Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L 1₹17.7 CrAccepted-AOC | ₹17.7 Cr | L 1 | Accepted-AOC Being lowest |
| 2 | L 2₹19.8 Cr+₹2.1 Cr (11.8%)Rejected-Finance 4 195 38 PARAMESHWARA NILAYA MARAKADA KUNJATHBAIL DAKSHINA KANNADA KARNATAKA 575014 UDYAM KR 11 0021217 | DAKSHINA KANNADA | KARNATAKA | 575014 | ₹19.8 Cr+₹2.1 Cr (11.8%) | L 2 | Rejected-Finance Not Being lowest bidder |
| 3 | L 3₹22.9 Cr+₹5.2 Cr (29.6%)Rejected-Finance | ₹22.9 Cr+₹5.2 Cr (29.6%) | L 3 | Rejected-Finance Not Being lowest bidder |
| 4 | L 4₹23.8 Cr+₹6.1 Cr (34.5%)Rejected-Finance MANATHA ENCLAVE 3RD FLOOR OLIMUGAL KAKKANAD P O KOCHI 682 030 KERALA | ERNAKULAM | KERALA | 682030 | ₹23.8 Cr+₹6.1 Cr (34.5%) | L 4 | Rejected-Finance Not Being lowest bidder |
| 5 | L 5₹26 Cr+₹8.3 Cr (47.0%)Rejected-Finance BRICHGUNJ JUNGLIGHAT PO SRI VIJAYA PURAM 744103 | SRI VIJAYA PURAM | SOUTH ANDAMAN | ANDAMAN AND NICOBAR ISLANDS | 744103 | ₹26 Cr+₹8.3 Cr (47.0%) | L 5 | Rejected-Finance Not Being lowest bidder |
| Sl No | Description | Qty | Unit | SUNDER BUILDERS L3 | Jas & Co L5 | GOVARDHAN AND COMPANY L2 | Mecone Construction Contractors L4 | CH GOWRI SHANKAR INFRA BUILD INDIA PRIVATE LIMITED L1 |
|---|---|---|---|---|---|---|---|---|
| .10SCHEDULE 'A' PART-I to SCHEDULE 'A' PART-XVI Note: Schedule 'A' Part-I to Part-XVI are prepriced by MES. Bidders shall insert their lump sum amount in green coloured field under Column 6 only. | ||||||||
| 1.00 | Lump Sum price worked out by the contractor for (BUILDINGS & STRUCTURES), as listed in SCHEDULE 'A' PART-I | 1 | EACH JOB | 18,70,25,000 ₹18,70,25,000 | 21,42,10,225 ₹21,42,10,225 | 15,75,00,000 ₹15,75,00,000 | 19,45,06,000 ₹19,45,06,000 | 13,94,89,239.55 ₹13,94,89,239.55 Lowest |
| 2.00 | Lump Sum price worked out by the contractor for 'Site Clearance/Area Development/Earth Work/Excavation', as listed in Schedule 'A' Part-II | 1 | EACH JOB | 90,00,000 ₹90,00,000 | 92,18,000 ₹92,18,000 | 83,80,000 ₹83,80,000 | 82,50,000 ₹82,50,000 | 65,00,000 ₹65,00,000 Lowest |
| 3.00 | Lump Sum price worked out by the contractor for 'Internal Water Supply', as listed in Schedule 'A' Part-III | 1 | EACH JOB | 1,25,000 ₹1,25,000 | 1,21,600 ₹1,21,600 | 1,10,000 ₹1,10,000 | 1,55,000 ₹1,55,000 | 97,331.36 ₹97,331.36 Lowest |
| 4.00 | Lump Sum price worked out by the contractor for 'Internal Electrification', as listed in Schedule 'A' Part-IV | 1 | EACH JOB | 12,19,000 ₹12,19,000 | 11,89,000 ₹11,89,000 | 10,00,000 ₹10,00,000 | 12,75,000 ₹12,75,000 | 9,75,939.24 ₹9,75,939.24 Lowest |
| 5.00 | Lump Sum price worked out by the contractor for 'External Water Supply', as listed in Schedule 'A' Part-V | 1 | EACH JOB | 1,25,000 ₹1,25,000 | 1,08,500 ₹1,08,500 | 1,00,000 ₹1,00,000 | 1,10,000 ₹1,10,000 | 90,272.04 ₹90,272.04 Lowest |
| 6.00 | Lumpsum price worked out by the contractor for 'External Electrification', as listed in Schedule 'A' Part-VI | 1 | EACH JOB | 10,50,000 ₹10,50,000 | 9,89,500 ₹9,89,500 | 8,50,000 ₹8,50,000 | 10,00,000 ₹10,00,000 | 8,29,883.29 ₹8,29,883.29 Lowest |
| 7.00 | Lump Sum price worked out by the contractor for 'Area Drainage', as listed in Schedule 'A' Part-VII | 1 | EACH JOB | 29,00,000 ₹29,00,000 | 29,35,000 ₹29,35,000 | 25,05,000 ₹25,05,000 | 30,75,000 ₹30,75,000 | 22,00,000 ₹22,00,000 Lowest |
| 8.00 | Lump Sum price worked out by the contractor for 'Sewage Disposal', as listed in Schedule 'A' Part-VIII | 1 | EACH JOB | 7,40,000 ₹7,40,000 | 7,32,000 ₹7,32,000 | 6,37,202 ₹6,37,202 | 7,10,000 ₹7,10,000 | 6,18,261.15 ₹6,18,261.15 Lowest |
| 9.00 | Lump Sum price worked out by the contractor for 'Road/Path/Culvert', as listed in Schedule 'A' Part-IX | 1 | EACH JOB | 93,20,814 ₹93,20,814 | 89,25,800 ₹89,25,800 | 72,00,000 ₹72,00,000 | 96,79,000 ₹96,79,000 | 60,00,000 ₹60,00,000 Lowest |
Tender Value
₹18.8 Cr
EMD Value
₹12.7 L
Closing Date
30 Mar 2026, 6:00 pmClosed
Chief Engineer (Navy), Visakhapatnam
Chief Engineer (Navy), Military Engineer Services, Station Road, Visakhapatnam-530 004
AUGMENTATION OF CHILDREN SCHOOL AT INS RAJALI ARAKKONAM
2025_MES_743713_2
88757
Open Tender
Civil Works
Lump-sum
630 days
ARAKKONAM
All as per NIT
12 documents required · 12 mandatory
₹3,000
Garrison Engineer (M) NAS Arakkonam
₹12.7 L
Yes
2 Jun 2026
9 Mar 2026
6 Apr 2026
9 Mar 2026
30 Mar 2026
23 Mar 2026
SCHEDULE 'A' PART-I to SCHEDULE 'A' PART-XVI Note: Schedule 'A' Part-I to Part-XVI are prepriced by MES. Bidders shall insert their lump sum amount in green coloured field under Column 6 only.
Lump Sum price worked out by the contractor for (BUILDINGS & STRUCTURES), as listed in SCHEDULE 'A' PART-I
Lump Sum price worked out by the contractor for 'Site Clearance/Area Development/Earth Work/Excavation', as listed in Schedule 'A' Part-II
Lump Sum price worked out by the contractor for 'Internal Water Supply', as listed in Schedule 'A' Part-III
Lump Sum price worked out by the contractor for 'Internal Electrification', as listed in Schedule 'A' Part-IV
Lump Sum price worked out by the contractor for 'External Water Supply', as listed in Schedule 'A' Part-V
Lumpsum price worked out by the contractor for 'External Electrification', as listed in Schedule 'A' Part-VI
Lump Sum price worked out by the contractor for 'Area Drainage', as listed in Schedule 'A' Part-VII
Lump Sum price worked out by the contractor for 'Sewage Disposal', as listed in Schedule 'A' Part-VIII
Lump Sum price worked out by the contractor for 'Road/Path/Culvert', as listed in Schedule 'A' Part-IX
Lump Sum price worked out by the contractor for 'AIR CONDITIONING', as listed in Schedule 'A' Part-X
Lump Sum price worked out by the contractor for 'LIGHTNING PROTECTION', as listed in Schedule 'A' Part-XI
Lump Sum price worked out by the contractor for 'R O PLANT AND SPECIAL iTEMS', as listed in Schedule 'A' Part-XII
Lump Sum price worked out by the contractor for 'WATER COOLER', as listed in Schedule 'A' Part-XIII
Lump Sum price worked out by the contractor for 'Rain Water Harvesting', as listed in Schedule 'A' Part-XIV
Lump Sum price worked out by the contractor for 'FIRE FIGHTING', as listed in Schedule 'A' Part-XV
Lump Sum price worked out by the contractor for 'DEMOLITION & DISMANTLING', as listed in Schedule 'A' Part-XVI
SCHEDULE 'A' PART-XVII: (MISCELLANEOUS ITEMS):
UPGRADATION & ADDITIONS/ALTERATIONS CIVIL WORKS:
INTERNAL WATER SUPPLY:
S&F angle stop valve 15mm dia., fancy type cast copper alloy, with capstan heads, chromium plated, screwed down high pressure pipes complete all as specified and as directed.
S&F health faucet 15mm dia., ABS rubbit cleaning system, with 1.25m long PVC flexible tube and ABS wall hook complete all as specified and as directed.
S&F bib taps 15mm dia., long body, cast copper alloy chromium planted fancy type with butterfly handle, screwed down for pipes complete all as specified and as directed.
INTERNAL ELECTRIFICATION:
Material and labour for point wiring of one light/ceiling fan/exhaust fan point controlled by one switch with 1.5 Sqmm single core PVC insulated FRLS unsheathed multi stranded copper conductor wire drawn into PVC conduit (concealed wiring) including provision of 1.5 Sqmm single core PVC insulated FRLS unsheathed multi stranded copper conductor as earth wire. Note: (i) Quoted rate deemed to include Rigid non metallic PVC conduit 20mm and suitable size junction box (ii) Quoted rate deemed to included cutting chases on brick walls concrete surfaces not exc 10cm girth and making good in cement mortar (1:3) the existing surface after carrying out the concealed wiring including necessary finishes all as specified and directed by Engr-in-Charge
All as per Srl item No. 21.00 here-in-before but for One light/fan point controlled by one switch with cable 1.5 Sqmm size.
All as per Srl item No. 21.00 here-in-before but for One bell/buzzer point controlled by one push button with other switches on independent board with cable 1.5 Sqmm size.
All as per Srl item No. 21.00 here-in-before but for one 3 pin socket outlet 5 Amps, same board with cables 1.5 Sqmm size.
All as per Srl item No. 21.00 here-in-before but for one 3 pin socket outlet 5 Amps, independent board with cables 1.5 Sqmm size.
All as per Srl item No. 21.00 here-in-before but for one 3 pin socket outlet 15 Amps, independent board with cables 4.0 Sqmm size.
All as per Srl item No. 21.00 here-in-before but for one light point controlled by 2 way switch with cables 1.5 sqmm size.
Supply and fixing Gl metal flush box suitable for mounting modular plate as per requirement of following modules:-
Gl metal flush box, 2 Module
Gl metal flush box, 3 Module
Gl metal flush box, 4 Module
Gl metal flush box, 8 Module
Gl metal flush box, 12 Module
Supply and fixing combined both frame and cover plates fixing on mounting boxes for following modules:-
Cover plate with frame, 2 Module
Cover plate with frame, 3 Module
Cover plate with frame, 4 Module
Cover plate with frame, 8 Module
Cover plate with frame, 12 Module
Supply and fix Rigid non-metallic PVC conduit of 20 mm dia exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified and as directed.
Supply and fix junction box complete of 1 to 4 way of 25 mm dia all each as specified and directed.
S&F TV Socket wall mounted outlet designed to connect television or other audio visual equipment like a cable or antenna all as specified and directed.
Supply and fix Telephone socket of suitable type complete all as specified and directed.
Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC cool white/ warm white colour, recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and as directed.
Supply and fix high efficiency wall mounted LED light fitting 4 feet white, 2 X 20W, integrated LED driver etc. complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and as directed.
Supply and fix high efficiency wall mounted LED light fitting 4 feet white, 20W, integrated LED driver etc. complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and as directed. (Philips Cat Part No. BN021C LED20S PSU CDL GR or equivalent)
Supply and fixing of LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size all as specified and directed.
S&F for Lamp holder angular/batten type, PVC/ polycarbonate type with back plate suitable for batten fitting including 10W LED lamp complete all as specified and as directed by Engr-in-Charge.
Supply and fix Buzzer, Ding Dong AC, 230 volts, single pole all as specified and directed by Engr-in-Charge.
Supply and high performance low wattage Street light not less than 25 Watts LED light fitting, IP66 protection powder coated pressure die cast aluminium high power street light with heat resistant toughened glass with lens by providing Gl pipe medium grade 25 mm dia 1.5 Mtr in length with suitable size MS Clamp two nos made out of 25x3 mm Fl incl two coat of synthetic enamel paint over a coat of red oxide primer, prewired and including connecting up with 3 core flexible copper conductor cable of 1.5 Sqmm from ceiling rose to fitting all as specified and directed by Engr-in-Charge.
M&L for Sub main wiring with Two run single core 1.5 sqmm for phase and neutral and one run single core 1.5 sqmm as earth wire with multi stranded copper conductor PVC insulated unsheathed FRLS cable 1100 volts grade confirming to IS-694 continuity conductor drawn into conduit (concealed wiring) through Wall/Ceiling/Floor complete all as specified and as directed. Notes: (i) Quoted rate deemed to include Rigid non metallic PVC conduit of suitable size and suitable size junction box (ii) Quoted rate deemed to included cutting chases on brick walls concrete surfaces not exc 10cm girth and making good in cement mortar (1:3) the existing surface after carrying out the concealed wiring including necessary finishes all as specified and directed by Engr-in-Charge (iii) The disturbed surfaces shall be made good with existing surface including finishes as applicable. (iv) Three different color wires shall be used for phase, neutral and earth. (v) Connections of cables with MCBs or bus bars shall be done through appropriate size brass/ copper thimbles.
All as per Srl item No. 41.00 here-in-before but for two run single core 06 sqmm for phase and neutral and one run single core 06 sqmm as earth wire (ie 3X6 Sq mm)
All as per Srl item No. 41.00 here-in-before but for two run single core 10 sqmm for phase and neutral and one run single core 10 sqmm as earth wire (ie 3X10 Sq mm)
All as per Srl item No. 41.00 here-in-before but for Four run single core 16 sqmm for three phases and neutral and two run single core 16 sqmm as earth wire (ie 6X16 Sq mm)
Supply and fixing ceiling fans complete with blades, down rods and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) complete all as specified and as directed.
Supply and fix exhaust fan, steel body AC single Phase. 230V of size 300 mm sweep with blades and frame and louvers complete all as specified and as directed.
Supply and fix exhaust fan, steel body AC single Phase. 230V of size 450 mm sweep with blades and frame and louvers complete all as specified and as directed.
Supply and fix for MCB SPN 230 V, 25-40 Amps with breaking capacity 10KA C curve complete all as specified and as directed by Engr-in-charge.
Supply and fix MCB TPN 415 V, 40-63 Amps with breaking capacity 10KA C curve complete all as specified and as directed by Engr-in-charge. (For each TPN DB, Incoming and outgoing)
S&F sheet metal enclosure VTPN 8 way MCCB DB double door with spreader terminals, insulating phase barrier and hardware, having IP 43 and IK 09 protection with necessary arrangements, MCCB and MCB's all as specified and directed
Supply and fix for MCCB 4 Pole, 415 V, adjustable Thermal & Fixed Magnetic setting type 125 Amps with breaking capacity 26 KA complete all as specified and as directed by Engr-in-charge.
Material and labour for Earthing complete with Gl earth plate electrode of size 600mm x 600mm x 6mm thick buried directly in ground vertically to a depth of not less than 2.25 mtr below ground level, with top edge of the earth plate at a depth of not less than 1.5 mtr below ground level connected with and incl Gl earth wire 4mm dia including alternate 5 layers of charcoal, salt crystal and including 15 mm dia Gl pipe light grade by means of nuts, bolts, washers and necessary earth work upto 7.5 mtr and connecting to test point, LT Switchgear, 20 mm dia medium grade earth protection pipe etc. as per site requirement including necessary excavation, earth work in any type of soil, PCC (1:3:6) type C-1 earth chamber, 40 mm thick RCC Cover with 6 mm dia MS bars 10 cm C/C on both ways as reinforcement complete all as shown in electrical plate No 3 of SSR Pt- I including testing on completion complete all as specified and as directed. Note: (i) Quoted rate deemed to include necessary earth work PCC chamber, RCC cover, reinforcement, removal of surplus soil, site clearance etc. (For VTPN DB)
EXTERNAL WATER SUPPLY:
Supply and lay Ductile iron pipes of size 100mm dia, class K7 with spigot and socket/double end flanged end of any length conforming to IS specification laid in trenches including tighten rubber gasket complete all as specified and directed. Note: The above rate is inclusive of the following points (i) Pipeline should be securely anchored at dead ends, tees, bends, tapers and valves to resist thrust arising from internal pressure. Anchors and thrust blocks should be designed in accordance with IS : 5330-1984. (ii) DI fittings, excavation and PCC as required shall be measured and paid separately under relevant items.
Supply and fix 300mm dia Cast Iron Double flange non rising type sluice valve of following sizes as per IS 14846, PN 1.0 with hand wheel Operation flange Drilling as per IS 1538 including rubber gaskets, MS bolts, nuts, washers etc., as required complete all as specified and as directed.
M&L for brick masonary valve chamber of size 900mmx900mmx900mm ( internal size) by providing PCC 1:4:8 type D2 foundation 100 mm thick brick work in CM 1:4 plastering 15mm thick in CM 1:4 internal surfaces completely and external surfaces completely and external surfaces upto 150mm below GL, 75mm thick PCC 1:2:4 type B1 as in coping valve chamber cover made up of 40x40x5mm thick angle iron frame and 3.15 mm thick MS sheet cover complete excavation and locking arrangement and handle including painting steel surfaces with two coats of enamel paint over a coat of red oxide primer including dismantling the existing damaged valve chamber and removing debris away from the premises etc complete all as specified and as directed.
M&L for brick masonary valve chamber of size 1.2mx1.2mx1.2mm ( internal size) by providing PCC 1:2:8 type D2 foundation 100 mm thick brick work in CM 1:4 plastering 15mm thick in CM 1:4 internal surfaces completely and external surfaces completely and external surfaces upto 150mm below GL, 75mm thick PCC 1:2:4 type B as in coping valve chamber cover made up of 40x40x5mm thick angle iron frame and 3.15 mm thick MS sheet cover complete excavation and locking arrangement and handle including painting steel surfaces with two coats of enamel paint over a coat of red oxide primer including dismantling the existing damaged valve chamber and removing debris away from the premises etc complete all as specified and as directed.
EXTERNAL ELECTRIFICATION:
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 1100 volts grade, of size 150 sqmm 3.5 core complete all as specified and as directed
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 1100 volts grade, of size 70 sqmm 3.5 core complete all as specified and as directed
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 1100 volts grade, of size 16 sqmm 4 core complete all as specified and as directed
Supply, laying & testing PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size2.5 sq mm ,3 core, 1100 Volts grade passing through PVC Conduit/GI Pipe (from junction box to Street light/flood light/post top light/bollard light fitting
S&F LED street light fitting 35/36 Watt 230 V AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics by providing GI pipe medium grade 25 mm dia 1.5 Mtr in length with suitable size MS Clamp two nos made out of 25x3 mm FI, prewired and including connecting up with 3 core flexible copper conductor cable of 1.5 Sqmm complete with IP 65/66 protection complete all as specified and as directed by Engineer-in-Charge.
Material and labour for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique without damaging existing road/hard standing/walls and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed
Supply and fixing post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver, lamp and pole of suitable size not less than 1.5 mtr complete for garden light complete all as specified and as directed.
Supply and fixing post top lantern LED type 40 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete for gate light complete all as specified and as directed.
Supply , Fixing and Testing Powder coated Outdoor street light control box of size not less than 280 x 200 x 100 mm CRCA 2 mm thick IP 65 , halogen free and weather proof for outdoor installation , in and including suitable terminal TPN SMC Connector for three phase Cable Line ( IN & OUT) , MCB 10 Amps SP 'C' Series , canopy weather proof hinged doors, Allen key locking system and arrangements for fixing on Steel Poles with MS clamps of suitable shape and size with nut, bolts and washers as per site requirement complete all as specified and directed by Engr In Charge.
Supply , Fixing and Testing PVC body heavy duty Post top/bollard light control box , in and including suitable terminal TPN SMC Connector for three phase Cable Line ( IN & OUT) , MCB 6 Amps SP 'C' Series , canopy weather proof hinged doors, Allen key locking system and arrangements for fixing on PCC/Steel Poles with MS clamps of suitable shape and size with nut, bolts and washers as per site requirement complete all as specified and directed by Engr In Charge (for gate light-2, garden light-12)
S&F Cable end jointing kit for indoor termination heat shrink type suitable for 3.5 core XLPE armoured aluminium conductor cable of 150 sqmm for complete with jointing material and accessories complete all as specified and directed by Engr In Charge
M&L for extension of busbar and insulator complete from existing VCB to proposed indoor VCB incl enclosure of bus coupler fitting jointing, nut and bolt etc all as specified and directed by Engr-in-Charge.
Materials & labour XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, 95 sqmm 3 core electric power cables (heavy duty) with aluminium conductor, 11000 volts Earthed, grade cross sectional area complete all as specified and as directed.
Supply, Installation, testing and commissioning of new 11 KV, 630 Amp Outdoor type load break switch (LBS) complete unit, extensible 1 way load break switch stand alone floor mounted, internal copper bus bars not less than 2 mm thick having MS Sheet Steel enclosure suitable for IP55 as per IEC 62271-200, LBS should complete with all accessories such as HRC fuse 11 KV- 3 Nos Manual Trip Push Button, terminal boots, Provision for receiving incoming/outgoing Cables through Bottom entry, including termination kit & glands, cable supports, all front cable terminations, mechanical indications for load break switch ON/OFF, Heater ON / OFF switch with filament type 200Watts space heater & thermostat, single phase switch with socket, Lamp for panel illumination with snap type door limit switch, Surge Arrester (9kV,10kA) including Control Wiring with appropriate size complete all as specified and directed with the following specifications as given :- Note : - (i) Factory inspection of load break switch and its testing shall be done by the representative of the Accepting Officer. (ii) The contractor shall produce drawing of load break switch (LBS) for according approval before the ordering of material to manufacturers. (iii) Foundation/ civil work as per manufacturer’s instructions shall be provided including weather proof paint on platform without any extra cost to the deptt.
Supply, install, testing and commissioning of copper wound Distribution Transformer step down latest Level 3 with amendment No 4, 11 KV/0.433KV, Three Phase complying with IS: 1180/IEC-76(Part-1) 2014 with latest amendments no.4, Indoor type double copper wound suitable for 50 Hz system of capacity 160 KVA, oil immersed naturally cooled delta connected on HT side and Star connected on LT side ,Vector Group Dyn-11. provided with OFF load tap changer to vary secondary voltage from -7.5% to + 7.5% in step of 2.5%. Losses should be confined to the limits specified as follows: maximum allowable losses at full load (100 %) & Half Load (50 %) shall not be exceeded 513W & 1547W respectively and as per GRIHA RATING, Percentage Impedance: 5%. Losses and Impedance are subjected to tolerance as specified in IS 1180. The transformers should be supplied with first filling of oil confirming to IS 335. The transformer should have both side cable end box with neutral brought out complete and installation of transformer shall be carried out comprising with the following standard fittings/Technical specifications : -
(a) Lifting lug for transformer and tank. (b) Earthing terminal rating and diagram plate. (c) Air release device on main transformer tank. (d) Oil filling inlet pipe with plug. (e) Drain outlet pipe with brass gate valve. (f) Conservator tank with oil level indicator (g) Silica jel breather (i) First fill of oil upto level including conservator tank with fresh new oil conforming to IS335. (k) Type of connection Delta/Star (1) Type of cooling: Oil and Natural Air. (m) Vector group:DYN 11. (n) Temperature rise over an ambient of 50 °C maximum. (o) Air insulated Cable end box on both side for HT/LT cables of suitable size.
(p) Provision of thermometer with pocket. (q) Provision of oil and winding temperature gauge. (r) Breather with silica gel with oil seal and first fill of silica gel (s) Rating diagram and terminal marking plate (t) Oil temp and winding temp indicator with maximum read pointer (u) Marselling Box Note : (i) All tests shall be carried out at factory as per IS-1180 before despatch of transformer in presence of inspecting officer as detailed by Accepting Officer and test certificate shall be submitted. (ii) Foundation/ civil work as per manufacturer’s instructions shall be provided including weather proof paint on platform without any extra cost to the deptt.
Supplying and fixing smart three phase four wire dual source prepaid energy meters BIS 15884 marked in existing meter board / floor panels with pre payment capacity touch keypad based digital having current range 10-60 Amp 415 Volt accuracy class 1.0 alongwith parallel home display split unit with inbuilt load control switch containing provision for TOD and RTC, inbuilt feature to sense the DG mode through PLSI, dual source registration wrt grid as well as DG supply and dynamic load allocation facility from grid and DG, capable to define for tariff slabs, happy hours and holiday definition complete all as specified and as directed.
Supply, Install, test and commissioning Outdoor type cubical panel board self supporting totally enclosed CPRI certified factory fabricated LT feeder pillar box, made out of 3.0mm thick CRCA sheet steel with projected globe roof for rain water protection, dust and vermin proof, hinged front opening double door shutters with neoprene rubber gasket, powder coated including danger plate, Provn of connection of GI earth strip 32mm x 6mm size - 02 Nos, ventilation louvers, bottom detachable gland plate complete cubicle panel board suitable for 3 phase 4 wire ,415 volts 50 HZ and 50mm x 50mm x 6 mm angle iron base frame, with locking arrangement, including provision of suitable size PCC M-15, type B1 pedestal for mounting of panel board fabrication of enclosure including base channel height outdoor type in and including the following Switch gear and necessary incl control copper cable flexible multi strand FRLS, Busbar supports, SMC finger/conical supports for vertical & horizontal bus bars, Fasteners ,bolts.,nuts incl vertical & horizontal bus bars, inter connection bus bar , Incomer & out going bus bar of 500 Amp rating 3 phase and neutral incl internal wiring and connections from bus bar to switch gear, testing on completion and commissioning complete all as specified and as directed internal wiring and connections from bus bar to switch gear, testing on completion and commissioning complete all as specified and as directed. :-(proposed to install near by the site)
Material and labour for Earthing complete with using galvanised steel earth plate electrode of size 600mm x 600mm x 6 mm thick buried directly underground vertically (earth pit not less than 2.25m deep below normal ground level) , with top edge of the plate at a depth not less than 1.5m below ground level connected with and incl galvanised iron strip 32 x 6 mm as earthing lead including 40 mm dia GI pipe light grade by means of nuts bolts, washers and necessary earth work in any type of soil PCC (1:3:6) type C1 chamber and RCC(1:2:4) type B-1cover with handle and watering pipe 20 mm dia GI medium grade with funnel complete with mesh , refilling with black cotton soil, alternate 5 layers of charcoal (250 Kg) & salt crystal (200Kg )and top two inches layers with Back filling compound (100 Kg), all as specified. Note: (i) Quoted rate deemed to include necessary earth work PCC chamber, 50mm thick RCC cover, reinforced with 8mm dia CTD bars at 100mm C/C on both directions, removal of surplus soil , site clearance etc. (ii) GI earth strip , GI tubing light grade upto 7.5m deemed to be included the rate quoted by the contractor. (iii) Beyond 7.5 M the GI earth strip & GI pipe light grade 40 mm dia shall be measured and paid separately under the respective item of the schedule (iv) Quoted rate include testing after completion from test point and the desired earth resistance shall be not more than 5 ohm .If the desired result is not obtained the earthing will be re done by the contractor at no extra cost.
Material and labour for Earthing complete with using galvanised steel earth plate electrode of size 600mm x 600mm x 6 mm thick buried directly underground vertically (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate at a depth not less than 1.5m below ground level connected with and incl galvanised GI wire 4mm dia including 25 mm dia GI pipe light grade by means of nuts bolts, washers and necessary earth work in any type of soil PCC (1:3:6) type C1 chamber and RCC(1:2:4) type B-1cover with handle and watering pipe 20 mm dia medium grade with funnel complete with mesh , refilling with black cotton soil, alternate 5 layers of charcoal (250 Kg) & salt crystal (200Kg )and top two inches layers with Back filling compound (100 Kg), all as specified. Note: (i) Quoted rate deemed to include necessary earth work PCC chamber, 50mm thick RCC cover, reinforced with 8mm dia CTD bars at 100mm C/C on both directions, reinforcement removal of surplus soil , site clearance etc. (ii) GI earth strip , GI tubing light grade upto 7.5m deemed to be included the rate quoted by the contractor. (iii) Beyond 7.5 M the GI earth strip & GI pipe light grade 15 mm dia shall be measured and paid separately under the respective item of the schedule (iv) Quoted rate include testing after completion from test point and the desired earth resistance shall be not more than 5 ohm .If the desired result is not obtained the earthing will be re done by the contractor at no extra cost.
Taking down serviceable HT cable of size 185 sqmm 3 core and cable cover of any size/ type from site and kept in safe custody for relaying in new route out side of KV complex play ground area, the cost deemed to be included in the quoted rate for excavation, removal of cable and cable cover, cutting old existing cables, disconnecting cable joints and also taking up loop from the under ground carefully and making good the disturbed surfaces in all respect where ever required as per site requirement complete all as specified and as directed.
Supply, laying XLPE insulated, screen, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor of size 185 sqmm 3 core, connecting with proper size Aluminium lugs, glands wherever necessary near ATC LT Panels to Bus bar chamber at ATC all as per site requirement , testing complete all as specified and directed.
Relaying of serviceable LT cable of any size as obtained from site complete all as specified and as directed.
Relaying of serviceable bricks as obtained from site complete all as specified and as directed.
Taking down serviceable LT cable and cable cover of any size/ type from site and kept in safe custody for relaying in new route out side of KV complex play ground area, the cost deemed to be included in the quoted rate for excavation, removal of cable and cable cover, cutting old existing cables, disconnecting cable joints and also taking up loop from the under ground carefully and making good the disturbed surfaces in all respect where ever required as per site requirement complete all as specified and as directed.
Supply, laying XLPE insulated, screen, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor of size 120 sqmm 3.5 core, connecting with proper size Aluminium lugs, glands wherever necessary near ATC LT Panels to Bus bar chamber at ATC all as per site requirement , testing complete all as specified and directed.
Relaying of serviceable HT cable of any size as obtained from site complete all as specified and as directed.
Relaying of serviceable HT cable covers as obtained from site complete all as specified and as directed.
Supply and fix cable jointing kit for HT under ground cable for straight through joint heat shrink type and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 185 sqmm, complete all as specified and as directed.
Supply and fix cable jointing kit for HT end joint heat shrink Indoor type and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 185 sqmm, complete all as specified and as directed.
Supply and fix cable jointing kit for LT under ground cable for cable for straight through heat shrink type and accessories suitable for 3 ½ core XLPE, armoured, Al conductor cable of size 120 sqmm complete all as specified and as directed.
Supply and fix cable jointing kit for LT under ground cable for end joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ core XLPE, armoured, Al conductor cable of size 120 sqmm, Indoor type complete all as specified and as directed.
Supply, fabricate, install and testing outdoor type LT bus bar chamber box of size 800x600x400mm from CPRI certified panel manufacturers including provision of DIN rail for mounting 1 No of MCCB incl S&F MCCB 250 Amp 4 Pole, 415 V, Adjustable type, with breaking capacity 36 KA, hinged door with Allen key locking arrangement made out of 3mm thick CRCA sheet steel powder coated with front and rear opening slanting canopy on roof and mild steel channels base frame angles of 50x50x5mm in and including TPN aluminium bus bar of 250A capacity for looping and branch connection, the bus bar placed on suitable capacity insulators including danger notice plate on both side, neoprene rubber gasket to make it completely dust and vermin proof the same will be fixed in ground with necessary PCC foundation made by (1:2:4) type B1 complete all as specified and directed by Engr-in-charge. Note - (1) The cost deemed to be included in the quoted rate for reconnecting Old existing cables to boxes carefully using a suitable glands and also taking up loop from the under ground and making good in all respect where ever required as per site requirement complete all as specified and as directed.
Material and labour for cutting of bituminous road / floor for laying of U/G cables not exceeding 1.5 meter wide and not exceeding 1.5 meter deep including refilling / with material and , watering well ramming / compacting and making good with PCC 1:3:6, type M-10 100mm thick complete all as specified and directed by Engr-in-charge. Note :- PCC shall be measured separately.
R O PLANT
Supply and fix Reverse Osmosis Plant stainless steel, 240 volts, Full automatic, 60-65% to 95% purity level, of out put capacity of 60 Litres per hour with RO+TDS technology including inlet valve set, spanner for bowl, inlet and reject pipe and all connected items, Auto shut off and start system, overflow protection complete all as specified and as directed.
WATER COOLER
Supply & Installation Voltage Stabilizer for automatic operation single phase natural air cooled indoor type and designed for input variation between 100 Volt to 290 volt with output voltage stabilized at 230 volt with accuracy +/- 2.5% and capacity 2 KVA complete all as specified and as directed. Make: V Guard VE 400 or equivalent in Microtek/Voltamp/Vinitec
LIGHTENING PROTECTION
Supply and fix Epoxy insulator of size 25 mm X 3 mm for fixing of aluminium strip on wall/ roof/ pole etc complete all as specified and as directed.
Material and labour for Earthing complete with using galvanised steel earth plate electrode of size 600mm x 600mm x 6 mm thick buried directly underground vertically (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate at a depth not less than 1.5m below ground level connected with and incl galvanised iron strip 32 x 6 mm including 40 mm dia GI pipe light grade by means of nuts bolts, washers and necessary earth work in any type of soil PCC (1:3:6) type C1 chamber and RCC(1:2:4)type B-1cover and watering pipe 20 mm dia medium grade with funnel complete with mesh , refilling with black cotton soil all as specified. Note: (i) Quoted rate deemed to include necessary earth work PCC chamber, 50mm thick RCC cover, reinforced with 8mm dia CTD bars at 100mm C/C on both directions, reinforcement removal of surplus soil , site clearance etc. (ii) GI earth strip , GI tubing light grade upto 7.5m deemed to be included the rate quoted by the contractor. (iii) Beyond 7.5 M the GI earth strip & GI pipe light grade 40 mm dia shall be measured and paid separately under the respective item of the schedule (iv) Quoted rate include testing after completion from test point and the desired earth resistance shall be not more than 2 ohm .If the desired result is not obtained the earthing will be re done by the contractor at no extra cost.
AIR CONDITIONING:
Supply and fix Air cooled split unit Air Conditioner electric driven single phase of capacity 2.0 TR with copper condenser coil and evaporator coil, green gas R32, mounting stand with all accessories 5 star rated inverter AC all as specified and as directed. Note :- The rate quoted be the tenderer shall inclusive of the following provisions :- (i) UPVC drain pipe not less than 20 mm dia from indoor unit (any floor) to upto ground level/near to drain to be fixed with proper size base plate with clamps complete. (ii) Copper pipe 20mm dia and 15 mm dia with 20SWG thickness refrigerant piping with 19 mm thick closed cell rubber nitrile, Class "O"- arm-flex insulation and including connection and extra length of copper wire and tubing as per site requirement to be included in the qu0ted rate. (iii) GI powder coated brackets 16 SWG of required size : 02 Nos including grouting with suitable size fasteners, bush etc for fixing of outdoor units as per site requirement. (iv) If any extra length of suction and delivery Copper pipes, drainage pipe and connection flexible cable (4 sq mm 4 core) is required at site up to 3 mtr.
Supply and fix plug and socket SPN enclosure with a two pin and earth complete with one MCB SP 32 Amps 'C' curve 10 KA breaking capacity of 240 Volts complete all as specified and directed.
S &F Copper tube with insulation for suction and discharge line combined (same size as for the AC installed ) for connection between indoor and outdoor unit (beyond 3 mtr) complete all as specified and as directed.
S & F 4 core 4 Sq mm multi stranded copper conductor cable for connection between indoor and outdoor unit (beyond 3 mtr) complete all as specified and as directed.
Supply & Installation Voltage Stabilizer for automatic operation single phase natural air cooled indoor type and designed for input variation between 90 Volt to 300 volt with output voltage stabilized at 230 volt with accuracy +/- 2.5% and capacity 5 KVA or 15 Ampere complete all as specified and as directed. Make: V Guard VE 500 or equivalent in Microtek/Voltamp/Vinitec
FIRE FIGHTING:
Material and labour for Earthing complete with using galvanised steel earth plate electrode of size 600mm x 600mm x 6 mm thick buried directly underground vertically (earth pit not less than 2.25m deep below normal ground level) , with top edge of the plate at a depth not less than 1.5m below ground level connected with and incl galvanised iron strip 32 x 6 mm as earthing lead including 40 mm dia GI pipe light grade by means of nuts bolts, washers and necessary earth work in any type of soil PCC (1:3:6) type C1 chamber and RCC(1:2:4) type B-1cover with handle and watering pipe 20 mm dia medium grade with funnel complete with mesh , refilling with black cotton soil, alternate 5 layers of charcoal (250 Kg) & salt crystal (200Kg )and top two inches layers with Back filling compound (100 Kg), all as specified. Note:(i) Quoted rate deemed to include necessary earth work PCC chamber, 50mm thick RCC cover, reinforced with 8mm dia CTD bars at 100mm C/C on both directions, reinforcement removal of surplus soil , site clearance etc. (ii) GI earth strip , GI tubing light grade upto 7.5m deemed to be included the rate quoted by the contractor. (iii) Beyond 7.5 M the GI earth strip & GI pipe light grade 40 mm dia shall be measured and paid separately under the respective item of the schedule (iv) Quoted rate include testing after completion from test point and the desired earth resistance shall be not more than 5 ohm .If the desired result is not obtained the earthing will be re done by the contractor at no extra cost.
Supply and installation of fire brigade connection consisting of 02Nos of 63mm dia instantaneous male coupling with built in check valve, sluice valve and non return value complete all as specified and directed.
M&L for supply and laying control cable of size 12 core x 1.5 sqmm, 1100 V grade, copper conductor, PVC insulated, armoured, and overall sheathed, laid on wall/surface using heavy-duty MS saddles and spacers at regular intervals not exceeding 0.6m, fixed with suitable rawl plugs and screws, including termination at both ends with compression type brass glands and crimping type copper lugs, testing on completion, complete all as specified and directed.
Supply of 12V 7Amp Batteries with rechargeable complete all as specified and directed.
Supply and install Water flow switch complete all as specified and directed.
Supply, laying, and fixing of 2 Core x 1.5 sqmm FRLS copper conductor cable (ISI marked) conforming to IS:1554 Part I, drawn through heavy-duty FRLS ISI-marked PVC conduit of not less than 20 mm dia, complete with all accessories such as bends, junction boxes, inspection boxes, conduit fittings, and concealed in walls/floors/ceilings including cutting, fixing, clamping, making good to the original finish and testing as required complete all as specified and as directed.
Supply and fixing fire instruction board of size 18 inch x 24 inch made from 3mm thick PVC / ACP sheet, duly printed in English and Hindi with clear fire safety instructions titled “IN CASE OF FIRE / IF FIRE OCCURS,” including emergency contact numbers, evacuation procedures, pictograms, and assembly point information. The board shall have photo luminescent text and symbols, be mounted on wall at eye level using brass screws and PVC sleeves, complete all as specified and directed by Engineer-in-Charge.
Supply and fixing of fire safety signage boards made of PVC/UPVC, 12”x6” size (or as directed), marked on both sides using reflective or photo luminescent tape/paint, including wording for fire hydrant, fire extinguisher, fire exit, hose reel, manual call point, etc., and suitable hanging/wall fixing arrangements, complete all as specified and directed.
Supply and fix 6 Kg Fire Extinguisher Dry Chemical Powder (ABC) Type complete all as specified and as directed.
Supply and fix 3 Kg Fire Extinguisher CO2 Type (light weight squeeze grip type) complete all as specified and as directed.
Supply and fix 9 Ltr Fire Extinguisher water stored pressure type complete all as specified and as directed.
Supply and fix 4 Kg Fire Extinguishers clean Agent Type complete all as specified and as directed.
Supply and fix 9 Kg Fire Extinguisher Dry Chemical Powder (ABC) Type complete all as specified and as directed.
Supply and fix 9 Ltr Mechanical Foam Extinguisher (stored pressure type) complete all as specified and as directed.
Supply and fix fire bucket (Dry sand) complete all as specified and as directed.
Supply and fix bucket stand for 02 Nos complete all as specified and as directed.
Supply and fix Gun Metal Gate Valve 80 mm dia complete as all specified and directed
LIGHTNING PROTECTION:
S&F epoxy insulator of suitable size for fixing of aluminium strip on wall/roof/pole etc. complete all as specified and as directed.
Material and labour for Earthing complete with using galvanised steel earth plate electrode of size 600mm x 600mm x 6 mm thick buried directly underground vertically (earth pit not less than 2.25m deep below normal ground level) , with top edge of the plate at a depth not less than 1.5m below ground level connected with and incl galvanised iron strip 32 x 6 mm as earthing lead including 25 mm dia GI pipe light grade by means of nuts bolts, washers and necessary earth work in any type of soil PCC (1:3:6) type C1 chamber and RCC(1:2:4) type B-1cover with handle and watering pipe 20 mm dia medium grade with funnel complete with mesh , refilling with black cotton soil, alternate 5 layers of charcoal (250 Kg) & salt crystal (200Kg )and top two inches layers with Back filling compound (100 Kg), all as specified. Note:(i) Quoted rate deemed to include necessary earth work PCC chamber, RCC cover, reinforcement removal of surplus soil , site clearance etc. (ii) GI earth strip , GI tubing light grade upto 7.5m deemed to be included the rate quoted by the contractor.(iii) Beyond 7.5 M the GI earth strip & GI pipe light grade 15 mm dia shall be measured and paid separately under the respective item of the schedule (iv) Quoted rate include testing after completion from test point and the desired earth resistance shall be not more than 2 ohm .If the desired result is not obtained the earthing will be re done by the contractor at no extra cost.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.75 MB
BOQ_846423.xls
BOQ • 0.39 MB
STRUC-DWG.rar
Additional Documents • 7.09 MB
88757.pdf
Tender Documents • 3.98 MB
ARCH_DWG.rar
Additional Documents • 13.39 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .