Tender Value
₹10.8 L
EMD Value
₹21,545
Closing Date
9 Sept 2020, 2:00 pmClosed
Executive Engineer(E)
BSNL Electrical Division, Room No. 124, 2nd floor, Telephone Exchange Building, Panbazar, Guwahati 781001
Providing Electro Mechanical installations/services and Safety security works, for Infrastructure works of IAF sites under NFS Project at Jorhat. FOR PACKAGE-I, New Communication Complex. SH Providing EI Fans, MV Distribution panel and cable laying
2020_BSNL_56447_1
36/NIT/BSNL/GHED/2020-21
Open Tender
Electrical Works
Item Rate
30 days
Guwahati
Please refer Tender documents.
12 documents required · 12 mandatory
₹590
AO(Cash), GMTD, Kamrup
₹21,545
Yes
11 Sept 2020
1 Sept 2020
10 Sept 2020
1 Sept 2020
9 Sept 2020
1 Sept 2020
Amount
SUB-HEAD : I (ELECTRICAL INSTALLATION)
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. a) (Group - 'C')
Wiring for circuit/ sub-main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. a) 2 X 1.5 Sq.mm. + 1 X 1.5 Sq.mm. earth wire.
b) 4 x 1.5 sq.mm. + 2 x 1.5 sq.mm. earth wire
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit along with 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit along with 2 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/PVC conduit/cable management system as required. A) 3 X 1.5 Sq.mm.
B) 6 X 1.5 Sq.mm.
Supplying & fixing following sizes of steel conduit along with accessories in surface/recess i/c painting in case if surface conduit of cutting the wall and making good the same in case of recessed conduit as required. (For AFD and CCTV & Access control systems) a) 20 mm dia.
b) 25 mm dia.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc., as required. (For light plugs to be used in non residential buildings). (Makes: Legrand/Crabtree/MK/ABB/ Schneider) (For wall mounted fans-7 nos, UPS Plug points -10nos)
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. (Makes: Legrand/Crabtree/MK/ABB/Schneider) (For 5/15A raw power sockets in various rooms)
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
Supplying and fixing 3 pin, 5A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
Supplying, Installation, testing and commissioning of pre-wired 2' x 2', surface mounting LED (with not less than 34W power) luminaire suitable for 230Volts A.C. supply complete with all accessories like akcrylic/opal diffuser etc. directly on ceiling including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. (Make: Bajaj/Havells/Philips/Wipro or superior make)
Supplying, installation, Testing and Commissioning of 2' x 2', recess mounted LED (with not less than 34W power) luminaries suitable for 230Volts A.C. supply complete with all accessories like acrylic/opal diffuser including suspension with 2Nos SS chains of 60 cm nominal length and fixing the chains to the ceiling with anchor fastners, connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable on surface/wall, flexible metallic conduit for covering the bare wires, and earthing etc. as required. (Make: Bajaj/Havells/Philips/Wipro or superior make).
Supplying, Installation of 450mm sweep heavy duty exhaust fan with metal blade suitable for 230Volts A.C. supply in the existing opening, including making good the damage, fixing the louvers/ shutters complete connection, testing, commissioning etc. as required. (Make: M/s Havells make, Model-Turbo Force SP or superior make)
Supplying and fixing of wall mounted fan 400mm sweep suitable for operation on 230volts 50Hz AC supply etc., as required. (Make: Havells- D'Zire or similar superior make)
Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required.
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders, etc., as required. a) 300mm width X 50mm depth X 1.6mm thickness
b) 150mm width X 50mm depth X 1.6mm thickness
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in signal red colour on front side as required.
SUB HEAD - II (MCB's & DB's)
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) (Makes: Legrand/Siemens/ABB/Hager/Havells or superior make) a) 4way (4 + 12), Double door (For Lighting-1no, Power-1 no. and AC units -1no.)
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) (Makes: Legrand/Siemens/ABB/Hager/Havells or superior make) (a) 12 Way , Double door (for UPS outgoing-1no)
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Makes: Legrand/Siemens/ABB/Hager/Havells or superior make) a) Single pole
b) Single pole and neutral
c) Blanking Plate
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Makes: Legrand/Siemens/ABB/Hager/Havells or superior make) A) 40A (For Lighting DB)
B) 63A (For Power DB)
Supplying and fixing 20A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, SP MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. (Makes: Legrand/Siemens/ABB/Hager/Havells or superior make)
SUB-HEAD : III (Main MV Panel)
Supply, Installation, Testing & Commissioning of factory fabricated cubical type floor mounted totally enclosed, extensible compartmentalized type dust and vermin proof powder coated indoor MV panel made out of CRCA sheet not less than 2.0mm thick (14G). The panel shall have a base channel of MS ‘C’ section of size 100 mm x 50 mm x 5 mm thickness, painted with anticorrosive paint followed by black enameled paint, air lovers with wire meshing having space and arrangement for incoming cable, insulated and properly supported compartmentalized busbars and busbar support, cable alley with following ratings of Incoming & Out going switch gears, meter, indicating lamps etc. suitable for 415Volts, AC supply system having detachable top & bottom MS plates for incoming & outgoing cable entry, i/c interconnections with suitable sizes of Copper conductor cables/strips, powder coated painting, sign writing and earthing the body with existing conductor complete as required.
A) INCOMING(s) : - a) 250Amps. 50kA breaking capacity (Ics=100% Icu), 4 Pole MCCB, with rotary extended handle) with thermal release of range (200-250Amps) along with extender rotary operating mechanism, spreader terminals, shunt release with electrical & mechanical inter lock provision - 02 Nos.(One no. for ASEB incoming supply & one no.for DEA incoming supply) (Make: Legrand/Siemens/Schneider/L&T)
B) Metering & Indication system in separate compartment : - a) Standard digital Multifunction Meter (flush type) 96mm x 96mm 3ph, 4-wire, IPM 50-550V (P-P) 5A Class 1 with 200/5 CTs alongwith protective HRC control fuses for metering of various parameters like V,A, F, PF, Power, Energy, THD, Maximum Demand (kW/kVA) etc. (M/s L&T make, Model 4420210000) = 1 set. b) LED indication lamps alongwith protective HRC control fuses for 3 phases.
C) OUTGOING(s) : - a) 100Amps., 30kA breaking capacity (Ics=100% Icu) 4 Pole MCCB having thermal release of range (80-100Amps) along with extended rotary operating mechanism, spreader terminals - 6 Nos. (Make: Legrand/L&T/Siemens/Schneider) (For PAC-3nos, Split AC DB-1no., -48V DC power system-2nos) b) 63Amps., 30kA breaking capacity (Ics=100% Icu) 4 Pole MCCB having thermal release of range (50-63Amps) along with extended rotary operating mechanism, spreader terminals - 4 Nos. (Make: Legrand/L&T/Siemens/Schneider) (For 10kVA UPS-2nos, LDB-1no, PDB-1no) c) Spare space provision for accommodating 3nos MCCB of 63A capacity. d) LED indication lamps alongwith protective HRC control fuses for ON & OFF position for outgoing feeders - 20nos. D. 400Amps, 4-strip Aluminium bus bars of suitable size and length with suitable no. of epoxy resin bonded insulating supports for bus bars, PVC colour coated sleeve etc. as required. E. Copper earth bus of 32x6mm size throughout the length of panel with earth studs at both ends.
F. Cable chambers for all incoming and out going circuit cables, including proper supports clip on terminals, clamping arrangements etc., complete as above ------- Note : - 1. All interconnections are to be made with suitable sizes of Copper conductor Cables/Strips. 2. The General Arrangement Drawing of above panel shall be got approved by Engineer-in-Charge before fabrication. 3. The M.V. Panel shall be fabricated by CPRI approved manufacturer.
SUB-HEAD : IV (Cabling Works)
Supplying of following sizes of PVC insulated and PVC sheathed / XLPE insulated Aluminium conductor armoured cable of 1.1 KV grade including transportation, loading, unloading upto site complete as required. a) 4 core 25 Sq.mm
b) 3 ½ core 150Sq.mm
Supplying of following sizes of PVC insulated and PVC sheathed / XLPE insulated copper conductor armoured cable of 1.1 KV grade including transportation, loading, unloading upto site complete as required. a) 4 core 16Sq.mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required. a) Above 95 sq. mm and upto 185 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL pipe as required. a) Above 95 sq. mm and upto 185 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing masonry open duct as required. a) Upto 35 sq. mm
b) Above 95 sq. mm and upto 185 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required. a) Upto 35 sq. mm (clamped with 1mm thick saddle)
b) Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. a) 4 X 25 sq. mm (28mm)
b) 3½ X 150 sq. mm (50mm)
Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 kV grade as required. a) 4 X 16 sq. mm. (25 mm)
Providing, laying and fixing following dia G.I. pipe (Medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc. as required a) 50 mm dia
SUB-HEAD : V (Electrical Earthing & Jack Earthing)
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. (For Body Earthing - 2sets, Jack Earthing - 2sets)
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. (For continuous earth ring inside equipment room, IDF room and Power room and for other connectivity)
Providing and fixing earth bus 0.50 mtr. Long 50 mm X 5 mm copper earth bus bar complete with 2nos. porcelain support, required nut, bolts, fixing the same on surface of wall etc for earth connections complete as required.
Providing & laying of 6mm dia. flexible Braided tinned copper wire for earthing the existing jacks of false flooring i/c wrapping, tightening with the alternate jacks, making terminal connection with the existing earth busbar, lifting of false floor tiles and re-positioning the same after laying copper wire, etc complete as required. (For False Floor of Equipment room & IDF room)
Providing and fixing of adjustable stainless steel hose clamps for binding of above tinned copper wire with the 25mm dia Jacks erected for false flooring, necessary nut & bolt arrangement, etc., as required.
SUB-HEAD : VI (External Lighting)
Supplying & fixing of 25 Watt LED New generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with mid power LED as lighting source and PC cover having TOP Opening driver compartment with IP66 protection and impact resistance of IK07, etc., as required. (M/s Philips/Havells/Crompton/Bajaj or superior make)
Supply & fixing of compound light mast arm made out of 1.5 Mtrs. long, 40mm dia. G.I. pipe bending at 1(one)meter distance with an angle of 100 - 110° (degree) from bottom vertical orientation including supplying & fixing of suitable size of M.S. clamps, nut-bolts, painting, drilling, etc. as required.
Supplying and fixing of out door type wall mounting/pole mounting junction box side hinged door fixed to the base with hinges for path way illumination, shock proof and rust proof, cable entry from bottom / side, 100% weather proof, wall mounting/pole mounting arrangement, tamper proof, fire retardant class FV-0 as per IS :11731 part II including 10A, 230V Base cut out & 2 point stud etc., as required. (Make M/s Sintex code No.GSJB 2014)
Supply & drawing of 3 core 1.5sq.mm PVC insulated PVC sheathed unarmoured flexible copper conductor cable of 1.1KV grade for extending supply from above junction box to fitting etc. complete as required.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. (To be fixed in security room) (Makes: Legrand/Crabtree/MK/ABB/Schneider) a) 8 Module (125 mmX125 mm)
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. (Makes: Legrand/Crabtree/MK/ABB/Schneider) a) 5/6 A switch
M/S ASHISH ELECTRICAL
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .