AC( Electrical)
STC BSF BANGALORE
REPLACEMENT OF MAIN DISTRIBUTION PANEL IN TYPE I AND II JAWAN FAMILY RESIDENTIAL AREA UNDER STC BSF BANGALORE
2025_BSF_892089_1
20/AE(E)/FTROD/BGLR/BSF/2025
Open Tender
Electrical Works
Works
60 days
IG STC BSF BANGALORE
Please refer Tender documents.
11 documents required · 11 mandatory
₹0
₹12,000
17 Jan 2026
1 Jan 2026
12 Jan 2026
1 Jan 2026
9 Jan 2026
1 Jan 2026
1 Jan 2026 - 9 Jan 2026
Providing and fixing following rating and breakingcapacity and pole MCCB with thermomagneticrelease and terminal spreaders in existing cubiclepanel board including drilling holes in cubicle panel,making connections, Ics=100% Icu and OperationalVoltage 690V etc. as required. A) 400 A, 35 KA,TPMCCB
B) 250 A, 25 KA,TPMCCB
C) 200 A, 25 KA,TPMCCB
D) 125 A, 16 KA,TPMCCB
E) 100 A, 16 KA,TPMCCB
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. A)3½ X 240 sq. mm (62mm)
B) 3½ X 185 sq. mm (57mm)
C) 3½ X 120 sq. mm (45mm)
D) 3½ X 150 sq. mm (45mm)
E) 3½ X 35 sq. mm (32mm)
F) 3½ X 70 sq. mm (38mm)
Providing and fixing of 315 A, 4 Pole On load Changeover with spreaders link in existing cubicle panel including drilling holes in cubicle panel, making connections, etc. as required. cat no. IS04 (Havells) or equivalent specification Standard/ Havells/ Siemens/ HPL/ Socomec/HPL
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.51 MB
BOQ_937671.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .