EXECUTIVE ENGINEER(E)
Engineering Unit, 3F Admin building, IIT Madras, Chennai-600036
Provision of additional AC facility to common instrumentation facility at NAC-1 and 3 rooms at NAC -2 in IIT Madras
2023_IITM_179255_1
38/2023-24/ELDB
Open Tender
Electrical Works
Item Rate
60 days
IIT MADRAS
All required documents as specified in the Tender
2 documents required · 2 mandatory
₹0
₹36,140
17 Jan 2024
26 Dec 2023
10 Jan 2024
26 Dec 2023
9 Jan 2024
26 Dec 2023
26 Dec 2023 - 27 Dec 2023
Amount
AIR CONDITIONERS
Supply installation Testing and Commissioning of 2.0 TR Hiwall split units with R-410 A refrigerant (both Indoor & outdoor) with hermatically sealed rotary/scroll type compressor, copper heat exchangers, 3 star rating & sound level not more than 47 db(A) for indoor and 54 db(A) for outdoor unit.
Supply and laying of Refrigerant Copper tubing with foam insulation suitable for 2.0TR Hiwall split ACs. The charges shall inclusive of copper control cabling and power cabling required for indoor/outdoor units.
Supply and laying of 32 mm dia PVC water line drain pipe(4 kg/sq.cm) with nitilre rubber insulation on wall
Supply and fixing of Mounting Frame for outdoor units.
DOUBLE SKIN FAN COIL UNITS - DECORATIVE TYPE CEILING SUSPENDED -INSIDE CONDITIONED SPACE
SITC of double skin chilled water Fan Coil Unit. It is proposed to install these units ceiling suspended inside the conditioned area without false ceiling. Hence, aesthetics of the unit is of parmount importance. The unit shall be constructed out of sandwiched panels minimum 43 mm thick RPUF insulation, with thermal break profile.The outer sheet of the panel shall be 0.8mm thick and the inner sheet shall be 0.63mm thick. The unit shall be provided with a Aluminium powdercoated grille for both supply air and return air. RA Grille on the rear side. SA Grille shall be provided in the front side. (please refer enclosed sketch). The units shall be with blow through design, units complete with pre-filters, fan section with DIDW forward curved fan directly coupled to a single phase motor operable in 3 speeds, 3 row deep cooling coil & extended drain tray. Coil section shall be with suitable air vent and drain points.The coil section and drain tray sections shall be provided with sandwiched insulation.The unit shall be sized to accommodate the isolation valves as well as the control valve. The FCU shall be factory fitted with isolation valves (ball valve with strainer at inlet and without strainer at outlet), 2 Way Motorised Valve(On/Off type) motorised valve with spring return (Valve to close when the power supply is cut off), necessary interconnections etc., Price to include for Room Thermostat compatable for BMS integration (Bacnet over MSTP) with On/Off, Fan Speed and Temperature Control with a digital display & upto 15Rmt of interconnecting wiring between FCU and Thermostat in GI conduits. Price also to include upto 3Rmt of copper flexible multicore cable with plugtop for power.
2.0TR, 800 CFM
SITC of Pre Insulated Chilled water piping inside buildings in welded construction with MS ERW pipes with factory made GI spiral pipe jacketed PUF insulation complete with all fittings, flanges, pressure testing as per specification. Pipes 150mm dia and below shall be C class as per IS1239.200 mm and above shall be as per IS3589 with wall thicness as specified. Cost to include necessary supports with PUF saddles.
40mm dia NB - jacket dia min 140mm
32mm dia NB - jacket dia min 125mm
25mm dia NB - jacket dia min 125mm
COPPER CHILLED WATER PIPING
SITC of Copper Soft / Hard drawn piping for smaller chilled water units (CSU, FCU, Hiwalls) with all fitting and insulated with class "O" tubular closed cell nitrile rubber 25mm thick insulation with factory made glass cloth backing. Thickness of the copper pipe shall be minimum 22G. Price to include necessary flare nuts, adaptors etc., Copper pipe routing shall be as per the attached tender layouts.
19.1mm dia
RECTANGULAR DUCT
Supply, Fabrication, Erection, testing and Commissioning of Factory fabricated rectangular ducts(boxed up in factory) of approved makes using GI Sheets. The price shall include TDF flanges, turning vanes, supports Gripple supports shall be used. Cost includes sealant, neoprene gasket, hangers, access door etc. Only flanged joints are acceptable for ducts above 150 mm size. All transverse joints shall be sealed with silicon sealant. The joints shall be with least leak. The duct gauge construction shall be for 2" static as per SMACNA 3rd edition. The quoted ratre shall be inclusive of loading, transportation, unloding, shifting & conduciting the pressure test as per the techical spcification & drawing details.
20 G - GSS (1.00mm)
Electrical
Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 amps "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in recessed medium class PVC conduit as required. The charges inclusive of chase cutting of wall using cutting machine including plastering with necessary cement, sand & bricks making the wall surface in good condition
2 x4.0 sq.mm + 1 x 4.0sq.mm earth wire
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Supply and Installation of the following Cable Trays / Accessories Prefabricated hot dip galvanized 1.6mm thick sheet perforated / Ladder type cable tray including all necessary curved bends-tees-reducers, coupler plates, fasteners etc.,for the following sizes. Inclusive necessary fixing arrangement etc.
200 mm x 100mm Perforated type cable tray along with top cover
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .