| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.7 LAccepted-AOC | L1 | Accepted-AOC BEING LOWEST BIDDER | |
| 2 | L2₹28.2 L+₹3.4 L (13.8%)Rejected-Finance 1257 SCHEME NO 5 NEAR HB COLLEGE VIJAY NAGAR JABALPUR MP PIN 482002 | JABALPUR | MADHYA PRADESH | 482002 | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 3 | L3₹28.8 L+₹4.0 L (16.4%)Rejected-Finance 1476 SARASWATI COLONY CHERITAL JABALPUR | JABALPUR | MADHYA PRADESH | 482001 | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 4 | Rejected-Technical PLOT NO 81 SHANTAJI COLONY JANKI NAGAR JABALPUR MP PIN 482002 | JABALPUR | MADHYA PRADESH | 482002 | - | Rejected-Technical Being not enlisted in category b(ii). |
Tender Value
Refer Docs
EMD Value
₹46,500
Closing Date
1 Dec 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE Jabalpur
HQ Commander Works Engineer, Supply Marg, P B No. 54, Jabalpur
PROVISION OF 600 KVA POWER SUPPLY AND WATER SUPPLY AT BTC FOR NFS NODE UNDER GE WEST JABALPUR
2021_MES_472016_2
81898/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
GE (W) Jabalpur
As per NIT
7 documents required · 7 mandatory
₹500
GE (W) Jabalpur
₹46,500
Yes
25 Jan 2022
2 Nov 2021
3 Dec 2021
2 Nov 2021
1 Dec 2021
17 Nov 2021
2 Nov 2021 - 16 Nov 2021
60 days
Amount
Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, for laying of pipe, cable etc or n. exc.10 Sqm on plan and n. exc. 1.5m in depth for shafts, cesspits, manholes, pier holes, etc and getting out in any type of soil complete all as specified and directed.
Returning, filling in excavated approved soil, including spreading, levelling, watering and well ramming in layers not exceeding 25cm each complete all as specified and directed.
Removing excavated soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Supply and spreading clean and dry fine sand free from sharp materials (unwashed) laying in trenches around the cable for cushioning in trenches, laid to a uniform thickness of 23cm (15cm under the cable & 8cm over the cable) and gently punned down to 18cm thickness complete all as specified and as directed.
Supply and laying un-reinforced precast concrete cable covers (ISI marked), Class HVP, type 2 with peak, size 450 mm x 180 mm x 40 mm complete all as specified and as directed.
Supply and laying or fixing or passing in trenches/ on pole/ through pipes, 11000 volts (E) grade, XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor of cross sectional area 95 sqmm, 3 core conforming to IS 7098/(PART-II) 1985 with latest amendments and testing on completion complete all as directed. Make:- Havells or Finolex or Gloster or Plaza or Universal as approved by GE. Note:- Excavation, earth work, sand cushioning and cable protection shall be measured and paid separately under respective items of BOQ.
M&L for preparation of new surfaces of iron/ steel of any description over 10cm width or girth and applying two coat of synthetic enamel paint of colour as approved by GE over and including a coat of red-oxide primer complete all as specified & directed.
M&L for preparation of new surfaces of iron/ steel of any description not exceeding 10cm width or girth and applying two coat of synthetic enamel paint of colour as approved by GE over and including a coat of red-oxide primer complete all as specified & directed.
Supply only mild steel TMT bars 10mm and above dia as in line wire including cranking, bending, hooking ends complete all as specified and directed.
S&F chain link fencing as per IS 2721-2003 of mesh size of 50x50mm of 4mm dia mild steel galvanised wire having minimum tensile strength 500N/ Sqmm including line wires (10mm or above dia MS TMT bars as line wire or stiffners shall be used as directed at site), binding wire fixed to any type of standards, rails, straining bolts, etc complete all as specified & directed. Notes:- (i) 10mm and above dia MS TMT bars used as line wire or stiffners shall be paid separately here-in-after as "supply only" in Kg. (ii) Binding wire rates shall deemed to be included in quoted rates for the item. (iii) The galvanizing of wire shall be of minimum 100 GMS as per IS-4826. Make:- TATA WIRON or SAIL or RINL or JINDAL as approved by GE.
M&L for PCC (1:3:6) type C-2 using 40 mm graded stone aggregate as in foundation, filling, mass concrete and sub base of floors, embedded of posts, path/ paving etc complete all as specified & directed.
Supply and fix mild steel screw bolts (machine made) with hexagonal or square head at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, not exceeding 5cm long and dia of shank 11 to 15mm complete all as specified & directed.
M&L for mild steel work Fe-410-W (Gde-E-250) quality -A conforming to IS-2062-2006 as in nosing to steps including embeding in concrete and screwing etc, wind ties for roof including securing bolts, posts & struts in fencing including cutting top to shape as directed, drilling holes, notching for wire, etc; flat iron fillets (for securing wire mesh etc) including all necessary drilling, bolting or riveting etc complete all as specified and directed. Note:- Embedded portion of fencing post shall be painted with two coats of tar coal and provision of the same shall be deemed to be included in quoted rate.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70sqmm to 120sqmm and testing on completion complete all as directed. Make:- M SEAL or RAYCHEM or DENSON or CAB SEAL as approved by GE.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70sqmm to 120sqmm and testing on completion complete all as directed. Make:- M SEAL or RAYCHEM or DENSON or CAB SEAL as approved by GE.
Excavation in post holes or similar holes, each not exceeding 0.50Cum, getting out in soft/ loose soil, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, watering, and removing surplus soil to a distance not exceeding 50 M and making good surface complete all as specified and directed.
Supply and fixing 11.0M long steel tubular swaged pole type 410 SP-55 complete with cast iron base plate, finial taper plug, nuts, bolts, screws and washers all as specified including two coats of painting with black bituminous paint upto embedded portion before fixing of poles and two coats of painting with aluminium paint over a coat of primer on exposed surface after fixing complete all as shown in TD drawing No. CEJZ/TD/824/91, Sht No1/2 dt 16.04.91 including following items/ works complete:- (a) Excavation in post holes in any types of soil, returning fillingin, well ramming and disposal of surplus soil to a distance not exceeding 50M from the starting points complete all as specified and directed. (b) PCC (1:3:6) type C-2 using 40mm graded stone aggregate as in foundation up to ground level complete all as specified and directed. (c) PCC (1:2:4) type B-1 using 20mm graded stone aggregate as in copings/ collars, bed plates, plinth block etc including weathering, slightly rounded or chamfered angles and throating as directed including necessary form work complete all as specified and directed. (d) M&L for writing letters or figures (Block, Roman, Italic or Indian) with and including thick enamel paint of approved shade not exc 5cm in height complete all as specified and directed. Make:- NATIONAL TUBING CO. or JINDAL or BHARAT ISPAT UDYOG or JAI BHARAT POLES as approved by GE.
M&L for earthing complete with galvansided steel earth plate electrode 600x600x6.0mm thick directly burried in the ground (earth pit not less than 2.25M deep below ground level) with top edge of earth plate not less than 1.50M deep below normal ground level, connected to galvanised iron strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, 40mm bore GI pipe medium grade including necessary fittings for protection of earthing strip, watering pipe 20mm bore GI medium grade, concrete chamber in PCC (1:4:8) type D-2 using 40 mm grade aggregate, coping shall be in PCC (1:3:6) type C-1 using 20 mm grade aggregate and internal surfaces of concrete chamber shall be given 12mm thick plaster in CM (1:4), funnel with wire gauge of 22 gauge (0.63 mm) 8 mesh per linear incl 50mm thick cover of RCC (1:2:4) type B-1 using 20mm grade stone aggregate reinforced with 8mm MS deformed bar @ 75 mm C/C both ways, char coal dust and common salt all as shown in electrical plate No. 3 of SSR Part-I (2009) including all necessary excavation & earth work and removal of surplus soil to a distance n. exc 50M and providing connection points with MS/ GI bolts & washers as required and connection from earth test point to earth electrode with same GI earth strip alongwith protection pipe and testing on completion complete all as specified and directed. Note:- GI strip and protection pipe from earth electrode to test point max upto 7.50M shall be deemed to be included in the unit rates as quoted by the contractor.
Supply and fix new pin type porcelain, vitreous, white/ brown/ green insulator 150mm high and 150mm dia including one galvanised mils steel spindle, two galvanised iron washers and one galvanised iron nut, suitable for HT 11000 volts grade complete all as specified and directed. Make : JAYSHREE or JAIPURIA or WS insulator as approved by GE
Supply and installation of advanced encapsulated compound based CPRI tested maintenance free, pipe-in-pipe technology upgraded (Zinc & Alloy coated), (80-100) microns Zinc Coating with pure Zinc (99.90%) & (200-250) Alloy Coating, dia of outer and inner pipe should be 76.2mm & 41.9mm respectively and 3.0M length of each, Zinc Coating with additional special alloy coating on the topside (300mm) for additional protection of the terminal, annuar space between the pipes should be COMPACTED FILL (CF) with & including Crystalline Conductive Compound by using machine, machine pressed COMPACTED FILL (CF) mixture in the pipes should not disintegrate or colloapse when outer pipe corrodes. The inner pipe should be extended with terminals for connectivity, digging the pits and refilling the same with & including Electrodite/ Conductolite back fill compound (Ground Enhancer) and back fill compound (BFC) should be eco friendly & should not contain environmentally hazardous material/ metal and also having RoHS certification from NABL accredited lab. The earth pit should be provided with a FRP earth pit cover for protection and safe guard of terminals. In areas, where soil condition is bad, good earth is to be arranged to fill the excavated pits by mixing the same with back fill compound (BFC) 2 to 4 bags (as per soil conditions) extra per pit/ unit. Since earth electrode of the earthing system should be in direct contact with the ground, hence, materials which to be used in the earthing, should have good electrical conductivity & anti corrosion property in wide range of soil conditions and complete earthing system conforming to IS : 3034 and connected with 32x6 mm GI strip up to testing point and making the earth pit of PCC as per sample as required at site and testing on completion complete all as specified and directed. Make:- INDELAG or ASHLOK or MACMET or HP Earth as approved by GE. Notes:- (i) Excavation and all earth work shall be deemed to be included in the unit rates as quoted by the contractor. (ii) Back fill compound (BFC) up to 2 bags (each of 25 Kg) shall be deemed to be included in the unit rates as quoted by the contractor. (iii) The earth resistance of each pipe earthing must be within 1.0 (one) ohm.
Supply and fix new disc type insulator, porcelain, vitreous white/ brown/ green 145mm high and 255mm dia ball & socket type single disc assembly for tension with GI tension clamps for conductors for working pressure of 11000 volts complete all as specified and directed. Make : JAYSHREE or JAIPURIA or WS insulator as approved by GE
Drilling (Horizontally) to existing road (maximum 10M wide) suitable for passing GI tubing of dia upto 80mm/ 100mm as required at site complete all as specified and directed. Note:- All necessary T&P required at site for drilling shall be arranged by contractor at his own cost and quoted rate shall be deemed to be included for all these provisions and nothing extra shall be paid on this account.
Supplying and fixing/ laying of 80mm bore dia GI pipe light grade in trenches/ under roads/ along pole/ wall including all fittings (ISI marked) as required for cable protection etc complete all as specified and directed.
Supplying and fixing/ laying of 50mm bore dia GI pipe light grade in trenches/ under roads/ along pole/ wall including all fittings (ISI marked) as required for earth strip protection etc complete all as specified and directed.
Supply & fix 50mm bore medium grade galvanised steel water tubes with all fittings such as bends, elbows, tees, short pieces, union etc and fixed complete to walls and ceilings or laid in floors/ trenches complete all as specified & directed. Note:- Excavation and earth work if required, same shall be measured and separately under respective items of BOQ.
Supply and fix gun-metal, globe or gate valves, ISI marked, class 150 with iron wheel head, screwed both ends for iron pipe and fixed, for 50mm bore dia of pipe complete all as specified. Make:- ZOLOTO or LEADER or KIRLOSKAR or UPADHYAY or AUDCO or IVC or L&T as approved by AGE(I).
M&L for cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminum paint complete all as specified and dircted.
M&L for anti climbing device; spikes type fabricated out of MS bars (round, square and flat) including bolts, buts, washers and welding in two halves made to shape to suite the cross section of the pole complete all as specified and dircted.
Supply and fixing of new switch air break gang operated triple pole mechanically operated horizontal type out door with all other fittings/ accessories mounted on & including porcelain insulators and steel frame with operating mechanism worked from ground level with & including operating rod of 25mm dia GI pipe medium grade (ISI marked) with MS handle with locking arrangement, for current rating up to 200 Amp 11000 Volts including dropout fuse set 12 insulators to suit gang operated triple pole 11 KV switch, connecting, commissioning and testing on completion complete all as specified and directed. Make:- JAIPURIA or PACTIL or BHEL or MEI as approved by GE.
M&L for earth continuity conductor or main earthing lead with 32x6mm galvanised iron strips, fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc including necessary welding/ jointing as required complete all as specified and directed. Note:- Excavation and earth work if required, same shall be measured and separately under respective items of BOQ.
M&L for earth continuity conductor or main earthing lead with 32x6mm copper strips, fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc including necessary welding/ jointing as required complete all as specified and directed. Note:- Excavation and earth work if required, same shall be measured and separately under respective items of BOQ.
Supply, installation, commissioning and testing of 12 kV SF6 Ring Main Unit, compact, out door type, 630 Amps, rated capacity 25 kA for 1 sec having 2 vacuum circuit breaker (VCB) insulated in SF6, one load break switch (LBS) insulated in SF6 and one Bus PT panel extensible to right side RMU/ Outdoor, motorised having metering panel and copper bus bar of suitable ampere ratings complete with and including the followings:- Make of RMU:- Schneider or ABB or L&T as approved by GE. Notes: (i) Brief description of this item is "12 kV, SF6 Ring Main Unit complete with 2 Vacuum Circuit Breaker + 1 LBS+ 1 Bus PT Panel (Right side extensible / OUTDOOR). FBX-RE/12-21/ M+CT2T2 /OUTDOOR - MOTORIZED". (ii) As per manufacturers design, cost of making of platform shall be deemed to be included in unit quoted rates. (iii) All necessary arrangements for performance testing of RMU shall be made by contractor without any extra cost to government.
(A) HT COMPARTMENT: VACUUME CIRCUIT BREAKER - Each module (Vaccume circuit breaker) enclosed in SF6 -02 Nos. (a) The function unit shall be consist a three position switch. The three position switch shall fulfil the operation of the disconnector function and the earthing function. The circuit breaker unit T2 shall equped with an over current time release for the protection of distribution transformer. (b) Vacuume circuit breaker shall be of 12kV, 630 Amps, 25 kA for one sec enclosed in SF6. (c) Spring assisted closing with stored energy tripping mechanism for T2-motorised operation with integrated earthing switch. (d ) Having auxiliary contacts on load break switch 1 NO+2 NC & auxiliary contacts on earth switch 1 NO+1 NC - 01 No. (e) Self powered electronic numerical protection relay providing 3 over current & 1 earth fault protection of make Schneider - DPX Relay or make C&S - CSDPR-V2 or equivalent of other make as approved by GE - 01 No. (f) Tape wounded protection CT shall be 100/5, 10P5, 2.5VA - 03 Nos. (g) Tape wounded metering CT shall be 100/5, Class-1.0, 2.5 VA - 03 Nos. (h) Shunt trip Coil - 24 V DC - 01 No. (j) Capacitive voltage indication fixed type (LED display) - 01 No. (k) On/ Off/ TRIP mechanical indication on the front mimic of the panel-01 Set. (l) Cable box for termination of XLPE cable of size 3 core 95 sqmm to 120 sqmm aluminium conductor- 01 No. (m) Cable cover standard - 01 No. (n) Emergency trip push button- 01 No. (o) Set of 12 kV cable termination boots - 1 Set (p) Ammeter of suitable capacity/ class -01 No. (q) Rated frequency - 50/60 Hz
(r ) Rated Power frequency withstand voltage directly earthed -28 kV (s) Level of insulation for the SF6, rated lightening impulse withstand voltage - 75 kV (t) Level of insulation for the SF6, rated power frequency withstand voltage - 28 kV (u) Level of insulation of the sectionalized distance for the cable test energized busbar, maximum AC feeder test voltage - 18 kV (v) Rated current busbar C-R-RE functions - 630 Amps (w) Rated current busbar SB functions - 630 Amps (x) Rated current outgoing feeder- 630 Amps (y) Rated short time current, main electrical circuit for 1 Sec - 25kA (z) Rated short time current, earthing circuit for 1 Sec - 25kA (aa) Rated network load and closed loop breaking current - 630 Amps (ab) Rated no load cable breaking current -160 Amps (ac) Rated breaking current under earth fault conditions - 630 Amps (ad) Rated no-load cable breaking current under earth fault conditions - 277 Amps (B) HT COMPARTMENT: LOAD BREAK SWITCH- C, 12 kV, 25 kA, 630 Amps - EACH MODULE (LBS) enclosed in SF6 -01 No. (a) The switching unit shall be so designed as a three position switch. The three position switch combines the functions of switch disconnector and earthing switch. The switch disconnector as well as the earthing switch shall be equipped with a separate drive unit. (b) Cable switch 11 kV, 630 A, 25 kA for 1 sec - 01 No. (c ) Spring assisted mechanisim for C-manual operation with integrated earthing switch - 01 No. (d) Cable bushing 630 Amps, Standard C-bushings - 01 No.
(e) Aux switch for load break (ON & OFF) - 01 No. (f) Cable Cover standard - 01 No. (g) Capacitive voltage indication fixed type (LED display) - 01 No. (h) On/ Off/ EARTH indication on the front mimic of the panel - 01 Set. (j) Cable box for termination of XLPE cable of size 3 core 95 sqmm to 120 sqmm aluminium conductor- 01 No. (k) Operation counter - 01 No. (l) Cable boot suitable for 11 kV - 01 Set, cable entry shall be provided from front bottom (m) Rated frequency - 50/60 Hz (n ) Rated power frequency withstand voltage directly earthed -28 kV (o) Level of insulation for the SF6, rated lightening impulse withstand voltage - 75 kV (p) Level of insulation for the SF6, rated power frequency withstand voltage - 28 kV (q) Level of insulation of the sectionalized distance for the cable test energized busbar, maximum AC feeder test voltage - 18 kV (r) Rated current busbar C-R-RE functions - 630 Amps (s) Rated current busbar SB functions - 630 Amps (t) Rated current outgoing feeder- 630 Amps (u) Rated short time current, main electrical circuit for 1 sec - 25kA (v) Rated short time current, earthing circuit for 1 sec - 25kA (w) Rated network load and closed loop breaking current - 630 Amps (x) Rated no load cable breaking current - 160 Amps (y) Rated breaking current current under earth fault conditions - 630 Amps (z) Rated no-load cable breaking current under earth fault conditions - 277 Amps
(C) BUS METERING PANEL (a) 03 Single phase PT 11 kV/ RT3/ 110V/RT3, 100 VA, class -1.0 (b) 01 Space heater (c ) RYB indication - one set (d) 01 No. Voltmeter (e) Microprocessor based three phase electronic tamper proof HT energy meter with optical communication port, accuracy class 0.5 rating 3 X 110 V, 1/5 A conforming to IS : 13779. (f) 24 V DC battery and battery charger - 01 Set
(D) Additional equipment to be mounted on each RMUs (a) Manometer - 01 No. (b) Operating Handle - 01 No. (c) Cable clamping provision (standard) - 01 Set (d) Cable testing Plug and Stud - 01 set (e) O&M Manual (f) I&C Manual
(E) The RUM shall also capable for the following : The RMU shall be gas insulated metal enclosed. The high grade steel gas tight tank shall inculde switch devices or circuit breaker, internal copper bus bar, bushings for cable connections, pressure relief device, copper earth bus bar. The drive cabinet shall contains a user friendly control panel with a mimic diagram, In this diagram the drive socket and position indicators for all switch devices are clearly arranged. there is an instrument compartment on top of the drive cabinet and it shall contain short circuit indicators for cable feeders, capacitive voltage detection system, standard Manometer. The auxiliary equipment like trip coils or aux contacts shall be wired to central termination blocks in each feeder . The switching devices shall have separate drive system, which are operated with non interchangable plug-in levers. A complete interrogator interlocking system reliably prevents control errors and ensures high operation convenience. The RMU shall compiled with stndarads IEC 62271-200, IEC 62271-200, IEC 62271-100, pressure of SF 6 gas shall be 1.3 bars at 20 deg C.
Supply, fixing and stretching of new aluminum conductor, steel reinforced on LT poles including copper binding wires or aluminium tape as required at site complete all as specified and directed.
M&L for new lightning arrestor Metal Oxide type complete with all fittings, transmision/ distribution class 10 KA, current rating 12 kA suitable for 11 KV system, discharge capacity 65 kilo amps and mounting on poles including all necessary bolts, nuts and washers and making electric connection and testing on completion complete all as specified and directed. Make:- SCHNENIDER or BHEL or GE POWER or W/S INSULATORS or SOUTHERN INSULATORS or OBLUM as approved by GE.
Supply and fix test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm, drilled screwed including 3 Nos, 8mm dia, 25mm long hexagonal head screws with and including 2mm thick CRCA sheet box of suitable size to enclose the test point in it and fixed on poles with 25 x 3mm flat iron clamps of suitable size & all necessary nuts, bolts and washers complete all as specified and directed.
Supply and fix cable route indicater comprising of CI riser of size 100mm dia embossed as HT power cable fixed to MS angle iron size 50x 50x 6mm duly embedded in PCC block of size 300x 300x 450mm with & including PCC (1:2:4) type B1 using 20mm graded stone aggregate and two coats of painting with aluminium paint over a coat of red oxide primer and all necessary excavation & earth work complete all as specified and directed.
M&L for 40mm graded broken stone aggregate for spreading/ loose filling in the substation or other places where directed including stacking materials in regular heap/ stack for measurement complete all as specified and directed. Note:- Stack measurements after considering engineering practice for voids shall be recorded in MB for payment of this item.
Cutting of existing CI pipes of 200mm bore and reducing to required length in position for insertion of new tees, collar, branches etc including all necessary excavation & earth work and bailing out of water if required complete all as specified and directed. Note:- Cost of CI specials (fittings), run lead joint etc as required shall be deemed to be included in the unit rates as quoted by the contractor.
Sachdeva Enterprises
RAINA SALES AND SERVICES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .