CWE (AF) Tughlakabad
HQ CWE (AF) Tughlakabad
REPAIR/MAINTENANCE AND PERIODICAL SERVICES OF HT CONTROL GEAR, VCB, RMU, TRANSFORMER, HT UG CABLE AND ALLIED WORKS FOR EXTERNAL ELECTRIC SUPPLY AT 54 ASP AF UNDER GE(P) AF GURGAON
2021_MES_475449_1
CA NO. CWE/TKD/GUR/TOKEN-35/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE(P) AF GURGAON
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE(P) AF GURGAON
₹78,260
Yes
12 Nov 2021
16 Sept 2021
9 Oct 2021
16 Sept 2021
7 Oct 2021
25 Sept 2021
Amount
M&L for rewinding of HT/LT coils of transformer of capacity 25 KVA to 500 KVA, (11KV/433V) with super enamelled copper winding wire of existing gauge and existing number of turns alongwith insulating material i.e leatheroid, paper insulation, cotton tapes, empire tapes, wooden block packings, PVC sleeves, soldering and varnishing with insulating varnish , heating/drying etc including replacement of top cover gasket made out of lethcrised celbatce sheet 4 mm thick including leak proofing by shalak solution complete all as specified and directed. Note :- (i) Transformer rewinding will be done at workshop of approved manufacturer available in CE zone list . (ii) Transformer will be inspected by 'Rep of HQ CWE(AF) TKD before and after repair.
Taking down/dismantling from foundation base and refixing back to the site after repair of any capacity of transformer by using Hydra mechine complete and including tranportation shifting to approved manufacturer/workshop including testing and commissioning complete all as specified and directed. Note- Dismantling and fixing after rewinding and transportation from 54 ASP to workshop and workshop to 54 ASP will be paid as one job
Replacement of breather assembly of approved make filled with silica gel suitable for transformers of following capacity
25 KVA to 100 KVA
150 KVA to 300 KVA
320 KVA to 400 KVA
Replacement of brass spindle for terminal on HT side threaded complete with nut, washers etc of suitable dia for transformers of tollowing capaicty :-
25 KVA to 100 KVA
150 KVA to 300 KVA
320 KVA to 400 KVA
All as per item No 4 here-in-before but for LT side of transformers of folliwing capacity :-
25 KVA to 100 KVA
150 KVA to 300 KVA
320 KVA to 400 KVA
Replacement of ceramic bushing and Gasket on LT side of transformers of following capacities. Make : Mysore Potteries/BHEL
25 KVA to 100 KVA
150 KVA to 300 KVA
320 KVA to 400 KVA
All as per item No 6 above, but on HT side of transformer of following capacites :-
25 KVA to 100 KVA
150 KVA to 300 KVA
320 KVA to 400 KVA
Replacement of arc horn surge arrester complete with amounting ring, nut bolt etc of approved make suitable for transformers of following capacity :-
25 KVA to 100 KVA
150 KVA to 300 KVA
320 KVA to 400 KVA
Dehydration/filtration of transformer oil by means of centrifugal filtration plant to achieve the specified dielectric strength of 40 KV at 2.5 mm gap as per IS-355 in existing position of transformer of any capacity and transformer oil for topping up at various sub station complete all specified and as directed. NOTE:- Transformer oil for TOP UP shall be measured and paid separately under respective item of this schedule.
Supply only transformer oil of approved quality (Dielectric strength not less than 50 KV) ISI marked for filling in transformer for topping up all as directed.
M&L for spray painting of transformer after cleaning the body surface of transformer after preparation of old painted surface by rubbing with emery paper to remove oil stains, dust etc and applying two coat of snthetic enamel paint by spray paint incl writing SM No/MES No , capacity of transformers of following capacity complete all as specified and directed. Note- The contractor has to arrange their own local generator for supply to the spray painting machine.
25 KVA to 100 KVA
150 KVA to 300 KVA
320 KVA to 400 KVA
M&L for laying of cable by trenchless technology under the road, path, culvert etc including HDPE/PPR pipe 100 mm bore as a cover to protect cable . Note:- (i) Cable will be measured and paid separately under respective item of Sch. (ii) Work will be carried out in civil area under the old Delhi Gurgaon High way starting from defence area and terminating to defence area. Any approval required to lay the trenchless cable will be obtained by the contractor from the respective department and no extra payment will be made to the contractor on this account. If the depatment found the negligency to obtain the permission by the contractor from the old Delhi Gurgaon Highway etc, no extention of time on this ground shall be allowed.
Supply, laying, jointing and testing in replacement of HT XLPE insulated ,screened,PVC bedded galvanised steel strip or wire armoured ,electric power cables(heavy duty) with aluminium conductor,11000 volts(earthed) , grade cross sectional area 95 sqmm 3 core for working voltage upto 11000 Volts, including cable lugs for providing connections as in repair complete all as specified and as directed.
Excavation in trenches n.exc 1.5 mtr wide and n. exc 1.5 mtr in depth and getting out in soft/ loose for laying cables, erection of poles complete all as specified and as directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm in soft/loose soil complete all as specified and as directed.
Removing surplus excavated soil n.exc 50 mtr and depositing where directed at a level n-exc 1.5 mtr above the starting point complete all as specified and as directed.
M&L for sand cushioning/sand covering including well ramming for underground cable protection complete all as specified and as directed.
Supply and laying reinforced precast concrete cable cover, class HV,type 1,flat ,size 300 mm X 180mm X 40 mm of approved make complete all as specified and as directed.
Supply and fixing in replacement of cable route indicator for HT UG Cable of 11000 Volts 80 mm dia CI plate marked on HT cable bolted with 40 x 5 mm flat iron member of height 0.9 mtr, embedded in PCC 1:3:6 type C-2 using 40mm graded stone aggregate of size 20 x 20 x 30 cm block complete all as specified and directed.
M&L in replacement for GI pipe light grade of size 80mm dia.for laying in trenches/ under floor/on walls for protection of UG cables complete all as specified and directed
Taking out old unserviceable damaged parts from VCB including servicing , greasing ,testing ,relay testing ,calibration, control wire checking etc complete all as specified and directed. Note:- New parts shall be measured paid seperattly under relevant items of this schedule
Supply and fixing in replacement of unserviceable spring charging mechanism unit assembly suitable for 11 KV VCB complete all as specified and directed. Make Crompton Graves,code No 558/SP
Supply and fixing in replacement of tripping coil, suitable for VCB 11 KV complete all as specified and directed. Make: Crompton Greaves, Code No.-MISC VCBPS
Supply and fixing in replacement of closing coil, suitable for VCB 11 KV complete all as specified and directed. Make: Crompton Greaves, Code No.-MISC VCBPS
Supply and fixing in replacement of Auxiliary switch, suitable for VCB 11 KV complete all as specified and directed. Make: Crompton Greaves, Code No.-33P024
Supply and fixing in replacement of Trip catch with all linkage assemblies, suitable for VCB 11 KV complete all as specified and directed. Make: Crompton Greaves, Code No.-626/SP
Supply and fixing in replacement of fixed resin type PT complete for VCB 11 KV complete all as specified and directed.Make: Crompton Greaves, Code No.-MISC VCBSP
Supply and fixing in replacement of PT Fuse for VCB 11 KV complete all as specified and directed. Make: Crompton Greaves, Code No.-MISC VCBSP
Supply and fixing in replacement of Small gear assembly with motor shaft, suitable for VCB 11 KV complete all as specified and directed.Make: Crompton Greaves, Code No.-11P009
Supply and fixing in replacement of Sigmantal gear, suitable for VCB 11 KV complete all as specified and directed. Make: Crompton Greaves, Code No.-MISC VCB SP
Supply and fixing in replacement of Big cam with main shaft with baring & cover, suitable for VCB 11 KV complete all as specified and directed. Make: Crompton Greaves, Code No.-568/SP1
Supply and fixing in replacement of Meghavin spout suitable for VCB 11 KV complete all as specified and directed. Make: Crompton Greaves.
Supply and fixing in replacement of motor charged mechanasim assembly including close/trip coils and charging handle suitable for VCB 11 KV complete all as specified and directed. Make: Crompton Greaves, Code No.-541/SP1
Supply and fixing in replacement of motor & gear assembly 110 Volt UMG 14 Type suitable for VCB 11 KV complete all as specified and directed. Make: Crompton Greaves, Code No.-536/Sp
Taking out old un searviceable, wear, tear and damaged parts from Ring Main Unit deposited at E/M store yard and replaced with new parts including servicing complete all as specified and directed.
Supply and fixing in replacement of contactor RT - 24VDC, suitable for RMU 11 KV complete all as specified and directed. Make: ABB Ltd, Cat No.-NHSN710013P11
Supply and fixing in replacement of close push button, suitable for RMU 11 KV complete all as specified and directed. Make: ABB Ltd, Cat No.-1SFA616199R1106
Supply and fixing in replacement of open push button, suitable for RMU 11 KVcomplete all as specified and directed. Make: ABB Ltd, Cat No.-1SFA616199R1104
Supply and fixing in replacement of operating handle standard, suitable for RMU 11 KV complete all as specified and directed. Make: ABB Ltd, Cat No.-1VDP000443R1
M&L for replacement of gang opearted air-break, triple pole off load switch with drop out use set with 15 insulator, mounted on channels outdoor, vertical mounting type HT 11 KV , 50 Hz of rating 200 Amps, ISI marked, mechanically operated, mounted on insulators and frame work with operating mechanism worked from ground level with adequate length of GI pipe 32 mm dia medium grade and locking arrangements including Godrej (Navtal) 65 mm pad locks with two keys, complete with fuse carriers and HT use elements having 10 Amp rating suitable and including necessary electric connections complete all as speciied and directed.
M&L for replacement of cable jointing kit of 11 KV (E) grade cable for indoor end termination cold shrinkable type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 3 core 95 sqmm complete all as specified and directed. Note : (i) Cost of necessary excavation and earth work (by hydra machine or manual which suits), labour, Jointing kit complete, fixing charges & T&P including removing of grass/shrubs nearby the fault location shall be deemed to include in quoted rates. (ii) The rate quoted are also included charges for exacavation in concrete/pitched road (by hydra) in case fault occurs in the cable below the road.
M&L in replacement cable jointing kit of 11 KV (E) grade cable for outdoor end termination cold shrinkable type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 3 core 95 sqmm complete all as specifiedand as directed. Note : Cost of necessary excavation and earth work (by hydra machine or manual which suits), labour, Jointing kit complete, fixing charges & T&P including removing of grass/shrubs nearby the fault location shall be deemed to include in quoted rates) for the following sizes :- Note- This item also includes charges for exacavation in concrete/pitched road (by hydra) in case fault occurs in the cable below the road.
M&L in replacement cable jointing kit of 11 KV (E) grade cable for straight through cold shrinkable type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 3 core 95 sqmm complete all as specifiedand directed. Note : (i) Cost of necessary excavation and earth work (by hydra machine or manual which suits), labour, Jointing kit complete, fixing charges & T&P including removing of grass/shrubs nearby the fault location shall be deemed to include in quoted rates) (ii) The rate quoted are also included charges for exacavation in concrete/pitched road (by hydra) in case fault occurs in the cable below the road.
Locating of fault in exixting HT 11 KV 3 core 95/120 sqmm XLPE 11 KV(E) under ground cable by means of hiring fault locating machine mounted on 4 wheeler vehicle to locate fault in Defence/Civil area approximately 1.0 to 5.0 KM range by deploying skilled supervisior and labour for the purpose complete with all T&P & labour to find fault as per direction of Engr-in-charge. Note-The area of this contract is very critical for safety reason so as to contractor has to arrange 24X7 hours fault locating machine and jointing kit when fault occurs. In case of failure to detect the fault within two to three hours, the contractor shall penalized double the quoted rate for per day.
Dismantling of old/damaged HT electric pole any size complete all as specified and directed.
M&L in replacement of unserviceable steel tubular swaged poles complete with cast iron base plate , finial taper plug,bolts,nuts and screws as specified type 410 SP-55 , 11 Mtr long including necessary earth work for foundation of pole, cement concrete PCC 1:2:4 type B-2 using 40mm graded stone aggreate stone aggregate in foundation and coaping in PCC 1:2:4 type B-1 using 20 mm stone graded aggregate complete all as specified and directed.
M&L for dismantling of upper cover of servo Voltage stabilizer of capacity 200/300 KVA after disconnecting electrical connection for overall servicing , cleaning of dust and replacement of complete old wiring with FRLS copper conductor of suitable size in proper layout and tight with tie including replacement of any unserviceable parts i.e main transformers and dimmerstat (Variac) three phase , servo moter , carbon bush or any other parts complete including testing complete all as specified and directed. Note :- Replacement of any unserviceable parts will be measured and paid separatly under relevant items except replacement of old wiring which are deemed to be included in the quoted rate.
M&L for dismantling of upper cover of servo Voltage stabilizer of capacity 500/600 KVA after disconnecting electrical connection for overall servicing , cleaning of dust and replacement of complete old wiring with FRLS copper conductor of suitable size in proper layout and tight with tie including replacement of any unserviceable parts i.e main transformers and dimmerstat (Variac) three phase , servo moter , carbon bush or any other parts complete including testing, all as specified and directed by Engr-in-charge . Note : Replacement of any unserviceable parts will be measured and paid separatly under relevant items except replacement of old wiring which are deemed to be included in the quoted rate.
Supply & fixing in replacement of main mransformer of suitable size upto the capacity of upto 200/300 KVA stabilizer complete all as specified and directed. Make Vintec electronic/Volina
Supply & fixing in replacement of main transformer of suitable size upto the capacity of upto 500/600 KVA stabilizer complete all as specified and directed. Make Vintec electronic/Volina
Supply & fixing in replacement of carbon bush of suitable size upto the capacity of upto 200 KVA stabilizer complete all as specified and directed. Make Vintec electronic/Volina
Supply & fixing in replacement of indicators of RYB of suitable size upto the capacity of upto 200 KVA voltage stabilizer complete all as specified and directed. Make Vintec electronic/Volina
Supply and fixing MS chequred sheet made to shape for duct cover complete all as specified and directed.
M&L for replacement of unserviceable DC power pack with battery back up complete enclosed in a sheet metal enclosures size not less than 2mm thick duly compartmentlise for battries, charging system and control system with LED indicator lamps and toggle switch and push button ON/OFF system for charging, discharging etc as per requirement , front openable and lockable with proper ventilaation as per latest IS, suitable for supply of 01 No of 24 volt DC 100 AH duly banked with 2 volt LED acid maintenance free battries including float and trickle battery charging system suitable for input single phase 220 volt/3 phase 440 volt 50 Hz AC supply including all electrical and control connection upto existing socket for charging and DC Supply to the existing VCBs upto 2 Nos. The connection of incomming and outgoing battery bank to VCBs willl be made by stranded copper conductor size not less than 2.5 sqmm for each core in case of multi core cable or single core cable PVC insulated unsheathed cable duly drawn into medium grade PVC conduit on floor/wall complete all as specified and directed. Location- Substation-1
M&L for replacement of danger notice plate of 1.6 mm thick mild steel sheet ,vitreous enamelled white with letters,figures and conventional skull and bones in signal red colour and fixed with MS clamps,bolts and nut of approved size,for HT ,25 X 20 cm size complete all as specified and directed.
M&L for replacement of Off load tap changer of transformer rating from 75 KVA to 500 KVA as per the existing make of transformer complete all as specified and directed.
Testing and calibration for VCB testing for proper tripping and making contact in case of fault. This item includes all routine test of VCB for proper tripping in case of fault and tripping time should be set lesser than DHBVN end so as to fault will not feed back to DHBVN. The contractor has to collect the data of tripping time from DHBVN and tripping time should be set lesser timing in our end. All control wiring of VCB should be cleaned and serviced and change the unserviceable part as per directed by Engr-in-Charge. The unserviceable item will be paid sepeartely. Note:- The test should be done by authorised dealer of VCB. The contractor should arraange the tool required to test and calibration the VCB.
Testing and calibration for SF6 CB testing for proper tripping and making contact in case of fault. This item includes all routine test of SF6 CB for proper tripping in case of fault and tripping time should be set lesser than our incoming end VCB. All control wiring of SF6 CB should be cleaned and serviced and change the unserviceable part as per directed by Engr-in-Charge. The unserviceable item will be paid sepeartely. Note:- The test should be done by authorised dealer of SF6. The contractor should arraange the tool required to test and calibration the VCB.
Taking down unserviceable cable 95 sqmm 3 core cable from trenches in the Delhi Gurgaon Highway in front 54 ASP complete all as sepecified and directed.
M&L for drilling hole under hard standing /road in different location as per site requirement (between 03 mtr to 12mtr maximum) for laying of pipe for protection of cable etc by means of manual bookie and without disturbing the top surface and making good the disturbed surface if any complete all as sepecified and directed.
Shiv Enterprises
Parveen Builders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .