Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹34.0 LAccepted-AOC C 33 3971 GALI NO 6 JALANDHAR CANTT 144005 | JALANDHAR | JALANDHAR | PUNJAB | 144005 | 1 | Accepted-AOC LOWEST AND REASONABLE | |
| 2 | 2₹38.0 L+₹4.0 L (11.9%)Rejected-Finance HOUSE NO 40 CHOTTI BARADARI PART I GARHA ROAD NEAR MEDICAL COLLEGE JALANDHAR PB 144022 | JALANDHAR | JALANDHAR | PUNJAB | 144022 | 2 | Rejected-Finance NOT LOWEST | |
| 3 | 3₹40.5 L+₹6.6 L (19.4%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | 3 | Rejected-Finance NOT LOWEST |
Tender Value
Refer Docs
EMD Value
₹98,680
Closing Date
10 Oct 2022, 6:00 pmClosed
MAJOR ANIMESH TRIPATHI
GE NORTH PATIALA MILITARY ENGINEER SERVICES SANGRUR ROAD PATIALA CANTT
PROVISION OF SPECIAL REPAIRS AND REVENUE WORK UNDER AGE E/M GE NORTH PATIALA AT PATIALA MILITARY STATION
2022_MES_551361_1
GE(N)/PAT-56/2022-23
Open Tender
Civil Works - Water Works
Lump-sum
240 days
PATIALA
AS,PER NIT
8 documents required · 8 mandatory
₹500
GE NORTH PATIALA
₹98,680
Yes
18 Nov 2022
12 Sept 2022
12 Oct 2022
12 Sept 2022
10 Oct 2022
26 Sept 2022
Amount
Schedule 'A'Part -I (EXTERNAL ELECTRIFICATION)
Total amount of Sch 'A' Part I (EXTERNAL ELECTRIFICATION)
Schedule 'A'Part -II (EXTERNAL WATER SUPPLY)
Total amount of Sch 'A' Part II (EXTERNAL WATER SUPPLY)
Schedule 'A' Part-III (Misc Schedule) Note : This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col. 5 siginifies this fact only.
EXTERNAL ELECTRIFICATION
M & L for precast concrete cable covers type 2 flat, size 250mmx150mmx40mm laid dry in trenches for cable protection all as specified and directed.
Supply and fix PVC insulated round/flat copper cable of size 3 core, 4.0 Sqmm for connection of LED lights complete all as specified and directed.
Supply,Install, Testing and commissioning of self supporting totally enclosed factory fabricated LT feeder pillar box , made out of 3.15 mm thick MS sheet with projected globe roof for rain water protection ,dust and vermin proof, hinged double door shutters with neoprene rubber gasket, epoxy powder coated including danger plate, earth strip, ventilation louvers, bottom detachable gland plate complete with suitable size zink chromium plated nuts, bolts and washers etc outdoor type cubicle panel board suitable for 3 phase 4 wire ,415 volts 50 hz and 50mm x 50mm x 6 mm angle iron frame ,weather proof ventilated with locking arrangement ,including provision of suitable size PCC pedestal for mounting of panel board and comprising the following of size not less than 0.8 m X 0.8 m X 0.50 m, including complete panel painting with one coat of primer and second coat of galvanized aluminium paint over the complete surface. Note :- Excavation and PCC for grouting/fixing of Panel is including in the quoted rate.
(i) Aluminium Bus Bar 63 A supported in suitable size porcelain strand lock with suitable size brass nut, bolt and washers with heat shrinkable colour coded PVC sleaving for three phase and neutral -01 Set (ii) MCB TPN 40 A 16 KA 415 Volts 50 Cycles-01 No (as incoming) (iii) MCB TP 10 A 16 KA 415 Volts 50 Cycles-1 Nos(as outgoing) (v) LED Phase Indication Lamp-03 Nos( R,Y,B) with switch control (vi) Contactor set for 3 pole contactor AC-3 phase 40 A 415 Volts (vii) Electro Mechanical Timer Switch 230V , 10Amp - 01 Nos (viii) The feeder pillar box shall be mounted on PCC pedestal of size 600 mm X 400 mm and 700 mm height (for panel board),with cement concrete 1:2:4 type B1 using 20 mm greaded stone aggregate. (ix) The rate quoted shall be demed to include for the above provisions.
Supply and fixing GI bracket 1.2 mtr long 40 MM dia complete with MS clamp bolts and nuts for fixing of bracket complete all as specified and directed.
Supply and fix junction box made out of PVC 30 cm x 20 cm x 10.5 cm complete including aluminium busher of suitable size three phase with insulators and MCB SP of 6 Amps complete all as specified and directed.
Supply and fix PVC insulated round/flat copper cable of size 3 core 1.5 sq mm for connection of LED lights from over head conductor to street light fittings complete all as specified and directed.
EXTERNAL WATER SUPPY
Supply and laying pipe ductile iron 200 MM dia spigot ends including special class "K-7" centrifugally cast confirming to IS-8329 specification with mettalic zinc spray with Bituminious coating outside and cement mortar lining, in any length laid in trenches with and including necessay rubber gasket confirming to IS : 15382/ tyton joint complete all as specified and directed.
Supply and laying pipe ductile iron 150 MM dia spigot ends including special class "K-7" centrifugally cast confirming to IS-8329 specification with mettalic zinc spray with Bituminious coating outside and cement mortar lining, in any length laid in trenches with and including necessay rubber gasket confirming to IS : 15382/ tyton joint complete all as specified and directed.
Supply and laying pipe ductile iron 100 MM dia spigot ends including special class "K-7" centrifugally cast confirming to IS-8329 specification with mettalic zinc spray with Bituminious coating outside and cement mortar lining, in any length laid in trenches with and including necessay rubber gasket confirming to IS : 15382/ tyton joint complete all as specified and directed.
Supply and fixing cast iron sluice valves ISI marked with hand wheel suitable for cast iron pipeDuctile iron of 150 mm bore, both ends flanged rating PN-1.0 with SS spindle as in repairs including jointing with New MS nuts and bolts, washers and gasket etc all as per IS No. 14846 complete all as specified and directed.
Supply and fixing cast iron sluice valves ISI marked with hand wheel suitable for cast iron pipeDuctile iron of 200 mm bore, both ends flanged rating PN-1.0 with SS spindle as in repairs including jointing with New MS nuts and bolts, washers and gasket etc all as per IS No. 14846 complete all as specified and directed.
M & L for constructing of brick mesonary pits of internal dimensions 1.2 mtr x 1.2 mtr x1.2 mtrs ( bottom PCC floor of the pit should be minimum 30 cms below the bottom surface of sluice valve flange to provide sufficient working space) , bottom floor of the pit be constructed in PCC (1:3:6) 15 cms thick with 20 mm stone aggregate, inner and exposed surfaces and bottom floor of the pit should be plastered in CM (1:4) 15 MM thick. The sluice valve and other fittings should be housed in center of the pit. the vertices of the pit should in right angle and champhered .The top cover of the pit will be made out of MS sheet min 5mm thick witth angle iron frame made out of MS angle 50mm x50 mmx 6 mm with galvanised steel hindges two nos ,and locking arrangements duly painted with two coats of water resistant synthetic enamelled paint over one coat of red oxide complete all as specified and directed.
All as per item No 15 here-in-above but of size 0.9mtrx0.9 mtrx0.9 mtr size complete all as specified and directed.
Cutting of road / PCC path upto the depth of pipes and making good the disturbed surface with PCC 1:2:4 (20mm aggregate) using extra cement including earth work complete all as specified and directed.
M&L for ductile iron fitting such as bend (any type , radius and angle ) taper any type (straight , bend , increasing, decreasing or double socket etc ) tee pieces , single branch 'Y' junction , double branch, cross (all socket or socket and spigot) colar, caps and plugs suitable for upto 300 mm bore centrifugally cast (spun) ductile iron pressure pipes complete all as specified and directed.
UNITED ENGINEERING CORPORATION
R D Bansal
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .