Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
Tender Value
₹14 L
Closing Date
9 Sept 2021, 4:00 pmClosed
Executive Engineer ED Handwara
office of the Executive Engineer ED Handwara
Improvement/Stabilization of HT/LT Network by way of replacement of Rotten Poles/Worn-out Conductor in Sub-Division Handwara and Langata falling under jurisdiction of ED Handwara under UT capex Budget 2021-22.
2021_PDD_136677_1
e-NIT 24 of 2021-22
Open Tender
Electrical Works
Lump-sum
20 days
Handwara/Langate
Refer to SBD
7 documents required · 7 mandatory
₹700
Executive Engineer ED Handwara
Exempted
11 Sept 2021
27 Aug 2021
10 Sept 2021
30 Aug 2021
9 Sept 2021
30 Aug 2021
Amount
Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site (including Head load) and erection of 9 Mtr. Long Poles (ST-410, SP-33) with pit excavation, refilling the pit with soil, boulders (Note: Poles to be supplied by deptt.)
Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site (including Head load)and Erection of S.T Poles 8 m long (410-SP-15) complete with pit excavation , refilling the pit with soil and boulders . (poles to be supplied by deptt.)
Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site , Laying , stringing, tensioning and binding of 50 mm2 ACSR Conductor , including joints by PG clamps wherever required.(conductor to be supplied by deptt)
Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site , Laying , stringing, tensioning and binding of 30 mm2 ACSR Conductor , including joints by PG clamps wherever required.(conductor to be supplied by deptt)
Cement bottoming of S T poles in 1:3:6 mix as per REC standard 0.5/0.45 cum/pole, muffing 20 cm above ground, including plaster and curing of concrete.
Supply and Painting of poles with one coat of redoxide and two coats of Aluminium paint of standard quality.
Supply and Erection of Galvanized stay set complete with 50 x 8 mm stay clamps, guy insulators 02 nos, anchor plate (200 x 200 x 6 mm), nut bolts ,02 No turn buckle ,1.8 m long, 16 mm dia solid GS rod & 7/3.15 mm dia G.I stranded wire complete.
Supply and fixing of pole Earthing by G.I pipe 40 mm dia or G.I rod 20 mm , 2.5 mtr long through GI strip.
Supplying and fixing of pole Earthing Complete by GI Spiral Earthing, 8 SWG 115 turn coil earthing as per REC Standard
Supplying and Fixing of Danger Plates with clamps with writing in English and Regional Language
Supply and fixing of anti-climbing GI Barbed wire binding with Clamps at a distance of 30 to 40 cm at a height of 3.5 to 4 m from ground level. At-least 3.5 kgs GI barbed wire(12 SWG) is to be used per pole for the purpose.
Supply , and fixing of GI “V’ cross-arm (75x40x40x6)mm with Pole Top Bracket including back clamps of 50X8 mm for fixing V-Cross arm and pole top bracket without making holes in the ST pole as per REC standard for single pole structure as per REC standard.
Supply & installation testing commissioning of 11 KV 3 -phase 3 pole , 400 Amps G.O AB Switch complete with all accessories as per REC standard
Supply and Fixing of 11KV,400 Amp Double Break Isolator with Earthing Blade along with Base Channels ,operating Handle complete with all accessories as per REC standard.
Supply & fixing ,testing, commissioning of 11 KV Disc. Insulators 45 KN (Polymer) with fittings as per REC specification.
Supply and Fixing of LT Structure Single shackle set (Mukhi Type) as per REC standard.
Supply & fixing, testing ,commissioning of LT shackle Insulators 16KN as per REC specification.
Supply & installation ,testing , commissioning of 11 KV Pin Insulators (Polymer) with pins 5KN as per REC specifications.
Dismantling and Re-erection of 9 Mtr. Long Poles (ST-540, SP33) with pit excavation, refilling the pit with soil, boulders and returning of same to Divisional Store.
Dismantling and Re-erection of 8 Mtr. Long Poles (ST-540, SP33) with pit excavation, refilling the pit with soil, boulders and returning of same to Divisional Store.
Dismantling of old stranded ACSR conductor and Re-conductoring of 0.03/0.05 ACSR conductor and returning of same to Divisional Store.
Supply & fixing of GI nuts and bolts of sizes
M/S KHAN ELECTRICAL CONSTRUCTION AND SUPPLIERS
Precision Engineers and Buildings
M/S BHAT ELECTRICALS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .