Loading…
Loading…
Tender Value
₹22.7 L
EMD Value
₹45,400
Closing Date
14 Oct 2026, 3:00 pm
GM/TZ-III,JSR
132/33 kV. Grid Campus Gamharia, P.O- Gamharia, Distt- Seraikella-Kharsawan, Pin- 832108
Arresting oil leakage along with filtration and painting of 132/33 kV, 50 MVA ECE make power Transformer at 132/33 kV GSS, Golmuri
2026_JSEB_119096_1
518/PR/JUSNL/2026-27
Open Tender
Electrical Works
Works
90 days
Golmuri
Please refer Tender documents.
2 documents required · 2 mandatory
₹5,900
₹45,400
Yes
24 Sept 2026
24 Sept 2026
15 Oct 2026
24 Sept 2026
14 Oct 2026
24 Sept 2026
Dismantalling of 50MVA Power Transformer, Including dismantlling of top ncover, radiators, inspection chamber pocket, OLTC Chamber,all conservator tank, air seal, HV&LV Bushing, MOG, Breather, Cooling Fan, Transformere protection relay& Valves, Local Control panel, all complete job Nos. as per direction of Engineer in Charge.
Spray painting of power transformer
Filterration of transformer oil machine supplied by the firm
Replacement of gasket of main tank top cover
Rate of replacement of gasket along with supply of Gasket of
(a). Radiator
(b). HV Bushing
(c). LV Bushing
(d). HV/LV Neutral Bushing
(e). Conservator Tank
(f). Oil Level Gauge
(g). Silica Gel
(h). Replacement of gasket of door of marshalling box & OLTC control cable
(i). Inspection cover, manhole cover, valves, connecting pipes, tightening & terminal arrangement of Buckholz relay, OTI, WTI
Erection testing & Commissionng of 50 MVA Power Transformer, including erection of top cover, radiators, inspection chamber pocket, OLTC chamder, all conservator tank, air seal, HV& LV Bushing, MOG Breather, transformer protection relay & Valves, Local control panel, Nitrogen purging, Testing of Transformer e.g. Tand, PI, IR, core balance, short circuit, open circuit, ratio test etc.and Testing of both HV (132KV) and LV (33 KV) side winding resistance.ncluding hiring charges of overhead crane of suitable capacity all complete job as per direction of Enginner in charge.
Construction of 1 x 10 ft treated earth pit (including supply of all materials) (40 mm dia pipe) HV-Neutral, LV-Neutral & Body earth respectively having (1x10) ft depth (including supply of all material).
Hiring Charges of 20 KL Oil Tank for storage of Transformer oil during Dismantaling, erection, oil filteration & Nitrogen purging process.
Hiring Charges for dry air plant
Drying vacuuming of transformer to remove moisture from core & winding
Oil Drain& Re-Filling of Power Transformer
Rectification of oil leakage/seepage problem in power transformer by applying high quality sealant and raising base epoxy compond after proper tightening of nuts & boltus.
Sub-Total
GST @ 18% on Sub-Total
Total (Sub-Total + GST)
L.cess@1% on Total(mailto:L.cess@1%25%20on%20Total塹ᴻ䡿ⲯ嶂藄挧ꮥ)
Grand-Total (Total+L.cess)
Say Rs.
Amount in words:-
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
pricepart518.xls
Additional Documents • 0.04 MB
BOQ518.pdf
Tender Documents • 1.06 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .