Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.6 LAccepted-AOC MILITARY HOSPITAL ROAD UDHAMPUR 182101 J K | UDHAMPUR | JAMMU AND KASHMIR | 182101 | ₹22.6 L Quoted ₹23.2 L | L1 | Accepted-AOC BEING L1 |
| 2 | L2₹25.5 L+₹2.3 L (10.1%)Rejected-Finance 15A 9 CHOWBHAGA ROAD KOLKATA KOLKATA 700039 | KOLKATA | WEST BENGAL | 700039 | ₹25.5 L+₹2.3 L (10.1%) | L2 | Rejected-Finance BEING L2 |
| 3 | L3₹26.6 L+₹3.4 L (14.8%)Rejected-Finance | ₹26.6 L+₹3.4 L (14.8%) | L3 | Rejected-Finance BEING L3 |
| 4 | L4₹28.0 L+₹4.8 L (20.8%)Rejected-Finance 6 RAILWAY STATION ROAD ONKAR INDUSTRIES GULAMALI PURA BAHRAICH UTTAR PRADESH 271801 | BAHRAICH | UTTAR PRADESH | 271801 | ₹28.0 L+₹4.8 L (20.8%) | L4 | Rejected-Finance BEING L4 |
| 5 | L5₹28.0 L+₹4.8 L (20.9%)Rejected-Finance | ₹28.0 L+₹4.8 L (20.9%) | L5 | Rejected-Finance BEING L5 |
Tender Value
Refer Docs
EMD Value
₹56,600
Closing Date
1 Jun 2023, 6:00 pmClosed
GE (AF) UDHAMPUR
GE (AF) UDHAMPUR
REPAIR / MAINT OF UNSV LT UG CABLES, LT PANELS, BUS BAR CHAMBER, MCCB OVERHEAD ACSR-CONDUCTOR INCLUDING LINE, POLE PAINTING, TIGHTENING ETC ALONGWITH CERTAIN MISC WORKS AT 901 SU AF STATION NATHATOP
2023_MES_593024_1
GE/AFU-12/2023-24
Open Tender
Civil Works
Item Rate
270 days
NATHATOP
AS PER NIT AND TENDER DOCUMENT
9 documents required · 9 mandatory
₹500
GE (AF) UDHAMPUR
₹56,600
Yes
20 Jun 2023
4 May 2023
3 Jun 2023
4 May 2023
1 Jun 2023
18 May 2023
4 May 2023 - 11 May 2023
Amount
Excavation in trenches in any type of soft / hard soil, not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation / laying of pipes and getting out complete all as specified & directed
Returning, filling in any type of soil, including spreading, levelling, watering and well ramming in layers not exceeding 25cm complete all as specified & directed
Removing excavated material (soils) not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified & directed
M & L for Sand cushioning for 8 cm before laying the cable and then after laying the cable 15 cm width of trenches for protection of cables including punning down complete all as specified. Note :- Thickness of sand cushioning shall be the thickness after punning down.
Supply and fixing of Brick tiles; common burnt clay building /ducts bricks’ sub-class `B’ Designation 75 (230mmx115mmx75mm) complete all as specified & directed
Taking out old rusted unserviceable GI tubing of any size and S&F 80 mm dia GI tubing,light grade, with all fiiting for protection of cable passing across the road,under floor etc,complete all as specified and directed by Engr-in-Charge.
Taking out old rusted unserviceable GI tubing of any size and S&F 50 mm dia GI tubing,light grade,with all fiiting for protection of cable passing across the road,under floor etc,complete all as specified and directed by Engr-in-Charge.
Taking out old rusted unserviceable GI tubing of any size and M&L new GI tubing 40 mm bore light grade,with all fiiting as in protection pipe for passing through cable etc fixed on wall/poles or laid in trenches/ducts or across road including necessary clamps required complete all as specified.
Re-Laying Re-Routing existing overground/underground LT Cable of size 10 Sqmm2/4 core to 240 Sqmm 3.5 core cable along with connection with LT Panel/Pole or Other including taking down old complete all as specified and directed by Engr-in-Charge Note : Excavation shall be got done alongwith other items, if cable requied for laying of cable shall be paid respective items for laying existing overground cables.(ii) Quoted rates shall be inclusive of cutting of cable , provision of thimbles,lugs ,stainless steel cable gland for connecting cable IN/OUT from Panels AND feeder Piller Boxes as per Site Requirement. (iii) The Crimping shall be done only by Hard Operated/Hydraulically Operated Crimping Tool after applying conduting jelly and no other method will be allowed. (iv) Extra use of cable shall be measured &Paid sepetrately in case of non availability of EM store.(v) Excavation /Returing & filling ,removing /sand and brick work shall be measured and paid seperately (vi) HDPE Pipe shall be measured and paid seperately (vii) if existing cable is not available, same shall be issued through store as Sch "B".
Supply and Laying Cable XLPE insulated screened PVC bedded galvanized steel strips or wire armoured, cables (heavy duty) ISI marked with stranded aluminium conductor, 1100 volts grade and connecting and testing in trenches, under floors/ roads or on walls complete including taking down old complete all as specified and directed by Engr-in-Charge of following sizes :- Note Item No 10.01 to 10.11 Earth work, excavation shall be measured & paid separately under respective item of Schedule and wherever cable laying on walls and uses of thimbles, Clamps, fastner,nut,bolt and washers etc rates shall deemed to be included in the quoted rates). Make- Havells/Gloster/Polycab/KEI
10 sqmm 4 core complete
16 sqmm 4 core complete
25 sqmm 3.5 core complete
35 Sqmm 3.5 core complete
50 sqmm 3.5 core complete
70 sqmm 3.5 core complete
95 sqmm 3.5 core complete
120 sqmm 3.5 core complete
150 sqmm 3.5 core complete
185 sqmm 3.5 core complete
240 sqmm 3.5 core complete
Disconnecting and taking down old unserviceable MCCB of any description and capacity and Material and labour for MCCB 4 Pole, 415 V,thermal magnatic load, ICS = 100% of ICU, 63 Amps with breaking capacity 16 KA including all accessories all as specified and directed by Engineer-in Charge. make Schneider/Havells/L&T/Standard/Legrand or equivalent as approved by GE.
Disconnecting and taking down old unserviceable MCCB of any description and capacity and Material and labour for MCCB 4 Pole, 415 V, thermal magnatic load, ICS 100% of ICU, 100 Amps with breaking capacity 16 KA including all accessories all as specified and directed by Engineer-in Charge. make SchneiderHavells/L&T/Standard/Legrand or equivalent as approved by GE.
Disconnecting and taking down old unserviceable MCCB of any description and capacity and Material and labour for MCCB 4 Pole, 415 V, adjustable type,thermal magnatic load, ICS 100% of ICU, 0.8 ln to 1 ln, 250 Amps with breaking capacity 35 KA as per IEC60947-2 including all accessories all as specified and directed by Engineer-in Charge. make Schneider ,/Havells/L&T/Standard/Legrand or equivalent as approved by GE.
Disconnecting and taking down old unserviceable MCCB of any description and capacity and Material and labour for MCCB 4 Pole, 415 V, adjustable type,thermal magnatic load, ICS 100% of ICU, 0.8 ln to 1 ln, 400 Amps with breaking capacity 35 KA as per IEC60947-2 including all accessories all as specified and directed by Engineer-in Charge. make Schneider ,/Havells/L&T/Standard/Legrand or equivalent as approved by GE.
Disconnecting and taking down old unserviceable MCCB of any description and capacity and Material and labour for MCCB 4 Pole, 415 V, adjustable type,thermal magnatic load, ICS 100% of ICU, 0.8 ln to 1 ln, 630 Amps with breaking capacity 50 KA as per IEC60947-2 including all accessories all as specified and directed by Engineer-in Charge. make Schneider ,/Havells/L&T/Standard/Legrand or equivalent as approved by GE.
Trimming of tree in vicinity of electric supply pole/street light pole/solar modules & depositing at places n exc 50m all as directed by Engineer-in-Charge.
Disconnecting and dismantling the electrical connection and shifting of Lt Panel boards by disconnecting incoming and outgoing cable including all accessories including nut, bolt, washer and thimble etc complete and refixing of the Lt panel on staging by embedding the panel legs minimum 30 cm in ground/staging and adding a layer of PCC 1:2:4, 100 mm thick and re-connecting base of panel shall be atleast 45 Cm from ground level. All metal work like provn of glands, civil work etc shall be deemed to be included in quoted rates all as specified and directed by Engr-in-Charge.
Disconnecting and taking down old unserviceable bus bar chamber/Lt panel of any description and capacity and Supply and fixing of Wheather proof outdoor, Lt panel ,made out of 3.15 mm thick MS sheet comprising 4 Nos copper bus bar strips each of 400 amps ,45 cm long duly insulated on insulators including incomming MCCB 200 amps 25 kA, Ics = 100% Icu, adjustable thermal & adjustable megnetic settings with spreader links, copper reducer etc 01 Nos and outgoing MCCB 100 amps 16 kA, Ics = 100% Icu, 02 Nos, TP 63 Amp 10 KA, C Curve = 01 Nos, complete with 4 nos mounting legs made out of 50 mmx50mmx6 mm angle iron grouted in PCC block of size 30cmx30cmx90cm (30cm depth below ground level and 60 cm above ground level) in cement concrete 1:3:6 ,type C-2 (using 40 mm grade crushed stone aggregate),and connection with size of aluminium thimbles,nuts,bolts and washers including Set of three LED lights RYB, complete internal wiring with suitable size of copper wire, digital voltmeter, ammeter, CT of ratio 50/5 of 3 nos and cable glands at entry and outlets points including excavation and earth work,returning filling and removal of surplus soils complete all as specifiedand directed by Engineer -in -charge.
M&L Earthing complete as per electrical plate No 5 of MES SSR Part I with galvanised steel plate earth electrode 60 cm x 60 cm x 6.0mm, burried directly vertically in ground in a pit of depth not less than 2.5 metres below ground level with the top edge of earth plate at a depth not less than 1.5 m below normal ground level connected to and including galvanised iron or steel earth strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel. Earthing wire protected by galvanised iron or steel pipe 50mm bore medium grade and connected to continuous earth wire on pole/ test point. Watering pipe shall be 20mm bore GI medium grade. The earthing shall be inclusive of excavation and earth work in any type of soil, charcoal, salt, funnel , PCC pit and RCC cover complete all as specified & directed by Engr-in-Charge. Note 1- following items deemed to be included in quoted rate (a) Earth electrode. (b) Main earthing lead from earth electrode to test point and further to equipment to be earthed upto 7.5 metre. (c) Material and labour for connecting earth electrode and earthing lead as specified. (d) Adequate quantity of charcoal dust and common salt as per direction. (e) All labour involved including testing of earth net work. (f) Excavation and earth work or drilling hole for electrode. (g) P.C.C. pit and C.I. cover. (h) Funnel with watering pipe, wire mesh and copper lugs etc. as specified. (j) G.I. protection pipe of size ordered specified for protection of earthing lead from mechanical injury or tempering. Note 2 - On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost.
M&L Earthing complete as per electrical plate No 5 of MES SSR Part I with copper earth plate earth electrode 60 cm x 60 cm x 3.15 mm, burried directly vertically in ground in a pit of depth not less than 2.5 metres below ground level with the top edge of earth plate at a depth not less than 1.8 m below normal ground level connected to and including cupper earthing strip 20 x 3 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel. Earthing wire protected by galvanised iron or steel pipe 50mm bore medium grade and connected to continuous earth wire on pole/ test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be inclusive of excavation and earth work in any type of soil,charcoal, salt,funnel , PCC pit and RCC cover complete all as specified & directed. Note 1- following items deemed to be included in quoted rate (a) Earth electrode. (b) Main earthing lead from earth electrode to test point and further to equipment to be earthed upto 7.5 metre. (c) Material and labour for connecting earth electrode and earthing lead as specified. (d) Adequate quantity of charcoal dust and common salt as per direction. (e) All labour involved including testing of earth net work. (f) Excavation and earth work or drilling hole for electrode. (g) P.C.C. pit and C.I. cover. (h) Funnel with watering pipe, wire mesh and copper lugs etc. as specified. (j) G.I. protection pipe of size ordered specified for protection of earthing lead from mechanical injury or tempering. Note 2 - On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles with the help of insulator or any other indicated situation for loop earthing etc, and provision of brass/copper nuts, bolts washers etc wherever required and making joints required 20x3 copper strip coplete all as specified and directed by Enginer-in-Charge.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles with the help of insulator or any other indicated situation for loop earthing etc and provision of brass/copper nuts, bolts washers etc wherever required and making joints as required 32 x 6 mm galvanised iron strip complete all as specified and directed by Enginer-in-Charge.
Test point terminal block made of gun metal or phosphorous bronze size 75 x 75 x 25mm drilled and screwed including 3 Nos. 8 mm dia 25 mm long hexagonal head screws complete all as specified and directed including taking down old unserviceable.
Supply and fix heat shrinkable End termination kits and accessories of following capacities and type:- Note for item No 24.01 to 24.04 :- Rate for the execavation, returing filling and removing of the earth work and provide labour and Electrician shall deemed to be included in the quoted price, not extra be paid for this items.
(a) Outdoor/indoor 185 to 240 Sqmm 3.5/4 core cable jointing kit for 1.1 KV grade cable
(b) Outdoor/indoor 120 to 150 Sqmm 3.5/4 core cable jointing kit for 1.1 KV grade cable
(c) Outdoor/indoor 95 Sqmm 3.5/4 core cable jointing kit for 1.1 KV grade cable
(d) Outdoor/indoor 35 to 50 Sqmm 3.5/4 core cable jointing kit for 1.1 KV grade cable
Supply and fix heat shrinkable straight through joint kit and accessories of following capacities and type:-Note for item No 25.01 to 25.04 :- Rate for the execavation, returing filling and removing of the earth work and provide labour and Electrician shall deemed to be included in the quoted price, not extra be paid for this items.
Straight through joint kit aluminium conductor cable of size 185 to 240 Sqmm and 3.5/4 core
Straight through joint kit aluminium conductor cable of size 120 to 150 Sqmm and 3.5/4 core
Straight through joint kit aluminium conductor cable of size 35 to 50 Sqmm and 3.5/4 core
Straight through joint kit aluminium conductor cable of size 95 Sqmm and 3.5/4 core
Supply and fix off LOAD change over switch 415 V in sheet metal enclosures 4 pole of capacity 100 Amps complete all as specified and directed.
Supply and fix off LOAD change over switch 415 V in sheet metal enclosures 4 pole of capacity 400 Amps complete all as specified and directed.
Supply and fix off LOAD change over switch 415 V in sheet metal enclosures 4 pole of capacity 630 Amps complete all as specified and directed.
Supply and fix off LOAD change over switch 415 V in sheet metal enclosures 4 pole of capacity 200 Amps complete all as specified and directed.
M&L for brazing work with copper brazing alloy rod with help of oxygen and LPG cylinder using required copper strip of size 20mmx3mm upto 2.5 feet length alongwith cleaning work of strip with descaling solution/ emery paper upto building height 15mtr all as specified and directed
M&L for brazing work with copper brazing alloy rod with help of oxygen and LPG cylinder using required copper strip of size 25mmx3/4 mm upto 2.5 feet length alongwith cleaning work of strip with descaling solution/ emery paper upto building height 15 mtr all as specified and directed
M&L for brazing work with aluminium/GI brazing alloy rod with help of oxygen and LPG cylinder using required GI strip of size 25mmx3/4 mm upto 2.5 feet length alongwith cleaning work of strip with descaling solution/ emery paper upto building height 15 mtr all as specified and directed
Cleaning the sub station in side and out side building/fencing/ two/four pole structure ,and also around 2 m radius out side the fencing every three month duly taking out unwanted material grass/vegitable/roots of tree/small tree etc complete as specified and directed
M&L for spraying the chemical (Roundup) in sub station in the ration 1: 3 for buring the grass every three month as specified and directed by Engr-in-charge.
M&L for Weather proof outdoor bus bar chamber wall mounted, made out of MS sheet comprising of Copper strips each of 200 Amps, 4 way,appx 60cm long duly insulated mounted on insulators including complete with all accessories and connections with copper thimbles, nuts, bolts & washers including cable glands at entry and outlet points including taking out old unserviceable bus bar chamber complete all as specified and directed by Engr-in-charge. Make :-Havells cat part No IHBC020004 or equivalent as approved by GE.
M&L for Weather proof outdoor bus bar chamber wall mounted, made out of MS sheet comprising of Copper strips each of 200 Amps, 8 way,appx 60cm long duly insulated mounted on insulators including complete with all accessories and connections with copper thimbles, nuts, bolts & washers including cable glands at entry and outlet points including taking out old unserviceable bus bar chamber complete all as specified and directed by Engr-in-charge. Make :-Havells cat part No IHBC020008 or equivalent as approved by GE.
S&F in replacement for Aluminium Lugs of size 16 to 25 qmm complete all as per specified and directed.
S&F in replacement for Aluminium Lugs of size 35 to 70 sqmm complete all as per specified and directed.
S&F in replacement for Aluminium Lugs of size 90 to 120 sqmm complete all as per specified and directed.
S&F in replacement for Aluminium Lugs of size 120 to 185 sqmm complete all as per specified and directed.
S&F in replacement for Aluminium Lugs of size 185 to 240 sqmm complete all as per specified and directed.
Repair/maint and overhauling of L.T.Panel 3 phase AC 415V, 50 Hz A of any make including Taking out old /UNSV MCCBs & MCBs /incoming and outgoing laminated copper busbar , DMC/epoxy insulators of any size ,Volt meter, Amp meter, phase indicator LED lamp,Change over switch of any capacity ,burnt out copper winding ,current coil ,potential coil and keeping aside for safe custody for re-use, opening the L.T. Panel, removing gasket, dismantling and taking out old parts carefully, disconnecting all conections, & re-assembling all serviceable parts to original position including cleaning , removing sludge, dirt, dust, cleaning of parts including removal of old paint with 02 coat synthetic enamel machine spray paint after 01 coat iron red oxide machine spray paint along with replacement of unsv nuts, bolts, thimbles, gasket etc as per site requirement including denting, welding and replacement of unsv hinges if requirement complete testing all as specified and directed by Engineer-in-Charge. Note : (a) All spare parts and control wiring will be measured and paid seperately under respective item of Sch 'A'. are as under. (b) Denting, welding, replacement of unsv hinges, locking arrangement, handle, unsv gasket, cable gland, nut, bolt, washer, minor repair of PCC foundation if required and removing of old paint alongwith reassembling, testing, commissioning etc shall be deemed included into the quoted rate.
Supply only in replacement MCB TPN, 'C' series capacity 32 Amps, 415V, 50 c/s 16 KA . Make : Legrand / Schnieder / L&T
Supply only in replacement MCB SPN capacity 32 amp, 'C' series-02 Nos Make : Legrand / Schnieder / L&T
Supply only in replacement Set of indicating lamp LED type-01 Set.
Civil work PCC 1:2:4 for grouting of panel complete Size- (0.25x0.25x0.25 cum x 04) including excavation, earth work.
Supply only in replacement Copper insulated bus bar with DMC/porcelain insulator etc made out of laminated as per existing size 25 mm x 3 mm
Supply only in replacement Copper insulated bus bar with DMC/porcelain insulator etc made out of laminated as per existing size 50 mm x 6 mm
Supply only in replacement Copper wiring 1.5 Sqmm as per existing size
Supply only in replacement for Rab Aldrop in L Shape of Galvanised Iron with Pad Lock not less than 6 liver all as specified and directed by Engr-in-Charge. Make :- Harrison/Godrej or equivalent .
Supply only in replacement MCCB 63/100 Amps complete all as per existing size all as specified and directed.
Supply only in replacement for CRCA MS Sheet of any size alongwith fixing arrangement through nut, bolts or welding etc suitable for panel base plate or panel canopy all as specified and directed by Engineer-in-Charge. Note :- (i) Rate include for making the hole in the gland according to the size of cable and re-connecting the cable in the existing panel etc. (ii) Size of sheet shall be as decided and directed by Engineer-in-Charge.
Supply and fixing of DWC HDPE tubing 40 mm internal bore including all fitting/fixtures such as Tee/Elbow/Socket/ Nipple etc.Conforming to IS 16205 etc for laying cable, cut to size and making the tubing for cable protection along with drawn in cable into the HDPE tubing on the surface/on the wall /along drainage etc cutting of road etc cutting of PCC and making the good surface complete all as specified and directed by Engr-in-Charge. Note :- (a) The using of GI Clamp in the wall/drainage,etc rate are deemed to be included in the quoted rate and nothing shall extra paid to contractor.
Supply and fixing of DWC HDPE tubing 50 mm internal bore including all fitting/fixtures such as Tee/Elbow/Socket/ Nipple etc.Conforming to IS 16205 etc for laying cable, cut to size and making the tubing for cable protection along with drawn in cable into the HDPE tubing on the surface/on the wall /along drainage etc cutting of road etc cutting of PCC and making the good surface complete all as specified and directed by Engr-in-Charge. Note :- (a) The using of GI Clamp in the wall/drainage,etc rate are deemed to be included in the quoted rate and nothing shall extra paid to contractor.
Supply and fixing of DWC HDPE tubing 80 mm internal bore including all fitting/fixtures such as Tee/Elbow/Socket/ Nipple etc.Conforming to IS 16205 etc for laying cable, cut to size and making the tubing for cable protection along with drawn in cable into the HDPE tubing on the surface/on the wall /along drainage etc cutting of road etc cutting of PCC and making the good surface complete all as specified and directed by Engr-in-Charge. Note :- (a) The using of GI Clamp in the wall/drainage,etc rate are deemed to be included in the quoted rate and nothing shall extra paid to contractor.
S&F insulating MAT of size 2m x 1m x 10 mm complete all as specified & directed
Cutting of road (in hard/ dense soil ) for laying pipe line or repair to pipes of any size upto 01 mtr. Depth and getting out incluiding forming bottom surface to required level and making good the road as per existing bitumens , concrete all as specified and directedby Engineer in charge ..
M/S M P Construction Co
PROACH ASSOCIATES BUILDERS & ENGINEERS
MOHAN LAL AND SONS
KARAN TRADERS
Kanwal Enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .