Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹86.2 LAccepted-AOC | ₹86.2 L | L1 | Accepted-AOC LOWEST |
| 2 | L2₹88.2 L+₹2.0 L (2.37%)Rejected-Finance 14 SURI LANE KOLKATA 700 014 | KOLKATA | KOLKATA | WEST BENGAL | 700014 | ₹88.2 L+₹2.0 L (2.37%) | L2 | Rejected-Finance HIGHEST |
| 3 | L3₹91.2 L+₹5.0 L (5.81%)Rejected-Finance | ₹91.2 L+₹5.0 L (5.81%) | L3 | Rejected-Finance HIGHEST |
| 4 | L4₹97.6 L+₹11.4 L (13.2%)Rejected-Finance D 1 1 GILLANDER HOUSE 8 N S ROAD KOLKATA 700001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | ₹97.6 L+₹11.4 L (13.2%) | L4 | Rejected-Finance HIGHEST |
Tender Value
Refer Docs
EMD Value
₹1.8 L
Closing Date
23 Nov 2022, 2:00 pmClosed
Superintending Engineer Electrical PWD
Superintending Engineer PWD North Bengal Electrical Circle P.W.D Inspection Bungalow Annex Building 1ST Floor Kutchery Road Venus More Siliguri
Construction of Himalayan Centre of Presidency University at Dowhill Kurseong Dist. Darjeeling S.I.T.C. of Compound Light LC and LED Glow Sign Board
2022_WBPWD_410149_1
WBPWD/SENBEC/NIT-02/2022-2023
Open Tender
ELECTRICAL WORKS ORG
Item Rate
45 days
Dowhill Kurseong
Please refer Tender documents.
5 documents required · 5 mandatory
₹1.8 L
Siliguri
29 Oct 2024
23 Sept 2022
25 Nov 2022
23 Sept 2022
23 Nov 2022
20 Oct 2022
17 Oct 2022
Amount
Supply of 6Mtrs height hot dip galvanised octagonal pole made of HT steel of grade S355 with 130 mm bottom A/F & 70 mm top A/F made up of 3mm thick G.I. sheet along with base plate of size 225 x 225 x 16 mm thick with inbuilt Sleek terminal box with required sizes studs for 4 core 16 sq mm A Al cable termination as required and 10A porceline fuse for each out going with proper pad locking arrangement (2 nos.). NOTE : Above 6 Mtr. & 8 Mtr. Octagonal pole should contain terminal box capable for fixing of 3 phase connector box including 8/F of 3 phase looping connector box with allied accessories as per requirement and as per direction of E.I.C.
Supply of 8Mtrs height hot dip galvanised octagonal pole made of HT steel of grade S355 with 135 mm bottom A/F & 70 mm top A/F made up of 3mm thick G.I. sheet along with base plate of size 220 x 220 x 12 mm thick with inbuilt Sleek terminal box with required sizes studs for 4 core 16 sq mm A Al cable termination as required and 10A porceline fuse for each out going with proper pad locking arrangement (2 nos.). NOTE : Above 6 Mtr. & 8 Mtr. Octagonal pole should contain terminal box capable for fixing of 3 phase connector box including 8/F of 3 phase looping connector box with allied accessories as per requirement and as per direction of E.I.C.
Supply and Fixing of single arm header assembly fabricated from 40mm dia. GI Pipe (ISI-M) of following length rigidly welded with 80 mm dia. GI Pipe (ISI-M) of 0.3 Mtr. long as pole sleeves at an angle of 105⁰ including S/F 3Nos ½” MS jam nut each with 1No. ½” dia. through bolt, pole cap and painting as to GS of the entire assembly.
i) 1 mtr length
ii) 1.5 mtr length
Supply and Fixing of double arm header assembly fabricated from 40mm dia. GI Pipe (ISI-M) of following length rigidly welded with 80 mm dia. GI Pipe (ISI-M) of 0.3 Mtr. long as pole sleeves at an angle of 105⁰ & suitable angle between the two arms including S/F 3Nos ½” MS jam nut each with 1No. ½” dia. through bolt, pole cap and painting as to GS of the entire assembly
i) 1 mtr length
ii) 1.5 mtr length
S & F Circular Ring Shapped GI Pipe (ISI-M) (40mm dia.) pole bracket of 600 mm dia with 0.3 Mtr long Sleeves of 80 mm dia. GI Pipe (ISI-M), including S/F 3Nos ½” MS jam nut each with 1No. ½” dia. through bolt, pole cap and painting as to GS of the entire assembly
Erection of Single octagonal pole of length 6/8Mtrs with 4 nos. 20mm dia 600/700 mm length "J" type Bolt projected 100 mm & Nut etc. in CC foundation (Proportion and dimension indicated below), having 600x600x150 mm thick CC (4:2:1) base block with hard jhama metal including 1300 mm depth x 500mm dia cylindrical type RCC (6:3:1) muffing and 0.50 mts. above ground level including 3 mm thick neat cemented finish and for alkathene/polythene pipe entry, for street light wiring, without Loop Box with GI earth bolt after making drilled holes etc. on base plate & carriage of pole upto 1.6 Km from Store to work-site including filling up the excavated earth pit with shifted soil and ramming properly.
S & Delivery of 3 mtr long Hot-Dipped galvanized mild steel step decorative pole, Eliptical Aluminium Sheet riveted to the pole, with grey UV stabilized pure polyester coating after HOT-Dipped, mild steel base plate of dia 260mm with 4 nos eliptical holes of 20x42mm on 210mm PCD suitable for M12 bolts, with inbuilt Sleek terminal box with required sizes studs for 4 core 16 sq mm A Al cable termination as required and 10A porceline fuse for each out going with proper pad locking arrangement (2 nos.) Pole design parameters vary depending on the type of bracket and loading factor. • All pole sections are welded using special v groove technique by certified welders using high end MIG welding processes. • Cast Iron made of ASTM A48 Class 25 • Built-in control box with cast aluminium service door and safety rope.
• Cast Iron door is contoured to the shape of the pole. • The control gear tray is prewired with MCB, terminal connectors for loop-in / loop-out arrangement. • The foundation bolt holes in the base plate are designed to be elongated for fine adjustments / alignment of the pole during installation. • Base plate made of steel grade E250 & foundation bolt of grade 4.6
Erection of Single 3 mtr long Hot-Dipped galvanized mild steel step pole with 4 nos. 12mm dia 400 mm length "J" type Bolt projected 80 mm & Nut etc. in CC foundation (Proportion and dimension indicated below), having 450x450x150 mm thick CC (4:2:1) base block with hard jhama metal including900 mm depth x 300mm dia cylindrical type RCC (6:3:1) muffing and 150 mm. above ground level including 3 mm thick neat cemented finish and for alkathene/polythene pipe entry, for street light wiring, without Loop Box with GI earth bolt after making drilled holes etc. on base plate & carriage of pole upto 0.5 Km from Store to work-site including filling up the excavated earth pit with shifted soil and ramming properly.
Fixing only outdoor / street light type LED light fitting complete with all accessories to be fixed/projected from the wall of the building incl. making holes to building, S&F 40 mm dia GI pipe (ISI-Medium) 1.50 mts. average length, with GI socket at one end and thread at the other end & suitable bend to house the fitting & making necy. connections with S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall and painting. [C03:19]
Supplying & Fixing MS/Steel water proof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for up to 2- core 16 sq.mm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint.
Supply & Drawing 1.1 KV grade 3Core 22/0.3 (1.5 sqmm) XLPE insulated Un-armoured Cu Cable (Brand approved by EIC) for connection from loop box to fittings through the Pole including making connections as necessary.
Supply only of 250V, 80W LED Street Light Minimum system lumen not less than 9600 luminaries in Pressure die cast Aluminum housing with heat resistant toughened glass cover & IP66 Protection complete with all accessories. (for 8 mtr pole). NOTE : All street light / compound light should contain internal surge protection with external 10KV surge protection (linline SPD).
Supply only of 250V, 60W LED Street Light Minimum system lumen not less than 4200 luminaries in Pressure die cast Aluminum housing with heat resistant toughened glass cover & IP66 Protection complete with all accessories. (for 6 mtr pole). NOTE : All street light / compound light should contain internal surge protection with external 10KV surge protection (linline SPD).
Supply F of 250V, 90W LED Flood Light Minimum system lumen not less than 10000 in Pressure die cast Aluminum housing with heat resistant toughened glass cover & IP66 Protection complete with all accessories. for back side of hostel & others residencial block (for circular type bracket) NOTE : All street light / compound light should contain internal surge protection with external 10KV surge protection (linline SPD).
Fixing only of SV/MV/LED street light fittings with arm bracket or pole top on pole.
Supply & Fixing 45W to 60W LED Decorative Post Top light fitting in Pressure die cast Aluminum base with Prismatic polycarbonate diffuser, LED lamp colour Temp-4000K Spun Aluminium top cover & IP66 Protection complete with all accessories..[K-LITE 4998 GADAI / PHILIPS : BGP300 LED 50757 PSU PCINS1 / WIPRO : LP07-671-XXX-40-CL] NOTE : All street light / compound light should contain internal surge protection with external 10KV surge protection (linline SPD).
Supply & Delivary LED Decorative Post Top light fitting in Pressure die cast Aluminum base with Prismatic polycarbonate diffuser, LED lamp colour Temp-4000K, Spun Aluminium top cover & IP66 Protection complete with all accessories as Gate Light.[K-LITE 4993 MAGUDAM / PHILPS : BGP161LED / WIPRO : LP09S-671-XX-57-XX] NOTE : All street light / compound light should contain internal surge protection with external 10KV surge protection (linline SPD).
Supply & Fixing of 80/40mm dia GI pipe (ISI-M) of 1.5M long on the existing piller of GATE including making arrangement for CC construction upon the piller for fixing of GATE light and making necessary connection.
Supply &Fixing of 10W inverted pyramid tripod type LED bollard with IP65 protection by providing CC (6:3:1) circular base block (1'dia & 6'' height) above ground level, neatly cemented finish (3mm thick) including holes for cable entry without loop box. [PHILIPS : BCP400LED09DCW PSU GR S1 / WIPRO : LB14-131-XXX-65-05]. NOTE : All street light / compound light should contain internal surge protection with external 10KV surge protection (linline SPD).
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required. 2x22/0.3 (1.5 sqmm)+1x22/0.3 (1.5 sqmm) ECC. [E14:1a(i)]
Supply & Fixing of 250V, 50W LED Flood Light in Pressure die cast Aluminum housing with heat resistant toughened glass cover & IP66 Protection complete with all accessories for Drive Way and Play ground. for Car parking Tunel & play ground (20 + 16 nos.)
Supply & fixing compound light timer Control Unit (Indoor type) for Academic building compound assembled with following accessories and wiring with 4sq.mm Cu wire(For MCB to Contractor / terminal block),1.5 sq.mm Cu wire (For control wiring). Suitable size 16 SWG CRCA sheet metal box having min depth 3.5" and should have adequate strength and space to accommodate the following accessories. i) 63 A TP MCB (Make: L&T / Legrand / ABB)-1no as incomer ii) Digital 24 hour time switch(Make-GIC)-1no. iii) 32A 3-Pole Power Contractor (L&T:Cat No-CS94981)-2nos. iv) 25 A TP MCB "C" curve (Make: L&T / Legrand /ABB) -2 nos. as out going v) Toggle Switch (ON-OFF-ON)-1No vi) Out going terminal stud with nut--8sets. vii) Indication lamp (R,Y,B)- 1 Set. viii) EI Danger Board (6”X4”) – 1No. Metal Box should have gasket arrangement inside the door and entry and exit points of IN-OUT power, which protect the dust insertion and two locking arrangement with allen key. The panel box should be painted by powder coated paint & the layout diagram of the panel board should be approved by the E.I.C before manufacturing
Supply & fixing compound light timer Control Unit (Indoor type) for Faculty building, Hostel Building compound and decorative light of Academic building, assembled with following accessories and wiring with 4sq.mm Cu wire (For MCB to Contractor / terminal block),1.5 sq.mm Cu wire (For control wiring). Suitable size 16 SWG CRCA sheet metal box having min depth 3.5" and should have adequate strength and space to accommodate the following accessories. i) 32 A TP MCB (Make: L&T / Legrand / ABB)-1no as incommer ii) Digital 24 hour time switch (Make-GIC)-1no. iii) 32A 3-Pole Power Contractor (L&T:Cat No-CS94101)-1no. iv) 25 A TP MCB "C" curve (Make: L&T / Legrand /ABB) -1no as out going v) Toggle Switch (ON-OFF-ON)-1No vi) Out going terminal stud with nut--4sets. vii) Indication lamp (R,Y,B)- 1 Set. viii) EI Danger Board (6”X4”) – 1No. Metal Box should have gasket arrangement inside the door and entry and exit points of IN-OUT power, which protect the dust insertion and two locking arrangement with allen key. The panel box should be painted by powder coated paint & the layout diagram of the panel board should be approved by the E.I.C before manufacturing
Supplying only the following 1.1 KV grade PVC insulated A/Al. Cable as below:
4 core 16 sq mm. [For Pole to Pole]
4 core 25 sq.mm. [ For LT-Panel to Control Box]
4 core 10 sq.mm. [ For wall fitted light]
Supply & Laying of 2 Core 6 Sq.mm PVC insulated A/Al cable [KEI / HAVELLS / POLYCAB] (for Botlard fittings).
Laying of cable upto 3/4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting. [F1:2b]
Laying only Cable upto 50 sq.mm through existing RCC/Hume/ GI Pipe / Open masonary trench for single, 2, 3, 3½ & 4 core. [F1:3a]
Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed. F02:1a]
Laying of cable as below, after cutting floor/pavement / wall / and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish. From 2.5 sqmm to 35 sqmm at an average depth of 75 mm in floor / pavement / wall etc. [F03:5(i)]
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below
4 core 16 sq mm. [F4:7c]
4 core 25 sq mm. [F4:7c]
4 core 10 sq mm. [F4:7c]
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials.
4core 16 sq mm. [F5:8b(xii)]
4 core 25 sq mm. [F5:8b(xiii)]
4 core10 sq mm. [F5:8b(x)]
Supplying & fixing medium gauge GI Pipe (ISI-Medium) Protection with necessary fittings and jointing materials as required.
40mm dia. [F06:11c]
50mm dia. [F06:11d]
Excavation of soil for installation of Earth Electrode and filling & ramming.For Morrum Soil. [G01 : 1b]
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. Long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. Long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. Long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. Below the ground level as below: a) By ISI-Medium GI pipe. [G01 : 2a]
S & L of heavy guage Polythen Rolled pipe of 40mm dia clamping with the retaining wall of boundary by S & F of suitable sizes MS/ Aluminium strip clamp and srew etc. For laying of compound light cable
PART-B--Lightning Conductor
M :- LIGHTING CONDUCTOR :- S & F Lightning Conductor Air Terminal made of 20 mm dia 1000 mm long GI pipe (ISI Medium) having five discharge prongs of 4 SWG GI (Hot Dip) wire at top duly soldered with 7/16 stranded GI (Hot Dip) wire and 85 mm dia 6 mm thick GI base plate at bottom incl. necessary holes etc. complete duly grouted on the parapet etc. in CC mortar ( 4:2:1), including thimble joints of 7/16 SWG wire and GI strip with SS nuts, bolts & washers. (P-J-2/Item-14 + NS)
Supply & fixing GI (Hot Dip) strips 20 mm x 3 mm thick for horizontal run on the Parapet/Roof/ Wall with GI Saddles 1100 mm apart incl. mending good the damages to building works, including welded lap joints, 'T' joints, etc. and painting the joints with 2 (two) coats of bituminous paint. (P-J1/Item-9)
Supply & fixing of GI (Hot Dip) strips 20 mm x 3 mm thick for vertical run on wall with GI saddles spaced not exceeding 1000 mm apart incl. mending good damages to building work, including welded lap joints, 'T' joints, etc. and painting the joints with 2 (two) coats of bituminous paint. (P-J1/Item-11a)
Cutting cornices/ steps etc. including cutting recess in buildings etc. & supply & fixing 15 mm bore (ISI-Medium) GI pipe protection as below and mending good damages to the building works: i) Length upto 0.5 Mtr
ii) Length above 0.5 Mtr
Hiring charges for scaffolding arrangement including dismantling at the end of work and carriage, for LC installation, per storey of building per vertical run. (P-J1/Item-7)
Supply & Fixing of Testing Joints by 20 mm x 3 mm thick GI (Hot Dip) strip 125 mm long on wall after making suitable arrangement to establish a clearance of 50mm from wall for making junction connection with vertical conductor and conductor from earth electrode complete with S & F GI bolts, nuts, check-nuts, spring washers etc. and provide a protective arrangement for that junction point by keeping it in a GI housing / enclosure (openable for maintenance procedure) , as required. (P-J2/Item-13 + NS)
Earthing with 65 mm dia GI pipe (TATA-Medium) 3.0 Mts. long with welded half circle bracket of GI strip (65 x 8) mm. with two holes on extended portion of the strip of length min. 200 mm, and 1 No. 50 mm x 6 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 65 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts. ( NS) --- For LC.
Supply, Laying & Fixing of 50mm x 6mm galvanized (Hot Dip) steel strip in underground trench for interconnection between the Earth Points by proper welding and painting the lap & 'T' joints with 2 (two) coats of bituminous paint for making a Earth Grid. (NS)
PART - C -- SITC of Cable Tray
Supply & Fixing of perforated GI cable tray with perforation notmore than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support [D-14/34(a)]
(i) With 25 x 25 x 3mm angle iron support
300 x 50 x 1.25mm (18SWG).
Supply & Fixing of following perforated GI cable tray fittings with perforation notmore than 17.5% suspended from ceiling with two nos. suspenders& 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fasteneretc. as required of the following size. Incl. Al painting of MS support.
300x50x1.25mm (18SWG) (Bend).[D-15/34(b)]
300x50x1.25mm (18SWG) (Tee).[D-15/34(c)]
S & F cubical shape structure made by 1 ½” x 1” of 14 Swg hollow bar. The size of the structure as per requirement of site (measurement will be made in square feet) incl. S & F hollow bars (support should be such that the distance between two intermediate support will be at least 2 feet) for extra support of the structure (Front side & back side) & 6 nos. rectangular hollow bars per square feet for jointing the front side & back side of the structure. The structure fabricated by proper wielding method and finished as per direction of E.I.C. Providing one no door is required at back side of the structure for maintenance the SMPS.
S/F aluminum sheet (24 SWG) for covering back side wall and also covering upper, lower & two side of the structure. The aluminum Sheet fixed on the structure by all thread screw.
S/F of 3 mm thick aluminum composite panel (Make - Aludacor). ACP sheet ( colour should be approved by EIC) to fixed on the front side of the structure & upper & lower side cover by ACP sheet with proper nut & bolts including finishing all side as per direction of E.I.C.
S/F Aluminum angle 1 ½” X 1” of 26 swg on the outer periphery of the ACP board for providing the extra support and beautification of the steel letter board. Front side of the angle painted by powder coating. as per direction of E.I.C. Painting the whole structure by two coats of Synthetic enameled paint over one coat of R.O primer after scrapping the structure as per direction of E.I.C. Carrying charges for the above work including loading- unloading charges (2 nos. Board of size 4 feet × 18 feet)
S/F of the special type of Imported Acrylic letter (male and female type) fixed on ACP sheet after router cutting .The letter Font = English, Hindi, Bengali (Bold) Letter colour = White. Acrylic letter illuminated with waterproof LED lights (Make - Samsung / Cray / Nichia/Panasonic) with waterproof power supply unit as follows. The modular LED lamp will be fixed inside of the acrylic letters including S/F 12V & 2.5W I Adopter/ SMPS. The LED fixed by adhesive & bound. The SMPS fixed on the back side of the structure including making necessary connection.( no of LED Module and power supply as per requirement and as per direction of EIC. NOTE- 1. Inscription of the board i.e matter will be supplied at the time of layout. Agency must verify the matter in demo form from the EIC before finalize in the same and also place for approval by the EIC. 2. Measurement of the acrylic lettering will be made as per actual layout and it will be considered in running inches i.e. height of letter multiplied by no of letter 3. Measurement as mentioned above may be increase or decreased as per actual layout. 4. Quality and grade of the letter should be strictly follow as per specification.
Scaffolding charge for the above mentioned work on the said building incl. all caring charges (from Kolkata to worksite) loading & unloading etc. including making arrangement for fixing the board on wall incl. S/F necessary books new bolt etc.
TERMS & CONDITIONS
a. Rate should be quoted inclusive of all applicable taxes and Duty etc.
b. The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
c. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
d. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
e. Make of the items will be as per approved make as uploaded herewith.
T.D.K. ENTERPRISE
NARAYAN THAPA
MACKINTOSH BURN LIMITED
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .