Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.5 LAccepted-AOC R C PANDIT LANE NAMOPARA PURULIA | PURULIA | PURULIA | WEST BENGAL | 723101 | L1 | Accepted-AOC L1 BIDDER | |
| 2 | L2₹23.8 L+₹34,139.11 (1.45%)Rejected-Finance KALYANESWARI PASCHIM BARDHAMAN WEST BENGAL | KALYANESWARI | PASCHIM BARDHAMAN | WEST BENGAL | L2 | Rejected-Finance NOT L1 BIDDER | |
| 3 | L3₹24.8 L+₹1.4 L (5.82%)Rejected-Finance RAJBARI PARA JALPAIGURI | JALPAIGURI | JALPAIGURI | WEST BENGAL | L3 | Rejected-Finance NOT L1 BIDDER |
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
23 Oct 2024, 4:00 pmClosed
Executive Engineer,Asansol Mechanica Division
Office of the Executive Engineer,Asansol Mechanical Division,Public Health Engineering Directorate,SEN-RALEIGH ROAD,PASCHIM BARDHAMAN 713 305
Providing and fitting, fixing of lighting luminaries, electrical wiring of pump house and Substation Buliding with Yard lighting arrangement and other allied works at Ethora Boosting Station under improvement of RCFA Part-I Water Supply Scheme.
2024_PHED_750347_1
WBPHED/EE/AMD/NIeT-26 of 2024-2025
Open Tender
Miscellaneous Works
Item Wise
30 days
ETHORA
Please refer Tender documents.
3 documents required · 3 mandatory
₹50,000
28 Feb 2025
13 Sept 2024
25 Oct 2024
13 Sept 2024
23 Oct 2024
13 Sept 2024
Amount
Supply and Delivery of Following Materials at site:-
90 Watt. LED Highly efficient IP66 LED street-light with aluminium pressure die-cast housing, toughened glass in the front and peanut lens for batwing light distribution,higher spacing between poles and maintenance-free system.(Make-Approved Make)(For Pump House-10 Nos+ For Sub-Station-12 Nos+ Yard Lighting-10 Nos).
4 ft. long 22 Watt LED Tubelight Slim LED batten with aluminium housing and polycarbonate diffuser is an ideal replacement solution for existing battens/fluorescent lamps with elegantly designed end caps.(Make-Approved Make)(20 Nos For Pump House+2 Nos for Chlorine Room+3 Nos for Guard Room Room+42 Nos For Sub-Station).
4 Core X 10 Sqmm, 1.1 KV Grade XLPE insulated Al.Ar Cable.( From LT PDB Cum MCC Panel to Pole)(Make:-Approved Make)
450 mm Sweep exhaust fan 220V-240 V,50 Hz, Single phase.(Make:-Approved Make)(For Pump House-8 Nos+ Sub-station-8 Nos)
3 CoreX 1.5 Sqmm industrial flexible copper cable wire/dia-30/0.25 PVC insulated with PVC sheathed.(Make:Approved Make).
4 Core X 4 Sqmm, 1.1 KV Grade XLPE insulated Al.Ar Cable.(From DBs to Street light outside of the Pump House+ Sub-Station)(Make:-Approved Make).
100 Watt High efficiency round LED high-bay luminarie with aluminium die cast housing with high lumen efficiency of>130 lm/Watt, a perfect energy-saving solution with IP65 Protection.(Make-Approved Make).
30 Watt. LED Highly efficient IP66 LED street-light with aluminium pressure die-cast housing, toughened glass in the front and peanut lens for batwing light distribution,higher spacing between poles and maintenance-free system.(Make-Approved Make)
4 Core X 16 Sqmm, 1.1 KV Grade XLPE insulated Al.Ar Cable.(From LT MCC Panel feeder to Chlorine Room+Guard Room)(Make:-Approved Make)
9.0 Mtr. Long swaged and welded steel tubular pole as per IS-2713-1980 with CI Base Plate & CI Cap.(Make:-Approved Make) a) Single arm bracket made of 40mm Dia 1.5 Mtr. Long.
Double arm bracket made of 40mm Dia 1.5 Mtr. Long.
3 Blade 1200 mm Sweep ceiling fan, 220V-240V,50 Hz,AC.(Make:-Approved Make)
50 Watt. LED Highly efficient IP66 LED street-light with aluminium pressure die-cast housing, toughened glass in the front and peanut lens for batwing light distribution,higher spacing between poles and maintenance-free system.(Make-Approved Make)(For Sub-station Lighting)
4 Core X 16 Sqmm, 1.1 KV Grade XLPE insulated Al.Ar Cable.( From LT PDB Cum MCC Panel to DB's)(Make:-Approved Make)
4 CoreX 4 Sqmm industrial flexible copper cable PVC insulated with PVC sheathed.(Make:Approved Make)(From Sub-Station DB's to Every Room)
Supplying and fixing double door 12 Way Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment.(40 Amp FP/TPN MCB as a Incomer+12 Nos 10 Amp SP MCB as a Outgoing)(For DB's at Pump House+ Sub-Station)
Supply of 25 mm dia GI Conduit 1.6mm thick.(Approved make)
Supply of GI Bend/Elbow.
Supply of GI saddle etc …
Two way Circular Box & cover.
One way Circular Box & cover.
3 way Ceiling Rose/Batten Holder.
Labour for fitting and fixing 25 mm dia 1.6mm thick G.I. Conduit above ground (exposed) in the wall with previously supplied saddle clamps including cost of jointing materials,holder bat clamps etc.,as necessary, including cutting pipe, making threads etc. complete in all respect with two coats of painting with approved paint any height.
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required.
3 X 22/0.3(1.5 Sqmm).(For LED Tube lighting Fixtures)
3 X 36/0.3(2.5 Sqmm).(For Exhaust Fans-8 Nos for Pump House+ For Sub-Station Building-8 Nos+4 Nos Highbay for Pump House+ 6 Nos Highbay for Sub-Station)
3 X 56/0.3(4 Sqmm).(For industrial Plug Sockets+ Sub-Station Room)
Supplying & Fixing GI Modular Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works.
12 Module.(For Pump House-3 Nos+For Sub-Station-5)
8 Module.(For Sub-Station-1 No)(WBSEDCL Room)
6 Module.(For Pump House + Office Room)
Supply & Fixing 240 V 6 A Modular type switch (Brand approved by EIC) on existing GI Modular type switch board having top cover plate and making necessary connections as required.(35 Nos For Pump House+59 For Sub-Station)
Supply & fixing modular indicator.(Brand approved by EIC)
Supply & Fixing 240 V, 6A, 5 pin Modular type plug socket (Brand approved by EIC), without switch & plug top, on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supplying & Fixing Industrial Plug & Socket board with 240 V, 20A, SPN & Earth Metal Industrial Plug socket & 20A Industrial top incl. S&F 20 A SP MCB breaking capcity 10kA (C- Curve) in SS enclosure fixed on wall and cecessary conection.
Supply & Fixing Socket type fan regulator (Step type) (Brand approved by EIC) on existing sheet metal switch board with bakelite/ perspex top cover by screw incl. making necy. connections etc.
Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed.(From LT PDB To Pole to Pole)
Fixing outdoor type fluorescent/SV/MV light fitting on pole including S&F 40 mm dia x 1.68 mts. long GI Pipe (ISI-Medium) bracket with 40 mmx10 mm thick, MS clamp etc. and providing wiring with 2x1/1.40 PVC insulated and sheathed wire (single core) from loop box at the base of pole to light fiting through pole & bracket (without control switch) including making connections & painting.(For 10 Nos Street Light for Pump House+1 No for Chlorine Room+1 Guard Room+12 Nos for Sub-Station Building)
Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter:45 cm (18").
Supply & Fixing GI sheet (20SWG) metal Cowl with MS flat iron frame & GI wire mesh on wall with necy. bolts & nuts (6 mm dia x 62 mm long).(8 Nos for Pump House+ 8 Nos for Sub-Station Building)
Fixing only single/twin fluorescent light fitting complete with all accessories directly on wall/ceiling by screws etc.
Fixing only Floodlight/High Bay Fitting with suitable tie clamps and MS plate for mounting top of the Ceiling or similar structure.(For Pump House-4 Nos+ Sub-Station Building-6 Nos)
Erection of Single Steel tubular pole of length as given below with/without sole plate & Cap etc. in CC foundation (Proportion and dimension indicated below), having 600x600x150 mm thick CC (4:2:1) base block below sole plate/pole with hard jhama metal including CC (6:3:1) muffing 0.30 mts. dia and 0.30 mts. above ground level including 3 mm thick neat cemented finish and GI earth bolt after making drilled holes etc. on pole & carriage of pole upto 1.6 Km from Store to work-site including filling up the excavated earth pit with shifted soil and ramming properly.
Upto 9.0 mtr. Size 0.6x0.6x1.70 mts.
Supplying and Fixing GI water proof looping cable box having hinged GI Top Cover having 4 mm thick with rubber gasket lining, railway type mechanical locking arrangement, earthing terminal with lug etc. of the following sizes as indicated below,Comprising of one 250 V,15 A Kit-Kat fuse unit, one NL on,porcelain insulator etc. and housing the same in pole muffing incl. addition and alteration to the existing CC muffing (6:3:1)after dismantling the damaged looping cable box etc. where necy. incl. painting.
200 x 150 x 100mm.(For Pump House -10 Nos + 1 No for Chlorine Room+1 No Guard Room+ Pole Light-6 Nos+ Sub-Station-12 Nos)
Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required.(For Flowmeter & Level Indicator)
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required.
2 X 22/0.3(1.5 Sqmm)+1 X 22/0.3(1.5 Sqmm)ECC.(For Chlorine Room)
Fitting & fixing of the outdoor lighting luminaries along with new accessories to the pole, Gate and O.H.R. Wall etc as per direction of EIC.(For Pole Light)
Connecting the pole to earth busbar including S & F GI (Hot Dip) wire of size as below,spiral on pole body as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages.
No. 12 SWG.
Earthing with GI earth spike(1822mmX20 mm) and grouted the same under the ground level as per direction.
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials.
4 Core X 10 Sqmm.
Laying of cable upto 3/4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting.(From LT Panel to DB's)
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire.
Supply and Delivery Electrode, Digital functionality with Inductive Data Transmission from Sensor to Transmitter Diaphragm: PTFE, Signal transmission: Digital. Reference system: Gel, Conductivity: min 50uS/cm Temperature sensor integrated. Transmitter liquid analysis for Chlorine Digital sensors; Memosens protocol, In built Digital Display. Input: 1x Memosens Sensor, Supply: 230VAC/24V DC Plug & Play for sensors modules, SD-slot data logger, alarm relay, Protection: IP66 Input: 1x Digital Sensor, Output: 1x 4-20mA, Supply: 24V DC, Flow Fit Assembly along with Standing Sample Handling Panel.(Make-Approved Make)
Supply of 2 CoreX 1.5 Sqmm industrial flexible copper cable wire/dia-30/0.25 PVC insulated with PVC sheathed. (Make:Approved Make)
Supply, Delivery and storage at site of Uninterruptible Power Supply (UPS) as per IS 16242 (part-1) with overload protection, micro controller based, boost & buck AVR having following specification:- Capacity- 600VA / 360W, Input- 230V AC, Single phaseFrequency- 50/60Hz; Out put- 230V+/- 10% (AC mode) (Make-Approved Make) (BX600C-IN) (For Flow meters & Level Meter)
6 mm Nominal Dia, SCH-40S, Stainless Steel Pipes.(Make-Approved Make)
Installation & Testing commissioning of above fluid analyzer unit at Rising Main by using necessary elctro-mchanical accessories & other requisite materials and mending good damages. This including the cost for making necy. connections with power, control, sensing wire and earth continuity wire etc including supplying sockets, soldering materials, tapes etc, to sesing the residual chlorine( in Ppm), fitting & fixing of Display board, making proper SS line for sensing and making connection also tapping from rising main, with switch to complete the job satisfactorly including testing all complete.
Add. GST@18%
Add. Cess@1%
SUNRISE ENGINEERING CORPORATION (BID ID -5705410)
MS S G Enterprise (BID ID -5712417)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .