Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.8 LAccepted-AOC | L1 | Accepted-AOC Contract is awarded to M/s K K Enterprises | |
| 2 | L2₹41.6 L+₹2.1 L (5.20%)Rejected-Finance BHAWANI KRUPA GANDHI CHOWK PULGAON | PULGAON | WARDHA | MAHARASHTRA | L2 | Rejected-Finance Rejected being other than lowest quoted rate | |
| 3 | L3₹42.3 L+₹2.8 L (7.04%)Rejected-Finance | L3 | Rejected-Finance Rejected being other than lowest quoted rate |
Tender Value
₹42 L
EMD Value
₹84,000
Closing Date
10 Feb 2024, 6:00 pmClosed
Shri Prakash G Kaleka AE (QSandC) AGE (Contracts)
Military Engineer Services, Garrison Engineer (South) Ahmednagar - 414002
REPAIRS / REPLACEMENT TO EXTERNAL WATER SUPPLY PIPE LINES CI/DI, FOOT VALVES, SLUICE VALVES, PUMP/ MOTORS, STARTERS, COOLING APPLIANCES, DG SET AND CONNECTED ITEMS INCLUDING WATER TREATMENT CHEMICALS AT MIL STN BHUSAWAL UNDER GE (SOUTH) AHMEDNAGAR
2024_MES_637424_1
8137/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
BHUSAWAL
Class D Cat a (ii)
8 documents required · 8 mandatory
₹500
Yes
Garrison Engineer (South) Ahmednagar
₹84,000
Yes
23 Feb 2024
13 Jan 2024
12 Feb 2024
13 Jan 2024
10 Feb 2024
27 Jan 2024
13 Jan 2024 - 20 Jan 2024
Amount
Excavation in trenches not exc 1.50 m wide and not exc 1.50 m deep for foundation, laying of pipe or for shafts, wells cesspits, man holes etc not exc 10 Sqm on plan and n exc 1.5m in depth and getting out in soft / loose soil complete all as specified and as directed.
Returning, filling, in soil including spreading, levelling, watering and well ramming in layers n.exc. 25cm thick complete all as specified and as directed.
Removal the excavated materials to a distance n.exc 50 m and depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified and as directed. Note : Removal of excavated material obtained under serial item No 1 & 49 shall be measured and paid under this item.
Taking up or down unserviceable CI/DI water mains, 150 mm bore including all fittings complete from trenches etc complete all as specified and as directed
M&L for DI pipes, 150 mm bore with spigot and socket ends centrifugally cast, class k-9 pressure pipe for water supply ISI marked ( IS-1536 of 2001as amended till date ) including suitable ring tyton joint & rubber ring, laid in trenches in proper alignment including testing complete all as specified and as directed.
Taking up or down old rusted and unserviceable GI water tubing 150 mm bore including all fittings complete from walls /floor or trenches all as specified and as directed.
All as per serial item No. 6 here-in-before but 100 mm bore pipe.
All as per serial item No. 6 here-in-before but 80 mm bore pipe.
All as per serial item No. 6 here-in-before but 50 mm bore pipe.
All as per serial item No. 6 here-in-before but 40 mm bore pipe.
All as per serial item No. 6 here-in-before but 25 mm bore pipe.
All as per serial item No. 6 here-in-before but 20 mm bore pipe.
S&F steel water tubing, galvanised, 150 mm bore, medium grade in any length, including necessary fittings, fixed complete to wall and ceiling or laid in trench, floors etc including jointing, testing and connections complete all as specified and as directed. Note : Excavation and earth work shall be measured and paid separately.
All as per serial item No 13 here-in-before but GI Pipe of size 100 mm dia
All as per serial item No 13 here-in-before but GI Pipe of size 80 mm dia
All as per serial item No 13 here-in-before but GI Pipe of size 50 mm dia .
All as per serial item No 13 here-in-before but GI Pipe of size 40 mm dia .
All as per serial item No 13 here-in-before but GI Pipe of size 25 mm dia .
All as per serial item No 13 here-in-before but GI Pipe of size 20 mm dia .
S&F in repairs, gate valve, 50mm bore, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or unions and fixed to pipe, complete all as specified and as directed.
All as per serial item No 20 here-in-before but of size 40 mm dia .
All as per serial item No 20 here-in-before but of size 25 mm dia .
All as per serial item No 20 here-in-before but of size 20 mm dia .
S&F sluice valve, cast iron, 150 mm dia, long body, both ends flanged as per IS-14846 and drilled with stainless steel spindle, iron wheel head and as per pressure rating PN-1.6 (Class-I) ISI marked alongwith with nut,bolt and washers and rubber gaskets etc and fixed in position including dismantling and taking out old unserviceable sluice valve from valve chamber/ trenches etc complete all as specified and as directed.
All as per serial item No 24 but sluice valve, cast iron, 200 mm dia.
S&F cast iron reflux valve (Non Return Valve) of size 200 mm bore, flanged type of pressure rating PN 1.6, ISI marked alongwith nuts, bolts, washers, gaskets etc, fixed in position including dismantling and taking out old unserviceable sluice valve from valve chamber/trenches etc complete all as specified and as directed.
S&F cast iron reflux valve (Non Return Valve) of size 150 mm bore, flanged type of pressure rating PN 1.6, ISI marked alongwith nuts, bolts, washers, gaskets etc, fixed in position including dismantling and taking out old unserviceable sluice valve from valve chamber/trenches etc complete all as specified and as directed.
S&F cast iron foot valve, 150 mm bore, flanged end swing type, ISI marked with neoprin rubber ball, ISI marked alongwith nuts, botls, washers, gasket etc including dismantling and taking out old unserviceable foot valve from valve etc complete all as specified and as directed.
Cleaning of sedimentation tank of size 6.5m x 6.0m x 8.0m as under :- (a) Pumping & draining out the water from sedimentation tank, removing of sludge and depositing the same at a distance exceeding 500 m and not exceeding 1000 m. (b) Cleaning all the inner surfaces including floor, channel, wall surface etc by removing moss, dirt and all stuck materials and cleaning by coir/wire and bleaching powder solution, repairing of damaged plaster surfaces with 15mm thick in cement mortar 1:4 and applying two coats of cement base paint on inner surface complete all as specified and as directed.
Cleaning of settling tank of size 6m x 6m x 7m as under :- (a) Pumping & draining out the water from settling tank, removing of sludge and depositing the same at a distance exceeding 50 m and not exceeding 100 mm (b) Cleaning all the inner surfaces including floor,channel, wall surfaces etc by removing moss, dirt and all stuck materials and cleaning by coir/wire and bleaching powder solution, repairing of damaged plaster surfaces with 15mm thick in cement mortar 1:4 and applying two coats of cement base paint on inner surface complete all as specified and as directed.
Cleaning of underground settling tank of size 8m x 3m x 2m attached with all filter beds as under :- (a) Pumping & draining out the water from settling tank, removing of sludge and depositing the same at a distance exceeding 50 m and not exceeding 100 m. (b) Cleaning all the inner surfaces including floor, channel, wall surfaces etc by removing moss, dirt and all stuck materials and cleaning by coir/wire and bleaching powder solution, repairing of damaged plaster surfaces with 15mm thick in cement mortar 1:4 and applying two coats of cement base paint on inner surface complete all as specified and as directed.
Cleaning, taking out, removing of any type of accumulated mud, silt, vegetation growth or any solid particles etc. from bottom surface and inner walls of under ground sump of capacity 100000 gallons with following stages :- a) Stage 1 : Draining out of remaining water after emptying through washout valves from the bottom of tank/sumps using submersible discharge pumps. b) Stage 2 : Cleaning of wall, ceiling and floor of tank/sump by using high pressure water jet having a requisite pressure rating to remove all the traces of any algea, moss or dirt etc. c) Stage 3 : Draining out of mud water with suction sludge pump. d) Stage 4 : Sucking out left over mud and dirty throughly with industrial vacuum cleaner to make the tank/sump clean and dry and repair of damaged plastering in cement mortar 1:3 and applying two coats of cement base paint on inner surface. e) Stage 5 : Spraying of antibacterial sterilising agents on inner wall, floors, ceiling and finally sealing the tank complete all as specified and as directed.
All as per serial item No 32 here-in-before but under ground sump of capacity 50000 gallons complete all as specified and as directed.
Complete removal of existing treatment on walls and roof including removing nails, making good holes cracks etc brooming down or steel wire brushing scrapping down or steel wire brushing scrapping down smoke soots etc and applying two coats of exterior Acrylic emulsion (Apex) any tint over one coat of exterior Acrylic primer complete all as specified and directed for 100000 gallon capacity overhead reservoir at 18 m staging including removal of vagitations, muds etc all as specified and as directed. Notes :- (a) All T&P and scaffolding and other sefety equipments required for working of man power for RCC overhead tank shall be arranged by the contractor under own arrangements & without any extra cost to the Govt. (b) The contractor shall be solely responsible for any mishap, accident and other mishapping to workmen during working time and settling all claims of workmen as per the labour commissioner or court laws and the rates quoted by the contractor shall deemed to be included this aspect and nothing extra shall be payable on this account.
Complete removal of existing treatment on walls and roof etc complete including removing nails, making good holes cracks etc brooming down or steel wire brushing scrapping down or steel wire brushing scrapping down smoke soots etc and applying two coats of exterior Acrylic emulsion (Apex) any tint over one coat of exterior Acrylic primer for 50000 ltrs capacity overhead reservoir near Bldg P-89 at 10 mtr staging including removal of vagetations, muds etc complete all as specified and as directed. Notes :- (a) All T&P and scaffolding and other sefety equiptments required for working of man power for RCC overhead tank shall be arranged by the contractor under his own arrangements without any extra cost to the Govt. (b) The contractor shall be solely responsible for any mishap, accident and other mishapping to workmen during working time and settling all claims of workmen as per the labour commissioner or court laws and the rates quoted by the contractor shall deemed to be included this aspect and nothing extra shall be paid on this account.
Disconnecting electric and mechanical connection like electric cable and inlet/delivery pipe, coupling connection etc and dismantling of pump and motor assembly from chassis and removing the DSM 100/36 high lift/Low lift pump to workshop for repair complete all as specified and as directed.
Dismantling impellers, neck rings, gland sleeve, gland check nut, bearing housing coupling, cooling fan, bearing end plate etc and preparation of bearing seat surfaces, refixing the same including matching to the original size and reassembly after replacing of unserviceable spares complete including using new stainless steel nuts, testing on completion of the DSM 100/36 high lift/low lift pump and delivery to working place and installing complete all as specified and as directed. Note : Spares shall be measured and paid separately under respective item.
Disconnecting of electrical connection, delivery and suction pipes, connections and taking out centrifugal horizontal 75 HP electric motor from foundation and removing the same to workshop for repair and dismantling of electric motor and taking out motor shaft, filling of metal at decayed portions including all welding turning and other machine works to required shape and the burnt windings, cleaning and washing of slots and rewinding the same with enamelled copper winding wire of existing gauge and quantity (as per original/manufacturer design) including replacement of all damaged parts, including insulating materials such as insulating sheets, insulating paper (Class ''F'' Make: EUROTHERM) insulating heat resistant sleeves, sealing compounds, varnish etc and reassembling the motor and reinstalling and reconnecting the suction and delivery pipes and electric connections of the same after completion of repair including testing complete all as specified and as directed. Note:- Spare parts shall be measured and paid separately under respective item.
S&F in repairs, ball bearing No 6314 suitable for 75 HP motor, complete all as specified and as directed.
S&F in repairs, roller bearing No N-314 for pump shaft, complete all as specified and as directed.
S&F in repairs, roller bearing No N-309 for pump shaft, complete all as specified and as directed.
S&F in repairs, rope manila of size 20 mm dia, complete all as specified and as directed.
S&F in repairs, gland packing size of 10/12 mm, complete all as specified and as directed.
S&F in repairs, foot valve leather, size of 300x300 mm and 10 mm thick, complete all as specified and as directed.
S&F in repairs, rubber packing for GI pipe jointing, 3 mm thick, complete all as specified and as directed.
S&F in repairs, motor terminal plate, moulded epoxy/bakelite, 6 terminal for 75 HP motor, complete all as specified and as directed.
S&F in repairs, socket weld flange, suitable for 150 mm dia suction pipe with threading complete all as specified and as directed.
S&F in repairs, low joint drum coupling of jointing pump and motor suitable for 75 HP pumps set complete all as specified and as directed.
M&L for cleaning of river channel 1 meter wide in Tapti river by means of rough excavation not exceeding 1.50m depth and getting out/ removing stones/ mud /sand/ sludge and other materials to divert the river water flow towards water suction point all as specified and as directed Notes :- (a) T&P required for cleaning and removal shall be be provided by contractor witout any extra cost to department . (b) Removal shall be measured and paid seperately under respective item.
Supply only Alumino Ferric, grade-1, ISI marked conforming to IS 299/1989 for purification of water containing lead (as Pb) 30 PPM max and Arsenic (As2 03) 6 PPM max complete all as specified and as directed.
Supply only bleaching powder, ISI marked grade-1 (Bag of 25 Kg each) for chlorination of filter water as approved by GE complete all as specified and as directed.
Supply only Calcium Hypochlorite granular, ISI marked (45 Kg plastic drum each) complete all as specified and as directed.
Supply only first quality grease for movable parts, bearings, pump lifting system and as required all as specified and as directed.
S&F in repairs, PVC reinforced flexible suction hose pipe suitable for 150 mm dia complete, all as specified and as directed.
S&F in replacement, heavy duty rubber hose with inbuilt flanged both side each 3 m long of size 150 mm dia for 10 kg/m pressure rating complete all as specified and as directed.
S&F in repairs, fully automatic star delta motor starter in with enclosure type ML-4 FASD, 415 volt, 3 phase, relay range 45-75 A (Size ML2F) suitable for 75 HP motor complete all as specified and as directed. Make: L&T Cat No SS90913 or equivalent as approved by GE
S&F in repairs, thermal relay MN5 with timer suitable for 75 HP pump starter fixed into ML-4 FASD, 415 volt, 3 phase complete all as specified and directed.
S&F in repairs, contactor ML-4 block with IS/IEC 60647-4-1, IEC 60947-4-1, AC-1 100A, AC-3-70A, 415 V, 50HZ suitable for ML-4 FASD strater complete all as specified and as directed.
S&F in repairs, ML-3 contactor block with IS/IEC-60947-4-1 & 45A AC 140 A AC3 415 Volt complete all as specified and directed.
S&F in repairs, XLPE insulated, PVC tape inner sheathed, multicore, armoured copper cable 35 sqmm 3.5 core, grade 415 Volt, ISI marked for connection of low lift 75HP motor complete all as specified and as directed.
S&F in repairs copper lugs, 35 Sqmm complete all as specified and as directed.
S&F in repairs aluminium lugs, 70 Sqmm complete all as specified and as directed.
S&F in repair, MCCB, 415 Volts, 36 KA breaking capacity, 4 pole, 400 Amps at pump house main panel complete with fixed thermal magnetic setting all as specified and as directed.
S&F in repair MCCB, 415 Volts, 36 KA breaking capacity, 4 pole, 200 Amps complete with fixed thermal magnetic setting all as specified and as directed.
S&F in repair, MCCB, 415 Volts, 36 KA breaking capacity, 4 pole, 250 Amps complete with fixed thermal magnetic setting all as specified and as directed.
M&L for construction of valve chamber of size 900 mm x 750 mm x1300 mm (Internal dimensions) including necessary earth work in any type of soil, PCC 1:3:6 in base concrete 100 mm thick, brick work built in cement mortar (1:6) with 10mm thick plaster internally and 15 mm thick externally in cement mortar (1:4), 6 mm thick MS sheet cover with hinges and locking arrangements fixed to angle iron frame made out of mild seel angle iron 50 mm x 50 mm x 6 mm complete with two coats of synthetic enamel paint over a coat of red oxide on all steel work, painting all the embedded portion of mild steel with two coats of black bituminous paint and three coats of white washing on plastered surface of valve chamber complete including dismantaling damaged and broken valve chamber and unserviceable rusted MS cover without distrubing the existing pipe lines, valves all as specified and as directed.
M&L in replacement for earthing complete at pump house area with galvanized steel earth plate electrode 600mm x600 mm x 6mm buried directly in ground vertically to a depth not less then 2.25 metre below normal ground level with top edge of the plate not less then 1.50 metre below normal ground level connected to galvanized earth 32mm x 6 mm GI strip by means of bolts, nuts, check nuts and washers complete up to and including test point made out of 40 x 6mm aluminium flat including earthing pit, charcoal, common salt 25mm dia medium grade GI watering pipe, PCC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate, PCC pit cover including earth work complete all as shown in electrical plate No-3 of SSR-2009 (Part-I) complete all as specified and as directed.
Inspection, maintenance and servicing of DG set, 200 KVA, including alternator, electric panel board connection to DG set for routine check ('A' check) of DG set for smooth functioning and carriying out maintenance as under :- Monthly Service (a) Checking engine oil level and topping up as and when required all as specified and as directed. NOTE : Oil shall be measured and paid separate. (b) Checking and adjusting the belt for tension and replacemnt of belt. Belt shall be measured and paid separate.(c) Checking of oil bath air cleaner level (d) Checking of exhaust system for leakage (e) Draining of sediment from fuel filter and fuel tank (f) Cleaning of air cleanerment. Replacement of Air Cleaner shall be measured and paid separately.(g) Checking engine alternator coupling, mounting bolts and alignment. (h) Tighting all nut, bolts, in alternator terminal block. (j) Checking of alternator carbon brush and connections in alternator. (k) Checking and tighting of all connection in DC control wiring. (l) Checking of all radiator rubber hose and replacement if required. Hose pipes shall be measured and paid separately (m) Checking and recording oil pressure, water and oil temperature (n) Checking anti vibration mounting and replacement if required. Antivibration pad shall be measured and paid separately (o) Checking throttle linkage (p) Checking battery for cell test, electrolyte level, gravity and topping up to required level (q) Routine check / repair work of panel, switch, MCCB, main switch, all contactor, engine control unit.
All as per serial item No. 68 but for 25 KVA DG set.
Material and labour required for `B' CHECK inspection, maintenance, servicing of DG set 200 KVA including items covered in `B' check of DG set for smooth functioning and carriying out maintenance complete all as per OEM instructions and directed as under :- (a) Repeat the activities of 'A' check. (b) Replacing lubricant oil. Lubruicant oil shall be paid separately. (c) Replacing lubricant oil filter element with `O' ring. (d) Replacing fuel filter element. (e) Replacing bypass filter. (f) Replacing air filter. (g) Replacing Governer oil. (h) Replacing coolant. NOTES : i) `B' check once in six month or 300-350 hrs running of DG set whichever is earlier. ii) `B' check kit, coolant, lubricant oil shall be measured and paid seperately under relevant item.
All as per serial item No. 70 but for 25 KVA DG set
Supply only B' Check Kit for DG set 200 KVA, complete all as per OEM instructions and as specified and as directed. Note : Quoted rate shall be included for oil filter (1.00 Ltr/0.5 ltr), Air Filter, Fuel/Diesel filter by pass filter with element etc.
All as per serial item No. 72 but for 25 KVA DG set.
Disconnecting all the connections from alternator of 200 KVA DG set, removing the alternator from foundations , transporting to workshop, dismaintling completely including starter, roter, removing rotor and bearing, cleaning all the parts with thinner and varnishing completely with F class varnishing, applying expoxy coating, rewinding & reassembling, dynamically balancing the alternator transporting and fixing on frame and reallignment within tolerance limit , connecting the alternator with all connections and testing on load completely all as specified and as directed.
All as per serial item No. 74 but alternator of 25 KVA DG set.
M&L in replacement, battery Lead with Brass Terminals of DG Sets of capacity 25/200 KVA all as specified and as directed.
M&L in replacement, emergency shutdown switch with wiring of DG Set 25 KVA to 200 KVA all as specified and as directed.
M&L in replacement, fan belt of DG set 200 KVA all as specified and as directed.
M&L in replacement, fan belt of DG Set 25 KVA all as specified and as directed.
M&L in replacement, oil seal of DG Set 25 KVA to 200 KVA all as specified and as directed.
M&L in replacement, fuel level float ball of DG Set 200 KVA all as specified and as directed.
M&L in replacement, radiator hose pipe set with clamps of DG Set 200 KVA all as specified and as directed.
M&L in replacement, air filter hose pipe set with clamps of DG Set 200/25 KVA all as specified and as directed.
M&L in replacement, dial type mechanical fuel level gauge meter of DG Set 200 KVA all as specified and as directed.
M&L in replacement, dial type mechanical water Temp gauge meter of DG Set 200/25 KVA all as specified and as directed.
M&L in replacement, dial type mechanical Volts gauge meter of DG Set 200 KVA all as specified and as directed.
M&L in replacement, coolant drum assembly of DG Set 200 KVA all as specified and as directed.
M&L in replacement, radiator fan metalic of DG Set 200 KVA all as specified and as directed.
M&L in replacement, radiator fan drive pulley of DG Set 200/25 KVA all as specified and as directed.
M&L in replacement, hydraulic aluminium pipe for engine of DG Set 25 KVA all as specified and as directed.
M&L in replacement starter solenoid valve of DG Set 200 KVA all as specified and as directed.
M&L in replacement, starter / solenoid complete Assembly of DG Set 200 KVA all as specified and as directed.
M&L in replacement complete silencer Assembly with wrapping of rope of DG Set 200 KVA complete all as specified and as directed
M&L for leakage rectification of radiator, cleaning, pressure testing etc for any make and capacity DG set complete as required and as directed.
Supply only engine oil 15W40 of approved and standard in seal packed containers all as specified and as directed. Make : Servo/BPL/IOCL/Castrol
Supply only coolant of approved and standard in seal packed containers all as specified and as directed.
Supply only battery water with electrolyte mix all as specified and as directed.
S&F in replacement, of battery 12 V, Capacity 180 AH, maintenance free battery, 12 Volt initially charged with suitable size of copper leads and brass terminals with 36 month warranty complete as directed.
S&F in replacement of battery 12 V, Capacity 88 AH, maintenance free battery, 12 Volt initially charged with suitable size of copper leads and brass terminals with 36 month warranty complete all as specified and as directed.
S&F in replacement, AC Sycronous motor, 230 Volt with RC network of 25 KVA stablizer complete all as specified and as directed .
S&F in replacement, auxiliary transformer primary (230 V AC) Scondary (15-0-15 Volt AC) of 25 KVA stabilizer complete all as specified and as directed.
S&F in replacement, bush assembly of 25 KVA stabilizer complete all as specified and as directed.
S&F in replacement, control card of 25 KVA stabilizer complete all as specified and as directed.
S&F in replacement, relay-18V/1 CO of 25 KVA stabilizer complete all as specidied and as directed.
S&F in replacement, alternator slip rings with bearings for 200 KVA complete all as specified and as directed.
S&F in replacement, alternator slip rings with bearings for 25 KVA DG Set, complete all as specified and as directed.
S&F in replacement, air filter complete of suitable sizes for the 200 KVA , DG Set, complete all as specified and as directed.
S&F in replacement, air filter complete of suitable sizes for the 25 KVA , DG Set complete all as specified and as directed.
M & L in replacement, auto control wiring with PVC insulated copper wire multistranded of 4 Sqmm 2 core cable for 200 KVA DG Set with all accessories, complete all as specified and as directed.
S&F in replacement, flexible fuel pipe (from Feed pump to Fuel filter, fuel filter to fuel pump and pre-filter to tank unit) of suitable size with banzo washers for DG Set 200 KVA complete all as specified and as directed.
S&F in replacement, flexible fuel pipe (from Feed pump to fuel filter, fuel filter to fuel pump and pre-filter to tank unit) of suitable size with banzo washers for DG Set 25 KVA complete all as specified and as directed.
M & L in replacement, motor winding of pump for radiator for DG set 200 KVA, 415 volts complete all as specified and as directed.
M & L in replacement, motor winding of pump for radiator for DG set 25 KVA ,415 volts complete all as specified and as directed.
Repairs/Maintainance of desert cooler including dismantling of fan motor, pump, diverter, fan blade, water pipe, side panels, scrapping of rusted inside of tank & body, painting of all dismantled items inside with one coat of red oxide metal primer and one coat of synthetic enamel paint of approved quality, reassembling fixing of woodwool with wiremesh, complete with and including wiring and testing all as specified and as directed Note : Spares replaced (except wood wool) shall be measured and paid separately.
Dismantling of unserviceable cooler fan motor from desert cooler including rewinding of fan motor with super enamelled double speed copper winding of correct size and gauge including insulating materials such as insulating paper, varnishing and reassembling and testing complete all as specified and as directed.
S&F in replacement new fan motor for desert cooler 1400 RPM, 450mm sweep, 1/8 HP, single phase, double speed complete with frame and blade complete confirming to relevant IS all as specified and as directed
S & F in replacement of water circulating pump motor 1/2 HP (Tullu pump) 230 V, single phase, 1440 RPM suitable for any type of air cooler/desert cooler fixed complete all as specified and as directed.
S & F in replacement of galvanised iron air diverter grill 20" size for desert coolers complete all as specified and as directed.
S & F in replacement of flexible cord PVC insulated and sheathed, 3 core flexible with copper conductor of size 2.5 sqmm, complete all as specified and as directed.
S&F water tray /tank for desert coolers of standard size and gauge as per sample complete all as specified and as directed.
Taking out hermetically sealed compressor unit (uncut) of refrigerator, single phase, 240 Volts, AC Supply for 165 to 180 ltr capacity of any make and replacing sealed unit with reconditioned sealed unit of same brand including following work all as specified and as directed. (Existing make - Godrej/ Whirlpool/ LG/ Voltas/ Carrier/ Blue star/ Kirloskar / Tuchmesh/ Usha Notes : (i) Connection to suction/ discharge pipe with necessary repairs and brazing. (ii) Replacing capillary tube of existing size and copper liquid filters. (iii) Flushing of entire system before gas charging. (iv) Gas charging and testing the unit to the entire satisfaction complete.
All as per serial item No 121 but compressor unit of refrigerator 190 to 290 litre capacity.
All as per serial item No 121 but compressor unit of deep freezer 200 to 410 litre capacity.
S&F in repairs, heater for frost free refrigerator of any type and capacity, as per existing make & model all as specified and as directed.
S&F in repairs, freezer chest with cooling coil suitable for refrigerator 165 to 290 litre capacity as per existing make & model and fixing, connecting and testing complete all as specified and as directed.
S&F in repairs, freezer chest with cooling coil suitable for Deep freezer of 300 to 320 litre capacity as per existing make & model all as specified and as directed.
S&F in repairs, over load protector suitable for refrigerator of 165 to 320 ltr capacity as per existing make & model all as specified and as directed.
S&F in repairs, thermostat switch (auto de-frost) suitable for refrigerator of 165 to 320 ltr capacity as per existing make & model all as specified and as directed.
S&F in repairs, electric lamp pin/ threaded type, 240 volts, AC supply suitable for refrigerator of 165 to 320 ltr capacity as per existing make & model all as specified and as directed.
S&F in repairs, leg, suitable for refrigerator/Water Cooler of any capacity as per existing make & model all as specified and as directed.
S&F in repairs, relay, suitable for refrigerator/deep freezer upto 410 ltr capacity as per existing make & model all as specified and as directed.
S&F in repairs, capillary tube and drier filter, suitable for refrigerator of 165 to 320 ltr capacity with brazing, nitrogen flushing, leak testing and gas charging all as specified and as directed. Note:- Charging of gas as specified by manufacturer shall be measured and paid separately under respective item.
Taking out old hermetically sealed compressor unit (uncut) from water cooler, storage type, 40/80 ltr/hour cooling capacity and replacing the sealed unit with factory made new sealed unit of same brand as per existing, including the following work all as specified and as directed. (Existing make - Godrej, Whirlpool, LG, Voltas, Carrier, Blue star, Kirloskar, Tuchmesh, Usha) Notes : (i) Connection to suction/discharge pipe with necessary repairs and brazing. (ii) Replacing capillary tube of existing size and copper liquid filters. (iii) Flushing of entire system before gas charging. (iv) Gas charging and testing after repairs including installing the machine at site and testing on full load for its smooth functioning complete.
All as per serial item No 133 but for water cooler 60/120 ltr/hr cooling capacity.
All as per serial item No 133 but for water cooler 120/150 ltr/hr cooling capacity.
S&F in repairs, copper condensing coil with fixing arrangement of water cooler of 40/80 litre capacity complete all as specified and as directed.
S&F in repairs, fan blade for motor suitable for water cooler of 40/80 litre capacity as per existing make & model all as specified and as directed.
S&F in repairs, thermostat suitable for water cooler of 40/80 litre capacity as per existing make & model all as specified and as directed.
S&F in repairs, relay, suitable for water cooler of 40/80 litre capacity as per existing make & model all as specified and as directed.
S&F in repairs, over load protector, suitable for water cooler of 40/80 litre capacity as per existing make & model all as specified and as directed.
S&F in repairs, capacitor 10 mfd including necessary electrical connections, lugs, insulation tape etc complete suitable for water cooler of 40/80 litre capacity, all as specified and as directed.
S&F in repairs, PVC flexible drain pipe length 2 meter, with proper fixing clip as per existing type & size suitable for water cooler any capacity all as specified and as directed.
S&F in repairs, fan motor, 240 volts, single phase, AC supply, suitable for water cooler of 40/80, 60/120 & 150/150 litre capacity all as specified and as directed.
S&F in repairs, copper condensing coil with fixing arrangement of water cooler of 60/120 & 150/150 litre capacity all as specified and as directed.
S&F in repairs, fan blade for motor, suitable for water cooler of 60/120 & 150/150 litre capacity as per existing make & model all as specified and as directed.
S&F in repairs, thermostate, suitable for water cooler of 60/120 & 150/150 litre capacity, as per existing make & model all as specified and as directed.
S&F in repairs, relay suitable for water cooler of 60/120 & 150/150 litre capacity as per existing make & model all as specified and as directed.
S&F in repairs, over load protector suitable for water cooler of 60/120 & 150/150 litre capacity as per existing make & model all as specified and as directed.
S&F in repairs, internal wiring with PVC insulated copper conductor wire with lugs and thimbles complete suitable for water cooler of 40/80, 60/120 & 150/150 litre capacity all as specified and as directed.
M&L in repairs, rewinding of fan motor suitable for water cooler of 60/120 & 150/150 litre capacity of any make with super enameled copper wire of existing size and weight as required including replacement of bushing and capacitor of 4.0 mfd complete all as specified and as directed.
S&F in repairs, PTMT float valve assembly of 15 mm bore with plastic ball with suitable connections galvanized iron nipple 3” long and suitable GI sheet for fixing float valve suitable for water cooler of any make all as specified and as directed.
S&F in repairs, 15mm bore stop cock, cast copper alloy, ISI marked, all as specified and as directed.
S&F in repairs, GI pipe connector (male and female) 15mm bore pipe all as specified and as directed.
S&F in repairs, 15 mm dia, concussive push taps of stainless steel alloy, screwed for iron pipe for water cooler all as specified and as directed.
Dusting using blower and cleaning the housing from inside/out side, cooling system, cooling coil, condenser, capillary tube complete washing with CTC liquid and leak detection, testing for water cooler of 40/80, 60/120 & 150/150 litre capacity all as specified and as directed.
M&L for gas charging to compressors of refrigerator, 165 to 180 litre capacity to its full capacity with specified grade of refrigerant including other connected process required for gas charging and testing complete all as specified and as directed.
All as per serial item No 156 but for refrigerator, 190/200/290 litre capacity.
All as per serial item No 156 but for water cooler of 40/80 litres capacity
All as per serial item No 156 but for water cooler of 60/120 litres capacity
All as per serial item No 156 but for water cooler of 150/150 litres capacity
All as per serial item No 156 but for deep freezer 200 to 410 litre capacity
Taking out hermetically sealed compressor unit (uncut) from the Split/Window Air conditioner of any make & type of 1.5 TR capacity and replacing the sealed unit with new sealed unit complete including following work all as specified and as directed. (Existing Make:- Voltas/ Carrier/ Blue star/ Kirloskar/ Tuchmesh/ Usha/ Godrej/ Whirlpool/ LG/ Kenstar) Note : (i) Connection to suction/discharge pipe with necessary repair and brazing. (ii) Replacing the capillary tubes of existing size and copper liquid filter. (iii) Flushing of entire system before gas charging. (iv) Gas charging and testing after complete repairs including installation of the machine at site and testing on full load for its smooth functioning complete.
All as per serial item No 162 but for Air Conditioner of 2.0 TR capacity.
S&F in repairs, relay for existing make and model of AC, window type, capacity 1.5 TR, single phase, 240 Volts AC supply, including connecting and testing of relay all as specified and as directed.
S&F in repairs, thermostat with switch for existing make and model of AC, window type, capacity 1.5 TR all as specified and as directed.
S&F in repairs, starting capacitor 80/100 mfd including necessary electrical connections, lugs, insulation tape etc for existing make and model of AC, window type, capacity 1.5 TR all as specified and as directed.
S&F in repairs, PCB electronic circuit for existing make and model of AC, window type, capacity 1.5 TR all as specified and as directed.
S&F in repairs, remote for existing make and model of AC, window type, capacity 1.5 TR all as specified and as directed.
S&F in repairs, running capacitor 50/60 mfd including necessary electrical connections, lugs, insulation tape etc for existing make and model of AC, window type, capacity 1.5 TR all as specified and as directed.
S&F in repairs, over load protector for existing make and model of AC, window type, capacity 1.5 TR all as specified and as directed.
S&F in repairs, capillary tube and drier filter of any make for 1.5 TR window AC with brazing, nitrogen flushing, leak testing and gas charging complete all as specified and as directed. Note:- Charging of gas as specified by manufacturer shall be measured and paid under respective item.
S&F in repairs, relay for existing make and model of split type AC of capacity 1.5 TR single phase, 240 Volts, AC supply including connecting and testing of relay all as specified and as directed.
S&F in repairs, thermostat with switch for existing make and model of split type AC of capacity 1.5 TR all as specified and as directed.
S&F in repairs, starting capacitor 80/100 mfd or suitable capacity including necessary electrical connections, lugs, insulation tape etc for existing make and model of split type AC of capacity 1.5 TR all as specified and as directed.
S&F in repairs, PCB electronic circuit including LCD of indoor/ outdoor unit of 1.5 TR of existing make and model of split AC all as specified and as directed.
Supply only remote for existing make and model of split type AC of capacity 1.5 TR all as specified and as directed.
S&F in repairs, swing assembly complete made of PVC, heavy duty for existing make and model of split type AC of capacity 1.5TR all as specified and as directed.
S&F in repairs, swing motor, single phase, AC supply, for indoor unit.of existing make and model of split type AC of capacity 1.5TR all as specified and as directed.
S&F in repairs, running capacitor 45/50 mfd including necessary electrical connections, lugs, insulation tape etc for existing make and model of split type AC of capacity 1.5 TR all as specified and as directed.
S&F in repairs, over load protector for existing make and model of split type AC of capacity 1.5 TR all as specified and as directed.
S&F in repairs, capillary tube and drier filter of any make of 1.5 TR split AC with brazing, nitrogen flushing, leak testing and gas charging complete all as specified and as directed. Note:- Charging of gas as specified by manufacturer shall be measured and paid under respective item .
S&F in repairs, relay as per existing make and model of split type AC of capacity 2.0 TR, single phase, 240 Volts, AC supply including connecting and testing of relay all as specified and as directed.
S&F in repairs, thermostat with switch of existing make and model of split type AC of capacity 2.0 TR all as specified and as directed.
S&F in repairs, PCB electronic circuit including LCD for existing make and model of split type AC of capacity 2.0 TR all as specified and as directed.
Supply only, remote for existing make and model of split type AC of capacity 2.0 TR all as specified and as directed.
S&F in repairs, swing assembly complete made of PVC, heavy duty of existing make and model of split type AC of capacity 2.0 TR all as specified and as directed.
S&F in repairs, swing motor, single phase AC supply for indoor unit.of existing make and model of split type AC of capacity 2.0 TR all as specified and as directed.
S&F in repairs, running capacitor 50/60 mfd or as per existing capacity including necessary electrical connections, lugs, insulation tape etc for split type AC of capacity 2.0 TR all as specified and as directed.
S&F in repairs, over load protector of existing make and model of split type AC of capacity 2.0 TR all as specified and as directed.
Servicing of AC, window type, 1.5 TR capacity of any make, by cleaning the whole equipment, washing of filters, minor adjustments/repair, washing condenser unit all as specified and as directed.
All as per serial item No 190 but AC, split type, 1.5/2.0 TR capacity, indoor and out door unit.
M&L for gas charging to compressors of AC, window type, 1.5 TR capacity of any make, installed machine / equipment to its full capacity with specified grade (as per OEM recommended) of refrigerant including other connected process required for gas charging and testing complete all as specified and as directed.
All as per serial item No 192 but but AC, split type, 1.5 TR capacity of any make.
All as per serial item No 192 but but AC, split type, 2.0 TR capacity of any make.
Removal and refixing of split AC of capacity 1.5/2.0 TR including making hole in the brick/ shelter/ stone walls and making connections, fixing of brackets and insulating pipe lines with nitrile rubber, brazing of copper tubes including testing/ commissioning complete as required at site, including shifting of service connection, metal clad box and voltage stabilizer to the new location all as required. SOP is to be followed by proper pumping down of refrigerant gas before dismantling all as specified and as directed. Note : (i) The rate quoted for this item shall include transportation, civil work and making good to the disturbed surfaces. (ii) Refrigerant pipes shall be measured and paid in respective item.
Removal and refixing of AC window type of capacity 1.5/ 2.0 TR of any make complete with metal clad box, voltage stabilizer and service connection from one location to another and refixing the same by cutting steel/ wooden window/ removing glass pans etc and making opening for AC air tight by providing bedding/ rubber packing wooden frame etc complete including testing/ commissioning complete as required at site all as specified and as directed. Note : (i) The rate quoted for this item shall include transportation, civil work and making good to the disturbed surfaces
S&F in repairs, connecting and testing copper refrigerant pipes, along with proper insulation with nitrile rubber of suitable size for incoming and outgoing pipes complete all as required at site for 1.5/2.0 TR TR split AC all as specified and as directed. Note : One run of both copper pipes incoming and outgoing shall be measured as 01 RM unit for payment purpose
S&F in repairs, nylon pipe, cotton breaded, size 15mm dia, suitable for drain of split type AC, capacity 1.5/2.0 TR all as specified and as directed.
S&F in repairs, mounting frame/ stand including fasteners and nut bolts suitable for outdoor unit of split AC of any size complete all as required at site all as specified and as directed.
S&F in repairs, sheet metal enclosure, single pole & neutral with two pin & earth plug and socket with one MCB, single pole, 20 amp, 240 volts complete all as specified and as directed.
S&F in repairs, metalic plug top, 3 pin for AC point, single phase, 240 volts, AC, ISI marked, all as specified and as directed.
S&F in repairs, metalic socket, 3 pin for AC point, single phase, 240 volts, AC, ISI marked all as specified and as directed.
M&L in repairs, PVC insulated, sheathed, flexible, round, 3 core cable with copper conductor of size 2.5 sqmm for AC all as specified and as directed.
M&L for cleaning surface of water cooler, refrigerator with detergent etc complete all as specified and as directed.
S&F in repairs, voltage stabilizer, 5 KVA capacity for automatic operation, single phase, naturally air cooled, indoor type and designed for input variation between 170V to 250V with output voltage stablized at 230V with accuracy of (+) 2.5% complete all as specified & as directed.
S&F in repairs, voltage stabilizer, 2 KVA capacity for automatic operation, single phase, naturally air cooled, indoor type and designed for input variation between 170V to 250V with output voltage stablized at 230V with accuracy of (+) 2.5% complete all as specified and as directed.
M/S JAI BHAWANI CONSTRUCTIONS
SONU ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .