| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.7 LAccepted-AOC 3RD FLOOR BHAKTAMAR RESIDENCY SOMNATHNAGAR ROAD PUNE 411014 | PUNE | PUNE | MAHARASHTRA | 411014 | L1 | Accepted-AOC Reasonable | |
| 2 | L2₹21.9 L+₹1.9 L (9.74%)Rejected-Finance | L2 | Rejected-Finance Quoted high rates | |
| 3 | L3₹23.2 L+₹3.3 L (16.7%)Rejected-Finance | L3 | Rejected-Finance Quoted high rates | |
| 4 | L4₹23.3 L+₹3.4 L (17.0%)Rejected-Finance | L4 | Rejected-Finance Quoted high rates | |
| 5 | L5₹23.5 L+₹3.6 L (18.0%)Rejected-Finance 171 NARAYAN PETH PUNE PUNE MAHARASHTRA 411030 | PUNE | MAHARASHTRA | 411030 | L5 | Rejected-Finance Quoted high rates |
Tender Value
₹24 L
EMD Value
₹48,000
Closing Date
7 Aug 2021, 5:00 pmClosed
GE NDA KHADAKWASLA
GE NDA KHADAKWASLA
REPAIR/ MAINT OF FOCUS / FLOOD LIGHTS, HIGH MAST AND ALLIED WORKS AT NDA KHADAKWASLA
2021_MES_458824_1
8517/E8
Open Tender
Civil Works
Item Rate
180 days
GE NDA KHADAKWASLA
As per tender documents
9 documents required · 9 mandatory
₹500
Yes
GE NDA KHADAKWASLA
₹48,000
Yes
29 Oct 2021
10 Jul 2021
9 Aug 2021
10 Jul 2021
7 Aug 2021
19 Jul 2021
12 Jul 2021 - 13 Jul 2021
Amount
Taking down the existing light fittings on multi mounting brackets from 16/21 mtrs highmast pole by taking on ground repairs/ replacing the defective parts like electronic drivers connection wires and refixing the same to its original position all as directed. Note: (i) Cost of spares , electronic drivers,connection wires replaced against above mentioned item will be measured & paid for separately under respective items of Sch 'A' here-in-below. (ii) The defects / repair of the floodlight making them functional after handing over defective floodlights of highmast (iii) Maintaining proper record of repair / maint in a binded register duly bringing out the details of spares replaced on each and every flood light and getting it authenticated. (iv) Safety of his men engaged for executing the work along with safety equipment and clothes for the men shall be maintained.
Supply only following flood light spares of branded make as mentioned in the list of make enclosed with Particular specifications for replacement, MCB TPN 230 volts C curve 63 amps .
All as per item ser No 2 but MCB TPN 230 volts C curve 40 amps .
All as per item ser No 2 but Digital time switch, DIN type daily / weekly with 2 change over (CO), 16 amps 230 volts
All as per item ser No 2 but Power contactor 16/18 amps 3 pole a.c. With 230 volts coil
All as per item ser No 2 but Power contactor 40 amps 3 pole a.c. With 230 volts coil.
All as per item ser No 2 but PVC insulated copper conductor FRLS grade two core cable 2.5 sqmm, ISI marked
All as per item ser No 2 butPVC insulated aluminium conductor FRLS grade two core cable 2.5 sqmm, ISI marked
All as per item ser No 2 but MCCB 63 Amps 4 pole 415 V .
All as per item ser No 2 but MCB DP 230 volts B curve 6-32 amps.
All as per item ser No 2 but Electronic driver for 400 watts flood lights Make should be as per the Existing manufacturer
All as per item ser No 2 but Electronic driver for 300 watts flood lights Make should be as per the Existing manufacturer
All as per item ser No 2 but Electronic driver for 200 watts flood lights Make should be as per the Existing manufacturer
All as per item ser No 2 but Surge protection device(SPD) of capacity 10/20 KV compatible with industrail & outdooor LED fixtures Make should be as per the Existing manufacturer
All as per item ser No 2 but Supply only self adhesive PVC electrical insulation tape 7 mtr long with superior quality complete all as specified and directed.
Dismantling/ taking down the pole upto 16/21 metre height of high mast light by engaging suitable crane and repairing by replacing the unserviceable top pully of pole and other part such as winch motor, steel wire, power cable and servicing ,toping of oil and greasing the gear wheel assembly and hoisting, refixing and connecting up complete all as directed . Note : a) The repair of light fittings and light fitting spares are measured and paid separately. b) Spares such as steel wire, motor, power cable etc will be measured and paid separately. c) The entire work shall be carried out with well experienced professionals who undertake the high mast poles dismantling /repair works. d) Minor spares such as screws, bolt/nuts, grease etc shall provided by the contractor without any extra cost over and above the quoted rate.
Supply & Fix stainless steel rope twisted of size10mm/6 mm dia with necessary connections proper binding on both sides from bottom drum mast top connecting hook including taking down old unsv one complete all as specified and directed.
M & L for gear box oil of grade EP 90/140 in standard packed/sealed container including drain out old gear box and filling up new gear box oil complete all as specified and directed Make : HP/Servo/valvoline
Disconnecting electric connection and taking down carefully Fractional motor from highmast housing of any type and capacity as described below: -removing the burnt winding of motor rewinding with super enameled copper winding wire of suitable gauge or of matching size to the exisiting wires including all insulating material such as insulation paper sleeve, tape, varnishing etc and reassembling, testing, transporting back to site and refixing to original position all as directed .
Supply & Laying, jointing & testing of UG LT cables XLPE insulated, aluminium conductor multi stranded armoured heavy duty 1100 Volt grade cross sectional area 16 sqmm 4 core laid in trenches/ ducts/ along poles/through pipe under road etc with new aluminium lugs of cable size all as specified and directed
All as per item No 20 above but size 10 sqmm 4 core
All as per item No 20 above but size 4 sqmm 3 core
Taking out existing defective worn out UG LT cable of any size 1100 volts grade from trenches of any size from different locations incl brick bats etc complete, all as specified and directed. (Note: Excavation & earth wk shall be measured and paid for separately),
Excavation in trenches in hard/dense soil n.exc 1.5 M wide and not exceeding 1.5 mts in depth for laying of cables and getting out incl dressing/trimming sides and levelling/grading and ramming of bottom of excavation complete all as specified and directed.
Excavation in trenches in soft/dis integrated rock n exc 1.5m wide and n.exc 1.5m in depth and getting out complete all as specified and directed.
Returning, filiing in incl spreading, leveling watering and well ramming excavated soil in layers not exceeding 25 cm thick each, filling back in trenches after cables have been laid and tested as specified
Removing excavated surplus soil obtained from excavation to a distance not exceeding 50 mtr and deposting where directed at a level 1.5 m above the starting point, complete all as specified.
M&L for laying of reinforced concrete pipe, dia of 150 mm 2 nos half round for bottom and top and before laying excavated area shall be levelling all as specified and directed. Note: One half round Top and One half round bottom together will be considered as one running meter. Make as per sample approved.
Supply and fix in replacement of sintex box thermo plast (weather proof) IP 66, on flood light poles made out of thermoplastic of size 140mm x 140 mm x 95 mm size with connector for connecting incomming and outgoing of cable including 01 No of MCB SP 6 Amps to control the pole light circuit and MS brackets made out of 32 x 4 mm flats for fixing the box on post complete with nuts, bolts and wahers and suitable size of double compression cable glands for incomming, outgoing of cable Complete all as specified and directed. Make Sintex Cat pat No GSJB-1414 or equivalent in any other approved makes.
S&F distribution box 2 Module 230V, 5 HZ, IP-65 & IK-09 Class-II, weatherproof cabinets, door and cabinet fully reversible, removable chassis and faceplates, including weatherproof glands, rails qty-1 Nos, coppper fork type 100 A busbars as short link including end caps, complete all as specified and directed.
M&L 32mm dia GI Pipe light grade including cutting hard standing by providing suitable T&P to make suitable size bore for fixing 32 mm dia pipe in road/cutting hardstanding etc. including the cost of making good the disturbed surface and matching with existing (Chequered tiles/Road/PCC) complete all as specified and directed.
S & F of 100 watts flood light white in colour, LM6 aluminium or higher grade powder coated and water proof pressure die cast aluminium enclosure, with inbuilt electronic drivers and IP 66 protection complete ,Single phase, etc fixing in MS chanel by drilling hole of suitable , size, using nut, bolts and washers of suitable size including suitable mounting structure as reqd at the site complete all as specified and directed.
S & F of 150 watts flood light white in colour, LM6 aluminium or higher grade powder coated and water proof pressure die cast aluminium enclosure, with inbuilt electronic drivers and IP 66 protection complete ,Single phase, etc fixing in MS chanel by drilling hole of suitable , size, using nut, bolts and washers of suitable size including suitable mounting structure as reqd at the site complete all as specified and directed
Suply & fixing in replacement of 200 watt LED flood light luminaire with inbuilt driver with secondary optics made in pressure die cast housing and heat sink in aluminium extrusion and IP 66, with suitable Mounting structure as per site requirement complete all as specified and directed.
Suply & fixing in replacement of 300 watt LED flood light luminaire with inbuilt driver with secondary optics made in pressure die cast housing and heat sink in aluminium extrusion and IP 66, with suitable Mounting structure as per site requirement complete all as specified and directed
Suply & fixing in replacement of 400 watt LED flood light luminaire with inbuilt driver with secondary optics made in pressure die cast housing and heat sink in aluminium extrusion and IP 66, with suitable Mounting structure as per site requirement complete all as specified and directed.
M&L for straight through joint (epoxy) for PVC insulated and sheathed aluminium conductor under ground cable incl freud , thimbles, nut & bolts, washers etc and testing afterjointing complete, all as specified and directed , 16 sqmm to 35 sqmm 3.5 core Make M-seal/Raychem/Cabseal/Denson
S & F PVC insulated multistranded copper conductor 3 core 10 sqmm for connection of floodlight on rooftop and fixing with suitable size clamp and connecting with suitable size copper lugs complete all as specified and directed.
S & F PVC insulated multistranded copper conductor 4 core 10 sqmm for connection from panel to high mast fitting, and connecting with suitable copper lugs complete all as specified and directed.
S&F in replacement of automatic timer switch distribution board, factory assembled in powder coated sheet steel enclosure, comprising of 40 Amps 3 Pole MCB, power contactor and 230V digital time switch for controlling LED/SV etc street lights , including earth work for fixing Timer switch distribution Board and shall be provided 4 Nos 35x35x4mm thick angle iron supports of not less than each 0.6 mt height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement all as specified and directed. Make Indoasina Cat Pat No.TL040DB0/L&T/Legrand
S & F in replacement Busbar panel weather proof outdoor type single door, fabricated out of 3.15 mm thick CRCA sheet with epoxy powder coating of RAL-7035 ( Siemens Gray) shade with matt finish with seven tank pre treatment process.The panel shall be provided with aluminium bus bars, 300mmX40mmX5mm(thickness) electrolytic grade of adequate rating. The bus bars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with 4. RYB & black colour coding and fix horizontally. The panel shall be provided with 04 Nos 25mmx25mmx3mm thick angle iron supports of not less than each .3 mtr height duly painted with anti corrosive black paint and grouted on wall (at Sudan Dome)and suitable fixing arranement as per site requirement. The overall size of the Busbar panel shall be 350mmx200mmx400mm (LxBxH).including PCC 1:3:6 all as directed and specified.
M&L for PVC insulated aluminum conductor FRLS grade two core cable 2.5 sqmm ISI marked including flexible conduit pipes of dia not less than 19 mm complete all as specified and directed.
M&L for earthing complete with galvanised steel earth plate electrode 600x600x6.3mm thick, burried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron strip 32 X 6 mm of 15m length by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 in SSR PART-I connected to earthing test point all as specified or indicated including provision of earthing lead protection pipe, PCC earth pit with cover, excavation & earth work, testing on completion etc all as specified and directed
Supply and Fix in replacement integral LED aviation light comprising housing with polycarbonate enclosure, aviation light is to be fixed on highmast light frame complete all as specified and directed. make Bajaj Catpart No: BGAV302LED or equivalent in Havells/Wipro/Luker/ Havells
Supply and Fixing 1x18 watt WW (3000K) LED bollard outdoor gate light with polycarbonate diffuser and IP 65 protection incl demolition of existing PCC and make suitable PCC for new bollard as per site requirement and fixing arrangements all as directed. Make Luker Catpart No: LGLRBGE-27 or equivalent in havells or philips
Supply and Fixing 1x10 watt WW (3000K) LED outdoor gate light with polycarbonate diffuser and IP 65 protection incl demolition of existing PCC and make suitable PCC for new bollard as per site requirement and fixing arrangements all as directed
Supply & fix GI tubing light grade 40 mm dia ISI marked appx 1 mtr to 1.5 mtr long with Flat Iron Base for mounting of Flood light with all fittings incl nut,bolt,washers suitable size and also make the hole for pole for entry of the 2.5 sqmm PVC conductor all as specified and directed at site.
Supply,install, commission and testing cubical type LT panel board,outdoor type, manufactured by a CPRI approved factory, floor mounted, dust & vermin proof,front and rear operated door with necessary locking arrangement made of 50 x 6mm MS angle iron frame work and CRCA sheet of 3.15mm thick duly painted with two coats of powder coated paint of approved shade after seven tank treatment process both internally and externally. The panel shall be suitable for 415 Volts, 50 HZ, 3 Phase 4 wire system and shall be complete with suitable capacity aluminium bus bar (1.5 times the incoming switch gear current rating) with suitable size of PVC insulated copper conductor, thimbles glands complete all as specified and directed with the following accessories : (a) MCCB 63 A 4 Pole 415 V 25 KA - 01 No (Incoming) (b) MCB 40 A SP Pole 10 KA L&T - 04 Nos (c) Street light timer Digital Switch - 1 No (d) Power contracts 32 MNX 3 pole - 1 No (e) Aluminium bus bar 4 strip (f) Internal wiring for panel incl insulators, sleeves etc (g) Painting and treatment as per CPRI
S&F in replacement of LED rope light out door 12 W 24V IP 68 with warm white incl 2 Pin power supply connector,Connector pin, and End cap as per site requirement fixing at roof of the bldg with suitable PVC saddles for every one mtr on rope. Make : Luker Cat part No LSO68 or equivalent in Wipro/ Polycab
S&F Connector for LED Strip suitable for LED rope light outdoor 12W, 24V IP 68 fittings.
Connector pin suitable for LED Strip ofLED rope light outdoor 12W, 24V IP 68 fittings
Supply and Fix in replacement integral 25 Watt LED post top lantern black/ copper dust painted cast aluminium spigot, spun aluminium canopy with clear acrylic cover and accessorieson on existing GI Pipe of diameter complete all as specified and directed.Make Bajaj (ARIAN) Cat No BGCTN 25W LED WW / Wipro/ Havells
Supply and Fixing 1x18 watt WW (3000K) LED bollard Integral decorative LED bollard with polycarbonate diffuser and IP 65 protection incl demolition of existing PCC and make suitable PCC for new bollard as per site requirement and fixing arrangements all as directed. Make Luker Catpart No: LOBRD60 or equivalent in havells or philips (Quoated rate includes PCC work also)
Suply & fixing in replacement of 60 W LED Out door post top light ,Correlated colour temperature 5700 K, post top with diecast aluminium body confirm to IP-66 , incl suitable arrangements for pole 3.5 mtr decorative pole complete directed. Make - Crompton Cat No LPTE-60-CDL/HPL/Luker
M&L PCC 1:2:4 type B-1 (using 20 mm graded stone aggregate) as in coping of pole sand including formed work and demolition of existing coping complete all as specifed and directed.
Sparkh Electricals & Works
SONU ENTERPRISES
Sneha Aircool
KESARI AND SONS
CHAITANYA WINDWELL
Mahindra Electric Stores
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .