Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.7 LAccepted-AOC 21 GREEN ENCLAVE SULLAR PATIALA 147001 | PATIALA | PATIALA | PUNJAB | 147001 | L1 | Accepted-AOC Being L1 and reasonable | |
| 2 | L2₹35.3 L+₹2.5 L (7.79%)Rejected-Finance 852 EKTA VIHAR 1 C NEAR ANAND NAGAR 9 B PATIALA 147001 | PATIALA | PATIALA | PUNJAB | 147001 | L2 | Rejected-Finance Being L2 | |
| 3 | L3₹36.1 L+₹3.4 L (10.5%)Rejected-Finance | L3 | Rejected-Finance Being L3 |
Tender Value
Refer Docs
EMD Value
₹55,000
Closing Date
27 Jun 2022, 6:00 pmClosed
CWE Patiala
HQ CWE, Bldg No 26, New Lal Bagh, Patiala 147001
PROVN OF MED STORE FOR ECHS AND RATION SHELTER FOR MH UNDER GE NORTH PATIALA
2022_MES_500647_3
CWE/PAT/T-75/2021-22
Open Tender
Civil Works
Lump-sum
180 days
Patiala
As per cover 1
6 documents required · 6 mandatory
₹500
Yes
GE North Patiala
₹55,000
Yes
10 Aug 2022
31 May 2022
29 Jun 2022
31 May 2022
27 Jun 2022
14 Jun 2022
31 May 2022 - 7 Jun 2022
Amount
Schedule 'A'Section-I (Building Works)
Total amount of Sch 'A' Sec I (Building Works)
Schedule 'A'Section-II (EXCAVATION AND EARTH WORKS)
Total amount of Sch 'A' Sec II (Excavation and Earth Works)
Schedule 'A'Section-III (INTERNAL ELECTRIC SUPPLY)
Total amount of Sch 'A' Sec III (Internal Electric Supply Works)
Schedule 'A'Section-VI (Road and Path Works)
Total amount of Sch 'A' Sec IV (Road and Path Works)
Schedule 'A'Section-V (Ext Elect Suppy)
Total amount of Sch 'A' Sec V (Ext Elect Works)
Schedule 'A'Section-VI(Misc Items of Works) Note : This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col. 5 siginifies this fact only.
Supply & fix 1 x 20 W, 4 feet 230 Volts necessary electric connection with twisted flexible PVC copper counductor cable from ceiling rose complete all as specified and directed by Engineer in Charge. Make : Cat Part No LHLDDCXCML8Q020 of Havells or equivalent in makes as per Appendix 'B'.
Supply & fix security LED light fitting 20 watt luminaries new generation energy saving ,with lens made of pressure die cast alluminium alloy powder coated housing LM24 incls necessary electric connection with twisted flexible PVC copper counductor cable clamp for fixing complete all as specified and directed by Engineer in Charge. Make : Cat Part No LHEXAYP7PN6K020 of Havells or equivalent in makes as per Appendix 'B'.
Supply and fix MCB SPN 40Amp ,10KA 240volts ISI marked all as specified and directed by Engr in charge.
Supply and fix MCB SP 06-32 Amps ,10KA 240volts ISI marked all as specified and directed by Engr in charge.
Earthing complete with galvanised steel plate earth electrode 60cmx60cmx6mm thick, burried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of earth plate not less than 1.5 Mtr below normal ground level connected to galvanised earth lead wire 4.0mm dia by means of bolt, nut check nuts and washer of galvanised iron or steel with protection of GI, medium grade 15mm bore upto adequate length watering pipe 25/40mm bore for protection of GI wire/strip from earth electrode to and incl the supplying and laying charcoal dust common salt, PCC 1:3:6 type CI (using 20mm gradedcrushed stone aggegrate) as in chamber and MS angle iron frame 40x40x3mm and RCC cover 40mm thick 1:2:4 type B1 (using 20mm gradedcrushed stone aggregate) reinforced with 8mm dia, TMT bars @75mm c/c both ways with MS handle 12mm dia, PGI funnel and wire mesh, 20 mmdia GI pipe light grade for watering all as shown in electrical plate No 3 of SSR Part-I of 2009 and connected to earth test point testing complete all as specified and directed
Machine pressed rubber moulded ISI marked precast cement concrete interlocking paver block any shape and size with grey cement and no pigment confirming to IS-15658-2006 of 60mm thickness M-35 Grade and including filling of interstices with fine sand over including 25mm thick layer of sand chusion complete all as specified.
S &F ceiling rose bakelite,63.5mm 3 terminals with base plate ISI marked, complete all as specified and directed by Engineer in Charge.
S&F ceiling fan complete with blades,down rod, electronic regulator and accessories 230V,1200mm, complete all as specified and as directed.
Sand cushioning with clean dry sand to cables with layer of sand 8cm before laying of cable and 15cm thick after laying of cable complete all as specified. Note : For payment purpose punned thickness of 18cm shall be measured against spread thickness of 23cm as mentioned in para 19.75 of SSR part-I.
MCB DB double door 240 volts with 200 Amps standard bus bar of suitable size and common neutral link all enclosed in standard sheet flush mounting type, drilling holes for incoming and out going cables complete suitable for 8 ways with IP43 protection complete all as specefied and as directed.
Supply and hanging exhaust fan with sweep 350mm single phase 250v AC supply heavy duty including all fixing material and arrangements, provision of 2 way PVC connector, copper bunched flexible cable 1 Sqmm twin twisted PVC insulated cable from ceiling rose / connector to fan complete all as specified and as directed.
Arneja Builders
HG construction
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .