Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.8 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹19.0 L+₹2.2 L (13.1%)Rejected-Finance | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹20.3 L+₹3.5 L (20.7%)Rejected-Finance | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹20.4 L+₹3.5 L (21.0%)Rejected-Finance | L4 | Rejected-Finance Other than L1 | |
| 5 | L5₹20.6 L+₹3.8 L (22.5%)Rejected-Finance NAGAR PANCHAYAT PATHARDEVA DEORIA | L5 | Rejected-Finance Other than L1 |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
8 Mar 2025, 6:00 pmClosed
GE (AF) SIRSA
GE (AF) SIRSA, PIN-125055
REPAIR/MAINTENANCE OF INTERNAL ELECTRIFICATION SYSTEM ALONGWITH REPAIR/MAINT OF VARIOUS TYPES OF FANS AND ALLIED WORKS AT AF STN SIRSA
2025_MES_697722_1
GE/SRA/T-72/2024-25
Open Tender
Miscellaneous Works
Item Rate
210 days
GE (AF) SIRSA
PLEASE REFER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE (AF) SIRSA
₹70,000
Yes
27 Mar 2025
13 Feb 2025
10 Mar 2025
13 Feb 2025
8 Mar 2025
22 Feb 2025
Amount
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, etc. (except light fittings), removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc complete all as specified and directed.
Taking down/out unserviceable Wires only from the existing Sub-main Wiring of any type and any description, without disturbing Existing Conduit, complete all as specified and directed.
Taking down carefully by unscrewing from boards/outlet boxes, unserviceable fittings and fixtures such as switches, sockets, ceiling roses, lamp holders, regulators, call bells, plug tops, etc. and removal from site complete all as specified and directed. (NOTE: This item is to be measured only when only existing fitting/fixture is required to be replaced. Not to be combined with taking down of point wiring under Item No 01 here-in-before).
Taking down carefully by unscrewing from boards/outlet boxes /walls, unserviceable light fittings, any type and removal from site complete all as specified and directed.
Taking down of unserviceable Distrubution Boards, any type or size including MCCB/RCCB/MCBs and disconnecting the serviceable MCCBs/MCBs and keeping in safe custody for reuse at site or removal from site complete all as specified and directed. (NOTE: Measurement shall be considered only for the DBs)
Taking down of unserviceable MCBs, any type or size and removal from site complete all as specified and directed. (NOTE: This item is to be measured only when only existing MCBs are required to be replaced. Not to be combined with taking down of DB under Item No 04 here-in-before).
Materials and Labour for concealed type point wiring with 1.50 Sq. mm (nominal area) FRLS-H PVC insulated and unsheathed, multi stranded copper conductor cable 1100 Volts grade, single core, laid in existing PVC conduit complete with all fittings and accessories, fixed to walls/ceiling, including mild steel terminal boxes 1.20 mm thick conforming to IS-5133 (Part-I) with 3.0 mm thick plastic laminated sheet top cover (ISI Marked) for mounting switches/ regulator /bell push etc and including 1.50 Sq. mm (nominal area) FRLS-H PVC insulated and unsheathed multi stranded copper conductor cable 1100 Volts grade, single core, earth continuity conductor connected to common earth dolly, for one light point /bell point/ ceiling fan/exhaust fan point controlled by one way switch complete all as specified and directed. (NOTE: Wiring shall be done in existing conduit. Quoted rate shall be excusive of the cost of conduit)
All as per item No. 06 above but for One 5 amps switch socket combination on independent board, complete all as specified and directed (concealed type point wiring with terminal box in existing conduit).
-Ditto- as item No 06 but for One 5 Pin Socket Outlet 6 Amps on the same board, complete all as specified and as directed. (concealed type point wiring in existing conduit).
All as per item No. 06 above but using 2.50 sqmm single core multi stranded copper conductor FRLS-H PVC insulated and unsheathed, cable for 3/6 pin 15 Amp socket outlet controlled by one switch on independent board with and incl 2.50 sqmm green FRLS-H PVC insulated and unsheathed, copper conductor as continuous earth wire with lugs complete all as specified and directed (concealed type point wiring in existing conduit).
All as per item No. 06 above but using 4.0 sqmm single core multi stranded copper conductor FRLS-H PVC insulated and unsheathed, cable for 3/6 pin 20 Amp socket outlet controlled by one switch on independent board with and incl 4.0 sqmm green FRLS-H PVC insulated and unsheathed, copper conductor as continuous earth wire with lugs complete all as specified and directed (concealed type point wiring in existing conduit).
S&F Sub-main Wiring with 2-Runs of 4.0 Sqmm (nominal area) 1100 Volt, PVC insulated unsheathed FRLSH multi-stranded Single Core Copper Conductor Cable and 1-Run of 4.0 Sqmm (nominal area) 1100 Volt, PVC insulated unsheathed FRLSH multi-stranded Single Core Copper Conductor Cable (Green Colour) as Earth Continuty Cable along with the Wiring drawn in PVC CONDUIT complete all as specified and as directed. (NOTE: The wires shall be provided in existing conduit. Quoted rates shall be exclusive of the cost of conduits. Three runs of wire shall be considered as one unit)
All as per item No 12 above, but sub main wiring with 2 runs of 6.0 sqmm wires for and one run of 6 sqmm wire for earth continityalong with the Wiring drawn in PVC CONDUIT complete all as specified and as directed. (NOTE: The wires shall be provided in existing conduit. Quoted rates shall be exclusive of the cost of conduits. Three runs of wire shall be considered as one unit)
S&F new Switch piano, flush type, 6 Amps, single pole, one way complete all as specified and directed.
S&F new Modular Switch 1 way 6 Amps, 1 module complete all as specified and directed.
S&F new Switch piano, flush type, 16 Amps, single pole, one way complete all as specified and directed.
S&F new Modular Switch 1 way, 16 Amps, 1 module complete all as specified and directed.
S&F new socket outlet, flush type, 6 Amps, 2-in-1, multi-purpose 5 pin type complete all as specified and directed.
S&F new Modular Socket 6 Amps, 3 pin type, 2 module complete all as specified and directed.
S&F new socket outlet, flush type, 16 Amps, 2-in-1, multi-purpose 5 pin type complete all as specified and directed.
S&F new Modular Socket 6/16 Amps, 2 module, 2/3 pin combined type complete all as specified and directed.
S&F new switch socket combination outlet, flush type, 6 Amps, 2-in-1, 5 pin type complete all as specified and directed.
S&F new switch socket combination outlet, flush type, 6/16 Amps, 2-in-1, 5 pin type complete all as specified and directed.
S&F new Bell push, flush type, 6 Amps complete all as specified and directed.
S&F new Modular Bell push 6A, 2 module complete all as specified and directed.
S&F new Fan Regulator, 5 Step, Socket type, 100 watt complete all as specified and directed.
S&F Fan Regulator, 5 Step, Piano type, 100 watt complete all as specified and directed.
S&F new Modular Fan regulator, 5 step, 120 watt, 2 module, 230 volts, single pole complete all as specified and directed.
S&F new Modular Fan regulator, 5 step, 120 watt, 1 module, 230 volts, single pole complete all as specified and directed.
S&F new Call bell, musical type, AC 230/240 volts, single pole complete all as specified and directed.
S&F new Call bell, ding dong type, AC 230/240 volts, single pole complete all as specified and directed.
S&F new Ceiling rose, 3 terminals, 230 volts, surface type, bakelite/polycarbonate, isolated body complete all as specified and directed.
S&F new lamp holder with back plate suitable for batten fittings or to be mounted on walls complete all as specified and directed.
S&F in repair Hylem sheet for mounting switches, sockets, fan regulator etc with 3 mm thick plastic laminated sheet cover of size 200 x 150 x 50 mm including cutting for mounting of switches and sockets, complete all as specified and as directed. (NOTE: This item shall not be measured for new point wiring)
All as per Item No 34 above, but with 3 mm thick plastic laminated sheet cover of size 250 x 200 x 50 mm complete. (NOTE: This item shall not be measured for new point wiring)
All as per item No 34 above, but with 3 mm thick plastic laminated sheet cover of size 350 x 300 x 50 mm complete. (NOTE: This item shall not be measured for new point wiring)
S&F new Modular type White cover plate with frame 1/2 module complete all as specified and directed.
-ditto- but for Modular type White cover plate with frame 3 module complete all as specified and directed.
-ditto- but for Modular type White cover plate with frame 4 module complete all as specified and directed.
-ditto- but for Modular type White cover plate with frame 6 module complete all as specified and directed.
-ditto- but for Modular type White cover plate with frame 8 module complete all as specified and directed.
S&F surface mounted LED luminaire, 1 X 20 Watt in aluminium housing, 110 lumen/watt, operating voltage 180-270 V, with acrylic/polycarbonate difuser & integrated constant current electronic driver complete with all other accessories internally prewired and including connecting up with three core flexible copper wire of suitable size complete all as specified and directed.
-ditto- as per Item No. 42 but of 1 X 9/10 Watt capacity in polycarbonate housing with lumen output not less than 105 lumen per watt
-ditto- as per Item No. 42 but of 1 X 05 Watt capacity in polycarbonate housing with lumen output not less than 105 lumen per watt
S&F LED Bulkhead fitting 09/10 watt, with IP65 degree of protection and with impact resistance of IK-08, mounted on wall /ceiling connected with insulated unsheathed flexible copper wire of suitable size complete all as specified and directed.
S&F recess mounted LED luminaire, of size 600 mm x 600 mm, 110 lumen/watt, in powder coated CRCA housing , having glare free diffuser, operating voltage 180-270V, with constant current electronic driver complete with all accessories with and including 36 Watt LED and incl all accessories, mounting frame etc and connecting up with three core flexible copper conductor wire of adequate size complete all as specified and directed.
S&F wall light/fixture light made up of high grade engineering plastic material suitable for 9 W LED lamp B22 base withn complete all type of fittings complte all as required and directed. (MAKE: HAVELLS (FLORET) Cat No : LHFHCHE1TL1W020 or equivalent model in other makes specified in tender)
S&F wall light/fixture, stainless Steel brushed nickle finish fixture with opal Glass diffuser suitable for 9 watt LED lamp B22 Base complete all type of fittings complte all as required and directed. (MAKE- HAVELLS (Florentine WL 1LS B22 SS) Cat Part No-LHFOAJE1TZ1I060 or equivalent model in other makes specified in tender)
Supplying, assembling & fixing in repairs Modular MCB protected Power Unit comprising of following accessories :- (i) Powder Coated Steel terminal box, 06 module - 01 No (ii) Modular Cover Plate with Frame, 06 Module - 01 No (iii) 16 Amps 3 Pin Modular Socket, 02 module - 01 No (iv) 16 Amps Plug Top - 01 No (v) 25 Amps Motor Starter, 02 Module - 01 No (vi) 25 Amps, Single pole Mini MCB, 10kA - 01 No
Supplying, assembling and fixing modular AC power unit comprising of 01 No 16 Amps socket and 01 No 32 Amps SP MCB, 3 modules along with GI metallic flush box, cover plate and frame duly concealed in wall incl dismantling of existing power unit complete all as specified and directed. NOTE: Quoted rate shall be deemed to include for the cost of MCB, socket, GI flush box, cover plate & frame. Concealed conduit wiring shall be measured seperately.
S&F in repairs 32 Amps modular motor starter with cover plate & frame, 2 modules along with GI metallic flush box duly concealed in wall complete all as specified and directed. NOTE: Quoted rate shall be deemed to include for the cost of cover plate & frame and GI flush box alongwith starter. Concealed conduit wiring shall be measured seperately.
S&F DB, VTPN, 4 way, vertical type, IP 43 protection, double door, 415 volts with provision for MCCB as incomer and MCB as outgoing and electrically connecting up complete all as specified and directed.
S&F TPN DB, IP 43 protection, double door, 415 volts, 4 way (8+12), with 100 Amps copper bus bar for each phase complete all as specified and directed.
S&F SPN DB, IP 43 protection, double door, 240 volts, 4 way, with 100 Amps copper Bus Bar complete all as specified and directed.
S&F Double Door, Sheet Metal Enclosure for DBs, for mounting of MCB for 240 Volts, 8 way, with 100 Amps rated copper bus bar, Single Pole & Neutral, complete all as specified and directed.
S&F Sheet Metal Enclosure, Single Pole with a 2-Pin and Earth Plug and Socket and Connecting up complete all as specified and as directed.
NOTE FOR ITEM NO. 52 to 56 :- (1) Incoming MCCB/RCCB/MCB and outgoing MCBs shall be measured and paid seperately. (2) Quoted rate is deemed to be inclusive of blanking plate for slots remaining blank after fixing of MCBs. (3) DB, MCCB, RCCB & MCB shall be of the same manufacturer.
S&F MCCB, 4 pole, 100 Amps, 16 kA, 415 Volts, AC, 50 Hz with and including adjustable thermal and magnetic setting, fixed in DB complete all as specified and directed.
S&F MCB, 'C' series, TPN, 415 volts, 63 Amps, breaking capacity 10KA complete all as specified and directed.
S&F MCB, 'B' series, TPN, 415 volts, 63 Amps, breaking capacity 10KA complete all as specified and directed.
S&F MCB, 'C' series, SPN, 40 Amps, breaking capacity 10KA complete all as specified and directed.
S&F MCB, 'C' series, single pole, 6 to 32 Amps, breaking capacity 10KA complete all as specified and directed.
S&F in repairs DB Cover (Double Door), mild steel CRCA duly powder coated suitable for VTPN 4 Way DB including all necessary fasteners, nut bolts, flanges and welding work for fixing in existing DBs complete all as specified and directed.
S&F in repairs DB Cover (Double Door), mild steel CRCA duly powder coated suitable for SPN 8 Way DB including all necessary fasteners, nut bolts, flanges and welding work for fixing in existing DBs complete all as specified and directed.
S&F in repairs DB Cover (Single Door), mild steel CRCA duly powder coated suitable for SPN 4 Way DB including all necessary fasteners, nut bolts, flanges and welding work for fixing in existing DBs complete all as specified and directed.
Supply, laying, jointing and testing, fixing to wall using clamps/ pole/ floor or in air or passing through pipes/ducts/road/path/drain, laid in trenches, 1100 volts grade heavy duty electric cable XLPE insulated, screened, PVC bedded, galvanised steel wire or wire armoured with electric power cable 1100 volts grade with stranded aluminium conductor of size 4 core 25 sqmm confirming to IS-7098 Part-1 and its latest amendments including taking down existing unserviceable cable complete all as specified and as directed by Engr-in-Charge.
S&F in repairs PVC electrical conduit, 25 mm dia, MMS type, medium grade complete all as specified and directed.
S&F in repairs PVC Casing caping pipe, 25 mm size, MMS type, medium grade complete all as specified and directed.
S&F in repairs, installation, commissioning and testing Polycarbonate ASTA CPRI approved OEM fabricated Meter Panel, made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistant, Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of CPRI TEST REPORT IN POLYCARBONATE OF DEGREE OF INGRESS PROTECTION IP65 IN ACCORDANCE WITH IEC 60529 and the share panel assembled by OEM , channel partner or sister concerned assembly will not be accepted. The ASTA CPRI report shall have mention of following tests performed and passed out satisfactorily Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak, short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits and submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The gasket should be internally embedded made of polyurethane. The panel should pass glow wire test 960°C in accordance with 60695-2-11 [flame retardant and self-extinguishing] complete all as specified and directed. Contd.....
NOTES FOR ITEM NO. 68 :- (1) Meter panel shall be designed for for fitment of 04 single phase meters. Existing meters shall be re-fixed in the panel. (2) The panel shall be provided with the following accessories :- (a) 04 Pole MCCB 100 A, 415 volts, 16 kA - 01 No (b) SPN MCB, 40 Amps, 10 kA. 'C' Curve - 04 Nos (3) The meter panel shall be wall mounted type. (4) MCCBs & MCBs shall be provided from the makes as specified in particular specifications. No claim shall be entertained at a later stage.
M&L for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground vertically to a depth not less than 2.25 meter deep below ground level with top edge earth plate at a depth not less than 1.5M below normal ground level connected to galvanized steel earth wire 4 mm dia (upto 7.5 metres) by means of bolts, nuts check nuts and washers of galvanized steel and connected to main switch board or main control board as directed and including provision of concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 45 cm x 45 cm x 5 cm reinforced with 8 mm dia. TMT bars @ 150 mm centre to centre both ways, with one handle for lifting made out of 8 mm dia MS bar, provision of funnel, wire mesh, 20 mm bore galvanized steel tubing (Medium grade) for watering, charcoal or coke and salt in alternate layers, 40 mm bore galvanized steel tubing medium grade for protection of earth lead connection, necessary excavation and earth work in any type of soil and including necessary testing and dismantling of existing unsv earthing complete all as shown in Figure 15A of IS 3043 :1987, complete all as specified and directed.
Taking up/down carefully AC Ceiling Fans / BLDC Ceiling Fans / Exhaust fans / Pedestal fans / Air circulator fans / Wall Mounting fans / Flame proof fans, of any size or sweep from various location/Bldgs (or collecting from MES E/M store yard) as directed, opening up for servicing/repairing, removing dust and dirt, cleaning fan motor, with cotton/waste material, washing blades with detergent powder, servicing/Oiling, Lathe work if any required and greasing of fan of any size/type by using appropriate grade of oil/grease and replacing defective parts such as armature, canopy, fan blade, ball bearing, fan down rod, shutter/louvers, MS shaft, bush, bearing split pin, rubber bush, holding clamps, capacitor as per suitable size, MS Clamps, rubber packing, split pins, rubber reel, springs etc, for the smooth and satisfactory functioning and reassembling complete, refixing ceiling fan/exhaust fan/wall fans with proper PVC flexible pipe 20 mm dia, in same position (or deposited to MES Store yard), connecting of copper flexible cable to electrical system and including proper testing complete all as specified and directed.
NOTES :- (I) Replacement of unserviceable parts shall be measured and paid separately under respective items as "Supply Only". Quoted rate shall be deemed to include for other petty spares, accessories and consumables. No claim shall be entertained during currency of work. (II) On testing after completion of repair of any items, if the proper speed/smoothness is not obtained at Engg-in-Charge satisfactory level, the repairing will be re-done by the contractor at his own costs and same will be deemed to be included in quoted rates. (III) The contractor shall maintain/open workshop and keep his electrician ready during working Hrs ( 0900 Hrs to 1700Hrs) for repair/rewinding purpose inside Mes Store yard so that all the repairing/re-winding of all type fans shall be done in proper manner. MES authorities will not be issue any fans of any make/type/size for repair/rewinding purpose to the contractor for outside the Air Force premises.
Rewinding of Ceiling fan Motor 240 Volt, 50 Hz, of any make with super enamelled copper winding wire of existing size including sleeves work, varnishing with 'B' class insulation varnish complete all as specified and directed for the following size of fans :- (NOTE: Motor shall be wound with machine with same or more No of turns as per existing provision).
Ceiling fan, AC, 1200 mm sweep, any make or type
Ceiling fan, AC, 1400 mm sweep, any make or type
Rewinding of Exhaust Fan Motor, 240 Volt, 50 Hz, of any make with super enamelled copper winding wire of existing size including sleeves work, varnishing with 'B' class insulation varnish complete all as specified & directed for the following size of fans :- (NOTE: Motor shall be wound with machine with same or more No of turns as per existing provision).
300 mm sweep
380 mm sweep
400 mm sweep
430/450 mm sweep
Supply only Capacitor 2.5 mfd, paper type suitable for Ceiling Fan / Exhaust Fan/ Wall Mounted Fan of any Make and any size, complete all as specified and as directed.
Supply only Capacitor 3.15 mfd, paper type suitable for Ceiling Fan/Exhaust Fan/Wall Mounted Fan of any Make and any size, complete all as specified and as directed.
Supply only Anti-suicidal Fan Rod, of size 200 / 250 / 300 / 450mm, as applicable with Load bearing Capacity 15 to 25Kg comprising / inclusive of the following Specifications :- (a) A pair of Supply Wire (b) Holes for Shackle fitting on Ceiling (c) Hole for Supply Wire bringing out after Inserting Caps (d) Wire to connect to fan motor (e) Hole for Safety screw fittings (f) Holes for Fan Motor Shaft. (MAKE: GOLD LIFE or any other make as approved by GE)
Supply only Connection wire consisting of PVC insulated Twin Core twisted copper Flexible Wire of 23/.0076 from connector block to ceiling rose for Ceiling/Exhaust Fan Connection, complete all as specified and as directed.
Supply only Connection wire consisting of PVC insulated Twin Core twisted copper Flexible Wire of 40/.0076 from connector block to ceiling rose for Ceiling/Exhaust Fan Connection , complete all as specified and as directed.
Supply only PVC connector with screws, suitable for ceiling fans complete all as specified and directed.
Supply only up/down Canopy, suitable for Ceiling Fan 1200mm /1400mm Sweep, of any Make or type complete all as specified and as directed.
Supply only Armature for ceiling fan suitable for 1200 mm sweep with prewired copper wound armature complete all as specified and directed.
Supply only Armature for ceiling fan suitable for 1400 mm sweep with prewired copper wound armature complete all as specified and directed.
Supply only holding clamp for capacitor of ceiling fans 1200/1400 mm sweep, any type complete all as specified & directed.
Supply only MS / D Clamps for hanging purpose of ceiling fans with proper rubber reel packing & split pin complete all as specified and as directed.
Supply only Ball Bearing 6201/6202 (as approved), complete all as specified and as directed.
Supply only Ball Bearing 6203/6204 (as approved) , complete all as specified and as directed.
Supply only Bush made up of Gun Metal suitable for Ceiling Fan/ Exhaust Fan / Wall Mounted Fan of any Make and any size, complete all as specified and as directed.
Supply only spare parts/components, for 1200 mm sweep BLDC Ceiling Fans (non-remote type) complete all as specified and directed as under :-
Rotor Ring Magnet, 16 poles, permanent ferrite type with high gauss and quality
PCB Controller Driver/Board with plastic casing/box incl all accessories
Top & Bottom Aluminium Cover Set, with screws, duly spray painted with two coats synthetic enamel paint over a coat of primer
MS Shaft
Stamping Stator, 16 Pole, made of CRNO steel alongwith Plastic Ring
S&F in Repairs Polycarbonate Fan Blade, comprising of 3 blades, suitable for Wall Mounted Fan, any Make, complete all as specified and as directed for the following size of fans :-
400 mm sweep
450 mm sweep
S&F in repair PVC Ventilating Fan, rectangular type including all electrical connection with suitable copper flexible wire complete all as specified and as directed for the following size of fans :-
250 mm sweep
300 mm sweep
S&F Metallic/Aluminium Blades, duly spray painted/powder coated, suitable for Ceiling Fans of any Make, complete all as specified and directed for the following size of fans :-
Ceiling Fans, AC, 1200mm Sweep
Ceiling Fans, AC, 1400mm Sweep
Ceiling Fan, BLDC, 1200mm Sweep
S&F Metallic Blades, comprising of three blades, duly painted, suitable for Exhaust Fans of any Make, complete all as specified and directed for the following size of fans :-
300 mm sweep
380 mm sweep
400 mm sweep
430/450 mm sweep
S&F in repairs Shutters/ Louvers suitable for Exhaust Fans, of any Make and Type/Shape, duly painted and fixed on Brick Wall and grouted with Nuts, Bolts and Washers complete all as specified and as directed for the following size of fans :-
300 mm sweep
380 mm sweep
400 mm sweep
430/450 mm sweep
S&F Ready Made Metallic Frame suitable for Exhaust Fans, of any Make and Type/Shape, duly painted complete all as specified and as directed for the following size of fans :-
300 mm sweep
380 mm sweep
400 mm sweep
430/450 mm sweep
S&F Plug Top 05/06 Amp, ISI marked, complete all as specified and as directed.
S&F Plug Top 15/16 Amp, ISI marked, complete all as specified and as directed.
M&L for complete painting of fans with two coats of synthetic enamel paint, tint of paint as per existing with spraying Machine, writing MES No after preparation of surfaces complete i.e. Holding Down Rod, Fan Blades, Fan Body, Canopies and removing old paint by scrapping, cutting, rubbing, etc. and filling of Putty as required, complete all as specified and as directed for the following types of fans :-
Ceiling Fan 1200 mm sweep, any type or make
Ceiling Fan 1400 mm sweep, any type or make
Metallic Exhaust Fan 250 mm to 300 mm sweep, any type or make
Metallic Exhaust Fan 380 mm to 400 mm sweep, any type or make
Metallic Exhaust Fan 430mm to 450 mm sweep, any type or make
Metallic Exhaust/Wall Fan 600 mm sweep, any type or make
AMBIKA ENTERPRISES (BID ID -3257301)
YOGINDER KUMAR GUPTA AND COMPANY (BID ID -3250390)
NISHTHA BUILDERS (BID ID -3247241)
M/s Shree Bala Ji Construction Company (BID ID -3256261)
M/S KAVYA ENTERPRISES (BID ID -3256438)
shiv shanker enterprises (BID ID -3251163)
POOJA CONSTRUCTION COMPANY (BID ID -3255359)
Aditi Formation Company (BID ID -3256734)
stage.html
html • 0.06 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .