| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹54.4 LAccepted-AOC PLOT NO 74 INDUSTRIAL AREA PHASE 1 CHANDIGARH | NA | NA | 160001 | ₹54.4 L | L1 | Accepted-AOC Being L1 |
| 2 | L2₹58.9 L+₹4.5 L (8.30%)Rejected-Finance | ₹58.9 L+₹4.5 L (8.30%) | L2 | Rejected-Finance L2 |
| 3 | L3₹65.4 L+₹11.0 L (20.2%)Rejected-Finance | ₹65.4 L+₹11.0 L (20.2%) | L3 | Rejected-Finance L3 |
Tender Value
₹62.3 L
EMD Value
₹1.2 L
Closing Date
25 Jun 2026, 12:00 pmClosed
Er. Gurpreet Singh Bhains
Office of the Executive Engineer, Electrical Division No. 1, Sector-9,Chandigarh.
PROVIDING 11 KV COMPACT SUB STATION FOR SCO 39-40, SECTOR-17, CHANDIGARH DUE TO SHIFTING OF BRANCHES FROM MAIN HIGH COURT BUILDING.
2026_CHD_92032_3
E1/TN-55
Open Tender
Electrical Works
Percentage
90 days
Chandigarh
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹1.2 L
21 Sept 2026
17 Jun 2026
25 Jun 2026
17 Jun 2026
25 Jun 2026
17 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning of 11 KV Outdoor Package Sub-Station consisting of 11/0.433 KV 3 phase, 50Hz, (As per Complete Item No. 1 of the DNIT) | 1 | Each | 38,75,100 | ₹38,75,100 |
| 2 | Supply, installation, testing & commissioning of 3 phase, 50Hz, 11KV VCB 800 Amp. (INCOMER) indoor type for Indoor sub Stations. The VCB should be floor mounted trolley type horizontal isolation, horizontal draw out, (As per Complete Item No. 2 of the DNIT) | 1 | Each | 9,26,535 | ₹9,26,535 |
| 3 | DSR item No.5.4 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. | 2 | Each | 8,351 | ₹16,702 |
| 4 | DSR item No.5.11 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. | 20 | P. Mtr. | 755 | ₹15,100 |
| 5 | DSR item No.5.6 Earthingwithcopperearthplate600mmX600mmX3mm thick including accessories, and providing masonry enclosurewithcoverplatehaving locking arrangement and watering pipe of2.7 metre long etc. withcharcoal/ cokeand salt asrequired. | 2 | Each | 15,004 | ₹30,008 |
| 6 | DSR item No.5.14 Providingandfixing25mmX5mmcopperstriponsurfaceor inrecessforconnectionsetc.asrequired. | 20 | P. Mtr. | 1,246 | ₹24,920 |
| 7DSR item No.23.4.1 supplyingandmakingindoorcableendterminationwithheat shrinkablejointingkitcompletewithallaccessoriesincluding lugs suitable for following size of 3 core, XLPE aluminium conductorcable of11 KVgradeasrequired: | |||||
| 7.01 | 50/70sq.mm | 6 | Each | 12,946 | ₹77,676 |
| 8DSR item No.15.15.3 Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. | |||||
| 8.01 | 120 mm dia (OD-120 mm & ID-103 mm nominal) | 20 | P. Mtr. | 264 | ₹5,280 |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 20.08 MB
BOQ_114381.xls
BOQ • 0.30 MB
55c.pdf
Tender Documents • 1.50 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .