Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance UDHAMPUR | Admitted-Finance |
| 4 | Admitted-Finance 135 CHAKRANA TIWARI CHAKA NAINI PRAYAGRAJ 211008 UTTAR PRADESH | PRAYAGRAJ | UTTAR PRADESH | 211008 | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹51,636
Closing Date
21 Jul 2022, 4:00 pmClosed
Executive Engineer
Electric Division JPDCL Udhampur
Erection of Substation and Poles
2022_PDD_177041_1
ED/UDH/57 of 2022-23, dt. 30-06-2022.
Open Tender
Electrical Works
Turn-key
90 days
At Sail Sallan under Sub Div II Udhampur
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Engineer Electric Division JPDCL
₹51,636
26 Aug 2022
1 Jul 2022
23 Jul 2022
1 Jul 2022
21 Jul 2022
1 Jul 2022
1 Jul 2022 - 8 Jul 2022
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11 KV line with 50mm² Rabbit Conductor on 9 mtr ST poles for creation/Installation of 250 KVA Sub Sail Sallan (IPS-2) under NRCP (GOI).
9 mtr. Long ST Pole (ST-410 SP-33)
11 mtr. Long ST Pole (ST-410 SP-56)
50 mm² ACSR Rabbit Conductor
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and braces
PG Clamps for 50mm² ACSR Conductor
Galvinized Nuts and Bolts.
11KV Disc Insulators (Polymeric 45KN ) creepage distance 320 mm with tension fittings
11KV Pin Insulator (Polymeric) with Pins (12kv, 5KN) Creepage Distance 320mm
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Rod 20mm 2.5 mtr long through GI Strip 25X3mm
Painting of 9 mtr & 11 mtr ST poles with one coat of Red oxide Paint.
Painting of 9 mtr & 11 mtr ST poles with two coat of Aluminium Paint.
Cement bottoming 1:2:4 mix as per REC standards, 0.5 cum/pole
Aluminium Jointing Sleeves
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11 KV line with 120mm² 11 KB ABC on 9 mtr ST poles for creation/Installation of 250 KVA Sub Sail Sallan (IPS-2) under NRCP (GOI).
9 mtr. Long ST Pole (ST-410 SP-33)
120 mm² AB (HT) Cable (3x120 + 1x95 mm²) (with Earthing)
Heat Shrinkable Outdoor Cable Termination Kit
Suspension/Tension Clamp with eye hook
Galvinized Nuts and Bolts.
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Rod 20mm 2.5 mtr long through GI Strip.
Painting of 9 mtr ST poles with one coat of Red oxide Paint.
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Cement bottoming 1:2:4 mix as per REC standards, 0.5 cum/pole
Mid Span Straight Through Jointing Kit for 11 KV ABC
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 250 KVA Sub Station atSail Sallan (IPS-2) under NRCP (GOI).
11/0.433kV, 3-phase 250 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, copper wound, and with LV Cable Box having detachable Aluminium Gland plate
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11kV GO, Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11 kV Horn Gap Fuse Set 3-Phase 200A
400 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST-410 SP33)
11KV Disc Insulators (Polymeric 45KN ) creepage distance 320 mm with tension fittings
11KV Pin Insulator (Polymeric) with Pins (12kv, 5KN) Creepage Distance 320mm
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
LT distribution box for 250 KVA DTR with MCCB for incomer and SfU's for outgoing circuits.
Cement bottoming of ST poles in 1:2:4 mix as per REC standards, 0.5 cum per pole
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
Painting of sub station with one coat of Red oxide and two coats of aluminium paint
Wedge connector/ PG Clamps
Danger Plates with Clamps
GI Barbed wire for Anti Climbing
3 phase, 4-wire trivector Meter with CT PT unit
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
M/S COMBINE GROUP OF ENGINEERS
M/S MENGI CONTRACTOR
vijay builders
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .