Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.0 CrAccepted-Finance 54 501 5TH FLOOR 2ND CROSS PILLAPPA LAYOUT VIRUPAKSHAPURA VIDYARANYAPURA POST BENGALURU 560097 | BENGALURU URBAN | KARNATAKA | 560097 | ₹18.0 Cr | L1 | Accepted-Finance L1 |
| 2 | L2₹18.1 CrRejected-Finance | ₹18.1 Cr | L2 | Rejected-Finance L2 |
| 3 | L3₹18.1 CrRejected-Finance | ₹18.1 Cr | L3 | Rejected-Finance L3 |
| 4 | L4₹18.4 CrRejected-Finance | ₹18.4 Cr | L4 | Rejected-Finance L4 |
| 5 | L5₹18.9 CrRejected-Finance | ₹18.9 Cr | L5 | Rejected-Finance L5 |
| Sl No | Description | Qty | Unit | BUILTECH ENGINEERING SOLUTIONS L7 | NANDI ASSOCIATES L5 | RAMESH KUMAR KOTHARI L2 | Anand Shree Infra Reality Pvt. Ltd L6 | NJR CONSTRUCTIONS PRIVATE LIMITED L9 | M.VENKATACHALAPATHI L3 | RN Constructions L4 | S SHIVARAJU AND CO L8 | S M CONSTRUCTION AND CO L1 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Demolition of Existing Buildings (Main building with Roofing & 3 ancillary buildings without roof) including disposal of unserviceable materials and crediting of Serviceable materials of Distressed/dilapidated building of RCC Single storey framed structure building with RCC/sloped roof at IISc, Bangalore, including upto 1500mm below the ground level completely and allied structures such as walkway, UG sump, walls, Drains,Stone slab Flooring etc., including disposal (outside to the BBMP limits) of building rubbish/malba/similar unserviceable, dismantled or waste materials from the site by mechanical means, including all operation i.e leveling, dressing, loading, transporting, unloading at approved municipal dumping ground for all leads including all lifts involved complete as per direction of Engineer-in-charge.(Bid is exclusive of land below & surrounding of the buildings). | 1 | L/s | 13,88,253 ₹16.4 L | 50,00,000 ₹59 L | 18,00,000 ₹21.2 L | 18,00,000 ₹21.2 L | 2,00,000 ₹2.4 L | 3,50,000 ₹4.1 L | 14,40,000 ₹17.0 L | 15,00,000 ₹17.7 L | 47,00,000 ₹55.5 L |
| 2.00 | Barricading
Hire charges for providing temporary barricading around the site using GI corrugated sheet to a height of 6.00 metre. The GI corrugated/Plain sheets of 0.35mm thick shall be fixed to the framework made out of 50mm dia MS pipe for vertical strut placed at about 3m center to center with required bracing using 40mm dia. MS pipe placed about 2m center to center and fixing diagonal middle braces using 25mm dia. MS pipe forming a rigid frame work as per the architectural drawing and direction of Engineer-in-charge. The barricade shall remain in the same location till the completion of the new work constuction project. No additional charges shall be paid for the extended period of contract. The rate quoted shall be including cost of conveyance of all required materials to work at site, erecting, removing and disposing the same after completion of work, cost of J bolts washers, cement concrete bed 45cm x 45cm x 75cm in CC 1:2:4 and labour charges etc., complete as per direction of Engineer-in-charge etc., complete as per direction of Engineer-in-charge.
(Note: One time payment shall be made for providing barricading from start of work till completion of the work i/c shifting, the barricading provided shall remain to the property of the contractor on completion of the work): | 1,199.4 | sqm | 1,472 ₹20.8 L | 1,120 ₹15.9 L | 1,300 ₹18.4 L | 950 ₹13.4 L | 1,500 ₹21.2 L | 1,500 ₹21.2 L | 1,670.4 ₹23.6 L | 1,600 ₹22.6 L | 350 ₹5.0 L |
| 3.00 | Earth work excavation by manual means for drains, canals, waste weir, draft, approach channels, key trenches, foundation of Buildings & bridges and such simillar works in all kinds of soils, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, removal of stumps and other deleterious matter, excavated surface leveled and sides neatly dressed disposing off the excavated stuff or sorting & stacking the selected stuff for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools & other appurtenaces required to complete the work. The Contractor shall dispose off surplus excavated soil at his own cost as directed by the Executive Engineer.
In all kinds of soils Depth upto 1.5 m | 65 | Cum. | 244 ₹18,714.80 | 232 ₹17,794.40 | 350 ₹26,845 | 160 ₹12,272 | 360 ₹27,612 | 220 ₹16,874 | 1,856 ₹1.4 L | 242 ₹18,561.40 | 252 ₹19,328.40 |
| 4.00 | Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work. The Contractor shall dispose off surplus excavated soil at his own cost as directed by the Executive Engineer.
In all kinds of soils Depth upto 3 m | 2,967 | Cum. | 103 ₹3.6 L | 95 ₹3.3 L | 100 ₹3.5 L | 200 ₹7.0 L | 261 ₹9.1 L | 100 ₹3.5 L | 269.12 ₹9.4 L | 102 ₹3.6 L | 270 ₹9.5 L |
| 5.00 | Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work. The Contractor shall dispose off surplus excavated soil at his own cost as directed by the Executive Engineer.
Depth 3m to 6m | 527 | Cum. | 117 ₹72,757.62 | 107 ₹66,539.02 | 100 ₹62,186 | 230 ₹1.4 L | 310 ₹1.9 L | 110 ₹68,404.60 | 380.48 ₹2.4 L | 117 ₹72,757.62 | 376 ₹2.3 L |
| 6.00 | Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work. The Contractor shall dispose off surplus excavated soil at his own cost as directed by the Executive Engineer.
Depth above 6m | 44 | Cum. | 145 ₹7,528.40 | 144 ₹7,476.48 | 120 ₹6,230.40 | 300 ₹15,576 | 350 ₹18,172 | 130 ₹6,749.60 | 501.12 ₹26,018.08 | 144 ₹7,476.48 | 600 ₹31,152 |
| 7.00 | Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work. The Contractor shall dispose off surplus excavated soil at his own cost as directed by the Executive Engineer.
In ordinary/soft rock without blasting upto 1.5 m depth | 50 | Cum. | 367 ₹21,653 | 333 ₹19,647 | 350 ₹20,650 | 280 ₹16,520 | 300 ₹17,700 | 300 ₹17,700 | 167.04 ₹9,855.50 | 363 ₹21,417 | 299 ₹17,641 |
| 8.00 | Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work. The Contractor shall dispose off surplus excavated soil at his own cost as directed by the Executive Engineer.
Depth exceeding 1.5 m, but not exceeding 3 m | 50 | Cum. | 429 ₹25,311 | 400 ₹23,600 | 500 ₹29,500 | 300 ₹17,700 | 330 ₹19,470 | 400 ₹23,600 | 269.12 ₹15,878 | 425 ₹25,075 | 445 ₹26,255 |
| 9.00 | Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work. The Contractor shall dispose off surplus excavated soil at his own cost as directed by the Executive Engineer.
Depth exceeding 3m, but not exceeding 4.5m | 50 | Cum. | 468 ₹27,612 | 423 ₹24,957 | 600 ₹35,400 | 320 ₹18,880 | 350 ₹20,650 | 450 ₹26,550 | 380.48 ₹22,448.50 | 463 ₹27,317 | 590 ₹34,810 |
| 10.00 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. | 1,567.36 | Cum. | 268 ₹5.0 L | 236 ₹4.4 L | 200 ₹3.7 L | 180 ₹3.3 L | 250 ₹4.6 L | 200 ₹3.7 L | 222.72 ₹4.1 L | 266 ₹4.9 L | 290 ₹5.4 L |
Tender Value
₹20.7 Cr
EMD Value
₹20.7 L
Closing Date
3 Sept 2025, 3:30 pmClosed
Registrar
IISc, Bangalore
Construction of Amenity Complex at IISc, Bangalore
2025_IISC_873359_1
IISc/Tender-CIV-11/2025-26
Open Tender
Civil Works
450 days
IISc, Bangalore
As Per Tender Documents
2 documents required · 2 mandatory
₹0
₹20.7 L
MS Teams Meeting
30 Oct 2025
14 Aug 2025
4 Sept 2025
15 Aug 2025
3 Sept 2025
28 Aug 2025
25 Aug 2025
Amount
Demolition of Existing Buildings (Main building with Roofing & 3 ancillary buildings without roof) including disposal of unserviceable materials and crediting of Serviceable materials of Distressed/dilapidated building of RCC Single storey framed structure building with RCC/sloped roof at IISc, Bangalore, including upto 1500mm below the ground level completely and allied structures such as walkway, UG sump, walls, Drains,Stone slab Flooring etc., including disposal (outside to the BBMP limits) of building rubbish/malba/similar unserviceable, dismantled or waste materials from the site by mechanical means, including all operation i.e leveling, dressing, loading, transporting, unloading at approved municipal dumping ground for all leads including all lifts involved complete as per direction of Engineer-in-charge.(Bid is exclusive of land below & surrounding of the buildings).
Barricading Hire charges for providing temporary barricading around the site using GI corrugated sheet to a height of 6.00 metre. The GI corrugated/Plain sheets of 0.35mm thick shall be fixed to the framework made out of 50mm dia MS pipe for vertical strut placed at about 3m center to center with required bracing using 40mm dia. MS pipe placed about 2m center to center and fixing diagonal middle braces using 25mm dia. MS pipe forming a rigid frame work as per the architectural drawing and direction of Engineer-in-charge. The barricade shall remain in the same location till the completion of the new work constuction project. No additional charges shall be paid for the extended period of contract. The rate quoted shall be including cost of conveyance of all required materials to work at site, erecting, removing and disposing the same after completion of work, cost of J bolts washers, cement concrete bed 45cm x 45cm x 75cm in CC 1:2:4 and labour charges etc., complete as per direction of Engineer-in-charge etc., complete as per direction of Engineer-in-charge. (Note: One time payment shall be made for providing barricading from start of work till completion of the work i/c shifting, the barricading provided shall remain to the property of the contractor on completion of the work):
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. For depth between 4.5m to 6.0m
Excavating, supplying and filling of local earth (including royalty) by mechanical transport up to a lead of 5km (minimum) also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete.
Providing and injecting chemical emulsion for Pre-constructional Anti-Termite Treatment, creating continuous chemical barrier under and around the column pits, walls, trenches, basement excavation, top surface of the plinth filling, junction of wall and floor, along the external perimeter of building, expansion joints, over the top surface of consolidated earth on which apron is to be laid, surrounding of pipes and conduits with Chlorpyriphos 20% E.C. / Lindane 20% E.C. @ 3.19 l/m2 including cost of chemical, diluting in water to one percent concentration, labour, usage charges of machinery, complete as per specifications. (Only Plinth area will be measured at ground floor level for payment)
Providing and laying in position plain cement concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machineries, curing, and all the other appurtenances required to complete the work as per technical specifications. Mix 1:3:6 (M10) Using 20 mm nominal size graded crushed coarse aggregates
Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. Mix 1:2:4 (M15) Using 20 mm nominal size graded crushed coarse aggregates
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth.
Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 12.5mm nominal size derived from natural sources)
Providing & applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7kg per square meter on damp proof course after cleaning the surface with brushes and finally with apiece of cloth lightly soaked in kerosene oil.
Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/welding joints, tying with binding wire / soft annealed steel wire and other ancilary operations complete as per drawing and technical specification. (for Buildings)
Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of formwork is included in the item, nothing shall be paid additional separately for shuttering/ formwork/ moulds). M30 Design Mix Using 20 mm nominal size graded crushed coarse aggregates. Isolated Footings
Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of formwork is included in the item, nothing shall be paid additional separately for shuttering/ formwork/ moulds). M30 Design Mix Using 20 mm nominal size graded crushed coarse aggregates. Other type of Foundation
Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of formwork is included in the item, nothing shall be paid additional separately for shuttering/ formwork/ moulds). M30 Design Mix Using 20 mm nominal size graded crushed coarse aggregates. Plinth Beam/Beams
Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of formwork is included in the item, nothing shall be paid additional separately for shuttering/ formwork/ moulds). M30 Design Mix Using 20 mm nominal size graded crushed coarse aggregates. Walls
Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of formwork is included in the item, nothing shall be paid additional separately for shuttering/ formwork/ moulds). M30 Design Mix Using 20 mm nominal size graded crushed coarse aggregates. Grade Slab
Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of formwork is included in the item, nothing shall be paid additional separately for shuttering/ formwork/ moulds). M30 Design Mix Using 20 mm nominal size graded crushed coarse aggregates. Column
Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of formwork is included in the item, nothing shall be paid additional separately for shuttering/ formwork/ moulds). M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates. Lintel
Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of formwork is included in the item, nothing shall be paid additional separately for shuttering/ formwork/ moulds). M30 Design Mix Using 20 mm nominal size graded crushed coarse aggregates. Slab Level Beams
Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of formwork is included in the item, nothing shall be paid additional separately for shuttering/ formwork/ moulds). M30 Design Mix Using 20 mm nominal size graded crushed coarse aggregates. Slabs
Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of formwork is included in the item, nothing shall be paid additional separately for shuttering/ formwork/ moulds). M30 Design Mix Using 20 mm nominal size graded crushed coarse aggregates. Walls
Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of formwork is included in the item, nothing shall be paid additional separately for shuttering/ formwork/ moulds). M30 Design Mix Using 20 mm nominal size graded crushed coarse aggregates. Staircases
Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of formwork is included in the item, nothing shall be paid additional separately for shuttering/ formwork/ moulds). M30 Design Mix Using 20 mm nominal size graded crushed coarse aggregates. Columns
Providing and laying in position plain cement concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machineries, curing, and all the other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement & formwork shall be paid separately). Mix 1:5:10 Using 40 mm nominal size graded crushed coarse aggregates
Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: (a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. (b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs.(c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge. (d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. “All above operations to be done in order and as directed and specified by the Engineer-in-Charge”: With average thickness of 120 mm and minimum thickness at khurra as 65 mm.
Providing and applying two coats of High Albedo paint having minimum Solar Reflective Index (SRI) 108 (with solar reflectance & thermal remittance tested as per ASTM) C 1549 and ASTM C 1371 respectively), VOC less than 10 cc/g. The coating thickness and the methodology of application shall strictly as per manufacturer's specifications and as approved by Engineer-in-Charge. Surface preparation includes cleaning with metal wire brush to remove all dust, fungus etc., washing with water all complete. The contractor shall give guarantee for the performance of SRI and also the durability of coating, all complete as per direction of Engineer-in-Charge.
Providing and laying water proofing treatment to the Roof with PU based single component elastomeric pure polyurethane based coating on New terrace/Chajjas/Sunken portion of WC:Bathroom, cold applied PU waterproofing membrane that is highly elastic with elongation greater than 400% and tensile strength greater than 2MPa as per ASTM D412. The waterproofing membrane to be applied in 2coats @ 1.6 kg/m2 to achieve final DFT (Dry Film Thickness) of 1mm including prime coat of epoxy primer @150 g/m2 and protection with 120gsm Geo-textile over the waterproofing membrane. The finished cost to include surface preparation, making coving at Junction, Bore Packing, treatment of construction joints completely as per specification.
Providing and laying water proofing treatment to the Retaining wall area with PU Elastomeric Single component liquid applied, cold applied, moisture cured high tensile elastomeric PU waterproofing membrane having elongation of more than 400% and having solid content of above 90% @ 1.6kg per m2 in 2 coats to achieve final DFT (dry film thickness) of 1mm including prime coat of epoxy primer @150 g/ m2. The cost is inclusive of surface preparation, crack filling, repair of loose mortar etc. completely as per specification & with a 10 years warranty on product & work from certified manufacturers as per the direction of the Engineer In charge.
Providing and laying water proofing treatment to the Rafts, Below grade slab, Lift pits, water retaining structures with fully bonded High Density Polyethlene Membrane (HDPE) of 1.2mm composite thickness and having tensile strength of >25 MPa (as per ASTM D 412), elongation of >500% (as per ASTM D 412), puncture resistance of >1000N (as per ASTM E 154), peel adhesion to concrete >1200N/m (as per ASTM D 903), hydrostatic head resistance >70m (as per ASTM D 5385). The system should be fully bonded to the RCC thereby conforming to IS 16471:2017 requirements of UG waterproofing structures. The membrane should be minimum 2.4m wide to reduce the number of joints with minimum 75mm factory made selvedge’s and comprising of an HDPE layer and a pressure sensitive adhesive layer which is covered by a weather proof protective and trafficable granular layer to protect self-adhesive polymer layer, etc, including surface preparation completely as per specification & with a 10 years warranty on product & work from certified manufacturers as per the direction of the Engineer In charge.
Providing and laying water proofing treatment to the Water tanks & Liquid Retaining structures with two component acrylic polymer modified cementitious waterproofing membrane with minimum elongation of 50% applied @ 1.5 kg/m2 for internal side waterproofing in two layers with waiting period of 4-6 hrs per layer and food grade epoxy coating in two coats certified by CFTRI Mysuru, including surface preparation completely as per specification & with a 10 years warranty on product & work from certified manufacturers as per the direction of the Engineer In charge.
Providing Brick work with common burnt clay Non Modular bricks of class designation 3.5 in foundation and plinth in Cement mortar 1:6 (1 cement : 6 coarse sand) including cost of all materials, labour, scaffolding and usage charges of machinery & other incidental charges complete as per the direction of engineer incharge of work.
Providing Brick work with common burnt clay Non Modular bricks of class designation 3.5 in superstructure above plinth level in all shapes and sizes in Cement mortar 1:4 (1 cement : 4 coarse sand) including cost of all materials, labour, scaffolding and usage charges of machinery & other incidental charges complete as per the direction of engineer incharge of work.
Providing and laying autoclaved aerated cement blocks masonry with 150mm/230mm/300 mm thick AAC blocks as per IS 2185 (Part III) in super structure above plinth level up to floor I level with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar including cost of all materials, labour, scaffolding and usage charges of machinery & other incidental charges complete as per the direction of engineer incharge of work.
Providing Half brick masonry with common burnt clay Non Modular bricks of class designation 3.5 in superstructure above plinth level up to floor 1 level cement mortar 1:4 (1 cement :4 coarse sand) including cost of all materials, labour, scaffolding and usage charges of machinery & other incidental charges complete as per the direction of engineer incharge of work.
Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at every third course of half brick masonry.
Providing and laying autoclaved aerated cement blocks masonry with 100mm/150mm/230mm/300 mm thick AAC blocks as per IS 2185 (Part III) in super structure above plinth level up to floor III level with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar including cost of all materials, labour, scaffolding and usage charges of machinery & other incidental charges complete as per the direction of engineer incharge of work.
Providing 12 mm cement plaster with cement mortar 1:4 (1 cement: 4 fine sand) to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge.
Providing 15 mm cement plaster with cement mortar 1:4 (1 cement: 4 fine sand) to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge.
Providing 18 mm cement plaster in two coats under layer 12 mm thick cement plaster with cement mortar 1:5 (1 cement : 5 coarse sand) and a top layer 6 mm thick cement plaster with cement mortar 1:3 (1 cement : 3 coarse sand) finished rough with sponge to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge.
Providing 6 mm cement plaster with cement mortar 1:3 (1 cement : 3 fine sand) including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge.
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete as per specifications and as per directions of Engineer in charge.
Providing & applying Exterior grade texture paint non-pigmented stone finish with Natural mineral aggregates combined with adhesives and resins. The Finish to be water repellent, anti-fungal, breathes out trapped moisture, having unique property of elasticity & flexibility (due to temperature variation no hairline cracks to appear) protective and decorative coating on exterior surfaces such as, concrete & plastered Surface (as per approved) in colour and pattern as per direction of engineer-in-charge. The works include providing and laying one coat of primer and sealer mixed in equal ratio followed by one coat of basecoat with steel trowel made of natural stone crushed powder, 2nd coat to be applied with steel trowel and finished by acrylic trowel or spray gun of natural stone crushed powder added with granite chips. Final coat of ultra protect shall be applied with roller/spray diluted with water, (as per manufacturer's specification and approval of E-I-C) including cost and conveyance of all material, labour, sundries, tools and machinery etc. all complete. (Guarantee of 10 years to be given by the Contractor on the Exteriro Texture paint works)
Finishing walls with water proofing cement paint of required shade :New work (Two coats applied @ 4.84 kg/10 m²) to give an even shade after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge.
Finishing walls with Acrylic Smooth exterior paint of required shade :New work (Two coat applied @ 1.67 ltr/10 m² over and including priming coat of exterior primer applied @ 2.20 kg/10 m²) with paint of approved quality to give an even shade, after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge.
Acrylic Emulsion Paint:- Finishing walls with 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives, New work (Two coats applied @ 1.43 litre/ 10 m². Over and including priming coat of exterior primer applied @ 0.90 litre/10 m² with paint of approved quality to give an even shade, after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge.
Ceramic glazed wall tile:- Providing and fixing 1st quality rectified ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer- in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per m2, including pointing in white cement mixed with pigment of matching shade complete.
Providing & Fixing in position Acoustical wall panelling with Integral Densified Square/Butt edged Fully Perforated Eco Friendly Lightweight Calcium Silicate panels/tiles with fabricated galvanised mild steel frame work for Auditoriums, Community halls, Offices, Institutions, Airports, Meeting halls, Indoor Stadiums and Studios. The Eco Friendly Lightweight Calcium Silicate wall panels/tiles shall be made from Non Cementitious Hydrated Calcium Silicate Slurry/Mixture, Reinforced recycled material with fibers and natural fillers. Free from Formaldehyde and other harmful materials. Doesn't contain any toxic ingrediants. The wall panels/tiles size of 595x595mm and 15mm thick should have Humidity Resistance (RH) of 100%, Water Resistance, Non Combustible: as per BS:476 Part-4, Fire Performance: as per BS:476 Part-6 for Fire Propagation, as per BS:476 Part-7 for Surface Spread of Flame, As per UK standards Fire Performace A1-S1-d0, Thermal Conductivity K= 0.048 to 0.050 w/m K as per ECBC code 2007, NRC (Noise Reductions Coefficient) 0.65 to 0.85 (Fully Perforated wall panels/Tiles) as per IS 8225:1987, Sound Attenuation (STA) 30-32dB,Thickness of tile should be 15mm thick with 450 kg/m3 density all around on edge resting portion with Integral Densified edge and 10mm thick with 350 kg/m3 density in the center of the body, Light Reflectance > 85%, Weight of material is 5-5.5 kg/m2 and Suitable for Green Building application with InOrganic Recycled content of 46- 50% out of which 18-20% should be FLYASH and meets the GRIHA & SVAGRIHA norms under the categories: GRIHA V.2015 criterion:11&12, GRIHA V.3 criterion: 17&29 and SVAGRIHA criterion:12. The frame work comprising of a frame made especially fabricated galvanised mild steel sheet of 0.50 mm thick pressed section (galvanizing @ 120 grams per m2 including both sides) i.e. vertical studs of size 48x34x36mm are placed at 600mm centre to centre in a floor and ceiling channel section of size 50x32mm fixed to the floor and soffit at 600mm centres using 12mm dia, 40mm long wedge type expanded zinc alloy dash fastner with 10mm bolt. This same channel is then to be fixed in horizontal direction at 600mm centre to centre so as to form a grid of 600x600mm. Glass wool of 50mm thickness with density of 16 kg/m3 is then to be inserted in the slots and finally Lightweight calcium silicate wall panels/tiles are to be screw fixed with self-tapping pan head nickle coated mild steel screws of size 13x3.2mm on to this grid leaving an even groove of 1 mm between the panels. The joints between the panels are to be duly jointed and finished using recommended jointing calcium silicate based compound and fibre joint tape roll 50mm wide (90metre) roll and two coats of premier suitable for panelling as per manfacturer's specification as per direction of engineer-in-charge all complete.
Providing and fixing Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge.
Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. Fixed to openings /wooden frames with rawl plugs screws etc. ( KPWD 23-24 SL NO 11.34B Page no 86: VOL- 2)
Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. 80x1.25 mm M.S. laths with 1.25 mm thick top cover including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge.
Providing and fixing ball bearing for rolling shutters including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge.
Finishing with Epoxy paint (two coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete. On steel work including preparing the surface after thorougly cleaning oil, grease, dirt and foreign matter, cost of materials, labour complete as per specifications and as per directions of Enginer-in-charge.
Applying 50 micron powder coating over MS work as per IS code 13871.
Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in- charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.) including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge.
Providing and fixing unglazed, uncoated, metal pressed, full body homogeneous anti-algal, all weather resistant ready to install step tile with built-in- bull nose and anti skid strip, smooth and anti skid surface confirming to IS: 4457-2007 and having water absorption of <0.05% in 12mm thickness in sizes as required as per site condition in flooring. These anti skid tiles are to be laid on 20mm thick cement mortar of mix 1:4 (1 cement: 4 coarse sand) and joints filled with polymer based cement grout with all labour, material, cement, tile, sand, grout etc as a complete job & as per direction of Engineer-in-charge. (Basic Rate for Full body vitrified tiles :- Rs. 983/- per Sqm)
Providing and fixing unglazed, uncoated, metal pressed, full body homogeneous anti-algal, all weather resistant tile with smooth and anti skid surface confirming to IS: 4457-2007 and having water absorption of <0.05% in 12mm thickness in sizes as required as per site condition in riser and skirting of stairs. These anti skid tiles are to be laid on 12mm thick cement mortar of mix 1:3 (1 cement: 3 coarse sand ) and joints filled with polymer based cement grout with all labour, material, cement, tile, sand, grout etc as a complete job & as per direction of Engineer-in-charge. (Basic Rate for Full body vitrified tiles :- Rs. 928/- per Sqm)
Providing and laying tactile tile (for vision impaired persons as per standards) of size 300x300x9.8mm having with water absorption less than 0.5% and conforming to IS:15622 of approved make in all colours and shades in for outdoor floors such as footpath, court yard, multi modals location etc., laid on 20mm thick base of cement mortar 1:4 (1 cement : 4 coarse sand) in all shapes & patterns including grouting the joints with white cement mixed with matching pigments etc. complete as per direction of Engineer-in-Charge. (Basic Rate for Tectile tiles :- Rs. 890/- per Sqm)
Providing and laying Double charged vitrified tiles in floor in 600mm x 600mm size (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only. Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. (Vitrified tile with at least 10% recycled content by weight. Preference should be given to GRIHA certified Vitrified tiles). (Basic Rate for Double charged vitrified tiles :- Rs. 476/- per Sqm)
Grouting the joints of flooring/ wall tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. Size of Tile 300x600 mm
Grouting the joints of flooring/ wall tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. Size of Tile 600x600 mm
Providing and installing 18 mm thick gang saw cut, mirror polished, pre-moulded and pre-polished granite counter, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) / adhesive, joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc., complete in all respects as per the direction of the Engineer-in-charge. Area of slab over 0.50 m2 (Basic Rate for 18mm thick granite :- Rs. 1700/- per Sqm)
Providing and fixing 20mm thick gang saw water cut granite of approved shade for cladding in CM 1:3 (1 cement : 3 coarse sand) proportion with a coat of rough plastering using CM 1:4 (1 cement : 4 fine sand), cut to required shape, pattern with paper joints, finished with cement mortar using white cement and colour pigments to match the colour of slab making through jointing with sealant, grooves in joints including cost of curing etc., complete including cost and conveyance of all materials, mortar, labour for all items of work, usage charges of machinery etc., complete as per specification. (Basic Rate for 20mm thick granite :- Rs. 2200/- per Sqm)
Providing and laying Polished Granite stone flooring as per approved colour/shade by Engineer-in-charge. in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-charge. (Basic Rate for 18mm thick granite :- Rs. 1150/- per Sqm)
Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge : Flamed finish granite stone slab Black, Cherry Red, Brown, Cat Eye, River Pink or equivalent. (Basic Rate for 18mm thick granite :- Rs. 1150/- per Sqm)
Making 3nos. Grooves 3mm x 3mm in treads of Granite/ Kota Stone/ Marble stone as direction of Engineers-in-charge/Architect.
Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator , vacuum dewatering process and finally finished by floating, brooming with wire brush etc. complete as per specifications and directions of Engineer-incharge. (The panel shuttering work shall be paid for separately). (Note:- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/ recoverable separately).
Extra for providing and mixing hardening compound of sodium silicate based transparent surface hardener, dust proofer, sealing and curing compound for concrete.
Extra for providing and mixing Glass fibre reinforcement in VDF Flooring.
Extra for providing and mixing high performance superplasticiser in conretre intended to high water reduction and long workability retention are required.
Providing and applying Acrylic emulsion cement modified and water based concrete bonding agent. Adhesion to concrete substrate:- 20N/mm2 (BS6319) The bonding agent shall be an acrylic based emulsified solution containing a minimum of 43% solids and compatible with cementitious materials. The bonding agent shall provide adequate bond strength when directly applied on concrete and also mixed with neat cement
Cutting of Control/Cold joint Groove in cement concrete flooring. Groove Size 4mm x 10mm
Cutting of Control/Cold joint Groove in cement concrete flooring. Groove Size 8mm x 18mm
Filling of Control/Cold joint Groove with Epoxy urethane joint Sealer with suitable backer rod. 4mm x 4mm groove with 6mm dia backer rod.
Filling of Control/Cold joint Groove with Epoxy urethane joint Sealer with suitable backer rod. 8mm x 8mm groove with 10mm dia backer rod.
Epoxy Tarrazo Flooring Providing & Laying 12.0 mm thick decorative epoxy resin flooring finishing contains varying sizes of Peran flakes scattered over approved shade pigmented base coat and finished with a clear sealer.Surface preparation by enclosed shot blasting or scarification or diamond grinding. Finish edges with hand tools. Remove all residues to leave a dry and dust free open textured surface. Supply and apply of primer (two coats if substrate porous) followed by screed and allow it to dry. Supply and apply of base coat followed by colored Flakes as per approved color and allow to dry. Supply and apply of lamination coat and followed by two coats of sealer and allow to dry. (Basic rate Epoxy Tarrazo Flooring Rs. 7650/- per Sqm Inclusive of laying and installation). Technical Profile: Fire Resistance-Bfl-s1(EN 13501-1), SLIPRESISTANCE:- Dry>40, Wet depends on specification (in accordance with (Method described in BS 7976-2 (typical values for 4-S rubber slider with HSE and UKSRG guidelines). THERMAL RESISTANCE:- Tolerant up to 60˚C CHEMICAL RESISTANCE:- (Contact Technical Department for chemical resistance chart) ABRASION RESISTANCE:- Class AR2 - Medium duty industrial and commercial as per BS8204:Part 2:2002l FLEXURAL STRENGTH:- >40 N/mm2((BS 6319) TENSILE STRENGTH:->15 N/mm2(BS 6319) WATER PERMEABILITY: Nil - Karsten test (impermeable) BOND STRENGTH:- Greater than cohesive strength of 25 N/mm2 concrete. >1.5 MPa
providing and fixing Luxury Vinyl Tile (LVT) flooring shall include: supplying LVT flooring of specified thickness (4mm), wear layer (1mm), and design approved by the architect/engineer; ensuring material is of high quality, durable, water-resistant, and compliant with environmental and fire safety standards; subfloor preparation, including leveling or priming if necessary; installation using appropriate methods (e.g., glue-down, click-lock, or loose lay) as per site conditions; inclusion of all necessary accessories such as trims, adhesives, and underlayments; proper alignment and seamless finish; and post-installation cleaning. The rate shall include all labor, materials, tools, and equipment required to complete the work to the satisfaction all complete as per the direction of Engineer-in-charge/ Architect. (Basic rate Luxury Vinyl Tile (LVT) Rs. 2540/- per Sqm Inclusive of laying and installation)
Providing and fixing 15mm thick industrial tiles over a 20mm thick cement mortar (1:4 mix) shall include: supplying high-quality, durable industrial tiles of specified dimensions and approved standards; preparing the base by cleaning and leveling the surface to ensure proper adhesion; laying 20mm thick cement mortar in the ratio of 1:4 (cement to coarse sand) evenly across the substrate; fixing the tiles over the mortar bed with proper alignment, ensuring level and uniform joint spacing; grouting the joints with approved material for a seamless and strong finish; and cleaning the completed surface. The rate shall include all materials, labor, tools, and equipment necessary to complete the work in accordance with the project requirements and to the satisfaction of the supervising authority. Size of Tile 1000x1000 mm
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm center to center, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm center to center, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm center to center, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm center, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes, finishing with jointing compound in 3 layers covering up to 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer-in-charge but excluding the cost of painting with : 12.5 mm thick tapered edge gypsum moisture resistant board
Providing & Fixing of Integral Densified Tegular/Butt edged Eco Friendly Lightweight Calcium Silicate Suspended Ceiling System in Module Size of 600x600x15mm with Exposed GI Plain T24 Grid for Offices, Hospitals, Institutions, Airports, Banking Sector, Auditoriums, Community halls, laboratories, Factories and All buildings in high humidity or coastal Areas. The Eco Friendly Lightweight Calcium Silicate Ceiling tiles shall be made from Non Cementitious Hydrated Calcium Silicate Slurry/ Mixture, Reinforced recycled material with fibers and natural fillers. Free from Formaldehyde and other harmful materials. Doesn't contain any toxic ingredients.The Tiles should have Humidity Resistance (RH) of 100%, Water Resistance, Non Combustible: as per BS:476 Part-4, Fire Performance: as per BS:476 Part-6 for Fire Propagation, as per BS:476 Part-7 for Surface Spread of Flame, As per UK standards Fire Performace A1-S1-d0, Thermal Conductivity K= 0.048 to 0.050 w/m K as per ECBC code 2007, NRC (Noise Reductions Coefficient) 0.5 to 0.75 (Semi Perforated & Fully Perforated Tiles) as per IS 8225:1987, Sound Attenuation (STA) 30-32dB,Thickness of tile should be 15mm thick with 450 kg/m3 density all around on edge resting portion with Integral Densified edge and 10mm thick with 350 kg/m3 density in the center of the body, Light Reflectance > 85%, Weight of material is 5-5.5 kg/m2 and Suitable for Green Building application with InOrganic Recycled content of 46- 50% out of which 18-20% should be FLYASH and meets the GRIHA & SVAGRIHA norms under the categories: GRIHA V.2015 criterion:11&12, GRIHA V.3 criterion: 17&29 and SVAGRIHA criterion:12 The tiles Shall be laid on 24mm Wide T-Sections Flanges colour white having rotary stitching on all T sections i.e. the Main runner with a web height of 38mm and 1200mm & 600mm Cross Tees with a web height of 32mm having thickness of 0.33mm and Wall angle of 24*24mm with 0.4 mm thickness , having load carrying capacity of 15 kg/m2. The T sections should have Galvanizing of 120 grams per m2 and need to be installed with Suspension system.
Providing and Fixing Wooden false Ceiling comprising of 50mm x 50mm solid Sal wood frame seciton with 12 mm thick water proof ply, followed by 6 mm thick ply for making groove and finished with approved shade of veneer of 3.5 mm thickness duly Spirit polished with Melamine coating of matt/Gossy finish. The ceiling shall be fixed to the roof soffit with adequate suspenders of GI 6mm dia threaded rod fastened in RCC roof at the maximum intervals of 450mm c/c. The item shall be inclusive of cutting & making cutouts for lights, diffusers etc. complete in all respect as per the direction of Engineer-in-charge. ( Base Rate of Veneer Rs. 2000/- per Sqm. ) Cost is inclusive of all necessary scaffolding.
Providing and installing vertical baffle system, exhibiting space-delineating characteristics. The carrier rails run perpendicular to the baffles. Individual baffle lengths varies between 300 and 2400 mm. Baffle ceiling should supplied with the end cap matching the similar finish of baffle. Tolerances according to TAIM, DIN EN 13964 and quality controlled to ISO 9001:2008 approved by TUV. Metal ceiling panels are tested for Fire propagation and spread of flame under BS476 Part 6&7.The best classification should be achieved by both parts combined has “CLASS 0” fire protection ratings. For acoustic performance perforated 0.5mm GMS inlay panels should be installed between open space of baffles in matt black finish. Baffles should be powder coated to approved RAL finish with minimum 50-60 microns paint thickness. Substructure for Vertical baffle system consisting of U shaped galvanized slotted carriers 1.2mm Thick (secondary profile]installed at maximum 1200mm centres. A primary grid of U shaped-Channel 40X40X40mm galvanized steel carrier is installed perpendicularly to perforated L angle of size 30x30mm in 2mm thickness at maximum 1200mm centres using cross connectors. The primary profiles must be connected to one another with longitudinal splice connectors.The entire ceiling module shall be suspended with 6mm diameter galvanized steel threaded rodsfrom the true ceiling officially approved anchor fasteners maximum at 1200mm Centres as per the requirements of DIN EN 13964 and the statics of the system. Ensure horizontal and flush alignment during installation. Perimeter Trims, Column Rings and other special items should be inclusive in the cost. Cost is inclusive of all necessary scaffolding. The system comprises baffles of size 150mm (H) x 40 mm(W) , 2400mm Length made out of 1mm Aluminium installed at 150mm c/c. (Basic rate Rs. 6750/- per Sqm Inclusive of laying and installation)
Rockwool/ stonewool Grid Ceiling Providing & Fixing Rockwool/ Stonewool Acoustic Ceiling having NRC value more or equal to 0.8, Fire Rating A1, RH 100% (No visible deflection/sagging in high humidity conditions), Superior Class Light Reflection 86%, SAG Resistant (Anti-Sag Warranty), Square Edge Ceiling Tiles of size 600x600mm, 12mm thick, Anti-Bacterial Properties & M1 Class Emission Certification made up rsv with Natural Stone (Bassalt Rock). The Visible side should be smooth white painted fleece, the Rear side should have back fleece with complete factory finish and Painted edges. (Basic rate Rs. 1450/- per Sqm Inclusive of laying and installation). The system consists of Stonewool 12mm Tiles 1200x600mm, laid in to Grooveline Black Reveal Grid Suspension System 15mm x 32 Xx0.30mm system. Main Runner: 3000mm x 32mm x 15mm ,Cross Runner:1200mm /600mm X 32mm x 15mm, Wall Angle: 3000mm x 20mm x 14mm. Main runners are suspended at 1200mm c/c by means of GI wire of 2 mm diameter wire only and not more than 150mm from spliced joints. Cross runners are inserted in to the main runners and locked in position by a slight downward pressure. The GI wire fixed by means of a dash fastener or by directly fixing it to soffit or sub structure. The last hanging wire at the end of each runner should not be more than 450mm from the adjacent wall. For perimeter treatments and wall ends, wall angle are used to secure false ceiling Tiles/profiles/boards etc. System should be copatible to use Axioms for floating ceiling installations. All level and alignment of the Grid shall be accurate. Material shall be installed in strict compliance with local codes and manufacturers recommendations and as directed by site in charge. Fire resistance as per BS 476. Tiles are not affected by humidity.
Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length. Second class teak wood.
Providing and fixing of architrave of section 75mm x 25mm as per approved design finish with same of finishing of wooden door frame.
Providing and fixing flush door shutter made out of solid core block board type, well seasoned , chemicaly treated hard wood battens and internal frame with minimum 45 mm wide wooden frame alround door shutters covered with cross bonded wooden sheets (core veneer) hot pressed and fastened on both sides of the door useing liquid phenol formaldehyde resin as per IS specifications 2202 (part-I) 1991. from manufacturer complete as per specification. 40 mm thick both side commercial
Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured).
Extra for providing rectangular/ square vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glass excluded) (overall area of door shutter to be measured): Rectangular or square
Extra if louvers (not exceeding 0.2 sqm) are provided in flush door shutters (overall area of door shutters to be measured).
Providing & fixing 1mm thick decorative high pressure laminated sheet of plain / wood grain in gloss / matt/ suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality.
Providing & fixing 1mm thick SS Kick Plate as per design & drawing, including all accessories etc. complete.
Providing and fixing IS : 12817 marked stainless steel butt hinges 125x64x1.90mm with stainless steel screws etc. complete :
Providing and fixing SS hanging floor single rubber door stopper, including all accessories etc. complete.
Providing and fixing SS Tower Bolt 300mm, including all accessories etc. complete.
Providing and Fixing Mortise cylinder lock case, 55mm backset, 72mm center distance, 24mm square forend, SS matt double cylinder, 40+40 = 80mm, non-master keyed, matt nickel hollow and SS lever handle with cylinder escutcheon. including all accessories etc. complete in all respect as per the direction of the Engineer-in-charge.
Providing and fixing of Aluminium Z Louver Casement Door on Hinge with suitable outer frame. The fixing shall be done in masonary / RCC by drilling holes inserting PVC sleeve and stainless steel counter-sunk screws of appropriate size, anchoring in the masonary. The periphery of frame shall be sealed by application of weather sealant with backer rod of colour as approved, both outside and inside between aluminium member and masonary/ RCC. The fabrication shall be done with joints mitred. including providing masking tape on the profile for safety against external scratches (masking tape to be removed only at the time of hand over).
Insulated Fire rated doorset FD 120 with 30 minutes insulation Providing and fixing of ISI marked fire doors as per IS 3614:2021, 120 minutes fire rating with 30 minutes insulation double leaf doorset tested to IS/ISO 3008. Doorset shall include grooved step frame profile of 125x75mm, made of 1.2mm GI (120GSM) and 60mm thick shutter made of 1.2mm GI (120GSM) with infill of 120kg density mineral wool. Grooved frame shall include EPDM smoke seal. Include hardwares, minimum 6nos SS ball bearing hinges of SS304 100x89x3mm, 1no of Single point Panic device and external trim with key cylinder on active leaf and 1no two point Panic device on the inactive leaf, tested as per EN1125 and CE marked. 2no of Door closer with spring size of EN 3-5, as per EN1154 and CE marked. 1no door coordinator for sequencing. 1nos vision panel 200 x 300 with 6mm clear fire rated glass and finished in desired colour of powder coating not less than 50microns including suitable anchors & fire rated puff grouting all inclusive for fixing of doorset - for staircase / exit pathway / Refuge area applications. Single Leaf doorset - Insulated Fire rated doorset (FD 120) - Staircase / exit pathway application / Refuge area.
Insulated Fire rated doorset FD 120 with 30 minutes insulation Providing and fixing of ISI marked fire doors as per IS 3614:2021, 120 minutes fire rating with 30 minutes insulation double leaf doorset tested to IS/ISO 3008. Doorset shall include grooved step frame profile of 125x75mm, made of 1.2mm GI (120GSM) and 60mm thick shutter made of 1.2mm GI (120GSM) with infill of 120kg density mineral wool. Grooved frame shall include EPDM smoke seal. Include hardwares, minimum 6nos SS ball bearing hinges of SS304 100x89x3mm, 1no of Single point Panic device and external trim with key cylinder on active leaf and 1no two point Panic device on the inactive leaf, tested as per EN1125 and CE marked. 2no of Door closer with spring size of EN 3-5, as per EN1154 and CE marked. 1no door coordinator for sequencing. 2nos vision panel 200 x 300 with 6mm clear fire rated glass and finished in desired colour of powder coating not less than 50microns including suitable anchors & fire rated puff grouting all inclusive for fixing of doorset - for staircase / exit pathway / Refuge area applications. Double Leaf doorset - Insulated Fire rated doorset (FD 120) - Staircase / exit pathway application / Refuge area.
Providing & fixing Toilet Cubicle ( Bottom Closed with Skirting) of following standard dimension which includes 600mm door size width made of heat, bacteria, water, chemical, scratch and impact resistant 12mm thick solid compact laminate panels including doors, pilasters & intermediate panels finished with approved texture/shade as per the detail drawings & as per IS 2046 (Indian Standard) and as per fire retardant BS-476/97 standard. The product should have Green Guard Certificate. This also includes providing and fixing in position necessary hardware made out of Stainless steel (Grade 304) as per manufacturer’s specifications & Engineer-in-charge's instructions like (1) Door Knob, (2) Gravity Hinges, (3) Thumb turn lockset with Occupancy indicators, (4) Coat hooks with Door stopper (5) U- Channels, (6) Adjustable foot/pedestal, (7) Top rail with Corner connector (8) Rubber noise deafening tape, (9) Screws & wall Plugs. The top fitting should consist of SS round top rail which will get fixed with pilasters, with SS panel tube holder, SS corner bend (connected with top rail) will be used on the corner of cubicle in absence of brick wall, SS wall fixing is used only on the wall which will hold the ss top rail. All screws will of 304 Grade in stainless steel with satin finish. All pilasters are supported by stainless steel Bottom Cladding. Toilet Cubicle size for approximate dimension of 1400mm x 950mm x 2050mm height/ as drawing, which includes 600mm door size width.
Accoustic door Providing and fixing of Medium duty accoustic door as per IS 16074 & IS 4351 made of pressed galvanized steel confirming to IS 277 with the following specification. Door shall be suitable for 39db, STC rating and manufcatured in ISO 9001: 2015 certfied company for quality management. Door frame shall be single rebate step grooved profile of size 125 x 75mm made out of 1.60mm (16gauge) minimum thick galvanized steel sheet. Frames shall be mitered and field assembled with self tabs. Frames to have inbuild grooved sealing system and shall be site fitted with PVC gasket as standard. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Permimeter seal of approved make Athmer/Legancy to be provided on all three sides of the frame jamb. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Frames shall be filled with puff. Door leaf shall be 60mm thick step design fully flush double skin door, insulated without vision lite. Door leaf shall be manufactured from 1.2mm (18guage) minimum thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware. The infill material shall be 120kg/sq.mt. high density rockwool/mineral wool material. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. Door shall be equiped with additional seals like auto door bottom. All doors and frames shall be finished Pure Polyster Powder coated and shall have passed minimum 500 hours of salt sprey test. Rate shall include supply and installation of frame, shutter as a complete assembly, hardware & accessories.
Supply and Installation of Blockout fabric made up of 100% Polyester with Acrylic coated of 0.32mm (PVC free) of thickness 0.50mm ±5% and wieghing 270-295gsm with openess factor of 0%. Shrinkage % Warp<0.5 & Weft <0.5,Color fastness>5-6. The Roller blind system consists of 38mm OD extruded out of Aluminium alloy with silver anodized to provide an everlasting finish and luster, the rotary unit shall be 36mm in OD incorporating a clutch mechanism composed of low – flexing braided polyster cord with nylon core, Control Ball chain shall be composed of braided nylon cord with high engineering grade plastic beads mounted co-axially on the cord. Bottom rail should be powder coated Aluminium flat bottom rail of 290 gm to finish it from the ends it should have rail end caps. The clutch will be at the tube. The return end cap bracket shall incorporate snap spring design to facilitate easy installation and removal for maintenance activities. The bracket shall be finished with a flush mounting cover on each side providing an aesthetic finish. It should handle up to 5 Kgs of material. The clutch should mount flush to the face of the bracket which minimize the light gap between the shade and the window frame.
Sliding and Folding Acoustic Partition up to False Ceiling level Providing and fixing Movable partition wall of individually operable elements with a frame construction of torsionally stiff, non-deflecting aluminum and steel profiles. Clad on both faces with MDF cover boards to DIN, top-hung vibration-free suspension for acoustic isolation, Acoustically isolated vertical profiles to ensure minimal structure-borne sound transmission. Integrated double-chamber sealing rails/ lip seals in aluminum finish. Element thickness not to exceed 88 mm. It must be possible to replace the cover panels without having to remove the elements from the track.To specifically and economically dimension the structurally bearing components to prevent flexure, partition element weights shall not exceed 32 kg/ m2 for 53 dB. Constructions exhibiting higher weights will therefore be rejected.Sound attenuation of the operable partition elements to be tested to EN 10140-3: 2010 (Annex A: Walls) and be validated by corresponding test certificates/reports. Testing and measurement to be conducted in a wall test facility compliant with EN ISO 12999-1: 2014. Calculation of the weighted sound reduction index and the spectrum adaptation terms to be in accordance with EN ISO 717-1: 2013. Complete in all respect as per the direction of Architect/ Engineer-in-charge. Extendable and retractable sealing rails, Each element to feature spring-loaded double-chamber sealing rails top and bottom operated by crank winding spindle mechanism (trapezoidal thread) for pressing against floor and ceiling track and automatically compensating for floor unevenness. Sealing rail end pieces comprised of polyurethane moldings to be fitted to ensure optimum vertical sealing between the extended sealing rails.Sealing rails to be primarily of aluminum and designed to meet the highest demands in terms of acoustic performance and stability. The elements must be inter-connected by means of a positive locking concave/ convex aluminium profile with an integrated magnetic strip and sealing lip having a linear attraction of 40N/m. Each element must have a spindle mechanism which should be connected to the spring loaded top and bottom retractable seal. The spindle mechanism should be operated manually by a bayonet connected crank handle that acts as a lock in function during cranking process. The horizontal top and bottom seals must be extended manually by crank handle and should ensure a contact pressure of 800N when the seals are completely extended. The seal spindle mechanism must be accessible while the panel is hanging for servicing and adjustment if necessary. Total disassembly of the panel frame to access internal components is not acceptable. No fixed sweep seals allowed in top and bottom of the element that would rub against the track or floor while moving the element. The telescopic element or the end closure element must open and close 120mm horizontally. Panels to be finished in fabric as per architect approval. Including Sound Barrier Partition above Operable Sliding/ Folding Partition
Providing and fixing factory made uPVC glazed/wire mesh windows/ doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and lnline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechani cally jointed duly sealed at all comers, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing confonning to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge. Wire mesh I Glazing of plain/ toughened/ laminated/ double glass unit with I without high performance coatings as per design requirements and confonning to IS: 3548 & IS: 16231 shall be paid separately. Note:- Structural design proof checked from a Government Engineering Institute, to be provided by the manufacturer for : (i) Sites with basic wind speed > 45 m/sec as per IS 875 - Part 3 (ii) Sites with structure height more than 20m for all wind speeds Fixed window I ventilator with mullion/ transom. Using R4 series with frame (64 mm & above ) x (50 mm & above) & mullion (64 mm & above) x (70 mm & above). (Height above 2.5 metre)
Providing and fixing factory made uPVC glazed/wire mesh windows/ doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and lnline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechani cally jointed duly sealed at all comers, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing confonning to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge. Wire mesh I Glazing of plain/ toughened/ laminated/ double glass unit with I without high performance coatings as per design requirements and confonning to IS: 3548 & IS: 16231 shall be paid separately. Note:- Structural design proof checked from a Government Engineering Institute, to be provided by the manufacturer for : (i) Sites with basic wind speed > 45 m/sec as per IS 875 - Part 3 (ii) Sites with structure height more than 20m for all wind speeds. Ventilator Casement window single panel with or without fixed panel with S.S. 304 friction hinges as per size and weight of sash, single point locking zinc alloy (zamak) powder coated handles. Using R1 series with frame (33 mm & above ) x (35 mm & above) & sash /mullion (33 mm & above) x (50 mm & above). (Height upto 0.90 metre).
Providing and fixing factory made uPVC glazed/wire mesh windows/ doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and lnline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechani cally jointed duly sealed at all comers, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing confonning to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge. Wire mesh I Glazing of plain/ toughened/ laminated/ double glass unit with I without high performance coatings as per design requirements and confonning to IS: 3548 & IS: 16231 shall be paid separately. Note:- Structural design proof checked from a Government Engineering Institute, to be provided by the manufacturer for : (i) Sites with basic wind speed > 45 m/sec as per IS 875 - Part 3 (ii) Sites with structure height more than 20m for all wind speeds. Casement cum fixed panel window having single casement panel at both ends & middle fixed panel with S.S 304 friction hinges as per size and weight of sash, multi-point locking system, zinc alloy (zamak) powder coated handles. Using R3 series with frame (55 mm & above) x (45 mm & above) & sash (55 mm & above) x (65 mm & above) & mullion (55 mm & above) x (65 mm & above). (Height upto 1.8 metre; each openable shutter upto 0.8m width)
Providing and fixing factory made uPVC glazed/wire mesh windows/ doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and lnline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechani cally jointed duly sealed at all comers, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing confonning to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge. Wire mesh I Glazing of plain/ toughened/ laminated/ double glass unit with I without high performance coatings as per design requirements and confonning to IS: 3548 & IS: 16231 shall be paid separately. Note:- Structural design proof checked from a Government Engineering Institute, to be provided by the manufacturer for : (i) Sites with basic wind speed > 45 m/sec as per IS 875 - Part 3 (ii) Sites with structure height more than 20m for all wind speeds. Casement cum fixed panel window having single casement panel at both ends & middle fixed panel with S.S 304 friction hinges as per size and weight of sash, multi-point locking system, zinc alloy (zamak) powder coated handles. Using R4 series with frame (64 mm & above ) x (50 mm & above) & sash (64 mm & above) x (70 mm & above) & mullion (64 mm & above) x (70 mm & above). (Height above 1.8 metre; each openable shutter upto 0.8m width)
Providing and fixing factory made uPVC glazed/wire mesh windows/ doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and lnline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechani cally jointed duly sealed at all comers, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing confonning to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge. Wire mesh I Glazing of plain/ toughened/ laminated/ double glass unit with I without high performance coatings as per design requirements and confonning to IS: 3548 & IS: 16231 shall be paid separately. Note:- Structural design proof checked from a Government Engineering Institute, to be provided by the manufacturer for : (i) Sites with basic wind speed > 45 m/sec as per IS 875 - Part 3 (ii) Sites with structure height more than 20m for all wind speeds. Casement door single panel with zinc alloy (zamak) 3D hinges, multi-point locking system with cylinder, zinc alloy (zamak) powder coated handles on both sides. Using R3 series with frame (55 mm & above) x (50 mm & above) & sash (55 mm & above) x (85 mm & above) (Height upto 2.5 metre).
Providing and fixing factory made uPVC glazed/wire mesh windows/ doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and lnline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechani cally jointed duly sealed at all comers, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing confonning to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge. Wire mesh I Glazing of plain/ toughened/ laminated/ double glass unit with I without high performance coatings as per design requirements and confonning to IS: 3548 & IS: 16231 shall be paid separately. Note:- Structural design proof checked from a Government Engineering Institute, to be provided by the manufacturer for : (i) Sites with basic wind speed > 45 m/sec as per IS 875 - Part 3 (ii) Sites with structure height more than 20m for all wind speeds. Casement door single panel with zinc alloy (zamak) 3D hinges, multi-point locking system with cylinder, zinc alloy (zamak) powder coated handles on both sides. Using R4 series with frame (64 mm & above) x (55 mm & above) & sash (64 mm & above) x (100 mm & above). (Height above 2.5 metre).
Providing and fixing factory made uPVC glazed/wire mesh windows/ doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and lnline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechani cally jointed duly sealed at all comers, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing confonning to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge. Wire mesh I Glazing of plain/ toughened/ laminated/ double glass unit with I without high performance coatings as per design requirements and confonning to IS: 3548 & IS: 16231 shall be paid separately. Note:- Structural design proof checked from a Government Engineering Institute, to be provided by the manufacturer for : (i) Sites with basic wind speed > 45 m/sec as per IS 875 - Part 3 (ii) Sites with structure height more than 20m for all wind speeds. Casement door double panel with French (False) Mullion with zinc alloy (zamak) 30 hinges, multi-point lockingsystem with cylinder, zinc alloy (zamak) powder coated handles on both sides. Using R3 series with frame (55 mm & above) x (50 mm & above) & sash (55 mm & above) x (85 mm & above) & French (False) mullion (55 mm & above) x (60 mm & above). (Height upto 2.5 metre).
Providing and fixing factory made uPVC glazed/wire mesh windows/ doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and lnline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechani cally jointed duly sealed at all comers, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing confonning to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge. Wire mesh I Glazing of plain/ toughened/ laminated/ double glass unit with I without high performance coatings as per design requirements and confonning to IS: 3548 & IS: 16231 shall be paid separately. Note:- Structural design proof checked from a Government Engineering Institute, to be provided by the manufacturer for : (i) Sites with basic wind speed > 45 m/sec as per IS 875 - Part 3 (ii) Sites with structure height more than 20m for all wind speeds.Casement door double panel with French (False) Mullion with zinc alloy (zamak) 30 hinges, multi-point lockingsystem with cylinder, zinc alloy (zamak) powder coated handles on both sides. Using R4 series with frame (64 mm & above) x (55 mm & above) & sash (64 mm & above) x (100 mm & above) & French (False) mullion (64 mm & above) x (60 mm & above). (Height above 2.5 metre).
INFILL MATERIAL IN WINDOW Providing & fixing 6 mm Toughened clear Glass/ performance glass with all required accessories & arrangement.
Providing and fixing dry cladding upto 10 metre heights with 30mm thick gang saw cut stone with (machine cut edges) of uniform colour and size upto 1mx1m, fixed to structural steel frame work and/ or with the help of cramps, pins etc. and sealing the joints with approved weather sealant as per Architectural drawing and direction of Engineer-in-charge. Cost includes all the necessary base preparations, stagings & scaffoldings etc. (The steel frame work, stainless steel cramps and pins etc. shall be paid for separately). Red sand stone - 30mm thick gang saw cut stone (Basic Price of the Granite is Rs. 524.00/sqm)
Providing and fixing dry cladding upto 10 metre heights with 30mm thick gang saw cut stone with (machine cut edges) of uniform colour and size upto 1mx1m, fixed to structural steel frame work and/ or with the help of cramps, pins etc. and sealing the joints with approved weather sealant as per Architectural drawing and direction of Engineer-in-charge. Cost includes all the necessary base preparations, stagings & scaffoldings etc. (The steel frame work, stainless steel cramps and pins etc. shall be paid for separately). Using 30mm thick Polished/ unpolished Granite of approved Shade. (Basic price of the Granite is Rs. 2,421.00/sqm)
Cement Concrete 1:2:4 Block in Brick Wall: The work involves cutting a neat and precise hole of minimum size 150mm x 150mm (or as specified) through the full depth of the brick wall using appropriate tools, followed by the preparation and placement of cement concrete (1:2:4 mix) blocks. The block shall be properly cured for at least 7 days, finished flush with the wall surface, and bonded using a cement slurry. The rate shall include labor, materials, equipment, cutting, curing, scaffolding, shuttering and making good adjacent surfaces. Work shall comply with IS 456-2000 and relevant safety standards.
Providing and fixing adjustable stainless steel cramps of approved quality, required shape and size, adjustable with stainless steel nuts, bolts and washer (total weight not less than 260 gms), for dry stone cladding fixed on frame work at suitable location, including making necessary recesses in stone slab, drilling required holes etc complete as per direction of the Engineer-in-charge.
GRC Jali:- Design, engineer, furnish, fabricate, package, deliver (to jobsite) and install: facade consisting of GRC at location as shown in elevation, supported on MS substructure , and GRC panels to mimic look of JALI AS PER DESIGN, custom designed to with stand design wind pressure of 190 kg/sq.mtr confirming to IS -875 part III. (The system must pass the proof test at 1.5 times design wind pressure i.e. 285 kg/sq.mtr without any failure). The system shall have drainage gutter profile with the possibility of drain container wherever exposed, for weather protection and complete air seal. The facade shall be designed as in architectural intent, supported with structural calculations to ensure stability under deflection . Panels shall be fixed as per design drawings. MS substructure to be designed as per drawing provided (architectural, sectional and detailed) . Intent to be maintained- the grid consistes of vertical members CHS 105 mm 2.5mm thick and interspersed by RHS 150 2.5 thick RHS at required interval meters, placed at groove intervals such that they are in tune with all the performance requirements. Form an interface between the Main structure through welded joints at roof level and come down to bear the GRC and the glass as per architectural intent.Further the structure shall carry a continous substructure made of MS to carry GRC panels in formation of a ring beam as shown in intent. This floating facade to have all the relevant drainage and water non- infiltration capacities in system inbuild. All extruded Mild steel section/brackets shall comply to IS 2062 Grade A and shall be coated with antirust paint of 275 microns comprising primer of 75 microns and two topcoat epoxy high performance architectural paint (Colour as per architect intent) of 100 microns each after shot blasting as per BS standards. The fastening materials like Anchors, Nuts, Bolts, Rivets, washers, clamps, straps etc required for fixing the framing members to the mild steel structure shall be of stainless steel 316 grade and corrosion resistant of approved make as per Architects/Consultants Specification. Provide exterior perimeter sealants where GRC cladding systems abutt adjacent materials including, but not limited to concrete shear walls, slab on grade and penetrations for ancillary equipment and accessories. The quote rate shall include all design, engineering & shop drawing approval FOR GRC JAALI AS DETAILED ABOVE from architect & consultant. The quote rate shall include all Taxes, duties, statutory obligations and safety code compliance as per PMC.(wt-06)
Removal of Unserviceable Soil with Disposal upto a suitable distance as directed by the Engineer incharge of work
Construction of sub-grade and earthen shoulders with approved material obtained from borrow pits with all lifts & leads, transporting to site, spreading, grading to required slope and compacted to meet requirement of table No. 300-2
Loosening, leveling and Compacting original ground supporting embankment to facilitate placement of first layer of embankment, scarified to a depth of 150 mm, mixed with water at OMC and then compacted by rolling so as to achieve minimum dry density as given in Table 300-2 for embankment construction.
Preparation and surface treatment of formation by removing mud and slurry, watering to the extent needed to maintain the desired moisture content, trimming to the required line, grade, profile and rolling with 8-10 t smooth wheeled roller, complete as per clause 310.
Construction of Granular Sub-Base of required grading as per design mixing in a mechanical mix plant at OMC, carriage of mixed Material to work site, spreading in uniform layers with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per clause 401. For Grading -I Material
Construction of Granular Sub-Base of required grading as per design mixing in a mechanical mix plant at OMC, carriage of mixed Material to work site, spreading in uniform layers with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per clause 401. For Grading -II Material
Providing, laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the Material with water at OMC in mechanical mix plant carriage of mixed Material by tipper to site, laying in uniform layers with paver/grader in sub-base / base course on well prepared surface and compacting with vibratory roller to achieve the desired density.
Filling of Control/Cold joint Groove with Epoxy urethane joint Sealer with suitable backer rod. 4mm x 4mm groove with 6mm dia backer rod.
Filling of Control/Cold joint Groove with Epoxy urethane joint Sealer with suitable backer rod. 8mm x 8mm groove with 10mm dia backer rod.
Supplying and fixing M15 grade precast cement concrete Kerb stones for Roadway, Sidewalls and gutters fixed with CM 1:3 fixed and finsihed in line as per direction of Engineer in charge. (The cost of PCC shall be paid extra) 300 x 250 x 100 mm Kerb Stone
Providing & Fixing Precast Saucer Drain as per requirement
Providing and laying factory made chamfered edge Cement Concrete paver block in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & Size/shape, made by table vibratory method using PU mould, laid in requried colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. Complete all as per direction of Engineer-in-charge. 80mm thick C.C. paver block of M-35 grade with approved colour design and pattern.
Providing, laying and rolling of bituminous cold mix on prepared base consisting of a mixture of unheated mineral aggregate and emulsified or cutback bitumen, including mixing in a plant of suitable type and capacity, transporting, laying, compacting and finishing to specified grades and levels. Using SS1 bitumen emulsion and 9.5 mm or 13.2 mm size aggregate.
Cleaning/clearing of land clearing of land by cutting of thick and sparse growth plants(0.25 mt thickness plants and clearing of bushes along with roots( throwing away to 1.5mtr height and 50 mtr far)
Planting of trees Digging pits of size 0.75 x 0.75x 0.75m, filling 50% of the pit with top soil and remaining 50% of pit with 1:2:3 proportion of sand (0.035cum) FYM (0.070cum) Red earth (0.105 cum) and planting of well grown tree saplings (excluding cost of plants). Normal soil
Planting of Shrubs Digging pits of size 0.45 x 0.45 x0.45m filling 50% of the pit with top soil and remaining 50% of pit with1:2:3 proportion of sand (0.007), FYM (0.014cm) red earth (0.021cm) and and planting of well grown tree saplings (excluding cost of plants). Normal soil
Planting of Creepers Digging pits of size 0.45 x 0.45 x0.45m filling 50% of the pit with top soil and remaining 50% of pit with1:2:3 proportion of sand (0.007), FYM (0.014cm) red earth (0.021cm) and planting of well grown (excluding cost of plants). Normal soil
Planting of Ground cover plants Digging of 1.0mx1.0mx0.45m area and filling 50% of the area with top soiland remaining 50% area with 1:2:3 proportion of sand (0.0375 cum),FYM (0.075 cum) red earth (0.0112 cum) and planting of well grown saplings/plants (excluding cost of plants). Normal soil
Rose garden/growing of rose plants Digging pits of 0.6x 0.6 x0.6m size and filling 50% of the pit with top soil and remaining 50% of pit with 1:6:6 proportion of sand (0.008), FYM (0.048cm) red earth (0.048cm), Neem oil cake (200 gram), Bone meal (100gram), Gingali oil (100gram),Suphala (10 gms), Rose mix (5 gms) and other plant protection chemicals and planting of different varieties of rose plants etc. (excluding cost of plants). Normal soil
Growing of Flower beds Digging of 1.0mx1.0mx0.45m area and filling 50% of the area with top soil and remaining 50% area with 1:2:3 proportion of sand (0.0375 cum),FYM (0.075 cum) red earth (0.0112 cum) and planting of well grown saplings/plants (excluding cost of plants). Normal soil
Growing of Flower beds using corms/bulbs (Cana,Tuberose,Gladiolus etc) Digging of 1.0mx1.0mx0.45m area and filling 50% of the area with top soil and remaining 50% area with 1:2:3 proportion of sand (0.0375 cum),FYM (0.075 cum) red earth (0.0112 cum) and planting of corms/bubs/tubers in the following spacing. Cana and tuberose-0.2mx0.3m,gladiolus and others-02mx0.2m((excluding cost of planting materail). Normal soil
Growing of Hedges Digging trench of size 1mx0.30mx0.45m and filling 50% of the trench with top soil and remaining 50% trench with1:2:3 proportion of sand (0.0112), FYM (0.0224cum) red earth (0.0336cum) and planting of well grown plants (excluding cost of plants). Normal soil
Lawn development : 1ST DIGGING:-Digging of the area for developing lawn including removing weeds, debris if any and breaking of clumps, watering etc. (1x1x0.45mt)
Lawn development : 2ND DIGGING:- Digging of soil by removing grass etc if any and levelling of the soil etc .. (1x1x0.45mt)
Lawn development : procurement of quality red earth/soil and heap around pit (1x1x0.15mt)
Lawn development : Supply of inputs such as sand, FYM, Red earth in 1:3:6 ratio.mixing and spreadingthe mixture to 7.50cm thickness wherever required. Red soil
Lawn development : Supply of inputs such as sand, FYM, Red earth in 1:3:6 ratio.mixing and spreadingthe mixture to 7.50cm thickness wherever required. Farm Yard manure
Lawn development : Supply of inputs such as sand, FYM, Red earth in 1:3:6 ratio.mixing and spreadingthe mixture to 7.50cm thickness wherever required. Sand
Supply of Fertiliser: Super Phosphate
Supply of Fertiliser: Neem oilcake
Supply of Fertiliser: Bone meal
Supply of Fertiliser: Potash
Supply of Fertiliser: Furadan
Supply of Fertiliser: Ammonium Sulphate
Supply of Fertiliser: Chlorophyriphos
Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS : 10910, on 12 mm dia steel bar conforming to IS: 1786, having minimum cross section as 23 mmx25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture’s permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design.
Providing and fixing 700mm long Hot Dip GI puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs for Underground & overhead tanks. 25mm dia
Providing and fixing 700mm long Hot Dip GI puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs for Underground & overhead tanks. 32mm dia
Providing and fixing 700mm long Hot Dip GI puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs for Underground & overhead tanks. 40mm dia
Providing and fixing 700mm long Hot Dip GI puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs for Underground & overhead tanks. 50mm dia
Providing and fixing 700mm long Hot Dip GI puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs for Underground & overhead tanks. 65mm dia
Providing and fixing 700mm long Hot Dip GI puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs for Underground & overhead tanks. 80mm dia
Providing and fixing 700mm long Hot Dip GI puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs for Underground & overhead tanks. 100mm dia
Providing and fixing 700mm long Hot Dip GI puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs for Underground & overhead tanks. 150mm dia
Providing and fixing 700mm long Hot Dip GI puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs for Underground & overhead tanks. 250mm dia
Diamond core drilling/cutting in RCC walls, slabs, and beams as per approved drawings and technical specifications, ensuring minimal vibration and structural integrity. The work involves cutting holes for pipe crossings as specified, including reinforcement cutting, debris removal, and edge finishing. Core cutting shall be performed using wet drilling methods to prevent dust and overheating, with proper alignment and tolerance. All cut surfaces shall be cleaned, treated with bonding agent, and made ready for pipe installation. For upto 75mm Dia pipes
Diamond core drilling/cutting in RCC walls, slabs, and beams as per approved drawings and technical specifications, ensuring minimal vibration and structural integrity. The work involves cutting holes for pipe crossings as specified, including reinforcement cutting, debris removal, and edge finishing. Core cutting shall be performed using wet drilling methods to prevent dust and overheating, with proper alignment and tolerance. All cut surfaces shall be cleaned, treated with bonding agent, and made ready for pipe installation. For 75mm to 125mm Dia pipes
Diamond core drilling/cutting in RCC walls, slabs, and beams as per approved drawings and technical specifications, ensuring minimal vibration and structural integrity. The work involves cutting holes for pipe crossings as specified, including reinforcement cutting, debris removal, and edge finishing. Core cutting shall be performed using wet drilling methods to prevent dust and overheating, with proper alignment and tolerance. All cut surfaces shall be cleaned, treated with bonding agent, and made ready for pipe installation. For 125mm to 200mm Dia pipes.
Providing and Placing in position suitable PVC water stops conforming to IS:12200 for construction/ expansion joints between two RCC members and fixed to the reinforcement with binding wire before pouring concrete etc. complete : Serrated with central bulb (225 mm wide, 8-11 mm thick)
Providing, fabricating installation and fixing of LED LIT Signage mantioning 'IISc AMENITY COMPLEX' 450mm height acrylic letters sides made of 5mm thick acrylic sheet of required size and shape with neatly fabricated joints properly grinded with all corners rubbed and polished. Face Acrylic Letters lit with Rich Samsung LED Illuminations. The Base of the Letters to be screwed to perforated iron sheets and fixing complete as per directions of engineer. Signage will be done in three languages English, Hindi & Kannada.
STAINLESS STEEL NAME PLATE WITH PICTOGRAM Providing and fixing of Steel Name plate,304 Grade,16 Guage with engraved texts and cutout pictograms .Fixing provision using 3M VHP double sided tape as required. Signage Size 14 "x 14" inch, all complete as per direction of Engineer-in-charge & Architect.
STEEL DIRECTIONAL HANGING SIGNAGE Providing and fixing of Steel directional hanging Signage,304 Grade ,16 Guage with engraved texts and cutout pictograms .Fixing provision SS Wires as required. Signage Size 48 "x 10" inch, all complete as per direction of Engineer-in-charge & Architect.
FLOOR DIRECTORY Providing and fixing of Steel directory wall mounted Signage,304 Grade ,16 Guage with engraved texts and cutout pictograms,directions signs .Fixing provision SS Studs/ 3M VHP Tape as required. Signage Size 14 "x 14" inch all complete as per direction of Engineer-in-charge & Architect.
FIRE EVACUATION MAP / SIGN. Providing and fixing of Clear Acrylic sandwich frame of 3mm & 2mm acrylic with Evacuation Plan Printed on photoluminescent media and inserted between the two frames. Should be fixed on the wall using 4 Screw/ SS studs. Size 12 inch x 17 all complete as per direction of Engineer-in-charge & Architect.
FIRE SAFETY SIGNAGE: Providing fabricating and fixing of Steel signage sheet at base with engraved plan Complete including fixing on wall with screws and washerzs all complete as per direction of Engineer-in-charge & Architect. Photoluminescent, Fire Hose Reel - 10"x8"
Providing fabricating and fixing of Steel signage sheet at base with engraved plan Complete including fixing on wall with screws and washerzs all complete as per direction of Engineer-in-charge & Architect. Photoluminescent, Fire Exit / Escape Sign - 18"x6"
Providing fabricating and fixing of Steel signage sheet at base with engraved plan Complete including fixing on wall with screws and washerzs all complete as per direction of Engineer-in-charge & Architect. Photoluminescent, Floor Level - 18"x6"
Providing fabricating and fixing of Steel signage sheet at base with engraved plan Complete including fixing on wall with screws and washerzs all complete as per direction of Engineer-in-charge & Architect. Photoluminescent, Fire Alarm Call Point - 10"x8"
Providing fabricating and fixing of Steel signage sheet at base with engraved plan Complete including fixing on wall with screws and washerzs all complete as per direction of Engineer-in-charge & Architect. Photoluminescent, Fire do not use lift- 10"x8"
Providing fabricating and fixing of Steel signage sheet at base with engraved plan Complete including fixing on wall with screws and washerzs all complete as per direction of Engineer-in-charge & Architect. Photoluminescent Signs, Fire Extinguishers - 10"x8"
Providing and fixing white vitreous china extended wall mounting water closet of size 780x370x690 mm of approved shape including providing & fixing white vitreous china cistern with dual flush fitting, of flushing capacity 3 litre/ 6 litre (adjustable to 4 litre/ 8 litres), including seat cover, and cistern fittings, nuts, bolts and gasket etc complete. (Make/ Model :- Jaquar-CNS-WHT-353SPPZ or approved equivalent)
Providing and fixing white vitreous china battery based infrared sensor operated urinal of approx. size 610 x 390 x 370 mm having pre & post flushing with water (250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer-in-charge. (Make/ Model :- Jaquar-URS-WHT-13255 or approved equivalent)
Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required: using White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer. (Make/ Model :- Jaquar-CNS-WHT-705 or approved equivalent)
Extra for providing opening of required size & shape for wash basin/kitchen sink in kitchen platform, vanity counter and similar location in Granite, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.
Providing and fixing granite stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in- charge and finished smooth.
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS:13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required : Kitchen sink with drain board. 510x1040 mm bowl depth 200 mm : ( Make/ Model:- Neelkanth-NK SBSD17 G/M or approved equivalent)
Providing and fixing Bidet spray made of Stainless steel with all concealed fitting arrangements & all necessary accesories complete - Class Premium Makes :-Jaquar-ALD-CHR-573 or approved equivalent.
Providing and fixing G.I. inlet connection for flush pipe connecting with W.C. pan.
Providing and fixing CP Brass 32mm size Bottle Trap of approved quality & make and as per the direction of Engineer - in - charge. (Make/ Model :- ALD-CHR-769LX190 or approved equivalent)
Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. Semi rigid Pipe. 32 mm dia.
Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : * 100 mm inlet and 75 mm outlet * Sand cast iron S&S as per IS - 3989
Providing and fixing in position 25 mm diameter mosquito proof coupling of approved municipal design.
Providing and fixing 600x450 mm beveled edge mirror of superior glass(of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
Providing and fixing Liquid soap dispenser made of Stainless steel with all concealed fitting arrangements & all necessary accesories complete - Class Premium. (Make/ Model :- Jaquar AKP-CHR-35735P or approved equivalent)
Providing and fixing Pillar cock with high neck with 265mm Extended body made of Stainless steel with all concealed fitting arrangements & all necessary accesories complete - Class Premium. (Make/ Model :- Jaquar SOL-CHR-6011 or approved equivalent)
Providing and fixing Angle cock with wall flange made of Stainless steel with all concealed fitting arrangements & all necessary accesories complete - Class Premium. (Make/ Model :- Jaquar FUS-29053 or approved equivalent).
Providing and fixing Bib cock Two way with wall flange made of Stainless steel with all concealed fitting arrangements & all necessary accesories complete - Class Premium. (Make/ Model :- Jaquar FUS-29041 or approved equivalent)
Providing and fixing Toilet paper holder made of Stainless steel with all concealed fitting arrangements & all necessary accesories complete - Class Premium. ( Make/ Model :- Jaquar or approved equivalent)
Providing and fixing Stainless Steel Grab Bar 600 mm Long with all concealed fitting arrangements & all necessary accesories complete - Class Premium. ( Make/ Model :- Jaquar AHS-CHR-1507 or approved equivalent)
Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete.
Providing and fixing SS wall mounted Hand Drier fixed in position by means of C.P. screws and rawl plugs embedded in the walls complete including cutting and making good the walls wherever required. ( Make/ Model :- Jaquar HDR-SSF-AK2803D or approved equivalent)
Providing and fixing Heavy class SS grating with cockroach trap of approved design including setting in floor with cement motor to match with floor finish as per architect requirement. Size 100mm x 100mm.
Supplying ...litres capacity vertical/horizontal type wall mounting Electrical water heater with 22 SWG copper/SS sheet metal inner Container tinned inside Fiber body outside, filled with glass wool between inner and outer container for thermal insulation complete. The inlet and outlet pipes so arranged that water flow inside results in water to flow out from the inner container without turbulence. The Inner container shall have direct immersion type copper tube nickel plate. 2kW capacity element with a neon indicator fitted with 20A capacity 25 to 85 degree Centigrade range thermostat. The water heater shall completely be wired with 40/0.0076 inch 3 core copper flexible wire of 1.5 meters length and the outer container provided with heavy gauge brackets for wall mounting. 5 Star With Fibre body. 25 ltrs capacity ( Make/ Model :- Jaquar META Digital or approved equivalent)
Making connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing tee, including cutting and threading the pipe etc. complete : 25 to 40 mm nominal bore
Making connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing tee, including cutting and threading the pipe etc. complete : 50 to 80 mm nominal bore
Providing and fixing Brass full way valve gate with C.I. wheel of approved quality (screwed end) : 32 mm nominal bore
Providing and fixing Brass full way valve gate with C.I. wheel of approved quality (screwed end) : 40 mm nominal bore
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete. 20 mm nominal bore
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete . 25 mm nominal bore
Supplying, installing , testing and commissioning of PN16 CI butterfly valves of confirming to IS 13039 with necessary nuts & bolts etc., complete ---- etc., complete as per specificaiton with all lead and lift, loading unloading, labour, hire charges of machineries and all such incidental charges necessary for successful completion of work and as per directions of the Engineer-incharge of the work. 50 mm dia
Supplying, installing , testing and commissioning of PN16 CI butterfly valves of confirming to IS 13039 with necessary nuts & bolts etc., complete ---- etc., complete as per specificaiton with all lead and lift, loading unloading, labour, hire charges of machineries and all such incidental charges necessary for successful completion of work and as per directions of the Engineer-incharge of the work. 65 mm dia
Providing and fixing gun metal non- return valve of approved quality (screwed end) : 40 mm nominal bore - Vertical
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall. 15 mm nominal dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall. 20 mm nominal dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall. 25 mm nominal dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall. 32 mm nominal dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall. 40 mm nominal dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall. 50 mm nominal dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 15 mm nominal dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 20 mm nominal dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 25 mm nominal dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work. 65 mm nominal dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work. 80 mm nominal dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work. 100 mm nominal dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work. 150 mm nominal dia Pipes
Cutting holes up to 15x15 cm in R.C.C. floors and roofs for passing drain pipe etc. and repairing the hole after insertion of drain pipe etc. with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including finishing complete so as to make it leak proof.
Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover 180 x 150 mm size P type & With Non Modular common burnt clay bricks of designation 3.5 & frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design:
Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors :
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes 75 mm diameter
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes 100 mm diameter
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes of 150mm dia conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes.
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone-III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design : Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) With common burnt clay (non modular) bricks of class designation 3.5
Extra for depth for manholes:Size 90x80 cm With common burnt clay (non modular) bricks of class designation
Constructing brick masonry chamber for underground C.I. inspection chamber and bends with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg), R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 fine sand : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand), finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design: Inside dimensions 455x610 mm and 45 cm deep for single pipe line : With common burnt clay (non modular) bricks of class designation 3.5
Extra for depth beyond 45 cm of brick masonry chamber : For 455x610 mm size With common burnt clay (non modular) bricks of class designation 3.5
Constructing brick masonry chamber for underground C.I. inspection chamber and bends with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) C.I. cover with frame (light duty) 500X700 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg), R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 fine sand : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand), finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design: Inside dimensions 500x700 mm and 45 cm deep for pipe line with one or two inlets :With common burnt clay (non modular) bricks of class designation 3.5
Extra for depth beyond 45 cm of brick masonry chamber : For 500x700 mm size With common burnt clay (non modular) bricks of class designation 3.5
Providing and fixing Sewer (SWR) pipes, including all fittings, This includes jointing of pipes & fittings with one step solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. 75mm nominal dia pipes
Providing and fixing Sewer (SWR) pipes, including all fittings, This includes jointing of pipes & fittings with one step solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. 110mm nominal dia pipes
Providing and fixing Sewer (SWR) pipes, including all fittings, This includes jointing of pipes & fittings with one step solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. 150mm nominal dia pipes
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 150 mm dia. R.C.C. pipe
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 250 mm dia. R.C.C. pipe
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 300 mm dia. R.C.C. pipe
Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete. 450 mm Dia
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) up to haunches of S.W. pipes including bed concrete as per standard design : 150 mm dia. R.C.C. pipe
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) up to haunches of S.W. pipes including bed concrete as per standard design : 250 mm dia. R.C.C. pipe
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) up to haunches of S.W. pipes including bed concrete as per standard design : 300 mm dia. R.C.C. pipe
Supply and fixing of Horizontal Mechanical Woltman type hemetically sealed water meters with copper Glass register with IP 68 protection. The meter shall be removable mechanism type manufactured as ISO 4064-1: 1993 with MID certification. The meters shall be capable of transmitting consumption data on daily basis to central server through GSM/GPRS. The meter interface unit shall be fitted to the meter without wire. The consumption data shall be collected , stored and analysed by data logger. The data logger should provide data like flow rate, total flow, consumption analyses, reverse flow, meter tampering, daily flow distribution, leakage detection. The data logger shall also send alams on blocked meter, flow rate above limit pressure below and above limit. 50 mm
Supply and fixing of Horizontal Mechanical Woltman type hemetically sealed water meters with copper Glass register with IP 68 protection. The meter shall be removable mechanism type manufactured as ISO 4064-1: 1993 with MID certification. The meters shall be capable of transmitting consumption data on daily basis to central server through GSM/GPRS. The meter interface unit shall be fitted to the meter without wire. The consumption data shall be collected , stored and analysed by data logger. The data logger should provide data like flow rate, total flow, consumption analyses, reverse flow, meter tampering, daily flow distribution, leakage detection. The data logger shall also send alams on blocked meter, flow rate above limit pressure below and above limit. 80 mm
Providing and fixing of ductile iron double flanged swing check valves with slanted seat or with lever weight with straight disc, with metallic corrosion proof and wear resistant seat faces with nickel overlay micro - finished/ Integral seat with body and disc in Ductile Iron in GGG 40/50 shaft of stainless steel and bearings of zinc free bronze and surface protection with epoxy liquid of GSK quality etc complete For PN 10.0. 50 mm
Providing and fixing in position pre-cast R.C.C. manhole cover and frame of required shape and approved quality. H D - 20. Circular shape 560 mm internal diameter
Design, manufacturing, supply, errection, trail running, performance test and commissioning of centrifugal pump of approved make conforming to IS:12699 (1989) (Reaffirmed 2009) having specified pump output under specified operating head coupled to HT/LT ,WITH motor of adeuate HP rating operating at suitable KV with flexible coupling, self water lubricated thrust bearings, discharge Tee with flanged end for connecting delivery pipe with all other standard accessories and saftey device& all necessary works complete as per specification. UPTO 3500 HP (Transfer Pump)
Supply, installation, testing & commissioning of Submersible, non clogging type pumps capable of handling solids minimum 20 mm having CI casing & impeller with SS Shaft complete with mechanical seal & all accessories,motor of required capacity. Delivery header with isolation valve, pressure gauge on delivery line with isolation cock. Pumps shall have following duty. Plant room sump pump (1W+1S) Flow rate = 6.0 m3/hr Head = 12-15 Mts
Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge.
Supplying, filling, spreading &leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer in-charge.
Supplying, filling, spreading &leveling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer -in-charge.
Gravel packing in tube well construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer in-charge.
Providing and fixing factory made precast RCC perforated drain covers, having concrete of strength not less than M-25, of size 1000 x 450 x 50 mm, reinforced with 8 mm dia four nos longitudinal & 9 nos cross sectional T.M.T. hoop bars, including providing 50 mm dia perforations @ 100 to 125 mm c/c, including providing edge binding with M.S. flats of size 50 mm x 1.6 mm complete, all as per direction of Engineer-in-charge.
Supplying, assembling, lowering and fixing in vertical position in bore well, ERW (Electric Resistance Welded) FE 410 mild steel screwed and socketed/plain ended casing pipes of required dia, conforming to IS: 4270,of reputed & approved make, including painted with outside surface with two coats of anticorrosive paint of approved brand and manufacture, including required hire & labour charges, fittings & accessories, all complete, for all depths, as per direction of Engineer-in-charge. 200 mm nominal size dia having minimum wall thickness 5.40 mm
Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by "V" notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge.
Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for borewell of: 200 mm dia
Providing and laying 100mm thick side wall & bottom slab of 600mm width for drain with opening using M20 concrete reinforced with Micro Alloyed High carbon steel with 3mm - 3ply wired steel @ 150mm spacing jointed in CM 1:3 proportion and nicely finished Including providing holes in the walls wherever necessary including of labour, materials, scaffolding, usage of machinery, curing, lead and lift charges etc, Complete.
Providing and laying 100mm thick pre-cast cover slabs over Road side drains / utility ducts / Rain water harvesting pit of width not exceeding 1000 mm using M20 concrete reinforced with TMT bars Fe 550 @ 6kg/ m2, slabs jointed in CM 1:3 proportion and nicely finished Including providing holes in the Cover slabs wherever necessary for easy drainage of surface water including of labour, materials, scaffolding, usage of machinery, curing, lead and lift charges etc, Complete.
Supply, Erection, testing and commissioning of AMF panel suitable for .200 kVA....kVA DG set. The panel is of cubical type base/floor mounting control panel with hinged doors, undrilled bottom gland plate, aluminium Bus Bar with the accommodation for .....A 4 pole contactor for alternator with thermal O/L relay,..... A 4 pole contactor for mains, HRC fuse for short circuit protection, Microprocessor based AMF module with supply failure timer, Restoration timer, 3 impulse automatic engine start/stop logic, Mains/generator voltage, ....capacity bypass switch and frequency sensing, PCC 1301controller with water temperature/Lube oil pressure/ engine speed, Voltage/ampere/Frequency/ kVA, Running-hour count, No of starts, Fault indication, over / under speed, Fails to start, Low oil pleasure, High engine temperature, Under/over voltage, over current, Earth fault relay, with indications for Mains on, Load on Mains, Battery charger on Push buttons AMF module by pass Mode, Battery charger unit with inbuilt Auto/Manual and Flat/Boost facility. The complete set shall have sufficient safety and adhere to NEC, NBC 2016, IEC, CPWD specifications, PCB norms and KSGEI Acts and Rules.
EXHAUST PIPING Providing, fixing, installing, testing and commissioning of 125 mm dia exhaust pipe of following dia fabricated out of 6 mm thick MS plate and all fixing accessories and hardwires. Supplying and fixing of first layer of 25 mm thick Ceramic wool (96 Kg. Per cubic RMT density) and second layer of 75 mm thick Rockwool insulation (of 150 Kg. Per cubic RMT density) over the exhaust pipes of following diameter including cladding, wrapped in chicken mesh with aluminium sheet of 26 SWG and covering from outside complete, as required. Exhaust pipe shall be inclusive of required supporting structure including heat resistant paint etc complete in all respect as required for successful operation of DG set in compliance with CPCB norms. Expansion bellows shall be provided at necessary location.
Supplying, laying, tesing & commissioning of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification in cable trays / ducts clamped to wall with suitable clamps including, saddles fixing bolts, connecting testing and commissioning complete in all respect as required as per site conditions.12 core 2.5 sq.mm shielded Cu. Cable
Supplying, laying, tesing & commissioning of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification in cable trays / ducts clamped to wall with suitable clamps including, saddles fixing bolts, connecting testing and commissioning complete in all respect as required as per site conditions.4 core 2.5 sq.mm Cu arm. Cable
Supplying, laying, tesing & commissioning of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification in cable trays / ducts clamped to wall with suitable clamps including, saddles fixing bolts, connecting testing and commissioning complete in all respect as required as per site conditions.2 core 4 sq.mm Cu arm. Cable
Supplying, laying, tesing & commissioning of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification in cable trays / ducts clamped to wall with suitable clamps including, saddles fixing bolts, connecting testing and commissioning complete in all respect as required as per site conditions.12 core 1.5 sq.mm shielded Cu. Cable
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed copper conductor armoured cables of 1100 volt grade including supplying and fixing of Copper crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions.4 core 2.5 sq.mm Cu arm.
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed copper conductor armoured cables of 1100 volt grade including supplying and fixing of Copper crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions.12 core 2.5 sq.mm Cu arm.
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed copper conductor armoured cables of 1100 volt grade including supplying and fixing of Copper crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions.2 core 4 sq.mm Cu arm.
SH-2 LT PANELS The rates for the distribution boards apart from the Breakers and instruments shall also include the following :Supporting rigid steel framework.Cubicle type, 16 gauge CRCA sheet steel enclosed & Type 3b modular construction.Complete with interconnections and distribution bus bars along with connector strip.Proper bonding to earth as per standard.Painting/lettering on Breakers and distribution boards, the location they serve, providing on each panel its circuit diagram.Providing cable clamps / supports within distribution boards cable alley.All MCB’s shall be of minimum 10 KA breaking capacity.Distribution panels / bus ducts / rising mains shall be Powder Coated with RAL-7032 shade or as approved.Following Degree of protection for all type of distribution panel enclosure shall be as per IS:13947-1993:IP 44 for indoor panels.IP 54 for kitchen and laundry panels.IP 65 for outdoor panels.Current density of aluminium shall be 1 sq mm for 1.0 Amps for rated current of bus bars.GI earth bus shall be provided through out the length of each board as per schematic diagram.All measuring instruments (Meters) shall be of digital electronic (LED Type) of approved make.All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire.All panels shall have provision of the Pad locking of MCCB’s handles in “OFF” Position.Additional set of C.T.s, potential free contacts, connectors, contactors with wiring etc are to be provided for BAS including space required for various transducers in main LT panel sections, etc. Only transducers shall be supplied by BAS tenderer.All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive (motor) load shall be of type “C” characteristic and discharge lamps and UPS etc. shall be of type D characteristic. All incoming and outgoing air circuit breakers shall be placed on middle portion of the vertical in single tier formation.CT’s shall be properly mounted and clamped. Connection of CT’s for measuring instrument / relays shall be done through connector / terminals.Model, current capacity location and frame size of switchgear shall be written inside of the panel doors with paint / permanent marker as approved shop drawings / site requirement.All electronic meters with RS - 485 port and ACB's communication port shall be wired with shielded wire upto separate marshalling box for termination of all control wires and communication system.Compliance to the technical specifications.Design, fabrication, assembling, wiring and supply, installation, testing and commissioning of Main LT Panels fabricated out of (load bearing member of 2mm and non load bearing member 1.6 mm thick) CRCA sheet steel in cubicle compartmentised modular 4b construction, free standing floor mounted with bottom cable entry, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels.All Panels shall conform to relevant IEC/IS (viz. IEC 61439, IS 8623 etc.) standard including the earth leakage protection complete as per specification & drawings as required and as given below. All internal wiring in the panels shall be carried out using high temperature FRLSZH wires.All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The busbars shall be insulated with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports suitably spaced shall be used. Hinged doors with padlocking facility shall be provided on all outgoing feeders with switch handles lockable in OFF position.Space provision @ 15% for future expansion All MCCBs shall be current limiting type microprocessor based, rated for requisite specified Service short circuit breaking capacity (Ics suitable for isolation conforming to latest IEC947-2/IS13947-2 duly marked on MCCB, at operating voltage (Ue) of 415 V, insulation voltage (Ui) 750 V and with trip free mechanism, handle indicating ON/OFF/tripped position. The breaking capacity as mentioned shall be Ics values.All MCCB has inbuilt feature of earth fault protection.MCCBs shall be compact (As the Engineer may decide), suitably designed to provide protection of motors, cables, busbars to suit rated current, unbalanced power distribution as required and with front adjustable overload and short circuit releases and minimum electrical endurance of the order of 7000-8000 operation cycles for capacity of 100-250 amps.MCBs shall conform to IEC898/IS 8828 (latest) and, with breaking capacity 9/10 kA at 415 V AC, current limiting type lower powerloss appx 40 - 70% of the stipulated value and suitable for magnetic releases operating between 3 to 5 times rated current for normal power distribution application and 5 to 10 times rated current for moter application duty, with minimum Electrical endurance of the order of 20000 operation cycles.Main Distribution Board-1 (L,P & HVAC PANEL) (ELECTRICAL ROOM) (GROUND FLOOR)Incomer From Existing S/S comprising of :630 Amps 4 POLE MCCB with Microprocessor based releases along with 630A 4 Pole Contactor. The release shall have following protection: • Over current• Short Circuit (S), • Ground Fault (G),Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port equivalent to Schneider make EM6436H with 630/5, 5 VA, CL 1, 3 No. CTs - 1 Set,ON / OFF / TRIP indicating lights with control MCB - 3 Set,RYB Phase indicating light protected by 2 amps MCB’s - 3 Set,Class – B+C surge arrestor (Lines to Neutral) & (Neutral to Earth) suitable for 3 phases with protection fuse.Incomer From New (200kVA) DG Set comprising of :400 Amps 4 POLE MCCB with Microprocessor based releases along with 400A 4 Pole Contactor. The release shall have following protection: • Over current• Short Circuit (S), • Ground Fault (G), - 1 Set,ON / OFF / TRIP indicating lights with control MCB - 3 Set,RYB Phase indicating light protected by 2 amps MCB’s - 3 Set.Class – B+C surge arrestor (Lines to Neutral) & (Neutral to Earth) suitable for 3 phases with protection fuse.Bus Bar comprising of :800 Amps 4P Aluminium Bus Bar with colour coded heat shrinkable sleeves,Outgoing comprising of :125 Amps FP MCCB with Thermal magnetic based releases for SC & OL protections etc. - 2 Set,100 Amps FP MCCB with Thermal magnetic based releases for SC & OL protections etc. - 5 Set,100 amps FP MCCB with Thermal Magnetic based releases for SC & OL Protechtions along with 100 Amps 4 Pole Contactor - 1 Set,63 Amps 4P MCB, C Curve - 6 No.40 Amps 4P MCB, C Curve - 7 No.32 Amps 4P MCB, C Curve - 1 No.Notes:-All breakers MCCB shall be minimum 25 kA rating & MCB 10 kA with Icu = Ics.All Outgoing feeders shall be provided with Dual Energy Meter for VAF, PF, Power & eneregy with RS - 485 port equivalent to Schneider make EM6438H and all meters wired at one point for BMS compatibility.
LT PANELS The rates for the distribution boards apart from the Breakers and instruments shall also include the following :Supporting rigid steel framework.Cubicle type, 16 gauge CRCA sheet steel enclosed & Type 3b modular construction.Complete with interconnections and distribution bus bars along with connector strip.Proper bonding to earth as per standard.Painting/lettering on Breakers and distribution boards, the location they serve, providing on each panel its circuit diagram.Providing cable clamps / supports within distribution boards cable alley.All MCB’s shall be of minimum 10 KA breaking capacity.Distribution panels / bus ducts / rising mains shall be Powder Coated with RAL-7032 shade or as approved.Following Degree of protection for all type of distribution panel enclosure shall be as per IS:13947-1993:IP 44 for indoor panels.IP 54 for kitchen and laundry panels.IP 65 for outdoor panels.Current density of aluminium shall be 1 sq mm for 1.0 Amps for rated current of bus bars.GI earth bus shall be provided through out the length of each board as per schematic diagram.All measuring instruments (Meters) shall be of digital electronic (LED Type) of approved make.All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire.All panels shall have provision of the Pad locking of MCCB’s handles in “OFF” Position.Additional set of C.T.s, potential free contacts, connectors, contactors with wiring etc are to be provided for BAS including space required for various transducers in main LT panel sections, etc. Only transducers shall be supplied by BAS tenderer.All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive (motor) load shall be of type “C” characteristic and discharge lamps and UPS etc. shall be of type D characteristic. All incoming and outgoing air circuit breakers shall be placed on middle portion of the vertical in single tier formation.CT’s shall be properly mounted and clamped. Connection of CT’s for measuring instrument / relays shall be done through connector / terminals.Model, current capacity location and frame size of switchgear shall be written inside of the panel doors with paint / permanent marker as approved shop drawings / site requirement.All electronic meters with RS - 485 port and ACB's communication port shall be wired with shielded wire upto separate marshalling box for termination of all control wires and communication system.Compliance to the technical specifications.Design, fabrication, assembling, wiring and supply, installation, testing and commissioning of Main LT Panels fabricated out of (load bearing member of 2mm and non load bearing member 1.6 mm thick) CRCA sheet steel in cubicle compartmentised modular 4b construction, free standing floor mounted with bottom cable entry, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels.All Panels shall conform to relevant IEC/IS (viz. IEC 61439, IS 8623 etc.) standard including the earth leakage protection complete as per specification & drawings as required and as given below. All internal wiring in the panels shall be carried out using high temperature FRLSZH wires.All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The busbars shall be insulated with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports suitably spaced shall be used. Hinged doors with padlocking facility shall be provided on all outgoing feeders with switch handles lockable in OFF position.Space provision @ 15% for future expansion All MCCBs shall be current limiting type microprocessor based, rated for requisite specified Service short circuit breaking capacity (Ics suitable for isolation conforming to latest IEC947-2/IS13947-2 duly marked on MCCB, at operating voltage (Ue) of 415 V, insulation voltage (Ui) 750 V and with trip free mechanism, handle indicating ON/OFF/tripped position. The breaking capacity as mentioned shall be Ics values.All MCCB has inbuilt feature of earth fault protection.MCCBs shall be compact (As the Engineer may decide), suitably designed to provide protection of motors, cables, busbars to suit rated current, unbalanced power distribution as required and with front adjustable overload and short circuit releases and minimum electrical endurance of the order of 7000-8000 operation cycles for capacity of 100-250 amps.MCBs shall conform to IEC898/IS 8828 (latest) and, with breaking capacity 9/10 kA at 415 V AC, current limiting type lower powerloss appx 40 - 70% of the stipulated value and suitable for magnetic releases operating between 3 to 5 times rated current for normal power distribution application and 5 to 10 times rated current for moter application duty, with minimum Electrical endurance of the order of 20000 operation cycles.MDB-1 (RESTAURANT PANEL) (GROUND FLOOR)Incomer comprising of :125 amps FP MCCB with Thermal magnetic based release for O/L & S/C proetction - 1 Set,Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port equivalent to Schneider make EM6436H with 125/5, 5 VA, CL 1, 3 No. CTs - 1 Set,ON / OFF / TRIP indicating lights with control MCB - 3 Set,RYB Phase indicating light protected by 2 amps MCB’s - 3 Set.Class – B+C surge arrestor (Lines to Neutral) & (Neutral to Earth) suitable for 3 phases with protection fuse,Bus Bar comprising of :150 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable sleeves,Outgoing comprising of :40 Amp 4P MCB with Digital Multifunction meter with RS - 485 port equivalent to Schneider make EM6436H with 40/5 15 VA, CL 1, 3 No. CTs - 1 No.,40 Amps 4P MCB, C Curve - 1 No.16 Amps DP RCBO, 30mA Sensivity - 21 No.32 Amps DP RCBO, 30mA Sensivity - 2 No.32 Amps 4P RCBO, 30mA Sensivity - 2 No.Notes:-All breakers MCCB shall be minimum 25 kA rating & MCB 10 kA with Icu = Ics.
LT PANELS The rates for the distribution boards apart from the Breakers and instruments shall also include the following :Supporting rigid steel framework.Cubicle type, 16 gauge CRCA sheet steel enclosed & Type 3b modular construction.Complete with interconnections and distribution bus bars along with connector strip.Proper bonding to earth as per standard.Painting/lettering on Breakers and distribution boards, the location they serve, providing on each panel its circuit diagram.Providing cable clamps / supports within distribution boards cable alley.All MCB’s shall be of minimum 10 KA breaking capacity.Distribution panels / bus ducts / rising mains shall be Powder Coated with RAL-7032 shade or as approved.Following Degree of protection for all type of distribution panel enclosure shall be as per IS:13947-1993:IP 44 for indoor panels.IP 54 for kitchen and laundry panels.IP 65 for outdoor panels.Current density of aluminium shall be 1 sq mm for 1.0 Amps for rated current of bus bars.GI earth bus shall be provided through out the length of each board as per schematic diagram.All measuring instruments (Meters) shall be of digital electronic (LED Type) of approved make.All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire.All panels shall have provision of the Pad locking of MCCB’s handles in “OFF” Position.Additional set of C.T.s, potential free contacts, connectors, contactors with wiring etc are to be provided for BAS including space required for various transducers in main LT panel sections, etc. Only transducers shall be supplied by BAS tenderer.All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive (motor) load shall be of type “C” characteristic and discharge lamps and UPS etc. shall be of type D characteristic. All incoming and outgoing air circuit breakers shall be placed on middle portion of the vertical in single tier formation.CT’s shall be properly mounted and clamped. Connection of CT’s for measuring instrument / relays shall be done through connector / terminals.Model, current capacity location and frame size of switchgear shall be written inside of the panel doors with paint / permanent marker as approved shop drawings / site requirement.All electronic meters with RS - 485 port and ACB's communication port shall be wired with shielded wire upto separate marshalling box for termination of all control wires and communication system.Compliance to the technical specifications.Design, fabrication, assembling, wiring and supply, installation, testing and commissioning of Main LT Panels fabricated out of (load bearing member of 2mm and non load bearing member 1.6 mm thick) CRCA sheet steel in cubicle compartmentised modular 4b construction, free standing floor mounted with bottom cable entry, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels.All Panels shall conform to relevant IEC/IS (viz. IEC 61439, IS 8623 etc.) standard including the earth leakage protection complete as per specification & drawings as required and as given below. All internal wiring in the panels shall be carried out using high temperature FRLSZH wires.All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The busbars shall be insulated with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports suitably spaced shall be used. Hinged doors with padlocking facility shall be provided on all outgoing feeders with switch handles lockable in OFF position.Space provision @ 15% for future expansion All MCCBs shall be current limiting type microprocessor based, rated for requisite specified Service short circuit breaking capacity (Ics suitable for isolation conforming to latest IEC947-2/IS13947-2 duly marked on MCCB, at operating voltage (Ue) of 415 V, insulation voltage (Ui) 750 V and with trip free mechanism, handle indicating ON/OFF/tripped position. The breaking capacity as mentioned shall be Ics values.All MCCB has inbuilt feature of earth fault protection.MCCBs shall be compact (As the Engineer may decide), suitably designed to provide protection of motors, cables, busbars to suit rated current, unbalanced power distribution as required and with front adjustable overload and short circuit releases and minimum electrical endurance of the order of 7000-8000 operation cycles for capacity of 100-250 amps.MCBs shall conform to IEC898/IS 8828 (latest) and, with breaking capacity 9/10 kA at 415 V AC, current limiting type lower powerloss appx 40 - 70% of the stipulated value and suitable for magnetic releases operating between 3 to 5 times rated current for normal power distribution application and 5 to 10 times rated current for moter application duty, with minimum Electrical endurance of the order of 20000 operation cycles.METER BOARD-1 (SHOP AREA) (ELECTRICAL ROOM) (GROUND FLOOR)Incomer comprising of :100 amps FP MCCB with Thermal magnetic based release for O/L & S/C proetction - 1 Set,Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port equivalent to Schneider make EM6436H with 100/5, 5 VA, CL 1, 3 No. CTs - 1 Set,ON / OFF / TRIP indicating lights with control MCB - 3 Set,RYB Phase indicating light protected by 2 amps MCB’s - 3 Set.Class – B+C surge arrestor (Lines to Neutral) & (Neutral to Earth) suitable for 3 phases with protection fuse.Bus Bar comprising of :150 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable sleeves,Outgoing comprising of :32 Amp 4P MCB with Digital Multifunction meter with RS - 485 port equivalent to Schneider make EM6436H with 32/5 15 VA, CL 1, 3 No. CTs - 12 No.Notes:-All breakers MCCB shall be minimum 25 kA rating & MCB 10 kA with Icu = Ics.
LT PANELS The rates for the distribution boards apart from the Breakers and instruments shall also include the following :Supporting rigid steel framework.Cubicle type, 16 gauge CRCA sheet steel enclosed & Type 3b modular construction.Complete with interconnections and distribution bus bars along with connector strip.Proper bonding to earth as per standard.Painting/lettering on Breakers and distribution boards, the location they serve, providing on each panel its circuit diagram.Providing cable clamps / supports within distribution boards cable alley.All MCB’s shall be of minimum 10 KA breaking capacity.Distribution panels / bus ducts / rising mains shall be Powder Coated with RAL-7032 shade or as approved.Following Degree of protection for all type of distribution panel enclosure shall be as per IS:13947-1993:IP 44 for indoor panels.IP 54 for kitchen and laundry panels.IP 65 for outdoor panels.Current density of aluminium shall be 1 sq mm for 1.0 Amps for rated current of bus bars.GI earth bus shall be provided through out the length of each board as per schematic diagram.All measuring instruments (Meters) shall be of digital electronic (LED Type) of approved make.All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire.All panels shall have provision of the Pad locking of MCCB’s handles in “OFF” Position.Additional set of C.T.s, potential free contacts, connectors, contactors with wiring etc are to be provided for BAS including space required for various transducers in main LT panel sections, etc. Only transducers shall be supplied by BAS tenderer.All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive (motor) load shall be of type “C” characteristic and discharge lamps and UPS etc. shall be of type D characteristic. All incoming and outgoing air circuit breakers shall be placed on middle portion of the vertical in single tier formation.CT’s shall be properly mounted and clamped. Connection of CT’s for measuring instrument / relays shall be done through connector / terminals.Model, current capacity location and frame size of switchgear shall be written inside of the panel doors with paint / permanent marker as approved shop drawings / site requirement.All electronic meters with RS - 485 port and ACB's communication port shall be wired with shielded wire upto separate marshalling box for termination of all control wires and communication system.Compliance to the technical specifications.Design, fabrication, assembling, wiring and supply, installation, testing and commissioning of Main LT Panels fabricated out of (load bearing member of 2mm and non load bearing member 1.6 mm thick) CRCA sheet steel in cubicle compartmentised modular 4b construction, free standing floor mounted with bottom cable entry, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels.All Panels shall conform to relevant IEC/IS (viz. IEC 61439, IS 8623 etc.) standard including the earth leakage protection complete as per specification & drawings as required and as given below. All internal wiring in the panels shall be carried out using high temperature FRLSZH wires.All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The busbars shall be insulated with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports suitably spaced shall be used. Hinged doors with padlocking facility shall be provided on all outgoing feeders with switch handles lockable in OFF position.Space provision @ 15% for future expansion All MCCBs shall be current limiting type microprocessor based, rated for requisite specified Service short circuit breaking capacity (Ics suitable for isolation conforming to latest IEC947-2/IS13947-2 duly marked on MCCB, at operating voltage (Ue) of 415 V, insulation voltage (Ui) 750 V and with trip free mechanism, handle indicating ON/OFF/tripped position. The breaking capacity as mentioned shall be Ics values.All MCCB has inbuilt feature of earth fault protection.MCCBs shall be compact (As the Engineer may decide), suitably designed to provide protection of motors, cables, busbars to suit rated current, unbalanced power distribution as required and with front adjustable overload and short circuit releases and minimum electrical endurance of the order of 7000-8000 operation cycles for capacity of 100-250 amps.MCBs shall conform to IEC898/IS 8828 (latest) and, with breaking capacity 9/10 kA at 415 V AC, current limiting type lower powerloss appx 40 - 70% of the stipulated value and suitable for magnetic releases operating between 3 to 5 times rated current for normal power distribution application and 5 to 10 times rated current for moter application duty, with minimum Electrical endurance of the order of 20000 operation cycles.MDB-2 (RESTAURANT PANEL) (FIRST FLOOR)Incomer comprising of :125 amps FP MCCB with Thermal magnetic based release for O/L & S/C proetction - 1 Set,Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port equivalent to Schneider make EM6436H with 125/5, 5 VA, CL 1, 3 No. CTs - 1 Set,ON / OFF / TRIP indicating lights with control MCB - 3 Set,RYB Phase indicating light protected by 2 amps MCB’s - 3 Set.Class – B+C surge arrestor (Lines to Neutral) & (Neutral to Earth) suitable for 3 phases with protection fuse.Bus Bar comprising of :150 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable sleeves,Outgoing comprising of :40 Amp 4P MCB with Digital Multifunction meter with RS - 485 port equivalent to Schneider make EM6436H with 40/5 15 VA, CL 1, 3 No. CTs - 1 No.40 Amps 4P MCB, C Curve - 1 No.16 Amps DP RCBO, 30mA Sensivity - 21 No.32 Amps DP RCBO, 30mA Sensivity - 2 No.32 Amps 4P RCBO, 30mA Sensivity - 2 No.Notes:-All breakers MCCB shall be minimum 25 kA rating & MCB 10 kA with Icu = Ics.
LT PANELS The rates for the distribution boards apart from the Breakers and instruments shall also include the following :Supporting rigid steel framework.Cubicle type, 16 gauge CRCA sheet steel enclosed & Type 3b modular construction.Complete with interconnections and distribution bus bars along with connector strip.Proper bonding to earth as per standard.Painting/lettering on Breakers and distribution boards, the location they serve, providing on each panel its circuit diagram.Providing cable clamps / supports within distribution boards cable alley.All MCB’s shall be of minimum 10 KA breaking capacity.Distribution panels / bus ducts / rising mains shall be Powder Coated with RAL-7032 shade or as approved.Following Degree of protection for all type of distribution panel enclosure shall be as per IS:13947-1993:IP 44 for indoor panels.IP 54 for kitchen and laundry panels.IP 65 for outdoor panels.Current density of aluminium shall be 1 sq mm for 1.0 Amps for rated current of bus bars.GI earth bus shall be provided through out the length of each board as per schematic diagram.All measuring instruments (Meters) shall be of digital electronic (LED Type) of approved make.All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire.All panels shall have provision of the Pad locking of MCCB’s handles in “OFF” Position.Additional set of C.T.s, potential free contacts, connectors, contactors with wiring etc are to be provided for BAS including space required for various transducers in main LT panel sections, etc. Only transducers shall be supplied by BAS tenderer.All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive (motor) load shall be of type “C” characteristic and discharge lamps and UPS etc. shall be of type D characteristic. All incoming and outgoing air circuit breakers shall be placed on middle portion of the vertical in single tier formation.CT’s shall be properly mounted and clamped. Connection of CT’s for measuring instrument / relays shall be done through connector / terminals.Model, current capacity location and frame size of switchgear shall be written inside of the panel doors with paint / permanent marker as approved shop drawings / site requirement.All electronic meters with RS - 485 port and ACB's communication port shall be wired with shielded wire upto separate marshalling box for termination of all control wires and communication system.Compliance to the technical specifications.Design, fabrication, assembling, wiring and supply, installation, testing and commissioning of Main LT Panels fabricated out of (load bearing member of 2mm and non load bearing member 1.6 mm thick) CRCA sheet steel in cubicle compartmentised modular 4b construction, free standing floor mounted with bottom cable entry, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels.All Panels shall conform to relevant IEC/IS (viz. IEC 61439, IS 8623 etc.) standard including the earth leakage protection complete as per specification & drawings as required and as given below. All internal wiring in the panels shall be carried out using high temperature FRLSZH wires.All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The busbars shall be insulated with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports suitably spaced shall be used. Hinged doors with padlocking facility shall be provided on all outgoing feeders with switch handles lockable in OFF position.Space provision @ 15% for future expansion All MCCBs shall be current limiting type microprocessor based, rated for requisite specified Service short circuit breaking capacity (Ics suitable for isolation conforming to latest IEC947-2/IS13947-2 duly marked on MCCB, at operating voltage (Ue) of 415 V, insulation voltage (Ui) 750 V and with trip free mechanism, handle indicating ON/OFF/tripped position. The breaking capacity as mentioned shall be Ics values.All MCCB has inbuilt feature of earth fault protection.MCCBs shall be compact (As the Engineer may decide), suitably designed to provide protection of motors, cables, busbars to suit rated current, unbalanced power distribution as required and with front adjustable overload and short circuit releases and minimum electrical endurance of the order of 7000-8000 operation cycles for capacity of 100-250 amps.MCBs shall conform to IEC898/IS 8828 (latest) and, with breaking capacity 9/10 kA at 415 V AC, current limiting type lower powerloss appx 40 - 70% of the stipulated value and suitable for magnetic releases operating between 3 to 5 times rated current for normal power distribution application and 5 to 10 times rated current for moter application duty, with minimum Electrical endurance of the order of 20000 operation cycles.MDB-3 (OFFICE AREA) (ELECTRICAL ROOM) (FIRST FLOOR)Incomer comprising of :100 amps FP MCB with Thermal magnetic based release for O/L & S/C proetction - 1 Set,Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port equivalent to Schneider make EM6436H with 100/5, 5 VA, CL 1, 3 No. CTs - 1 Set,ON / OFF / TRIP indicating lights with control MCB - 3 Set,RYB Phase indicating light protected by 2 amps MCB’s - 3 Set.Class – B+C surge arrestor (Lines to Neutral) & (Neutral to Earth) suitable for 3 phases with protection fuse.Bus Bar comprising of :150 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable sleeves,Outgoing comprising of :40 Amp 4P MCB with Digital Multifunction meter with RS - 485 port equivalent to Schneider make EM6436H with 40/5 15 VA, CL 1, 3 No. CTs - 2 No.40 Amps 4P MCB, C Curve - 4 No.32 Amp DP MCB with Digital Multifunction meter with RS - 485 port equivalent to Schneider make EM6436H with 32/5 15 VA, CL 1, 3 No. CTs - 7 No.32 Amps DP MCB, C Curve - 3 No.Notes:-All breakers MCCB shall be minimum 25 kA rating & MCB 10 kA with Icu = Ics.
LT PANELS The rates for the distribution boards apart from the Breakers and instruments shall also include the following :Supporting rigid steel framework.Cubicle type, 16 gauge CRCA sheet steel enclosed & Type 3b modular construction.Complete with interconnections and distribution bus bars along with connector strip.Proper bonding to earth as per standard.Painting/lettering on Breakers and distribution boards, the location they serve, providing on each panel its circuit diagram.Providing cable clamps / supports within distribution boards cable alley.All MCB’s shall be of minimum 10 KA breaking capacity.Distribution panels / bus ducts / rising mains shall be Powder Coated with RAL-7032 shade or as approved.Following Degree of protection for all type of distribution panel enclosure shall be as per IS:13947-1993:IP 44 for indoor panels.IP 54 for kitchen and laundry panels.IP 65 for outdoor panels.Current density of aluminium shall be 1 sq mm for 1.0 Amps for rated current of bus bars.GI earth bus shall be provided through out the length of each board as per schematic diagram.All measuring instruments (Meters) shall be of digital electronic (LED Type) of approved make.All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire.All panels shall have provision of the Pad locking of MCCB’s handles in “OFF” Position.Additional set of C.T.s, potential free contacts, connectors, contactors with wiring etc are to be provided for BAS including space required for various transducers in main LT panel sections, etc. Only transducers shall be supplied by BAS tenderer.All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive (motor) load shall be of type “C” characteristic and discharge lamps and UPS etc. shall be of type D characteristic. All incoming and outgoing air circuit breakers shall be placed on middle portion of the vertical in single tier formation.CT’s shall be properly mounted and clamped. Connection of CT’s for measuring instrument / relays shall be done through connector / terminals.Model, current capacity location and frame size of switchgear shall be written inside of the panel doors with paint / permanent marker as approved shop drawings / site requirement.All electronic meters with RS - 485 port and ACB's communication port shall be wired with shielded wire upto separate marshalling box for termination of all control wires and communication system.Compliance to the technical specifications.Design, fabrication, assembling, wiring and supply, installation, testing and commissioning of Main LT Panels fabricated out of (load bearing member of 2mm and non load bearing member 1.6 mm thick) CRCA sheet steel in cubicle compartmentised modular 4b construction, free standing floor mounted with bottom cable entry, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels.All Panels shall conform to relevant IEC/IS (viz. IEC 61439, IS 8623 etc.) standard including the earth leakage protection complete as per specification & drawings as required and as given below. All internal wiring in the panels shall be carried out using high temperature FRLSZH wires.All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The busbars shall be insulated with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports suitably spaced shall be used. Hinged doors with padlocking facility shall be provided on all outgoing feeders with switch handles lockable in OFF position.Space provision @ 15% for future expansion All MCCBs shall be current limiting type microprocessor based, rated for requisite specified Service short circuit breaking capacity (Ics suitable for isolation conforming to latest IEC947-2/IS13947-2 duly marked on MCCB, at operating voltage (Ue) of 415 V, insulation voltage (Ui) 750 V and with trip free mechanism, handle indicating ON/OFF/tripped position. The breaking capacity as mentioned shall be Ics values.All MCCB has inbuilt feature of earth fault protection.MCCBs shall be compact (As the Engineer may decide), suitably designed to provide protection of motors, cables, busbars to suit rated current, unbalanced power distribution as required and with front adjustable overload and short circuit releases and minimum electrical endurance of the order of 7000-8000 operation cycles for capacity of 100-250 amps.MCBs shall conform to IEC898/IS 8828 (latest) and, with breaking capacity 9/10 kA at 415 V AC, current limiting type lower powerloss appx 40 - 70% of the stipulated value and suitable for magnetic releases operating between 3 to 5 times rated current for normal power distribution application and 5 to 10 times rated current for moter application duty, with minimum Electrical endurance of the order of 20000 operation cycles.MDB-U1 UPS PANEL (ELECTRICAL ROOM) (GROUND FLOOR)Incomer comprising of :63 amps FP MCB with Thermalmagnetic based release for O/L, & S/C proetction - 1 Set,Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port equivalent to Schneider make EM6436H with 60/5, 5 VA, CL 1, 3 No. CTs - 1 Set,ON / OFF / TRIP indicating lights with control MCB - 1 Set,RYB Phase indicating light protected by 2 amps MCB’s - 1 Set.Class – B+C surge arrestor (Lines to Neutral) & (Neutral to Earth) suitable for 3 phases with protection fuse.Bus Bar comprising of :100 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable sleeves,Outgoing comprising of :40 4P MCB, C Curve - 4 No.40 DP MCB, C Curve - 1 No.32 DP MCB, C Curve - 6 No.Notes:-All breakers MCCB shall be minimum 25 kA rating & MCB 10 kA with Icu = Ics.
SH-3 DISTRIBUTION BOARD Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clamps, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure.II-Double Door 8 way (SP + N), Double door
Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clamps, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure.II-Docuble Door 12 way (SP + N), Double door
Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clamps, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure.III-Double Door 6 way (TP + N), Double door
Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clamps, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure.III-Double Door 8 way (TP + N), Double door
Supplying&fixing miniature circuit breakers on existingMCB distribution boards using necessary fixing materials and 'C' Type curve, indicatorON/OFF, energycross-3 withShort circuitbreaking capacityof10Kandcomplete wiringas requiredconfirmingtoIEC 60898. 6-32 A SP
Supplying&fixing miniature circuit breakers on existingMCB distribution boards using necessary fixing materials and 'C' Type curve, indicatorON/OFF, energycross-3 withShort circuitbreaking capacityof10Kandcomplete wiringas requiredconfirmingtoIEC 60898. 6-32 A DP
Supplying, fixing andwiringResidualcurrentcircuitbreaker(RCCB) 240/450V upto 300mA sensitivity on existing wood/ panel board.32-40A 2 pole
Supplying & fixing of following rating, four Pole,415 volt, Isolator in existing MCB DB complete with connection, testig and commissioning etc as required,63A
SH-4 LT CABLE & CABLE TRAY Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions.3.5 core 300 sq. mm Al arm.
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions.3.5 core 70 sq. mm Al arm.
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions.4 core 25 sq. mm Al arm.
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions.3.5 core 50 sq. mm Al arm.
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions.4 core 16 sq.mm Cu arm.
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions.4 core 10 sq. mm. Cu arm.
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions.4 core 6 sq.mm Cu arm.
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions.4 core 4 sq.mm Cu arm.
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions.3 core 6 sq.mm Cu arm.
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions.3 core 4 sq.mm Cu arm.
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions.1 core 10 sq.mm Cu Unarm. FRLS for UPS Connectivity
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3.5 core 300 sq. mm Al arm.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3.5 core 70 sq. mm Al arm.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 core 25 sq. mm Al arm.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3.5 core 50 sq. mm Al arm.
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions.4 core 16 sq.mm Cu arm.
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions.4 core 10 sq. mm. Cu arm.
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions.4 core 6 sq.mm Cu arm.
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions.4 core 4 sq.mm Cu arm.
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions.3 core 6 sq.mm Cu arm.
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions.3 core 4 sq.mm Cu arm.
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions.1 core 10 sq.mm Cu Unarm. FRLS for UPS Connectivity
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.450 mm width X 50 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.600 mm width X 50 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.150 mm width X 50 mm depth X 1.6 mm thickness
Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff 2.5 to 25 Sqmm
Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff 35 to 95 Sqmm
Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff 300 to 400 Sqmm
Supplying and Providing Pre cast Cable Route/ Joint marker using M15 grade Concrete, MS rods of approved size/shape (as per the approved drawings) to be laid in UG cable works. The rate includes the cost of material, labour charges, loading, unloading, handling, transportation charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer-in-charge of works as per the standard procedure.
SH-5 Earthing GI/Copper strips for grounding connections, using necessary fixing materials as required.25 x 6 mm GI strip
SH-5 Earthing GI/Copper strips for grounding connections, using necessary fixing materials as required.50 x 6 mm GI strip
SH-5 Earthing GI/Copper strips for grounding connections, using necessary fixing materials as required.25 x 6 mm Copper strip
Supplying & Fixing Chemical earthling for grounding. Conduits, IC cut-outs & other equipments backfill compound which is noncorrosive, thermally conductive, potential to permissible limits, superior Fault conduction capacity, non toxic, weather resistance & capable of achieving ohmic value less than one ohm Using 10ft. Copper bonded rod with backfill compound
Lightning Protection Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required.
Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required.
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run)
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run)
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.
Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required.
Supply, installation, testing, and commissioning of insulator cover suitable for mounting on building surfaces, over which earthing/GI strip can run, including all necessary fixtures, supports, and accessories for complete installation
SH-6 POINT WIRING, Point wiring, using Copper wire with switch Supplying and wiring adopting loop system in existing PVC Conduit /casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) with a 6Amps flush type SP control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet Short point upto 3Mtr from tapping point to out let via switch
SH-6 POINT WIRING, Point wiring, using Copper wire with switch Supplying and wiring adopting loop system in existing PVC Conduit /casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) with a 6Amps flush type SP control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet Medium point above 3Mtr upto 6Mtr from tapping point to out let via switch
Point wiring using Copper wire without switch Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box,the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet Short point upto 3Mtr from tapping point to out let via switch box
Point wiring using Copper wire without switch Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box,the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet Long point above 6Mtr upto 10Mtr from tapping point to out let via switch
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS694:2010 1.5 mm 2
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS694:2010 2.5 mm 2
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS694:2010 4 mm 2
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS694:2010 6 mm 2
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.6A One Way Switch
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.6A Three Way socket
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.Stepped Fan Regulator Two Module
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.16A One Way Switch
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.6/16A Universal Socket
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.TV/Telephone Socket
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.RJ45/I.O Outlet Cat-6
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 1-2 Way
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 3 Way
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 4-5 Way
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 6 Way
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box.1 to 2 Module
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box.3 Module
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box.4 Module
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box.6 Module
Supplying and fixing of metal clad industrial plugs and sockets.2pole+earth 250V PLUG 16A
Supplying and fixing of metal clad industrial plugs and sockets.2pole+earth 250V PLUG 32A
Supplying and fixing of metal clad industrial plugs and sockets.3pole+earth 440V PLUG 32A
Supplying and fixing of metal clad industrial plugs and sockets.2pole+earth 250V SOCKET 16A
Supplying and fixing of metal clad industrial plugs and sockets.2pole+earth 250V SOCKET 32A
Supplying and fixing of metal clad industrial plugs and sockets.3pole+earth 440V socket 32A
Supplying heavy gauge PVC conduit pipe ....... dia ....... mm thick confirming to IS 2509 with suitable size bends, junction boxes, adhesive paste etc , and fixing using inverted wood plugs in case of RCC ceiling and RCC wall/ stone structure or rawl plugs in case of brick walls and cement plastering the damaged portion using heavy gauge saddles at an interval of 700mm using NF screws 19/20 mm dia 2 mm thick
Supplying heavy gauge PVC conduit pipe ....... dia ....... mm thick confirming to IS 2509 with suitable size bends, junction boxes, adhesive paste etc , and fixing using inverted wood plugs in case of RCC ceiling and RCC wall/ stone structure or rawl plugs in case of brick walls and cement plastering the damaged portion using heavy gauge saddles at an interval of 700mm using NF screws 25 mm dia 2 mm thick
Supplying heavy gauge PVC conduit pipe ...... mm dia..........mm thick confirming to IS 2509 with suitable size bends, metal/PVC Junction boxes, adhesive paste etc., and running before concreting the slab. The conduit should be tied to the reinforcement rods by using binding wires and unused ways of junction boxes and pipe ends should be covered using PVC end enclosures, run with 18SWG GI fish wire wherever necessary.19/20 mm dia 2 mm thick
Supplying heavy gauge PVC conduit pipe ...... mm dia..........mm thick confirming to IS 2509 with suitable size bends, metal/PVC Junction boxes, adhesive paste etc., and running before concreting the slab. The conduit should be tied to the reinforcement rods by using binding wires and unused ways of junction boxes and pipe ends should be covered using PVC end enclosures, run with 18SWG GI fish wire wherever necessary.25 mm dia 2 mm thick
SH-7 LUMINAIRS / LIGHT FIXTURES & ACCESSORIES Supply, Installtion, Testing & Commissioning of 40W LED batten luminaires with housing made up of scratch resistant unbreakable polycarbonate in grey finish. cable gland is used for maintaining ingress protection. Luminaire should be suitable for Wall/Ceiling mounting with SS clamps. Luminaire shall deliver excellent illumination & visual comfort with CRI of >80, High transmittance Opal Polycarbonate diffuser for glare-free symmetric light distribution. Luminaires should be with 110 lm/W System Efficacy and designed for Avg. LED Life (L70 B50) 50,000 Burning Hours & with high efficient Photobiologically safe LEDs. Luminaire should be Powered by an integral electronic constant current Potted driver offering THDi<10% , IP66 protection and impact resistance of IK07.Operating temperature: -10°C to + 40°C , Output Short-circuit protection, Surge Voltage protection, and other reliability tests as per IS:15885 Part 2/Sec 13. Luminaires should be provided with 4kV surge protection. Luminaires manufacturer to have an in-house NABL-accredited Laboratory for testing Photometric parameters.
Supply, Installtion, Testing & Commissioning of 1137 mm X 54mm 25W Recessed Linear Profile luminaires with housing made of Aluminum Extrusion for thermal management. Luminaire shall deliver excellent illumination & visual comfort with CRI of >80, High transmittance Opal Polycarbonate diffuser for glare-free symmetric light distribution. Luminaires should be with min 100 lm/W System Efficacy and designed for Avg. LED Life (L70 B50) 50,000 Burning Hours & with high efficient Photobiologically safe LEDs. Luminaire should be Powered by an integral electronic driver offering THDi<10% , Complete with other joining acessories for connecting fixture and suspension kit, Output Short-circuit protection, Surge Voltage protection, and other reliability tests as per IS:15885 Part 2/Sec 13. Luminaires should be provided with 2.5kV surge protection. Luminaires manufacturer to have an in-house NABL-accredited Laboratory for testing Photometric parameters.
Supply, Installtion, Testing & Commissioning of 36W Reces 600 X 600 LED Luminaire with housing made up of CRCA for efficient dissipation and diffuser made up of High quality opal diffuser to enhance the aesthic of the fixture and to provide glare free uniform light distribution, Powered by an independent output electronic LED driver (SMPS based constant current supply) with Output Short-circuit protection, Surge Voltage protection & other safety test as per IS:15885 Part 2/Sec 13. Power Consumption not greater than 36W and System Efficacy not less than 120 Lumens/Watt, CCT 5700K PF>0.95, CRI>80 ,THD<=10%. LED Average life L70B50: 50000 hours.Operating temperature: -10 °C to +40°C , Operating voltage range: 140 V - 270 V,. Luminaire Should conform to IP20 Classification. Test report to be submitted; photo biological safety norms: IS16108, test certificate to be submitted; certification: LM 79 for luminaire and LM80 for led source, Driver and Fixture to be BIS certified.
LED Downlight Supplying of recess mounting non integrated type LED down light...... W luminaire comprising of pressure decast/ extruded aluminium housing, with spring loaded false ceiling clamps, LED of Power/COB with CCT 6500 degree K, CRI> 70%. efficacy >100 lumen per W, 120degree beam spread, life> 25000 burning hours and Compliance to IS10322/IEC 60598, LM 79 & LM 80. The lamp compartment is enclosed with anti glare opal diffuser which enhances the lighting level. LED's are driven by HF electronic driver integrated in a separate control gear assembly., with PF > 0.95, power loss should< 5% of lamp Wage, short circuit & open circuit protection to be integrated in the circuit, THD less than 20%, Life as per LM 79. The operating input voltage should be between 130 to 275 V. BIS Approved and Tested by NABL/CPRI accredited laboratory with 2 years Warranty against any manufacturing defect working under standard electrical condition 10-12 W
Supply of round/square recess/surface mounted rolling type LED Down light with ...... W GU 10 LED Lamp Rib Fabricated from diecast aluminium with white powder coated prewired to mains connector & has swivelling unit of aluminium die cast eye ball & LED Lamp position retained by circular wire spring, with Life of 25000 burning hours & 70% lumen maintenance with CRI > 80. Power Input: 220-240V @50/60Hz & Power factor >0.9 along with CE approved. 2years Warranty against any manufacturing defect working under standard electrical condition LED square or round down light 10-12W
Supply of round/square recess/surface mounted rolling type LED Down light with ...... W GU 10 LED Lamp Rib Fabricated from diecast aluminium with white powder coated prewired to mains connector & has swivelling unit of aluminium die cast eye ball & LED Lamp position retained by circular wire spring, with Life of 25000 burning hours & 70% lumen maintenance with CRI > 80. Power Input: 220-240V @50/60Hz & Power factor >0.9 along with CE approved. 2years Warranty against any manufacturing defect working under standard electrical condition LED square or round down light 15-18W
LED Down lighter (SMD Type) (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of LED Recessed / surface Down lighter (Round /square/Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range - 15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), life time of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K / 6000°K /6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminum Body including trim. 30 watt
Supplying and fixing of LED Bulkhead of 10W with IP65 protection and IK 08 impact resistance suitable for surface and wall mounting applications.
Supplying of .....feet -PVC Batten with integrated LED tube .... W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI > 80. Power Input: 220-240V@ 50/60Hz & Power factor >0.9 along with CE approved. 2 years Warranty against any manufacturing defect working under standard electrical condition.LED light fitting 1 x 2' - 9/10 W
Supplying of .....feet -PVC Batten with integrated LED tube .... W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI > 80. Power Input: 220-240V@ 50/60Hz & Power factor >0.9 along with CE approved. 2 years Warranty against any manufacturing defect working under standard electrical conditionLED light fitting 1 x 4' - 36/40 W
Supplying capacitor type ceiling fan complete with down rod blades, shackle, canopies etc, for operation on 230 V, 50 cycles. Single phase AC supply conforming to ISS-374- 1979 and with double ball bearing system.48" Sweep (1200 mm) Regular model
Fixing all types and all capacities of fluorescent /false ceiling / spot light / CFL / LED fittings indoor on the wall/ ceiling / rafters / girders using 23/0.0076" twin twisted PVC insulated wires, required Nos of round blocks and clamps On wall/ ceiling / Rafter / Girders
Fixing a ceiling /wall mounting fan of all capacities and all types, with necessary clamps and 'S' hook made out of 15mm dia MS rod, with 5 A. ceiling rose of approved quality with necessary length of 23/0.0076 inch PVC insulated twin twisted wire of approved quality, mounted on a suitable size wooden board and wired
SH-8 UPS Supplying, erecting, testing & commissioning of ON-LINE UPS system suitable for operation on 230V, 50Hz, A/C supply, with isolation transformer all accessories complete and Excluding batteries and wiring complete.10 kVA ON LINE UPS
Supplying, installation, testing & commissioning of 12V ..AH batteries in poly propylene container for D.G. sets. Low maintenance batteries, plate type.60 AH capacity
Supplying, installation, testing & commissioning of 12V DC, AH batteries in poly propylene container for U.P.S. Sealed maintenance free batteries.42 AH capacity
Supplying, erecting, testing & commissioning of ON-LINE UPS system suitable for operation on 230V, 50Hz, A/C supply, with isolation transformer all accessories complete and Excluding batteries and wiring complete 3kva online ups
Supply of LED Bollard light fitting of ...W with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti glare clear diffuser with Injection moulded polycarbonate/clear glass material, delivering superior light output Rated life Burning Hrs 50000 hr @ Lumen Maintenance of 70%, CCT > 5500K, IP 66 optical and electrical compartment & impact resistance of complete luminaire > IK08. Power Factor >0.9 with mains, Surge Protection- Min 5KV along with Over voltage/Overload, short circuit/ miss-wiring protection. Universal Voltage driver to operate wide voltage range from 100V to 270V 50/60Hz application. Compliance to IS 10322/IEC 60598, LM 79 & LM 80 Adherence with RoHS. UL approved MCPCB, with 2 years Warranty against any manufacturing defect working under standard electrical condition.8W 1 m Height
SH-9 External lighting:Supply of LED pole mounting type post top lantern with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti glare clear diffuser with Injection moulded polycarbonate/ clear glass material, delivering superior light outputRated life Burning Hrs 50000 hr@ Lumen Maintenance of 70%, CCT > 5500K, IP 66 optical and electrical compartment & impact resistance of complete luminaire > IK08. Power Factor>0.9 with mains, Surge Protection- Min 5KV along with Over voltage/Overload, short circuit/ miss-wiring protection. Compatible for pole mounting with outer dia of 40mm to 50mm. Universal Voltage driver to operate wide voltage range from 100V to 270V 50/60Hz application. Compliance to IS 10322/1 EC 60598, LM 79 & LM 80 Adherence with RoHS. UL approved MCPCB LED Efficiency>1301m/w, nominal CRI >75. Luminaire manufacturer should have in- house facility accredited by NABL/CPRI & any Government certified agency & Design & Development facility certified by ISO 9001:2008. Housing with supplier word mark /name shall be Engraved / Embossing on the die cast housing/ Body part Warranty of 2 Years against any manufacturing defect working under standard electrical conditions as mentioned above should be given by LED manufacturer & Cree/Nichia/ Lumileds/Osram make LED Source. LED Post Top Lantern with 15/20 W
Supply of 4M height post top Pole Made of mild steel pipe sections 114mm dia. & 76mm dia. Entire pole shall be made to provide pleasing aesthetics as approved by Concerned Engineer in-charge. After Fabrication, Entire Pole is hot dip galvanized(60 microns Minimum ) for the effective corrosion resistance . The hot dip Galvanised pole should be provided with an inbuilt junction box to fix 32A connectors and 6A MCB, at the bottom - the inbuilt box should have a flush door of suitable size. The pole to be provide with suitable size base plate. This base plate along with foundation bolts of suitable size to be used for ensuring firm grouting into the specially designed RCC foundation. wind pressure calculation as per IS 875(part-3) & structural calculation report as per EN40 should be submitted to verify the pole design.
Circular Ground Buried Uplight Body made made of die cast aluminium using pressure die casting process.Protection screen in clear tempered glass with high impact resistance 15-20W,LED,3000k, IP 67. Pure Polyester powder coating in Standard Grey Colour. Precise structure and multi-protection silicon rubber seal guarantees the fixture IP67 rated. Dia.–210mm, Height.-120mm, Weight - 2.4Kgs. Power LED Module with high efficacy LED's, on Printed Circuit Board with metal core plate. Lens made of PC which should offer wide range of narrow,medium & wide beam angles. Estimated LED Lifetime is L70-50,000 hours minimum.LM80 report from LED Manufacturer should be submitted.Minimum Light fixture Lumen output is 1200Lumens. Sample Should be submitted for concerned engineer incharge for approval of light fixture.
Linear Wall Washer The housing in light weight, made of high strength aluminium and coated by static powder making it weather resistant.Protection screen in clear tempered glass with high impact resistance 25-30W,LED,3000k, IP 66. High precision dial ensures precision angle adjustment. Pure Polyester powder coating in Standard Grey Colour. Precise structure and multi-protection silicon rubber seal guarantees the fixture IP66 rated. Length-1000mm,Height – 66mm, Width.-64mm, Weight - 3.95Kgs. Power LED Module with high efficacy LED's, on Printed Circuit Board with metal core plate. Lens made of PC which should offer wide range of narrow,medium & wide beam angles. Estimated LED Lifetime is L70-100,000 hours minimum.LM80 report from LED Manufacturer should be submitted.BIS safety test report with manufacturer name same as brand proposed, as per IS10322 from Intertek/UL lab & BIS Certificate with manufacturer name same as brand proposedshould be submitted. Minimum Light fixture Lumen output is 1600Lumens. Sample Should be submitted for concerned engineer incharge for approval of light fixture.
Feeder Pillar (For External Landscape lighting) IP 55 for outdoor Protection Incomer 63 Amps 4 pole MCB, Photocell Sensor Bus Bars 100 Amps TPN Aluminium bus bars with heat shrinkable insulation sleeve. - 1 Set Outgoing 40 Amps 4 pole MCB incomer with 40 Amps TP contactor 0-24 hours timer auto / manual and outgoings including 5 No. 10/16/20 Amps SP MCB with 3 Nos. 25 Amps DP RCCB’s of 30 mA leakage current with separate neutral link of each phase- 1 set (50%) 40 Amps DP MCB - 2 set,63 Amps 4 Pole MCB - 2 set
Fixing charges of post top/ Gate/ Garden fitting /LED on the existing CI/ GI or any other pipe using required size of reducer, wiring using suitable wires.
SH-10 NETWORKING & TELECOMUNICATION Supplying and drawing UTP-CAT 6E LAN cable.
Supplying and drawing PVC flexible one pair telephone unarmoured tinned copper cable.2 Pair
Supplying and drawing PVC insulated gas injected physical foamjelly flooded co-axial TV cable.RG-6.
Supplying &Fixing of switch mounting rack with power manager & Cable manager.18U with 650mm depth
Supplying and fixing of MDF krone junction box with KRONE Module / Telephone cable termination.50 pair
Supplying heavy gauge PVC conduit pipe ...... mm dia..........mm thick confirming to IS 2509 with suitable size bends, metal/PVC Junction boxes, adhesive paste etc., and running before concreting the slab. The conduit should be tied to the reinforcement rods by using binding wires and unused ways of junction boxes and pipe ends should be covered using PVC end enclosures, run with 18SWG GI fish wire wherever necessary.19/20 mm dia 2 mm thick
Supplying heavy gauge PVC conduit pipe ...... mm dia..........mm thick confirming to IS 2509 with suitable size bends, metal/PVC Junction boxes, adhesive paste etc., and running before concreting the slab. The conduit should be tied to the reinforcement rods by using binding wires and unused ways of junction boxes and pipe ends should be covered using PVC end enclosures, run with 18SWG GI fish wire wherever necessary.25 mm dia 2 mm thick
Supplying and fixing of CAT6A cable
SH-11 CCTV SECURITY SYSTEM Smart Surveillance System (CCTV): using PTZ & Fixed cameras, OFC monitoring system, HMI etc., as per specification Fixed Camera Specifications: • Lens type: Bi‐focal auto iris with 10x digital zoom • Mode :Day/Night • Image size: 720x486 (NTSC) • Streaming: High speed • Weather Proof: IP 66 compliant • Network Protocol: TCP/IP should be compliant of any other protocol required. • Connectivity : Cat 6 / Optical fibre • Ethernet:10Base‐t/100Base‐TX(RJ45) • Power source : both self powered and externally powered
Fibre:6F Armoured Multimode with LIU along with required number of SC/ST connectors and required accessories
HMI (Industrial Grade PC) • Operating System : Windows 10 Professional • CPU : Intel i7 quad core processor or latest • RAM : 32 GB or higher • Network : TCP/IP • Graphics adaptor : NVIDA Quadra digital video pipeline or higher • Hard disk : 1.5 TB (500x3) RAID 1 configuration • External drives : Blu‐Ray RW and DVD RW • Monitor : 24 inch dual screen • Keyboard / Mouse : Wireless • Network adaptor • LAN switch • Fibre LIU
Supplying and drawing UTP-CAT 6E LAN cable.
Supplying & Fixing of switch mounting rack with power manager & Cable manager.12U with 450mm depth
Supplying & Fixing of Power strip
Supplying of shelf
Supplying & fixing of Castor wheels to the Shelf (set of 4)
Supplying & Fixing of Fan
Supplying fixing of Network Switches 24 Port Gigabyte (manageable)
Supplying & Fixing of ... ms Cat 6 Patch Cable 1 m
Supplying & Fixing of Patch panel for LAN cabling 24 Port 10/100/1000 patch panel
SH-12 ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM Supply, installation, testing and commissioning of addressable peer to peer Networkable analogue addressable type fire alarm control panel with minimum 1500 Character / 240X64 Pixel / 7inch Touchscreen graphic LCD display. The panel should be equipped with sufficient numbers of loop with 20% spare capacity, with each networkable intelligent fire alarm Control Panel having SLC with capacity of min 126 /240 detectors/ devices in any combination with key pad, dual flash-based microprocessor technology, inbuilt USB Port for upload and down load the configuration tools, RS232 serial port for direct PC or modem connection, inbuilt NAC's, min 20 programmable Zonal LEDs and operates on 240V AC + 10% with 50 Hz with built in charger. The panel shall have fire, fault relays, option of BMS integration MODBUS/ BACKNET, graphical software for provision of TCP/IP modules, Remote Access, Class 'X' wiring with provision of both class 'A' and class 'B' wiring in the SLC circuit, user friendly with communication facility to monitor & control the FACPs from a single window. The pane shall be suitable for minimum of 5000 event record facility, event fetch from FACP facility and the single panel shall be suitable for min 2000 fire zones and 200 Panels/ Nodes in one network with all other accessories required to successfully run the system. (The System cost shall be included of all necessary cards, modules, Panel enclosure, CPU and associated accessories to complete the system design). Approval: VDS/UL/EN-54 Std 2 Loop Panel
Smoke Detector Model Supply, installation, testing and commissioning of analogue addressable Smoke Sensor detector and standard base (For Detectors/Device without inbuilt isolator, Fault
Multi Sensor Detector Model Supply, install, test and commissioning of analogue addressable Multisensor having three sensors (OH2) i.e. one optical and dual heat sensor (Static and ROR both), It shall have multiple modes with min five different optical sensitivity adjustment from 1.1%/m to 4.2%/m and to be possible to configure the detector to work in any of the modes such as only optical type or only heat type or combined type. 360° Visible Tri- coloured led for Normal, Fault and alarm condition, addressing shall be by means of Soft addressing or dip switches or decade switches, or suitable punched cards. (For Detectors/Device without inbuilt isolator, Fault Isolator or Isolator base to be provided with each detector/device) Approval: VDS/UL/EN54.
Supply, installation, testing and commissioning of analogue addressable dual heat detector and standard base, It shall have multiple modes with min five different heat sensitivity adjustment from 57 Degree to 90 Degree for static response while working on Rate of Rise response. 360° Visible Tricoloured led for Normal, Fault and alarm condition, addressing shall be by means of Soft addressing or dip switches or decade switches, or suitable punched cards. (For Detectors/Device without inbuilt isolator, Fault Isolator or Isolator base to be provided with each detector/device) Approval: UL/VDS/EN54.
Supply, install, test and commissioning of Analogue addressable Monitor Cum Control (Input/Output) module (1+1) with inbuilt relay and isolator with LED indicator, approved to operate in –10°C to +55°C temperature, complies with the essential requirement of the EMC Directive to be supplied with Junction Box, Glands and other mounting accessories for proper installation. In case of Manufacturer with single Input or Output module need to supply One quantity of each for line item. (For Detectors/Device without inbuilt isolator, Fault Isolator or Isolator base to be provided with each detector/device) Approval: EN54.
Manual Call Point Supplying Installing, testing and commissioning of Resettable type Manual Call point . works on 24V DC LED indicator with glass Fronted. Fire Symbol .The red Manual Call Point is approved to EN54-11 standard. MECHANICAL CONSTRUCTION The component parts of the call point are moulded in polycarbonate or ABS, depending on their function.
Supplying Installing, testing and commissioning of electronic Hooter, it conists of electronic circuit to give dual Fire alaram sound with works. 24V DC with speaker all encased in suitable in MS 16 gauge red painted box. complete including cost of materials, labour, usage charges of machinery complete as per specifications.
Supplying and fixing sheet metal box made out of 18 SWG sheet metal with necessary holes for cable/conduit entry as required with one coat of primer of approved make etc. including cost of materials, labour, usage charges of machinery complete as per specifications.
Supplying and drawing of 2 Core X 1.5 Sqmm copper conductor armoured cable
Supplying Installing, testing and commissioning of Public address system (Two way comminication type) as per requirement of Fire Force authority and which Generally comprise of Supplying Installing, testing and commissioning of Approved make 6 W.wall mounted speaker with talk back facility with store enamel painted M.S.Sheet hosing etc. complete including cost of materials, labour, usage charges of machinery complete as per specifications.
Supplying Installing, testing and commissioning of P.A.System console panel with push button with speaker and indictoron Accomdated in M.S.Cabinet with painting including cost of materials, labour, usage charges of machinery complete as per specifications 10 Zone cansole.
P.A.System amplifier 250W RM S out put with complete wiring and controls accessable form front
Supplying Installing, testing and commissioning of MIKE suitable to I.A.System. Complete
HVAC SH-1 EQUIPMENT Supplying of TR Invertor type split Air conditioners suitable for operation on A/C supply single phase 50 Hz 230 V with hermetically sealed inverter compressor with air cooled condenser, latest R410A / R-32 refrigerant fan motor, start & run capacitors, relay & over load protector internal unit, with one indoor & one outdoor unit The condenser unit will be placed outside the room avoid noise including standard length of suitable size copper tubing covered with nitrile rubber insulation tube. suitable capacity 3 core sheathed/ PVC copper cable and a battery operated wireless remote unit.2.0 Hi Wall Unit ( 5 star)
Installation charges for split type air conditioner with allied works for one indoor and one outdoor unit is to be mounted on suitable Angle Iron support upto 3.0 Ton split/cassette type A/C.
Supply erection, testing, commissioning of Cassette type split Air conditioners suitable for operation on single/three phase AC supply,hermetically sealed compressor with air cooled condenser motorcapacitor start, capacitors run relay and over load protection,one ceiling mounted indoor unit and one outdoor condenser unit including standard accessories covered with insulation tube including battery operated cordless unit 3.0 TR Cassette Units
Supplying, installing, testing and commissioning of inline Fan suitable for installing in any position in vertical or horizontal ducts.Constructed with sheet steel with epoxy polyester paint, acoustic isulation within the outer shell. Two speed motor (IP 44 Rated) with removable fan body with two speed motor, single phase speed controlable class F external rotor motor with capacitor and thermal protection. All units shall be complete with duct flexible connector, speed regulator (with wiring of 3 m included between fan & regulator) and volume control damper and static pressure or to suit the system, shall be as follows:The sound level shall be mesured at three metre distance. Actual static to be checked by the vendor during the shop drawings,800 CFM Inline Fan 10-15 mm static Pressure .
Supplying, installing, testing and commissioning of inline Fan suitable for installing in any position in vertical or horizontal ducts.Constructed with sheet steel with epoxy polyester paint, acoustic isulation within the outer shell. Two speed motor (IP 44 Rated) with removable fan body with two speed motor, single phase speed controlable class F external rotor motor with capacitor and thermal protection. All units shall be complete with duct flexible connector, speed regulator (with wiring of 3 m included between fan & regulator) and volume control damper and static pressure or to suit the system, shall be as follows:The sound level shall be mesured at three metre distance. Actual static to be checked by the vendor during the shop drawings,650 CFM Inline Fan 10-15 mm static Pressure .
Supplying exhaust fan of 1440 RPM of 300 mm (12") size with bracket blades complete for light duty suitable to operate on 230V 50Hz, AC Supply ,300 dia , Noise level 38 DB at 3m,fan suitable for 220±6% volts 50 cycles, 1 phase AC supply.
Fixing one exhaust fan after making a suitable notch in the wall, finishing with cement mortar and matching paint/colour to blend with the existing wall. The fan shall be mounted on brackets using bolts and nuts, and connected electrically through a 5A ceiling rose with sufficient length of 23/0.0076 inch PVC insulated twin-core wire of approved make. The exhaust opening shall be covered with wire mesh and a wooden frame to ensure safety and prevent foreign objects from entering.
SH-2 PIPING-COPPER AND DRAIN Supplying and installation of insulated refrigerant copper tubing of 5/8" and 3/8" with polythene foam insulation 3 core 80 standcopper wiring between indoor and outdoor unit Leak testing oil and gas charging for additional piping length of tube.Split Unit
Supplying and installation of insulated refrigerant copper tubing of 5/8" and 3/8" with polythene foam insulation 3 core 80 standcopper wiring between indoor and outdoor unit Leak testing oil and gas charging for additional piping length of tube.Cassette
DRAIN PIPE Supplying, installing and testing of UPVC pipe (heavy duty) with 6 mm thick nitrile rubber insulation with protective coating as per the approved shop drawings and specifications.25 mm dia
SH-3 AIR DISTRIBUTION Supply, fabrication and installation of GI Ducting Along with flanges, supports & all fixing materials.24 Gauge (Thickness 0.63mm)
Supply, fabrication and installation of GI Ducting Along with flanges, supports & all fixing materials.22 Gauge (Thickness 0.8mm)
Supply, fabrication, installation, balancing and commissioning of Site fabricated GSS sheet metal rectangular ducting as per SMACNA standards complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings. 24 Gauge (Thickness 0.63mm)
Duct for Kitchen Exhaust Supply,fabrication,installation and testing of sheet metal ducts of following thickness including necessary supports,hangers,nut&bolts,gaskets,splitterdampers,vanes,etc complete as per IS 655 standard in accordance with the approved shop drawings.Ducts shall be factory fabricated/Site fabricated (as directed by Client) of following gauge :-Duct shall be insulated with 75 mm thick 60kg/m3 density pre-laminated glasswool. PVC strap of 25mm width shall be fixed at 300mm interval to secure the insulation in position.Note:As per NBC 2016 The ducting within compartment would require minimum fireresistance rating of 30min, so quote accordingly. 18 gauge galvanised sheet
Supply, installation, testing and commissioning of GI Volume control duct damper complete with neoprene rubber gasket, nuts, bolts, screw linkages, flanges etc., as per specifications.
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
Supplying & fixing of powder coated extruded aluminium Exhaust Air Grills with louvers but without volume control dampers complete as required.
Supply, installation, testing and balancing of Powder coated/Anodised extruded aluminium construction inlet air louvers with bird screen for fresh air alongwith GI construction volume control damper.The louvers will be powder coated in shade approved by Client and installed as per approved shop drawings and specifications. Note:All exposed surfaces & duct shall be painted in black mat finish by the HVAC contractor.
Supplying, erecting, testing and commissioning of voltage stabilizer suitable for 170 to 270v input and load variation from no load to full load,with overload protection,spike suppression, operating at 00C to 400 C. Range etc., complete.5kVA Capacity
FIRE FIGHTING WORK SH-1 Supply, erection, testing & commissioning of electrical motor driven end suction back pull out centrifugal pump capable of delivering,adequate LPM at required head. when running at 2900 rpm directly coupled to TEFC electrical motor of adequate HP to operate on 400/440 V 3 phase, 50 cycles AC supply with required foundation for pump, a terminal box suitable for reception, common bed plate with necessary anti vibration pads, necessary foundation bolts and accessories,neoprine gaskets (16 kg/sq.cm) Control panel is excluded.Required GA drawingfor the pump/ foundation shall be submitted by the contractor.2280 lpm at 70 m Head
Supply, installation, testing & commissioning of diesel engine driven pump, horizontal mounted, Horizontal spiltcase centrifugal single stage pump, capable of delivering required flow at required head when running at 1800 RPM with adequate BHP automatic diesel engine driven pumpset having the residential silencer system and other accessories like fuel tank, necessary radiator cooling system, flanges, neoprene gaskets (16.0 kg/sqcm), 200 litres fuel storage tank with piping, valves as per detailed specification and two separate starting mechanisms (automatic starting by battery power, electric starting motor as well as manual starting by electric start motor) common bed plate with anti vibration pads, necessary foundation, foundation bolts etc., complete in all respects as per the detailed specifdication. Control panel excluded. Required GA drawingfor the pump shall be submitted by the contractor. Required GA drawingfor the pump/ foundation shall be submitted by the contractor.2280 lpm at 70 m Head
Supply, Installation, testing and commisioning electrically driven jockey pump of capacity 180.0 Lpm at required head end suction type bronze impeller pump oupled to electrical driven motor with suitable HP with all the necessary accessories, operating on 3Ph 50Hz, 400/440 V AC supply including foundation, foundation bolts, anti vibration pad,etc. complete.including cost of materials, labour, usage charges of machinery complete as per specifications. Control panle is excluded. Required GA drawingfor the pump/ foundation shall be submitted by the contractor. 180 lpm at 70 m Head
Supply, installation, testing and commissioning electrically driven Terrance pump of capacity 450.0 Lpm at 35.0m Head bronze impeller pump coupled to electrical driven motor with suitable HP with all the necessary accessories, operating on 3Ph 50Hz, 400/440V AC supply including required foundation for pump, anti vibration pad, founadtion bolts etc. complete. Including cost of materials, labour, usage charges of machinery complete as per specifications and control panel is not included. Required GA drawingfor the pump/ foundation shall be submitted by the contractor.450 lpm at 35 m Head
Wraping and Galing of U/G pipe line work includes one coat of anti corrossion paint (Black) and two coats of Bituminous cloth. Including cost of materials, labour, usage charges of machinery complete as per specifications.150 mm dia
FIRE HYDRANT SYSTEM Supplying Installing, testing and commissioning of 63mm mm dia single headed Gun mental Hydrant Valve with flanged inlet, stop valve, spindle and cast iron hand wheel. It has a female instantaneous outlet with Blank Cap and is Hydrostatically tested to 21 Kgf/cm2 pressure having a flow rate of 900 LPM at 7 Kgf/cm 2 of pressure with blank cap and wheel as per IS 5290 etc. complete including cost of materials, labour, usage charges of machinery complete as per specifications.
Supplying, installing , testing and commissioning of PN16 CI butterfly valves of confirming to IS 13039 with necessary nuts & bolts etc., complete ---- etc., complete as per specificaiton with all lead and lift, loading unloading, labour, hire charges of machineries and all such incidental charges necessary for successful completion of work and as per directions of the Engineer-incharge of the work,65 mm dia
Supplying, installing , testing and commissioning of PN16 CI butterfly valves of confirming to IS 13039 with necessary nuts & bolts etc., complete ---- etc., complete as per specificaiton with all lead and lift, loading unloading, labour, hire charges of machineries and all such incidental charges necessary for successful completion of work and as per directions of the Engineer-incharge of the work,80 mm dia
Supplying, installing , testing and commissioning of PN16 CI butterfly valves of confirming to IS 13039 with necessary nuts & bolts etc., complete ---- etc., complete as per specificaiton with all lead and lift, loading unloading, labour, hire charges of machineries and all such incidental charges necessary for successful completion of work and as per directions of the Engineer-incharge of the work,100 mm dia
Supplying, installing , testing and commissioning of PN16 CI butterfly valves of confirming to IS 13039 with necessary nuts & bolts etc., complete ---- etc., complete as per specificaiton with all lead and lift, loading unloading, labour, hire charges of machineries and all such incidental charges necessary for successful completion of work and as per directions of the Engineer-incharge of the work,150 mm dia
Supplying installing, testing and commissioning of PN16 CI "Non Return Valve " confirming to IS 13039 with necessary bolts and nuts etc complete includes cost of all materials labour charges with all lead lift loading and unloading transportation etc complete. ---- etc., complete as per specificaiton with all lead and lift, loading unloading, labour, hire charges of machineries and all such incidental charges necessary for successful completion of work and as per directions of the Engineer-in-charge of the work,65 mm dia
Supplying installing, testing and commissioning of PN16 CI "Non Return Valve " confirming to IS 13039 with necessary bolts and nuts etc complete includes cost of all materials labour charges with all lead lift loading and unloading transportation etc complete. ---- etc., complete as per specificaiton with all lead and lift, loading unloading, labour, hire charges of machineries and all such incidental charges necessary for successful completion of work and as per directions of the Engineer-in-charge of the work,80 mm dia
Supplying installing, testing and commissioning of PN16 CI "Non Return Valve " confirming to IS 13039 with necessary bolts and nuts etc complete includes cost of all materials labour charges with all lead lift loading and unloading transportation etc complete. ---- etc., complete as per specificaiton with all lead and lift, loading unloading, labour, hire charges of machineries and all such incidental charges necessary for successful completion of work and as per directions of the Engineer-in-charge of the work,100 mm dia
Supplying installing, testing and commissioning of PN16 CI "Non Return Valve " confirming to IS 13039 with necessary bolts and nuts etc complete includes cost of all materials labour charges with all lead lift loading and unloading transportation etc complete. ---- etc., complete as per specificaiton with all lead and lift, loading unloading, labour, hire charges of machineries and all such incidental charges necessary for successful completion of work and as per directions of the Engineer-in-charge of the work,150 mm dia
supply and installing testing and commissioning of CI " Y " stainer confirming to IS standard with necessary bolts and nuts complete includes cost of all materials labour charges with all lead lift loading and unloading transportation etc complete. ---- etc., complete as per specificaiton with all lead and lift, loading unloading, labour, hire charges of machineries and all such incidental charges necessary for successful completion of work and as per directions of the Engineer-in-charge of the work ,100 mm Dia CI " Y " stainer.
supply and installing testing and commissioning of CI " Y " stainer confirming to IS standard with necessary bolts and nuts complete includes cost of all materials labour charges with all lead lift loading and unloading transportation etc complete. ---- etc., complete as per specificaiton with all lead and lift, loading unloading, labour, hire charges of machineries and all such incidental charges necessary for successful completion of work and as per directions of the Engineer-in-charge of the work ,150 mm Dia CI " Y " stainer.
Supplying Installing, testing and commissioning of Reinforced Rubber Lined 2nos .RRL Fire hose of 63mm dia 15m length as per IS 8423 binded with one set of male and Female lnstantainious Gun metal coupling as per IS 903 complete including cost of materials, labour, usage charges of machinery complete as per specifications.
Supplying Installing, testing and commissioning of 19mm dia 40.0m length hose with rubber lining smooth bore, reinforced of natural/synthetic fibres, a rubber cover finish shall be smooth, fluted or fabric marked with minimum thickness of 1.50mm and to with stand a working pressure of 10Kgf/sqcm confirms & tested as per IS 444/ IS 12585 including cost of materials, labour, usage charges of machinery complete as per specifications.
Supplying Installing, testing and commissioning of Gun metal Branch pipe size of 63mm dia x19mm dia as per IS 903 complete including cost of materials, labour, usage charges of machinery complete as per specifications.
Supplying Installing, testing and commissioning of 150mm dia 4 way Fire brigade inlet connection with Non retrn valve of 4 nos. 63 mm dia. including cost of materials, labour, usage charges of machinery complete as per specifications.
Supplying Installing, testing and commissioning of 100mm dia 2 way Fire brigade inlet connection of 2 nos. 63 mm dia. including cost of materials, labour, usage charges of machinery complete as per specifications.
Supplying fixing and testing of Air cushions vessel. Fabricated out of 8mm thik It is a 250 mm dia MS pipes (the ends should be dished) 1.2 M high installed verically on suitable legs. Flange connection shall be provided for connection with wet riser pipe Cylinder connected with 25 mm dia gunmetal gate valves , pressure guage. The air vessel shall be tested at 25 Kg/cm2 at the bottom of the cylinder absorbs and water hammering blow in the pipe line. The price includes 25 mm dia connection MS pipes and supporting etc., complete ---- Including all lead, lifts, loading unloading, transportation, labour, hire charges of machinery curing for concrete works, cost and convene of all material and all other such incidental charges necessary for successful completion of works as per the detailed technical specification and direction of Engineer - in –charge of this work.
Pressure Switch including Isolation Valve and forged siphon Tube including with all accssories as per IS:Spec. ---- etc., complete as per specificaiton with all lead and lift, loading unloading, labour, hire charges of machineries and all such incidental charges necessary for successful completion of work and as per directions of the Engineer-in-charge of the work
Supplying Installing, testing and commissioning of Hose cabinet made out of 18 gauge M.S.sheet with double glass door with lacing arrangement and painted with two coats of Fire red Enamel paint at outer ise of the Box and two coats of white enamel paint at inner side of the box is to accomodated 2 Nos. of Fire hose box size 20"x24"x10" complete including cost of materials, labour, usage charges of machinery complete as per specifications.
Supplying Installing, testing and commissioning of Gun metal AIR RELEASE VALVE SIZE OF 25mm dia including cost of materials, labour, usage charges of machinery complete as per specifications.
Supplying Installing, testing and commissioning of Hose reel cabine for external hydrants)
Providing & fixing neoprene rubber double flanged double arch expansion joint (anti vibration bellow) resilient rubber lined of standard length as per manufacturers specifications including all necessary fittings i.e. rubber gasket, nuts, bolts, washers etc complete as required.65 mm dia
Providing & fixing neoprene rubber double flanged double arch expansion joint (anti vibration bellow) resilient rubber lined of standard length as per manufacturers specifications including all necessary fittings i.e. rubber gasket, nuts, bolts, washers etc complete as required.150 mm dia
Supply, installation in position, testing, and commissioning of a 4.5 Kg CO₂ gas-type fire extinguisher (trolley mounted) complete with dual easy weight management system (used/unused indication mechanism), squeeze grip operation, and controllable discharge mechanism. The extinguisher shall have a gross weight of 19.1 Kg and an empty weight of 14.6 Kg, with a can height of 860 mm and a diameter of 140 mm. The discharge time shall be less than 13 seconds. The extinguisher shall be suitable for Class B and C fires and shall have a fire rating of 13B. The canister construction shall be through hot spinning or forging, and the valve construction shall be through forging and machining. The internal coating of the canister is not applicable, while the external coating shall be finished with spray painting. The sheet metal thickness shall be 4.5 mm. The extinguisher shall include a high-quality EPDM rubber hose pipe and an integrated internal alert system. The product must be ISI approved and shall come with a minimum 1-year manufacturer's warranty. The scope of work includes the cost of all materials, labour, and machinery usage charges, complete in all respects as per specifications.
Supply, installation of 4kg Fire Extinguisher Mono Ammonium Phosphate Powder 50, Stored Pressure Type, Pressure Gauge, Gross Weight 6.9 Kg, empty weight 2.9 Kg, Can Height 440MM, Diameter 140MM, Discharge Time less than 13 Sees, Controllable discharge mechanism (Squeeze grip with easy snap safety seal), Range minimum 4 meters, applicable on Class A,8, C and electrically started Fire, A Rating 2A, 8 Rating 218, Can construction : Deep drawn & Co., Mig welded, valve Construciton Forging and Mechining, Internal Coating of Can: Epoxy powder coating, External Coating of Can: Epoxy Polyster power coating, Sheet metal thickness: 1.60MM, 5 years Warranty with installation system with Superior quality EPDM Rubber Hosepipe etc., including cost of supporting materials like MS stand & accessaries if it is fixing n floor / MS brackets & accessories if it is fixing on wall, , labour, usage charges of m ( IN FHC AND CORRIDOR AREA)
Refilling of existing Ceiling mounted Fire Extinguisher Mono Ammonium Phosphate Powder 90, 5kg. The refilling rate shall include cost of all lead and lifts, transportation, loading, unloading, fixing and all other incidental charges etc. complete as per specification and directions of the engineer in charge of the work (IN ELECTRICAL ROOM)
Providing 22.5Kg C02 Gas Type Fire Extinugisher, Trolley Mounted, Easy Weight Management used Unused Mechanism, Gross Weight 93.5 Kg. empty Weight 71.0Kg. Can Height 1333M M Diameter 232MM, Discharge Time less than20 Sees, Controllable discharge mechanism, Applicable on Class 8&C Fire, Can Constuction: Hot spinning/Forging, Valve Construction : Forging & Machining, Internal Coating of Can : Not Applicable, External coating of Can : Spray Painting, Sheet metal thickness : 5.20 MM lSI Approved, 1 Year Warranty. including cost of materials, labour, usage charges of machinery complete as per specifications. complete (IN FIRE PUMP ROOM )Providing 22.5Kg C02 Wheel Type
Supply and installation of 2 kg Fire Extinguisher (Mono Ammonium Phosphate Powder 90%), stored pressure type, complete with pressure gauge. The extinguisher shall have a gross weight of 3.6 kg and an empty weight of 1.6 kg. The can height shall be 344 mm, and the diameter shall be 108 mm. Discharge time shall be less than 8 seconds, with a controllable discharge mechanism (squeeze grip with easy snap safety seal). The discharge range shall be a minimum of 2 meters. The extinguisher shall be suitable for use on Class A, B, and C fires, as well as electrically started fires. Fire ratings shall be 1A and 8B. The can shall be constructed using deep drawn and CO₂ MIG welding methods. The valve shall be made through forging and machining processes. Internal coating of the can shall be with epoxy powder coating, and the external coating shall be with epoxy polyester powder coating. The sheet metal thickness shall be 1.60 mm. The extinguisher shall include a superior quality EPDM rubber hose pipe and carry a 5-year warranty with an integrated instalert system. The supply shall include all required materials, labour, and usage charges of machinery for complete installation as per specifications. The product shall conform to IS 15683 standards and shall be CE approved. FOR KITCHEN Providing ABC Powder based MAP 90, 2Kg
Supply and installation of 9 Ltr Water type Fire Extinugisher, Stored Pressure Type, Pressur Gauge, Gross Weight 15.1kg. empty weight 6.1kg Can Height 615MM, Diameter 175 MM, Discharge Time less than 120 Sees, Controllable discharge mechanism (Squeeze grip with easy snap safety seal), Range minimum 6 Meters, applicable on Class A Fire, A Rating 3A, Can Construction; Deep drawn & CO, Mig welded, Valve Construction: Forging & Machining, Internal Coating of Can : Epoxy Powder coating, External Coating of Can : Epoxy Polyster Powder coating, Sheet metal thickness: 2.OM M, lS 15683 and CE Approved. Years Warranty with instalert system with Superior quality EPDM Rubber Hosepipe etc., including cost cost of supporting materials like MS stand & accessaries if it is fixing n floor / MS brackets & accessories if it is fixing on wall,, labour, usage charges of machinery complete as per specifications. complete (IN OFFICE AREA) Providing Water type- 9 Ltr -Stored Pressure
LIFTS (ELEVATORS)Design, supplying, erecting, testing, and commissioning of Passenger/Bed-cum-passenger hospital lift with a speed of 1 mtr per second, variable voltage variable frequency drive, with or without machine room for the available well size, operating at 415V, 3-phase, 50 cycles AC supply. The lift shall include powder-coated/stainless steel car entrance door enclosures with suitable color vinyl flooring, LED car illumination, emergency light, intercom, and fan as desired by the user. Options include central opening/side opening doors with or without attendant operation, 7-segment display buttons, call register indicator, fireman drive, stainless steel (SS) handrails inside the car, full-length infrared curtain in the car door, automatic rescue device with batteries, voice announcement in regional/international languages, and Braille buttons. The scope includes one-year warranty and maintenance, necessary scaffolding, and minor civil works such as fixing guide rails, counterweights, etc.The total product and services shall adhere to IS 14665/2016 (with latest amendments) Part/Section 1 to 5, covering general guidelines for fire safety-rated doors, MRL L-beams, pressure switches, manual changeover for doors during emergencies, automatic rescue device (ARD) with 10-cycle battery backup, and standard dimensions for car and door openings across all lift sizes and capacities. Compliance is required for fitness certificates, CPWD specifications, PCB norms, National Electricity Code (NEC), NBC-2016, IEC standards, and the Karnataka State Lifts, Escalators, and Passenger Conveyors Act 2012 and Rules 2014. All other prescribed safety norms must be observed.The Supplier must be registered with the Government Electrical Inspectorate in the State of Karnataka.Without Machine Room-SS Finish 13 Passengers - 3 Stops
Providing & fixing dumb waiter shall be a heavy-duty, electrically operated vertical lift system with a load capacity of 250kg, designed for ground plus two upper floors, conforming to relevant safety standards (EN 81-31 or equivalent). The car dimensions shall fit within a 1400-1655mm x 1200mm shaft, constructed from galvanized steel with smooth interior finishes, and include dual-speed automatic doors (manual override optional) at each landing (G+2). The system shall feature a robust steel-frame car with laminated or stainless steel lining, guided by precision rails, and powered by a quiet, energy-efficient motor with fail-safe electromechanical braking. Control systems shall include call/send buttons at each floor, key-operated access, overload protection, and emergency stop. Installation includes all structural reinforcements, interlocking doors, shaft enclosures, and fire-rated finishes where required. Testing, commissioning, and certification by a licensed provider shall be provided, ensuring compliance with local regulations.
RAMESH KUMAR KOTHARI (BID ID -3276810)
M.VENKATACHALAPATHI (BID ID -3277030)
RN Constructions (BID ID -3276939)
NANDI ASSOCIATES (BID ID -3276214)
Anand Shree Infra Reality Pvt. Ltd (BID ID -3276940)
BUILTECH ENGINEERING SOLUTIONS (BID ID -3274339)
S SHIVARAJU AND CO (BID ID -3276992)
NJR CONSTRUCTIONS PRIVATE LIMITED (BID ID -3276604)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.40 MB
BOQ_918075.xls
BOQ • 1.01 MB
ServicesAmenityDrawings.pdf
Tender Documents • 16.19 MB
TDAmenity.pdf
Tender Documents • 7.83 MB
Download all tender documents and submit your bid