to the representative of contractor at 9.00 A.M by JE E/M or his rep at AGE E/M yard service centre and same will be handed over back to JE E/M or his rep after completing the job /complaint upto 5.00 PM same day. (v) Store required for compliant will be deposit in office by the contractor in advance. No direct store will be issued by contractor to the electrician for complaint. Sotre issued by contractor without knowledge of JE or Engr-in-Charge will not be paid to the contractor. (vi) Complaint petaining to same locations/ pole and rectification of fault one point considersd as one job and rectifications of two points at same location will also be measured and paid as one job Similarly more than two will be measured additional job. (vii) If the complaint has not been atteneded within 48 hours, the penality of Rs 150/- per complaint will be recovered from contractor. (viii) In case if the contractor/his rep does not attend the office to recieve complaint from JE E/M or his rep,penality of Rs 500/- per day will be recovered from contractor.
Supply and fixing LED street light 60 W 230 volts with surge protectin not less than 4 KV inbuilt driver & minimum 10 KV separate in the light housing. powder coated pressure die cast aluminium housing, IP-66 protection, high power LED street light with the heat resistant toughened glass lens and making electrical connections with and incl PVC insulated, sheathed 3 core, 1.5 sqmm copper conductor from street light to junction box complete all as specified and directed. Notes : (i) Driver shall be potted antivibration type. (ii) LM-79 and LM-80 for 50000 burning hours. CRI(Colour Rendering Index) of fixture shall be > 70. (iii) CCT (Colour correlated Temp) of fixture shall be 5700K+ 300K. (iv) System Lumen Efficiency shall be >100Lm/W (v) 10 KV separate Surge protection shall be provided as a part of fitting. (vi) PCB used shall be MC PCB type. (vii) The fitting shall have arrangement so that maintenance required, if any can be carried out from Top cover. CAT PART :- WIPRO: LR02-671-XXX-57-G3 ORIENT : LSFT-060-CT HAVELLS : ENDURAOMNIPLUSSL60WLED757SASYTOPC
Supply and fixing LED street light 70/72 W 230 volts with surge protectin not less than 4 KV inbuilt driver & minimum 10 KV separate in the light housing. powder coated pressure die cast aluminium housing, IP-66 protection, high power LED street light with the heat resistant toughened glass lens and making electrical connections with and incl PVC insulated, sheathed 3 core, 1.5 sqmm copper conductor from street light to junction box complete all as specified and directed. Notes : (i) Driver shall be potted antivibration type. (ii) LM-79 and LM-80 for 50000 burning hours. CRI(Colour Rendering Index) of fixture shall be > 70. (iii) CCT (Colour correlated Temp) of fixture shall be 5700K+ 300K. (iv) System Lumen Efficiency shall be >100Lm/W (v) 10 KV separate Surge protection shall be provided as a part of fitting. (vi) PCB used shall be MC PCB type. (vii) The fitting shall have arrangement so that maintenance required, if any can be carried out from Top cover. CAT PART :- WIPRO: LR02-781-XXX-57-G3 ORIENT : LSFS-072-CT HAVELLS : ENDURAOMNIPLUSSL70WLED757SASYTOPC
Supply and fixing LED street light 90 W 230 volts with surge protectin not less than 4 KV inbuilt driver & minimum 10 KV separate in the light housing. powder coated pressure die cast aluminium housing, IP-66 protection, high power LED street light with the heat resistant toughened glass lens and making electrical connections with and incl PVC insulated, sheathed 3 core, 1.5 sqmm copper conductor from street light to junction box complete all as specified and directed. Notes : (i) Driver shall be potted antivibration type. (ii) LM-79 and LM-80 for 50000 burning hours. CRI(Colour Rendering Index) of fixture shall be > 70. (iii) CCT (Colour correlated Temp) of fixture shall be 5700K+ 300K. (iv) System Lumen Efficiency shall be >100Lm/W (v) 10 KV separate Surge protection shall be provided as a part of fitting. (vi) PCB used shall be MC PCB type. (vii) The fitting shall have arrangement so that maintenance required, if any can be carried out from Top cover. CAT PART :- WIPRO: LR02-102-XXX-57-G2 ORIENT : LSFS-090-CT HAVELLS : ENDURAOMNIPLUSSL90WLED757SASYTOPC
Supply and laying, in replacement, of LT underground cable XLPE insulated, inner PVC sheathed, galvanized steel strip armoured, PVC sheathed electric power cable with stranded compact aluminium conductor 1100 volts grade 25 Sq mm 4 core confirming to IS:7098 (Part-I) with latest amendements, suitable for earthed system laid in duct/trench/along pole etc . Note : 1. The cost of Aluminium thimbles/ lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it. 2. Excavation, earth work, DWC protection pipe will be measured and paid separately under respective items.
Ditto As per Ser Item No 5 but 16 Sqmm, 4 core
Ditto As per Ser Item No 5 but 10 Sqmm, 4 core
Excavation in trenches in any type of soil by not exceeding 1.5 mtr wide and not exceeding 1.5 mtr depth below ground level for foundation of poles/ stays/cable and getting out complete all as specified .
Returning, filling in, any type of soil and spreading in layers not exceeding 25cm thick each layer including watering & well ramming complete all as specified.
Removal of surplus soil to a distance not exceeding 50 mtr & depositing where directed at a level not exceeding 1.5mtr above the starting point complete all as specified .
Labour for drilling hole under the road with the help of drilling machine without damaging the road horizontally for rod crossing including laying GI tubing of any size for cable protection complete all as specified and directed.
Supply,laying & fixing double wall corrugated (DWC) pipes made of high density polyethyelene (HDPE) with all accessories i.e. all type of joints, Sockets, Elbows,bends and End caps etc.. all as specified and directed by Engr in Charge.of size75 mm outer dia and 61 mm inner dia of Make;-Telerex/Tirupati or Engr-in-Charge approved Make
Supply and fixing in replacement PVC insulated, multistranded copper conductor wire cross section 4 Sqmm size, single core all as specified and directed.
Supply and fixing in replacement FR grade thermoplastic polycarbonate outdoor cable junction box hinged/screwed door type of size 200x160x 98 mm for 3 Phase and neutral incoming cable, 3 Phase and neutral outgoing cable with terminals/connectors and single Phase & neutral connection for light fitting, 4 pole, 415 volt and one MCB SP 6 Amp, 240 Volt and clamp system (screw less), shock proof safe IP-66, weather proof, rust, dust and water proof internally embedded gasket with provision metric knockouts for cable entry through gland suitable for 16sq mm to 25sq mm cable as required at site complete all as specified & directed. Make : Legrand/Hensel/Hager
Material & labour for painting of steel / PCC poles with two coats of synthetic enamel paint in black and white strip 30 cm wide each up to 1.5 mtr height from coping over a coat of primer including numbering of poles complete all as specified and directed.
Supply and fixing in replacement micro prismatic reflective sheet, minimum 50 mm wide, with adhesive base for dirtectly fixing on HT/LT steel tubular/PCC pole without nail or any other fixing material at suitable height, in Red/White/Yellow colour complete all as directed.
Supply and fixing in replacement 1100 volts grade heavy duty cable PVC insulated aluminium conductor , served with inner sheating of PVC tape and overall PVC sheated in service connection suspended twin core cable flat or circular size 4 Sqmm all as specified and directed.
Ditto As per Ser Item No 17 but 6 Sqmm, 2 core
Supply and fixing / laying in replacement galvanized iron pipe of 40 mm nominal dia light grade fixed to poles with clamps nuts, bolts and washers or laid under road crossing or fixed to wall including painting with two coats of aluminium paint over a coat of red oxide paint complete all as specified and directed.
M&L fabricating and fixing in replacement of cross arms (any type) supports, bracketing, stiffness etc made out of MS channel, angle iron, flat iron of any size including drilling of holes, making clamps, eye hooks, nuts, bolts and washers etc, welding if required including painting with two coats of aluminium paint over a coat of red oxide paint complete all as specified and directed.
M&L for earthing complete with galvanised steel earth plate electrode of size 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below ground level, connected to galvanized earth lead wire 4.00 mm dia by means of bolts nuts check nuts & washers of galvanized iron or steel , procteded by GI pipe 15 mm bore( light grade) and watering pipe 20 mm bore GI pipe (light grade ) and chamber of pcc 1:4:8 type D2 using 40 mm graded stone aggregate and coping shall be in PCC 1:3:6 type C1 using 20mm graded stone agg. 50 mm thick cover of RCC 1:2:4 type B1 using 20 mm graded stone agg. reinforced with 8 mm dia MS tor bar @ 80 mm c/c both ways including excavation and earth work and removal of surplus soil and connecting to earth up to 6 meter length complete all as shown in electrical plate no 5 of SSR PART 1 , with charcoal dust and salt complete and earth lead connected to earthing test point (up to main switch, DBs) complete all as specified & testing on completion.
Supply and fix in replacement for automatic street light switch of 63 amp 3 pole 230 volts using photoelectric switch for automatic switching of street light based on LUX level of natural light . the infrared sensor based nature switch alongwith suitable power contactors and MCBs (incoming -outgoing) should be enclosed in pole/wall mountable enclosure made of rust proof , electric shock proof ,termite proof and FR grade thermoplastic polycarbonate enclosure conforming to IP-66 protection class 2. The contactor , MCB and copper circuit wiring (min 10 sqmm) should suitable enough to take single phase load of 8-10 kw with suitable contactor and MCBs complete as specified and as directed.
Supply and fix in replacement for automatic street light switch of 40 amp 3 pole 230 volts using photoelectric switch for automatic switching of street light based on LUX level of natural light . the infrared sensor based nature switch alongwith suitable power contactors and MCBs (incoming -outgoing) should be enclosed in pole/wall mountable enclosure made of rust proof , electric shock proof ,termite proof and FR grade thermoplastic polycarbonate enclosure conforming to IP-66 protection class 2. The contactor , MCB and copper circuit wiring (min 10 sqmm) should suitable enough to take single phase load of 5-8 KW with suitable contactor and MCBs complete as specified and as directed.
Supply and fixing inreplacement street light mounting bracket made out of GI pipe 40 mm dia light Grade not less than with 1.5 (90cmx60cm) mtr long in any shape including clamps, nuts, bolts, washers etc and painting with aluminium paint,all as specified and directed by Engr in Charge
Supply and fixing in replacement of fwg accessories in timer panels:-
MCB 40 Amps , 4 pole , 415 volts, 10 KA all as specified and directed.
Power contractor 3 pole, 415 volts, 40 Amps , C1 Series of current rated 40 Amps all as specified and directed.
Digital time switch programmable every 1 minutes with back up of 6 years, 28 memory locations , current capacity 16 A weekly program, with 1 changover (1 CO), total 28 programme.
Relay 32/40 amps 3 Pole 415V all as specified and directed.
Contactor coil of 32 amps / 40 amps, 415 Volts all as specified and directed.
Supply only in replacement of LED type street light Drivers of Operating Voltage 140-270 Volts, PF (0.95)LED driver current > 700 mA, suitable for existing size and make to functional the fitting LED complete all as specified and directed the following capacities. (i) LED Street light driver suitable for 120 Watt of make as per exists.
All as per item above but LED Street light driver suitable for 90 Watt of make as per exists.
All as per item above but LED Street light driver suitable for 60 Watt of make as per exists.
All as per item above but LED Street light driver suitable for 45 Watt of make as per exists.
All as per item above but LED Street light driver suitable for 25/35 Watt of make as per exists.
S & F in replacement of MCCB Capacity 25 KA 3 pole 100 Amps with preader and aluminium lugs all as specified and directed.
S & F in replacement of MCCB Capacity 25 KA 3 pole 125 Amps with preader and aluminium lugs all as specified and directed.
Supply & fixing in replacement shackle/Pin type porcelain vitreous white, brown or green insulator including one galvanised mild steel straps, washers and nut 75 mm height, 90 mm dia for 1100 volts grade, including removal of existing insulators complete all as specified and directed.
Supply & Fix in replacement flood Light Luminaire 200 watt with .high power LED cool white, supply voltage 220/240/50 Hz, light engine driver base, pole adapter, pressure die cast polycarbonate, powder coated in IP 66 life of 50000 hrs.Including protection of O/C, S/C, O/V, over temperature and lightning protection inbuilt complete all as specified and directed. CAT PART :- Wipro: LH20-272-060-57-XX ORIENT : LFSMP-200-CT-HL Havells : JETAADORNFLS200WLED757SSYMTOTG
Supply & Fix in replacement flood Light Luminaire 150 watt with .high power LED cool white, supply voltage 220/240/50 Hz, light engine driver base.pole adapter, pressure die cast polycarbonate, powder coated in IP 66 life of 50000 hrs.Incliding protection of O/C, S/C, O/V, over temperature and lightning protection inbuilt complete all as specified and directed. CAT PART :- Wipro: LF20-192-060-57-G2 ORIENT : LFSMP-150-CT-HL Havells : JETAADORNFLS150WLED757SSYMTOTG
Supply & Fix in replacement integral post top lanterns complete with black ABC plastic spigot,spun aluminium funnel shape with clear cover light opening on canopy with baffles and accessories with 10watt LED lamp complete all as specied and directed.
Material and labour for replaclement of bamboo ladder 28 feet long , suitable for swan neck pole 10 mtr long complete all as specified and as directed.
Supply and fixing in replacement PVC insulated, PVC sheathed, multistranded copper conductor wire 1.5 Sqmm size, twin core all as specified and directed.
Supply and fixing in replacement PVC insulated, PVC sheathed, multistranded copper conductor wire 2.5 Sqmm size, twin core all as specified and directed.
M&L for PVC conduit not less than 20 mm dia suitable for security light including 2 Nos of clamps fixed with nut and bolts complete all as specified and as directed.
Supply and fix in replacement of PVC enclosures DB's 2 way 240V complete with steel clamps suitable for fixing on LT Pole all as specified and directed.
Supply and fix in replacement of MCB Isolator 32 amp- 63 Amp complete all as specified and as directed.
Material & labour for painting to steel pole including mild steel supports, clamps etc fixed on LT Poles any height with providing two coats of aluminium paint over a coat one coat of red oxide primer in and including writing pole number with black paint complete all as specified and directed. Note:- Steel members fixed on single LT pole shall be considered as 'One Unit'.
Material and labour for ACSR conductor any size drawn stright horizontal on LT over head lines on existing poles including binding with insulators weight of conductor shall be measured straight horizontal distance between centre of two adjacent LT poles and calculating weight of conductor of size length by adding 3% extra for sag, jointing , jumpers etc complete all as specified and as directed.
supply and fixing of straight through heat sinkable joint suitable 10 sqmm to 50 sqmm LT 3.5 core 1100 volts XLPE all as specified and as directed.
Taking out existing U/S faulty LT cable of any size , detecting the fault and relaying after repair complete all as specified and as directed by E-in-C. Note : 1. The cost of Aluminium thimbles/lugs and cable gland etc is incl in quoted rate and no extra payment will be made for it. 2. Excavation, earth work, DWC protection pipe will be measured and paid separately under respective items.
Repair/maint of high mast pole,checking of control panel, motor stater, control wiring, gear box, switches for Up / down travel light frame,rope and gear box etc including oiling, greasing, welding of shaft etc complete if required complete all as specified and directed by Engr-In-Charge.
Supply and fix in replacement of steel wire rope 6 mm dia
Taking out electric motor 1.0 HP 3 Phase 415 V dismantling , taking out burnt winding wire and rewinding with new supper enameld copper wire baking, varnishing etc and reassembling testing complete all as specified and directed
Supply and fix in replacement of bearing suitable for 1.0 HP 3 Phase 415 V motor
Supply and fix in replacement of irreversible DOL motor starter 3 Phase 415V relay range 2.0 to 3.0 Amp suitable for 1.0 to 1.5 HP motor E-in-C Approved make.
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .