Superintending Engineer
Office of the Superintending Engineer, Western Electrical Circle , PWD, Purta Bhavan, 1st floor, Burdwan-713103
Construction of 100 beded Critical Care Block (CCB) at hooghly district hospital under PM ABHIM..Electrical WORK ...... SITC of DG Set
2025_WBPWD_820120_1
WBPWD/SEWEC /HED /NIQ-95 /2024-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
45 days
Hooghly
Please refer Tender documents.
5 documents required · 5 mandatory
₹1.3 L
Office of the Superintending Engineer, Western Ele
8 May 2025
25 Feb 2025
24 Mar 2025
25 Feb 2025
20 Mar 2025
28 Feb 2025
25 Feb 2025 - 28 Feb 2025
28 Feb 2025
Amount
SITC of 500 KVA, 415V, 50Hz, 3Phase silent new DG Set incl. full tank HSD oil, comprising of ingine, alternator, separate AMF panel, Base frame, Fuel tank, Batteiy, .CPCB-IV ± approved Ingine & Acoustic Enclosure having following specifications (ISO-8528 Part-lV) :
Engine :
Make: CUMMINS/ Caterpillar/ Parkins/ MTU/ Volvo Penta/ Kirloskar/ Greaves)
Engine Type : 4 Stroke Diesel Engine.
Rated Output: 594 ВНР or Higher
Duty : PRIME
Cooling : Coolant with radiator
Cylinder : As per OEM Standard
Aspiration : Turbo Charged
Type of Governor : Electronic
Fuel Tank Capacity : Minimum capacity 740 Ltrs.
Fuel Consumption As per OEM Standard
Overload Capacity : 10% overload for one hour for every 12 hours continuous running at full load or better
Engine instrument Panel : Consisting of starting switch with Key, Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter.
Safety Controls : Emergency Stop, Low Lube Oil Pressure warning/ Shutdown, High Engine Water Temp, warning/ Shutdown, Sensor failure Indicator, Engine over speed indicator Battery charging and low battery indicator.
Exhaust Silencer : Residential Type/Hospital Grade
Starting system : 12V/ 24 V starting system complete with starter motor, charging alternator with reclifier and Cutout as per manufacturer standard.
Battery : Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning.
Alternator
Make: Stamford/ Leroy Somer/ Kirloskar/ ЛВВ/ GE/ Alsthom/ Crompton)
Rating - 415 V., 3Ph. 50 Hz., 500 KVA, 1500 rpm
Type - Brushless, self excited and self regulated through an AVR.
Insulation class - H
Protection - Screen-protected drip proof with Min.IP-23 degree of protection
Rated Current: 695 A
Voltage Regulation [max] - ±1%
Winding connection - Star with Neutral
Total Distortion factor - No load < 1.5%, Non distorting balanced linear load < 5 %
Power Factor - 0.8 pf [lag]
Total Harmonic distortion in output waveform - <5%
AMF Panel
Cubical type floor mounted AMF panel made from 14 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, suitable for controlling of 500 KVA DC set having following specification/features. Manufactured by the OEM / CPRI approved panel builder.
i] 415V, 800 A or higher , 5OKA, EDO type ACB with 0/L, S/C, E/F protection and microprocessor based protection release , U/V release etc. [make: Legrand / Siemens / Schneider Electric / L&T /ABB ] - 2 Sets
ii] S &F of 1200A, capacity 99.9% -99,5% electrolytic tinned copper (Certificate should be produced by manufacturer) with multicolor heat shrinkable PVC sleeve 4 Bus Bar (Size uf flat 4 nos 100 mm x 10 mm) of required length mounted on non-hygroscopic porcelain insulator having sufficient di-electric strength duly insulated by multicolor (Red, Yellow, Blue & Black) heat shrinkable PVC sleeve for phases & neutral identification. All interconnection/branches should be made with required size of cu bars (Cu-bar extensions of required shape and current carrying capacity may have to be provided at terminals of ACB as per direction of E1C) & remote monitoring of internal temparature of every bus section & cable alley should be provided -1 set.
iv) In Built By-Pass switch for rated capacity
v) On -delay timer for load change over
vi) On-delay timer for engine shut off
vii) Engine On-Off switch [Push button type)
ix) Minimum five number indicating lamps to indicate 'mains ON', 'load on mains', Set running', 'load on set' and ’battery charger on'.
x) Audio visual alarm for 'Low lubricating oil pressure', 'High coolant temperature, Start failure', and DG over load'.
xii) Microprocessor based relay with composite meter for digital display of following.
a) Generator voltage/AC Mains voltage.
b) Generator Current in all phases
c] Frequency
d) Power Factor
e) Indication for alternator supply
f) Running time indications number of hours of operation and service intervals, service due indications.
The AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15 (fifteen) second from the instant of mains failure.
Acoustic Enclosure
The DG set should have integrated acoustic enclosure at the manufacturing state itself. High quality acoustic enclosure must be certified as per CPCB-1V+ norms.
Base Framed-
Common iron channel fabricated base frame containing the engine and alternator, mounted on AVM pads and having provision for lifting Hook.
Supply & Installation exhaust pipe line (thickness 4 mm.) connection with MS black pipe ISI approved necessary flange, nuts, bolts, washers & gasket incl. electrical welding where necessary.
150 mm (6") dia.
S&F 150 mm MS heavy type long bend.
S&F 150 mm MS Plug incl socket with short piece.
S&F rain protection canopy suitable for 150 mm MS pipe.
S&F of MS angle iron structure made of (80x80x6)mm / (50x50x6) mm MS angle 50mm x 8mm MS flat, nut, bolt, washer etc to support 150 mm dia MS pipe, chair for fuel tank & AMF pane etc incl painting as per GS.
Painting the 150 mm dia MS black pipe (approx 35 Mtrs) by Aluminum paint of two coat over the RO primer (Approved make).
Wrapping the residential exhaust silenser pipe for 500 KVA DG Sets.
Wrapping the exhaust pipe line (150 mm) with Al. sheet high quality with necessary wire mesh & 50mm thick glass wool as per direction of EIC.
Providing Cement concrete foundation for the DG set with 1:2:4 (M20 ) Grade, including excavation, providing base concrete with 1:5:10 cement concrete required centering shuttering/finishing the exposed portion by net cement plastering ect. As required (item will be paid base on measurement for 1:2:4 CC but excluding the 1:5:10 leveling course of base concrete) as per direction of EIC and manufacturer recommendation.
S & delivery of 200 ltrs. Capacity barrel made of 2 mm thick MS Sheet.
Supply & delivery of best quality oil hand pump with 1” dia PVC flexible pipe [12' ft. approx.) [Brand approved by EIC)
Excavation of soil for installation of Earth Electrode and filling & ramming as to GS [For soft soil).
Earthing with 80 mm dia G1 pipe [TATA-Mediurn)x 6.0 Mts. long and 1 No. 65 mm x 8 mm galvanised [Hot Dip) steel trip [4 Mts. long), 20 inm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 80 mm dia GI pipe [lSl-Medium) protection [3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 6.65 Mts (For Neutral earthing for 500 KVA DG Set)
Earthing with 65 mm dia GI pipe [TATA-Medium)x 3,0 Mts. long and 1 No. 50 mm x 6 mm galvanized [Hot Dip) steel strip [4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 65 mm dia GI pipe [ISl-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts (Body & AMF panel earthing for 500 KVA DG Set).
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(l;6) of 25 cm width duty plastered with sement morter (inside) Cl hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe »
Extra for treatment oi soil by using salt & charcoal or coke for plate electrode.
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 65 mm x 8 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required
Extra for connecting Earth busbar to earth electrode including S & F 50 mm x 6 mm Galvanized (Hot Dip) steel strip on wall/floor with GI saddles 8 s insulating the same by one layer of PVC strip over one layer of ampere tape
Supply & laying of 1.1 KV grade PVC copper conductor control cable (Finolex/Gloster/Havells) partly recessed and partly by shaddle on wall to interconnect DG set with AMF panel.
a) 14 core 2.5 sq.mm, for communication.
b) 5 core 2.5 sq.mm, for sequence of power.
c) 2 core 4 sq.mm, for DC power
S & F compression type brass cable gland & finishing the cable of following size.
a) 14 core 2.5 sq.mm.
b) 5core 2.5 sq.mm.
c] 2 core 4 sq.mm.
Sohum Industrial Sales Corporation (BID ID -6254026)
Shakti Industries (BID ID -6254889)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .