Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.2 LAccepted-AOC RZ 1 7 167 GALI NO 6 DURGA PARK NASIRPUR SOUTH WEST DELHI DELHI 110045 | SOUTH WEST | DELHI | 110045 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹31.8 L+₹3.9 L (13.9%)Rejected-Finance | L2 | Rejected-Finance Being L2 | |
| 3 | L3₹33.8 L+₹5.9 L (21.1%)Rejected-Finance | L3 | Rejected-Finance Being L3 |
Tender Value
₹35.5 L
EMD Value
₹71,000
Closing Date
7 Feb 2023, 6:00 pmClosed
Col Jigar Trivedi, SM
HQ CWE (AF) Gurgaon, Old Palam Road, Delhi Cantt-10
REPAIR / REPLACEMENT OF HT /LT UG CABLES AND ELECTRICALS APPLIANCES AT SUB STN, CONTROL SWITCH GEAR, EARTHING, SECURITY LIGHT AND CONNECTED ITEMS AT AF STN RAJOKRI UNDER GE (AF) GURGAON
2023_MES_574241_1
CWE/GGN/GT-31/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AF STN Rajokri
As per NIT
8 documents required · 8 mandatory
₹500
GE AF Gurgaon
₹71,000
22 Mar 2023
11 Jan 2023
15 Feb 2023
11 Jan 2023
7 Feb 2023
25 Jan 2023
11 Jan 2023 - 24 Jan 2023
Amount
Taking down Air termination, single pointed, copper rod 12mm dia and 300mm long all as specified and as directed .
Supply and fixing Air termination, single pointed, copper rod 12mm dia and 300mm long all as specified and as directed
Taking down copper strip 20 x 3.15 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground all as specified and as directed.
Supply and fixing Copper strip 20 x 3.15 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground all as specified and as directed.
Supply and fixing test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled, screwed including 3 nos. 8mm dia 25mm long hex. head screw & brezing all joints complet all as specified & directed
Taking down test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 Nos. 8mm dia 25mm long hex. head screw all as specified and as directed.
M & L for Earthing complete with Copper earth plate electrode 60cmx60cmx3.00mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including using Copper strip 20×3mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel, earth plate surrounded by packed layer of char coal dust and common salt, 15cm thick all around bottom and top and watering pipe 20mm bore of GI medium grade with funnel, wire mesh and 40 mm dia GI protection pipe light grade all as shown in electrical plate No 3 of SSR Part-I and connected to earthing test point, main switch board and testing on completion including excavation, earth work concrete pit with 80mm thick RCC cover in RCC 1:2:4 type B-1 duly reinforced with MS bars 8mm dia @ 150C/C both ways and pit chamber in PCC 1:2:4 type B-1 with 2 Nos suitable lifting handles of 12mm MS bar complete all as specified. Note : Copper strip 20x3mm upto 7.5 mtrs to be included in the quoted rate.
Supply and installation in replecement of Hot dipped Octagonal galvanized iron pole 8 mtr height, with necessary Foundation RCC 1:1:5:3 with 8Nos.16 mm dia tor bar as main bars and 8mm dia.Tor bars strips@190mm c/c as this reinforcement shall confirm to IS : 1786 latest edition.The foundation shall extend above surroundings ground/drive way level for 200 mm and have DWC 63 mm dia,PVC sleeve cast foundation for cable entry,Excavation,RCC and reinforcement etc as per manufacturer recommendation and the cost of necessary foundation , steel bars , strip as per Manufacturer instructions .
Excavation in trenches not exceeding 1.5 m wide and and not exceeding 1.5 m depth in loose/soft soil and getting out soil all as specified and directed.
Returning, filling in, with excavated soil including spreading, levelling, watering and well ramming in layers not exceeding 25 cm complete all as specified and directed.
Removal of surplus soil to distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete as specified and directed.
M&L for boring/auguring suitable hole & insertion of pipe not less than 300 mm below existing PCC/road/hard standing complete all directed. Notes :- Cost of equipment, tools & plants & material required for boring shall be deemed to be included in the rates quoted.
Supply and filling sand in trenches including spreading for cushioning of LT UG cable complete all as specified and as dirceted. Note : Punned down thickness shall be measured and paid .
Supply and laying burnt clay fly ash building bricks for protection of LT cable cover complete all as specified and directed.
Taking down the existing cables from trenches of size 3.5/4 core, 25 Sqmm to 120 sqmm 1100 Volt grade complete all as specified and directed.
Supply, laying, jointing and testing XLPE LT Cable insulated, PVC outer sheathed, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 4.0 core x 25Sqmm and laid in trenches/ducts/pipe or on poles complete all as specified and directed.
Supply, laying, jointing and testing XLPE LT Cable insulated, PVC outer sheathed, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 2.0 core x 25Sqmm and laid in trenches/ducts/pipe or on poles complete all as specified and directed.
Supply, laying, jointing and testing XLPE LT Cable insulated, PVC outer sheathed, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 4core x16 Sqmm and laid in trenches/ducts/pipe or on poles complete all as specified and directed.
Supply, laying, jointing and testing XLPE LT insulated, PVC outer sheathed, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 3.5core x 35 Sqmm and laid in trenches/ducts/pipe or on poles complete all as specified and directed.
Supply, laying, jointing and testing XLPE LT insulated, PVC outer sheathed, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 3.5core x 50Sqmm and laid in trenches/ducts/pipe or on poles complete all as specified and directed.
Supply, laying, jointing and testing XLPE LT insulated, PVC outer sheathed, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 3.5core x 70Sqmm and laid in trenches/ducts/pipe or on poles complete all as specified and directed.
Supply, laying, jointing and testing XLPE LT insulated, PVC outer sheathed, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 3.5core x 95Sqmm and laid in trenches/ducts/pipe or on poles complete all as specified and directed.
Supply, laying, jointing and testing XLPE LT insulated, PVC outer sheathed, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 3.5core x 120 Sqmm and laid in trenches/ducts/pipe or on poles complete all as specified and directed.
Taking down the existing cables from trenches of 95 sqmm 11000 Volt grade (HT) complete all as specified and directed.
Supplying and laying in repair XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electrical power cable ( heavy duty ) with aluminum conductor, 11000 volts grade cross sectional area 95 Sqmm x 3 core complete all as specified and directed
M&L for repair of transformer, disconnecting electrically and mechanically indoor/outdoor transformers step down 11000V/440V from substation or outdoor type plate form upto 400 KVA capacity, for detecting of leakage and rectification incl draining of transformer oil and refilling complete all as specified and directed.
(a) Transformer 400 KVA
(b) Transformer 250 KVA
(c) Transformer 200 KVA
(d) Transformer 160/100/75 KVA
M&L for ON load Centrifuging and dehydration including filteration and cleaning of transformer/servo voltage stabilizer oil by dehydration machine of 11/0.433 KV transformer installed at various site on plinth/4/6 pole structure of any capacity and topping up deficient transformer oil including testing of samples before and after dehydration and filteration complete all as specified and directed. Note :- Deficient quantity of Transformer oil required for top up shall be measured and paid separately.
Supply only transformer oil of approved quality as per IS having dielectric strength of 45-60 KV in 2.5mm gap for filling in transformer or topping up as required and directed
Supplying and fixing in replacement, Porcelain transformer bushing on LT (440 Volt) side, including brass stems conical bush and gasket after disconnecting electrically and mechanically for indoor/outdoor transformer of capacity upto 400 KVA and re-connecting electrically and mechanically, testing complete all as specified and directed. Note.The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transforer oil, opening of top cover by unscrewing nut, bolts washers and provision of pad type bus bar almuminium of approppiate size /capacities of transformers with nut bolt & washers.
Supplying and fixing in replacement, Porcelain transformer bushing on HT (11 KV) side, including brass stems conical bush and gasket after disconnecting electrically and mechanically for indoor/outdoor transformer of capacity upto 400 KVA and connecting electrically and mechanically, testing complete all as specified and directed. Note.The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transforer oil, opening of top cover by unscrewing nut, bolts washers and connections.
Supplying and fixing in replacement, silica gel breather assembly including vent pipe and silica gel for indoor/outdoor transformers, capacity upto 400 KVA complete all as specified and directed.
Material & Labour for painting of transformer installed on plinth/4/6 pole structures at various site of capacity 100 to 400 KVA with existing colour, with spraying machine, after cleaning, preparation of outer surface of transformer, including writing of SM No, MES and capacity of transformer complete all as specified and directed.
M&L for repair and maintenance of servo controlled/AC voltage stabilizer upto 450 KVA capacity 3 phase 415 volts, disconnecting from electric mains , by unscrewing the nuts bolts etc repair/maintenence by draining out the voltage stabilizer oil through the drain plug , for finding out fault and rectifying minor repairs and testing complete all as specified and as directed by Engineer -in - charge. respective items of BOQ.
(a) Supply in replacement of Electronic sensing Control card (PCB). Suitable for Existing Make - Volina & Other ISI marked.
(b) Supply in replacement of PVC Connector 12 pin as per existing Make - Volina
(c) Supply in replacement of Dimmer varic state unit 150 Amps for 250 KVA stablizer suitable for Existing Make.
(d) Supply only trigger (control) transformer with primary voltage 230 Volte and secondary voltage any desired voltage between 18 volt 500 mA suit the control cercuit of the stabilizer as per sample.
M&L for lifting of unserviceable servo voltage stabilizer of cap upto 450 KVA by opening of top cover and other items for checking of faults & rewinding of single phase dimmer unit one and reassembeling the same in its original position at workshop including transportation of unservicieable servo voltage stabilizer upto 450 KVA capacity from site location to workshop and back after repair and refixing/connection the same complete all as specified and directed. Note : (i) Rate is deemed to be inclusive of transportation, T&P, men power and testing. (ii) Testing to be done by authorised dealer/ service center
M&L for defect rectification of LT XLPE cable 1100V grade of size 3.5/4 core 25 Sqmm to 185 Sqmm, laid in trenches by locating fault with help of electronic fault locating machine comprising of surge generator pules, ECHO fault locator with high frequency distance calculator complete all as specified and directed
M&L for defect rectification of HT XLPE cable 11000 grade of size 3 core x 95 to 120 sqmm, laid in trenches by locating fault with help of electronic fault locating machine comprising of surge generator pules, ECHO fault locator with high frequency distance calculator complete all as specified and directed
Supply, jointing and testing indoor/outdoor type cold shrinkable end termination cable joint including all material and accessories suitable for 3 core X 50-95 Sqmm XLPE cable of 11000 volts (E) grade complete all as specified and directed. Note :- Cost of cutting of existing end termination joint deemed to be included in unit rate.
Supply, jointing and testing indoor / out door type cold shrinkable end termination cable joint including all material and accessories suitable for 3 core X 120-185 Sqmm XLPE cable of 11000 volts (E) grade complete all as specified and directed. Note : Cost of cutting of existing end termination joint deemed to be included in unit rate.
M &L for cable jointing kit for 11 KV (Earthed) grade cable for straight through cold shrink type complete with joining material and accessory suitable for 50 to 120 sqmm 3 core XLPE armored aluminum conductor cable complete all as specified and directed
M &L for cable jointing kit for 1.1 KV (Earthed) grade cable for straight through Heat shrink type complete with joining material and accessory suitable for 25 sqmm to 50 Sqmm 3.5 core XLPE armored aluminum conductor cable complete all as specified and directed
M &L for cable jointing kit for 1.1 KV (Earthed) grade cable for straight through Heat shrink type complete with joining material and accessory suitable for 70 sqmm to 120 Sqmm 3.5 core XLPE armored aluminum conductor cable complete all as specified and directed
Supply ,installation ,testing and commissioning in replacement of feeder pillar board of size 60 cm X 45 cm X 30 cm Kiosk type ,LT(415 Volts, 50 Hz , 3-phase, 4 wire supply) floor mounted , factory assembled, outdoor type weather and vermin proof (Protection Class IP-65) made out of 40m x 40mm x 6mm angle iron frame and 3.15 mm thick MS Sheet CRCA sheet with front hinged opening, rubber lining, locking arrangement ,powder coated externally and internally after seven tanks treatment and lifting channel, fully compartmentalized design comple Bus Bar chamber comprising 4 Nos aluminium strip bus bars air insulated and PVC sheathed capacity 400 Amps with colour coding complete all as specified and as directed.
Supply and fixing in repair MCCB 250 Amp ,4 pole, 36 KA including under voltage/over voltage relay all as specified and directed.
Supply and fixed in repair MCCB 200 Amp ,4 pole, 25 KA including under voltage/over voltage relay all as specified and directed.
Supply and fixed in repair,MCCB 125 Amp ,4 pole, 16 KA including under voltage/over voltage relay all as specified and directed.
Material and labour for laying GI tubing of size 50 mm bore ,light grade for protection of under ground cable in trench /under road /croosing or fixed to wall /pole all as specified and directed
M&L for repair/maintenance of HT VCB 11 KV 3 phase 630/400 Amp , 21 kA (Make :- Siemens/CG), taking out VCB trolley from HT control panel and cleaning the trolley with CRC removing all dust , carbon etc greasing the mechanical parts, gears box, lever charging motor, male female contacts and spring holders all as specified and as directed. Note : Additional items/Spare parts required to make serviceable, shall be measured and paid separately under respective items of BOQ.
(a) Supply only bushing insulator with current type carrying parts 630 amp complete all as specified and directed
(b) Supply only in replacement Spring charging motor for HT VCB 11 KV 630/400 Amps controled by 110V DC complete all as specified and directed.
(c) Supply only in replecement of Spring charging Gear for 11KV VCB panel complete all as specified & directed
(d) Supply only in replecement of moving contact block for 11KV VCB panel complete all as specified & directed
(e) Supply only in replecement of spout with rod for 11KV VCB panel complete all as specified & directed
Material and labour for calibration of IDMT numerical relay as per existing load for earth fault , over current and short circuit ,including setting the relay on required electric load and testing on earth fault and short circuit and over load with the help of relay testing kit for 11 KV system complete in all respect all as specified and as directed. Note: Calibration to be done authorised service centre/dealer
S&F in replacement of power pack with battery back up of 110V DC complete all as specified and directed
Supply and fixing IDMT non directional shunt trip relay with two poles arrangement for over current protection with setting 50% to 200% and one pole for earth fault protection with setting 20% to 80% and under voltage protection. Relay should be microprocessor based numerical type. The relay shall be complete with a wide range of standered cominication protocols (Modbus , DNP 3.0, IEC 60870-5-103 etc. ) Relay shall be provide simple and powerfull operation interface. The LEDs and LCD display on the front panel shall be fully programmable to requirments including necessory wiring . The relay should be capable for minimum control following function:- i. Phase over current protection ii. Instantaneous short circut protection iii. earth fault over current protection iv. output relay latching
M&L For taking out old unserviceable ACB from LT control panel 415 V 3 phase 630 Amp , 50 kA, 4 Pole etc all as specified and as directed.
Supply, installing, testing and commissioning in replacement of Air Circuit Breaker 4 Pole, 415 V, Manual Drawout type with release of capacity 630 Amps, factory made and tested (including CPRI type tested certified panel) LT Panel board ,cubical compartmentalized , out door type double door , plate form mounted, suitable for 415 volts, 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with insulated aluminium bus bars four pole installed on porcelain/SMC insulator. The panel shall be dust and vermin proof. IP-65 class protection and shell be made of 3.15 mm CRCA MS sheet, and 45x45x5mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front and rear opening type, with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked, 1100 volts grade of appropriate size ( but not less than 2.5 Sqmm) complete all as specified and as directed.
S&F in replacement lightning arresters expulsion type complete with all fittings, 65 kilo amp discharge capacity, distribution class maximum working pressure 11000 volts after taking down old existing un serviceable lightning arrester etc complete all as specified and directed.
S&F in replacement Gang Operated Device triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for 11000V, current rating upto 200 Amps after taking down old existing un serviceable GOD etc complete all as specified and directed.
M & L for Earthing complete with GI earth plate electrode 60cmx60cmx6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including using GI strip 25×4mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel, earth plate surrounded by packed layer of char coal dust and common salt, 15cm thick all around bottom and top and watering pipe 20mm bore of GI medium grade with funnel, wire mesh and 40 mm dia GI protection pipe light grade all as shown in electrical plate No 3 of SSR Part-I and connected to earthing test point, main switch board and testing on completion including excavation, earth work concrete pit with 80mm thick RCC cover in RCC 1:2:4 type B-1 duly reinforced with MS bars 8mm dia @ 150C/C both ways and pit chamber in PCC 1:2:4 type B-1 with 2 Nos suitable lifting handles of 12mm MS bar complete all as specified. Note: GI Strip 25x4 of 7.5 mtr length included in unit rate
Supply,install, testing and commissioning of maintenance free chemical earthing system (Grid type, set of 03 earth) conforming to IS: 3043 using 77mm dia, 3000mm long copper solid rod with exothermic 'T' point rod with 7.5 mtr long copper strip of size 50mmx6mm and 90mm dia terminal copper pipe of thickness 1.6mm and 3000mm long with test certificate 99.99% . The ground enhancing compound made of Marconite conductive aggregate (consist of Marconite resin-based cements, adhesive and gypsum plaster) shall not be less than 45Kg. The electrode shall be provided on its top with an earth termination clamp made out of electrolytic grade copper for connecting earth continuity conductor with copper wire/strip. PCC chamber of size 300x300x300mm with cover shall be provided on top of earth system on 100mm thick PCC 1:3:6 bed concrete. The chamber shall burried in ground with top edge projecting upto 75mm from ground surface complete all as specified and directed. Note :- (i) The earth resistance value should be less than 1 ohm. (ii) The quoted rate shall include cost of copper strip 50mmx6mm upto 7.5mtr length and earth pit bore in hard/disintegrated rock. (iii) The contractor shall give a written guarantee for maintenance earth resistance of less than 01 ohm for a period of 5 years from the certificate date of completion and to arrange security deposit of Rs 5000.00 each earthing for 05 years. (iv) The short time and peak with standing current capacity for 1 second should be 25KA and 52.5KA respectively. In this regard CPR/ERDA/NABL approved Lab test report is mandatory of Marconite conductive aggregate. (v) The size of bore should not be less than 1500mm dia. Make- SN Engineering or equivalent from marconite conductive aggergate.
Supply and fixing LED street light fitting 45 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and as directed.
Supply and fixing LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and as directed.
Supply and fixing in replacement LED flood light 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp, after taking down old existing un serviceable floof light etc complete all as specified and directed.
Supply and fixing LED flood light 210 watt 230 VAC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp after taking down old existing un serviceable floof light etc complete all as specified and directed.
Supply and fixing post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete.
Supply and fixing in replacement of steel weather proof, dust proof, duly powder coated street light junction box of size 300 x 200 x 105mm comprising of 60 Amps 4 nos aluminium strip mounted on DMC insulator including one number MCB SP 6 Amps and connecting with street light poles using necessary MS GI clamps, nuts, bolts washers, aluminium lugs/thimble for incoming and out going cables, gland for cable etc of suitable size complete all as specified and as directed. Note : The rates quoted are inclusive of provision and fixing of suitable lugs/thimble and glands for cable connection.
Supply and fixing in replacement PVC sheathed multi-stranded copper conductor cable of size 1.5 sqmm x 2core and 1100 volts grade drawn through in and including steel conduit medium grade of not less than 20 mm dia with conduit accessaries GI clamp, screw nut and bolts etc for street light complete all as specified and as directed .
Supply and fixing in renewal of 3 pole power contactor ML-6, 40 Amps,mounted on any type/description LT panel/feeder pillar/wall after taking down old existing un serviceable contactor etc complete all as specified and directed.
Supply and fixing in renewal of 3 pole power contactor MNX-110, 63 to 110 Amps mounted on any type/description LT panel/feeder pillar/wall after taking down old existing un serviceable contactor complete all as specified and directed.
M&L for preparation, cleaning of surface and painting of old street/security light pole upto 11 mtrs long with one coat of red oxide primer and two coat synthetic enamel aluminium paints including marking of pole numbers with black colour paint complete all as specified and as directed.
Net Contract Sum will be after deducting Sch of Credit of Rs 76259.00
DHARAMRAJ BUILDERS & ENGINEERS
D P ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .