watermist and caf fire extinguisher high pressure back pack type Experience with Gov. Required 5 Year (s) Watermist And Caf Fire Extinguisher High Pressure Back Pack Type ( 20 ) Technical Specifications Specification Specification Name Values Allowed Values Genric "Conformity to EN 3-7:2004+A1:2007-0 8 standards " The complete system shall be tested for compliance from an int ernationally/nationally accredited laboratory for compliance to all 30 clauses (3.2
3.15
4.2
4.3
4.4
4.5
6.1
6.2
6.3
7.1.1
7.1.2
7.2
7.3
7.4
8.1
8.2
9.2
10.1
10.2
10.3
10.4
10.5
10.6.1 & 10.6.2
14.1
14.2
15.2
15.3
16.1
16.2) of EN 3 - 7:2004 + Al: 2007-08 (E) Standard mandatorily applicable for the complete system 8(e)standardmandatoril yapplicableforthecompl etesystem Mounting type Backpack - Configuration ( Shall be mounted on a sturdy frame suitably cushioned for comfort
provided with shoulder pads for carrying as a Yes - 1/7 backpack and a handle to be carried by hand. All materials used shall be of fire retardant type. Backpack shall be supplied with two air cylinders.) Model Number as per Accredited Laboratory Test Report to Be declared ASKA HI PRESS 02/010 - Main Components: Pressure vessel to hold the media with safety valve
compressed air cylinder coupled with a reducer
hose pipes for discharge of water mist media
extinguishing gun. Yes - Constructional Air Cylinder Material Steel Steel Type of Foam Special AFFF Compound conforming to manufacturer own specifications for higher fire rating A55
B233
Spreading coefficient for special AFFF Compound shall be +5 minimum
concentration shall be 6%. Special AFFF Compound conforming to manufacturer own specifications for higher fire rating A55
concentration shall be 6%. If special foam mention the composition for special
otherwise put NA Water 96%
1
2-Ethandiol
Fluorinated surfactant < 0.5%
Octylsulfate < 1%
Decylsulfate<1%
Akylpolyglycoside<1% - Commercial Brand Name of the Special foam (fire extinguishing medium) as per accredited laboratory test report wherein higher fire ratings i.e A55
E1000 V (Die Electric Suitability) achieved
to be declared.Write NA if not applicable. ASKA FX AGENT - Characteristics of extinguishing medium of Special AFFF Compound Density 1.12
Viscosity 2.0
pH factor 8.5
Refractive index 1.3692 at 20 ± 2deg C - 2/7 (manufacturer own specifications) with infrared spectrogram to be furnished.NA if not applicable Pressure Vessel Material & Capacity (Nominal Charge) Corrosion Free Aluminum alloy vessel of 10 litre capacity . Corrosion Free Aluminum alloy vessel of 10 litre capacity . Minimum wall thickness of pressure vessel (mm) 5 - Extinguishing gun material Stainless Steel - if others Mentions the material for Extinguishing gun
otherwise put NA na - Extinguishing gun weight (750 grams approx) 750 - Length of EN marked Hose 1.3 meter for backpack system Yes - Weight of fully charged Backpack system between 25kg to 27kg having Corrosion Free Aluminum Alloy vessel and below 20 kg having Ultralite Carbon Composite with PET Liner Vessel for 25.9 - performance Air Cylinder Capacity (Ltrs) 2 - Air Cylinder pressure (Bar) 200 - High Pressure Type (Dynamic Operating pressure to be tested in the accredited laboratory test report which will be considered as high pressure for as per clause No. 3.15 of EN 3 - 7:2004 + Al: 2007-08 (E) Standard.) ≥ 30 for Aluminium vessel
≥ 35 for Ultralight Carbon composite with PET Liner vessel (Bar) 30 - 3/7 Lancing Distance of Gun : More than 12 meter (meter) 15 - The air hoses shall be suitable for minus 40 deg C to 100 Deg C temperature and EN mark on hose Yes - Minimum operating time in full throttle for aluminium alloy vessel 22 - Minimum operating time in full throttle for Ultralight Carbon composite with PET Liner vessel 29 - System shall be designed for maximum operating temperature TS max and minimum operating temperature TS min of 60 deg C or more and 5 Deg C or less respectively and certified by the manufacturer accordingly as per Clause 7.4 of EN 3-7:2004+A1:2007-08 standards as per the accredited test report for backpack system. Yes - Fire Rating 55 A
233B
1000V with Special AFFF Compound as per manufacturer own specn 55 A
1000V with Special AFFF Compound as per manufacturer own specn Certification PED approval as per Directive 97/23/EC Yes - Pressure Vessel shall include a pressure gauge fitted on the vessel (CE Marked from notified body). Yes - No objection certificate (NOC) for Pressure Vessel from Petroleum and Explosives Safety Organization (PESO) Nagpur Yes - Pressure Vessel should have CE Marking from Yes - 4/7 Notified body The air cylinders shall have PESO
Nagpur approval yes - Specific consent of the OEM for the value additions made along with a confirmation that fire ratings of the equipment would not be affected by these value additions. Yes - Test Report No - - Test Report Date - - Name of ILAC/NABL/Central Govt.Accredited Laboratory where Test Conducted - - NOC Letter No. Date of PESO Nagpur for Pressure Vessel - - * Bold specifications are the golden parameters. Consignees and Quantity S.No. Consignee Address Quantity Delivery Days 1 Ridhima Singh 400024
Office of the DSL Kurla East
Central Railway Mumbai 20 15