Loading…
Loading…
Tender Value
₹80.9 L
EMD Value
₹1.6 L
Closing Date
19 Jan 2026, 11:00 amClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
TECHNICAL
15 conditions · 4 needing a document upload
The tenderer must have minimum average annual contractual turnover of [V/N or 'V' whichever is less; where V = Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
Tenderer must have to submit valid Electrical Contractor license as per Indian Electricity Rules for the respective category of works issued by Government Electrical License Board on or before the closing date of tender. Copy of the electrical contractor license should be submitted along with the tender offer, otherwise, the tender will be summarily rejected.
The Similar nature of works for this instant tender shall be "Supply, installation, testing and commissioning of any LT/HT electrical work." The tenderer should have executed the similar nature of works in Central /State Government department or PSUs of Central /State Government."
52 conditions · 4 needing a document upload
Whether the cost of earnest money deposited
WHETHER VALID ELECTRICAL CONTRACTOR LICENCE SUBMITTED
Migration to GST regime - Special Tender Conditions: The rates should clearly indicate the rate of applicable duties and taxes included in the prices quoted by them. Any variation in tax structure/ rate due to introduction of GST, shall be dealt with under Statutory Variation Clause. It should be ensure that bidders/tenderers are GST compliant and quoted tax structure/rates are as per GST Law.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Contractor should submit the GSTIN number and same should be mentioned in the bills along with a copy of GSTIN registration certificate while submitting the bills to accounts for audit and payment, As GST is scheduled to implemented wef 01.07.2017. Without GSTN, no bill will be accepted w.e.f. 01.07.2017
From 01.07.2017 GST has been implemented but the detail guideline is still not clear. Hence, new tax structure on materials and labour will be applicable to both Railway & contractor after getting proper notification
Payment of Earnest Money deposit (EMD) , in respect of e- tendering,should be accepted through net banking or online payment gateway only
RUB in lieu of Level Crossing near ART/NGC (Electric portion)
EL-LM-25-26-41~NFR
EL-LM-25-26-41
Open
Works - General
120 Days
Hojai, Assam
₹0
₹1.6 L
19 Jan 2026
26 Dec 2025
5 Jan 2026
120 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 70,89,306.08 | ||
| — | 36.00 | — | — | ||
| Supply, fixing, testing and commissioning of HT heat shrinkable type outdoor cable end termination kit suitable for single core 11 KV grade XLPE120 sq.mm armoured cable including all accessories for jointing 11 KV cable to over head through PG clamp as per direction at site Engineer. | — | — | — | 1,43,942.4 | |
| — | 24.00 | — | — | ||
| Supply, fixing, testing and commissioning of HT heat shrinkable type outdoor cable jointing kit suitable for single core 11 KV grade XLPE 120 sq.mm armoured cable including all accessories the work will ne exucuteed as per direction at site Engineer. | — | — | — | 5,84,400 | |
| — | 8.00 | — | — | ||
| Supply & erection of GI tubular pole 12 Mts. long type -410 SP-66 with step length 5.8-3.1 3.1 Mts. section diameter 193.7 x 165.1 x 139.7 mm sectional thickness 4.85 x 4.50 x 4.50 mm as per IS 2713 of 1980 including suitable size of base plate and cap on top and digging of pit to 1/5 th of the pole height and supply and construction of CC foundation in ratio 1:2:4 by cement, Sand and Ships of size 19 mm. The CC block will be 30cm x30cm from bottom of the pole up to. 30cm above the GL. | — | — | — | 3,47,760 | |
| — | 700.00 | — | — | ||
| Provision of HDT machine for horizontal boring in outside of the Road/Railway track Embankment at aminimum distance of 6 Mts. from the embankment GL and depth of 2 Mts. below from G.L. with preparation of site for boring by placing of pipes for electric cable protection through contractor's own arrangement for 200 mm diameter hole as per direction of site Engineer. | — | — | — | 24,87,751 | |
| — | 700.00 | — | — | ||
| Supply,laying of 200 mm diameter HDPE pipe | — | — | — | 2,52,000 | |
| — | 200.00 | — | — | ||
| Supply, laying,fitting & fixing of HDPE pipe 80 mm dia | — | — | — | 57,398 | |
| — | 210.00 | — | — | ||
| Supply & commissioning of 50 (OD) mm diameter Double wall corrugated PN-6.0 Kgf/cm2 HDPE pipe partly through over ground & partly through underground including provision of necessary socket etc. as per direction of site engineer in-charge of Railway | — | — | — | 12,900.3 | |
| — | 800.00 | — | — | ||
| Supply, laying,fitting & fixing of DI pipe 200 mm dia for protection of cable under track crossing/ under the road.(IS Code -83292000 with classes not less then K9 or K10) | — | — | — | 81,656 | |
| — | 30.00 | — | — | ||
| Earthing complete with 50mm dia, 3.65mm thick , 4 mtr long GI pipe to be erected inside an earth pit of height 3.75 mtr& diameter 30 cm to be filled by alternate layers of salt (2) & charcoal (3) of width 50 cm each from the bottom and the rest by earth. Perforated holes of dia 12 mm each to be made in the pipe by drilling and a gap of 30 cm is to be maintained between the holes up to a height of 2.5 mtr from bottom. A second layer of perforated holes of same dimension are also to be made at an angle of 90o with the earlier layer of holes by keeping a vertical distance of 15 cm. A cement concrete chamber of size 30x30x30 cm and thickness 6 cm in ratio 1:3:6 by cement sand & 19mm and down stone chips is to be made around the pipe. The size of CC top cover is 24cmx24cmx4cm with provision of metallic folding handle is to be made. The cover to be provided on the 3mm top groove of earth pit (flash) as per direction of Railway Engineer. Earth continuity by 25x 5mm GI strip through alkathene pipe.75x16 mm GI nut, bolt and spring/flat washer has to be provided as per instruction of Railway Engineer. The connection of earth continuity wire with earth electrode to be made by GI soldering terminal socket of suitable size. The distance of earth electrode form building/other earthing system to be maintained by observing IE rules. As per Drg .No. DRG NO: PCEE/ELG/DRG/2024/1/REV-1, dated 28.07.2025 GI pipe Make - TATA, BANSAL, JINDAL | — | — | — | 48,294 | |
| — | 200.00 | — | — | ||
| Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) | — | — | — | 28,800 | |
| — | 2.00 | — | — | ||
| Supply, fixing, testing and commissioning of distribution class lightening arrestor suitable for 11 K.V O.H with rated voltage 9 KV (RMS) and a normal discharge current rating of 5 KA complete. Make- ELPRO / Raychem/JAYSHREE/ Thyrister | — | — | — | 5,234.16 | |
| — | 30.00 | — | — | ||
| Supply & fixing of GI angle size 65x65x6mm, 2.5 mtr long bracket clamped with above pole made by MS flat 50x5mm with 50x16mm bolts, nuts for holding insulators, lightning arrester with necessary hole by drill including painting . | — | — | — | 30,268.5 | |
| — | 30.00 | — | — | ||
| Supply and fixing of galvanised channel of size 100x50x50x6mm, 2.4mtr long clamped with the pole by 50x5mm GI flat & 50x16 mm GI nut/ bolt/washer including drilling of holes by drill as per direction of site incharge. | — | — | — | 61,976.1 | |
| — | 2.00 | — | — | ||
| Supply, fitting, fixing, testing &commissioning of 11 KV 400 amps GO-DOset with operating handle and fixing of thesame with pole by 2200 mm long MSchannel ( 75x40x40x5) mm with ( 50x5)clamp with necessary nut/bolts.etc. Thewhole work shall be executed as perdirection of Engineer in charge at site. | — | — | — | 11,728.88 | |
| — | 800.00 | — | — | ||
| Excavation of cable trench 1.0 m x 0.5 m below the GL with laying of armored HT/LT cableand refilling the same by supply of Brick, Sand and Soil after digging the earth asper direction of Engineer at site & connection of armored Cable by supply and fixingof crimping lugs etc.The whole work will be executed as per drawing No. PCEE/ELG/DRG/2024/2 dated 04.10.2024. | — | — | — | 97,432 | |
| — | 100.00 | — | — | ||
| Supply erection of reinforced cement concrete Cable Trench made of Cement Bricks with Cement plaster and the RCC Cover. The Cable trench should be in ratio 1:3:6 by cement,Sand and Ships of size 19 mm.including digging of pit to 500mm and MS rod of Suitable size asper instruction of Engineer incharge at site. | — | — | — | 1,00,387 | |
| — | 2500.00 | — | — | ||
| Supply, fitting and laying of Single core 1.5 sqmm Flame Retardant PVC insulated industrial grade multistrand copper conductor(unsheathed) flexible cable voltage grade upto1100 Volt.(Conforming to IS 694:2010). | — | — | — | 51,108.75 | |
| — | 2.00 | — | — | ||
| Construction of 4 pole structureby supply, erection, fixing ofthe following GI channel andangle clamp with pole by 50 x 5mm GI flat with 50 x 16 mmdiameter bolt and nut includingmaking of hole by drill as perrequirement with anti climbingdevice shall be provided by GIBarbet wire along with 33 KVdanger board of size 8 x6 showing the voltage grade ,skull symbol etc. (i)GI Channel(100 x 50 x 50 x 6 x2200)mm=4 nos. conductorbracket (ii) GI Angle50x50x6x2200mm=8 nos.bracing (iii) GI Channel (75 x40 x 40 x 6 x 2200mm=2 nos.guard wire (iv) GI Angle50x50x6x3200mm=8 nos.cross bracing. | — | — | — | 32,281.2 | |
| — | 2.00 | — | — | ||
| Construction of 2 pole structure by supply, erection,fixing of the following MS channel and angle clamp with pole by 50 x 5 mm MS flat with 50x16 mm diameter bolt and nut including making of hole by drill as per requirement of site (i)MSChannel (100 x 50 x 50 x 5)mm x 2200 mm=1 No.conductor bracket. (ii) MSAngle (50x50x6) mm x2200mm=2 nos. bracing(iii)MS Channel (75 x 40 x 40x 4.8) mm x 2200mm= 1No.guard wire (iv)MS Angle (50x50x6) mm x3200mm=2nos. cross bracing. | — | — | — | 6,611.08 | |
| — | 250.00 | — | — | ||
| Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. 150 mm width X 50 mm depth X 1.6 mm thickness | — | — | — | 1,79,000 | |
| — | 6.00 | — | — | ||
| Supply, installation, testing & commissioning of SMC outdoor water proof junction box TPN for 400 A busbar with suitable angle/channel and foundation work | — | — | — | 1,62,840 | |
| — | 6.00 | — | — | ||
| Supply, installation, testing & commissioning of SMC outdoor water proof junction box TPN for 200 A busbar with suitable angle/channel and foundation work. | — | — | — | 1,12,830 | |
| — | 6.00 | — | — | ||
| Supply, installation, testing & commissioning of SMC outdoor water proof junction box TPN for 100 A busbar with suitable angle/channel and foundation work. | — | — | — | 96,480 | |
| — | 9000.00 | — | — | ||
| Laying, commissioning of LT/HT cable XLPEinsulated power cables with armoured aluminum conductors of different sizes (4core 95 sqmm) partly along the pole andpartly through ground in cable trench.Loading, unloading & carrying of cable toactual work site by contractor own arrangement as per instruction of Engineer incharge at site. (Cable will be supplied by Railway.) | — | — | — | 3,68,370 | |
| — | 300.00 | — | — | ||
| Supplying and laying of 200 mm dia size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. | — | — | — | 1,64,400 | |
| — | 250.00 | — | — | ||
| Supply, stringing & binding of ACSR conductor Rabbit of size6/1/ 3.35mm conforming to IS:398-Pt.II-1976 as per direction at site Engineer in - charge of Railway. | — | — | — | 8,602.5 | |
| — | 22.00 | — | — | ||
| Supply & erection of 2P composite polymer 11 KV Pin insulator ( 10 KN) with minimum creepage distance 340mm & sectional length 235mm made of one piece injection molded directly to high quality, corrosion resistant, fibre glass discharge rod and sealed to the hot dipped galvanised carbon steel end fittings by bead of silicon rubber complete with all accessories conforming to IEC : 1109 standard or as per IS : 731 (1971) & 2488 (Pt-II) 1974 complete with hardware fitting. | — | — | — | 8,078.84 | |
| — | 20.00 | — | — | ||
| Supply & erection of 2P composite polymer 11 KV ball & socket type Disc insulator (>70 KN) with minimum creepage distance 320mm & sectional length 300mm made of one piece injection molded directly to high quality, corrosion resistant, fibre glass discharge rod and sealed to the hot dipped galvanised carbon steel end fittings by bead of silicon rubber complete with all accessories conforming to IEC : 1109 standard or as per IS : 731 (1971) & 2488 (Pt-II) 1974 complete with hardware fitting. | — | — | — | 12,329.8 | |
| — | 150.00 | — | — | ||
| Supply & erection of Color coated maintenance free, noncorrosive nature FRP fencing for substation of height 6 feet of fence panels 25 mm deep, 50x50 mm mesh with the load bars oriented parallel to the edge of the panels, vertical and horizontal Line posts of 4" x 4" x 1/4" wide flange sections, Corner Posts of 6" x 6" x 3/8" angles with lock and key arrangement. Line and corner posts are to be manufactured by the pultrusion process with a glass content minimum of 45%, maximum of 55% by weight. The structural shapes shall be composed of fiber glass reinforcement and resin in qualities, quantities, properties, arrangements with supply and construction of foundation pad with suitable ramp and fixing of suitable channel on the top of the bed. The CC foundation should be in the ratio 1:2:4 by cement sand and chips of size 19 mm and down and dimensions as per site requirement as per instructions of the Engineer In charge. | — | — | — | 9,28,893 | |
| — | 1.00 | — | — | ||
| Fabrication, design, supply, erection & commissioning of 6 ft height fencing with MS angle of size (75x75x 5) mm. The size of fencing shall be 5X4.5 mtr & height of fencing 2.5 mtr. above Ground Level. The MS angles shall be put to a depth of 0.5 mtr. Below GL. The MS angles will also be used for top & bottom runner of fencing on 3 sides.( Total quantity of MS angles to be used in the work shall not be less than 68 mtr.) There shall be CC foundation block for supporting the MS angle structure. The size of each CC 18 1 Job 29658.87 At Par 29658.87block shall be 0.250mtr.X 0.250mtr. and depth of each CC block shall be 0.5 mtr. Below GL and height of each CC block shall be 0.250mtr. above GL( There shall be a total of seven7 nos. of such CC blocks in the said work). CC shall be in proportion 1:2:4 with stone, chips of maximum aggregate size 20mm and less including cement, sand etc. The fencing shall be covered on all sides by GI flat of size (25X3) mm in square mesh design.(total quantity of GI flat to be used in the work shall not be less than 483.25mtr.) The MS angle and GI flat are to be welded properly with each other to make the fencing strong. There shall also be a provision of two part/double leaf hinged door locking arrangement on one side of the fencing. The door shall also be fabricated from MS angles of size (75X75X5)mm and GI flat of size (25X3) mm in square mesh design and fitted with MS sliding door bolts bright satin finish or black stone enameled of size(300X16)mm with nuts/screws etc. The MS angles shall also be cleaned of any dust/oily/grease impurities and then painted by one coat of primer over which two coats of aluminum paint of any ISI marked quality. The entire work to be executed as per the direction of engineer in charge at site. | — | — | — | 22,534.81 | |
| — | 10.00 | — | — | ||
| LT termination kit for 240 Sqmm XLPE 4 core | — | — | — | 31,130 | |
| — | 12.00 | — | — | ||
| LT termination kit for 300 Sqmm XLPE single core | — | — | — | 65,400 | |
| — | 10.00 | — | — | ||
| LT termination kit 120 sqmm XLPE 4 core | — | — | — | 22,231 | |
| — | 10.00 | — | — | ||
| LT termination kit 70 sqmm XLPE 4 core | — | — | — | 22,231 | |
| — | 10.00 | — | — | ||
| LT termination kit 35 sqmm XLPE 4 core | — | — | — | 21,340 | |
| — | 10.00 | — | — | ||
| Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for 25 sqmm 2 core size of XLPE insulated aluminium conductor cable of 1.1 KV grade as required. | — | — | — | 14,100 | |
| — | 2.00 | — | — | ||
| Heat Shrinkable jointing kit for 240 sqmm XLPE 4 core | — | — | — | 13,976 | |
| — | 2.00 | — | — | ||
| Heat Shrinkable jointing kit for 120 sqmm XLPE 4 core | — | — | — | 6,734 | |
| — | 2.00 | — | — | ||
| Heat Shrinkable jointing kit for 70 sqmm XLPE 4 core | — | — | — | 6,734 | |
| — | 1.00 | — | — | ||
| "Fabrication, design, supply, erection. testing & commissioning of floor mounted LT Main Control panel 8 way outdoor type MCCB consisting of (I) 400 AMP 4 pole MCCB, 50KA Ics = 01 no. II) 250 AMP 4 pole MCCB- 03 nos, 50KA Ics=100%Icu (iii) 125 AMP 4 pole MCCB- 02 nos, 50KA Ics=100%Icu with adjustable thermal magnetic setting confirming to IEC 60947-2 , Ics=100% Icu, conforming to IEC 60947-2. with copper bus bar 400 Amp., incicator lamp ammeter, voltmeter etc. - The panel shall fabricated from 2 mm thick sheet steel, powder coated, dust and vermin proof duly wired with PVC insulated copper wire confirming to IS: 694. The panel shall also comprise of suitable size & quantity of MCCB door interlocks, spreader link terminals, Aux contact, CT reverse current relay, led indicating lamps, 6A control MCB. The busbar shall be of electrolytic grade copper of size (50 x6) mm for 3 phase neutral. The panel to be manufactured by any CPRI approved. " | — | — | — | 3,12,420 | |
| Each Span | 12.00 | — | — | ||
| Dismantling of unusable corroded ACSR conductor, Guardwire, brackets etc. and the same released materials in full quantity have to be deposited tothe concerned Supervisor under challan after proper accounted bared on the CA | — | — | — | 1,223.76 | |
| — | 30.00 | — | — | ||
| Dismantling/Uprooting of existing Rail/Tubular Pole with all accessories without damage from the work site and handing over to SSE incharge office asper instruction of site Engineer in-charge of railway. | — | — | — | 28,644 | |
| — | 5.00 | — | — | ||
| Supply and erection of Galvanizedstay set for HT OH line completewith 19/20 mm diameter 1.8 Mts.long stay rod, Anchor plate of size30x30 cm x 6 mm thick, thimble,stay clamp turn buckle (20 x 600)mm, 7/10 SWG stay wire andstrain insulator etc. in CCfoundation of ratio 1:2:4:including excavation/refilling etc.as per direction at site Engineer in- charge of Railway | — | — | — | 2,430.05 | |
| — | 15.00 | — | — | ||
| Supply and erection of CC foundation in ratio 1:2:4 cement,sand and good quality chips of size 19 mm and down size as per direction at site Engineer in-charge of Railway. | — | — | — | 23,782.35 | |
| "Making of Dyna Roof shed at (4x4 ) Sq.m i.e. Supply & installation of precoated galvanized iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in- charge) 0.50mm +/- 5% total coated thickness (TCT) thick Zinc coating 120gsm as per IS:277 in 240mpa steel grade, 5-7microns(including all other accessories). " | — | 1.00 | — | — |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .