| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.6 LAccepted-AOC 106 DR LALIT BANERJEE SARANI GROUND FLOOR KOLKATA 700073 | KOLKATA | KOLKATA | WEST BENGAL | 700073 | L1 | Accepted-AOC Stands Lowest | |
| 2 | L2₹35.6 L+₹4.0 L (12.8%)Rejected-AOC 11 CROOKED LANE KOLKATA 69 | KOLKATA | KOLKATA | WEST BENGAL | 700069 | L2 | Rejected-AOC Stands 2nd Lowest | |
| 3 | L3₹37.0 L+₹5.4 L (17.1%)Rejected-Finance 8 TOWNSHEND ROAD KOLKATA 700025 | KOLKATA | KOLKATA | WEST BENGAL | 700025 | L3 | Rejected-Finance Stands 3rd Lowest |
Tender Value
Refer Docs
EMD Value
₹67,688
Closing Date
27 Oct 2021, 1:30 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer
Office of the Executive Engineer, Purba Medinipur Electrical Division, P.W.Dte, Tamluk, Hospital More
Electrical Installations work for establishment of 24 bed hybrid critical care unit at Purba Medinipur District Hospital,Tamluk,Purba Medinipur---SITC of AC system.
2021_WBPWD_346810_1
PWD/EE/PMED/eNIQ-24/21-22
Open Tender
ELECTRICAL WORKS ORG
Item Rate
21 days
Tamluk
Please refer Tender documents.
5 documents required · 5 mandatory
₹67,688
14 Dec 2021
11 Oct 2021
29 Oct 2021
11 Oct 2021
27 Oct 2021
11 Oct 2021
120 days
Condensor Unit for 11 TR capacity system- SITC of 11.0 TR Capacity Microprocessor based air cooled Condensing Unit Eco Friendly refrigerant,thermastatic expansion valve, Double scroll compressor arrangement for operation with Dx type AHU, and suitable for operation on 415+/-10% Volt, 50Hz, 3 PH AC supply With protection of crankcase heater, HP/LP Cut outs, thermostats, Power and Control contactors for Evaporator Fans, Condenser fans, Compressors and matching condenser units, isolator switch for condenser units. Outdoor Air cooled Condenser unit shall comprise of Copper coil with Aluminium fins and Axial fan with fan Speed Controller. The static pressure of the outdoor unit shall be more than 75 Pa to avoid hot air circulation. The system should give non-stop cooling at 48-52 degrees of outside ambient temperature and provide test certificate. (Make:General/ Hitachi / Voltas/ Daikin/ Bluestar) No extra shall be payable for refrigerant gas & transportation/ shifting work.(For HDU 1 & 2)
Condensor Unit for 5.5 TR capacity system- SITC of 5.5 TR Capacity Microprocessor based air cooled Condensing Unit Eco Friendly refrigerant,thermastatic expansion valve, single scroll compressor arrangement for operation with Dx type AHU, and suitable for operation on 415+/-10% Volt, 50Hz, 3 PH AC supply With protection of crankcase heater, HP/LP Cut outs, thermostats, Power and Control contactors for Evaporator Fans, Condenser fans, Compressors and matching condenser units, isolator switch for condenser units. Outdoor Air cooled Condenser unit shall comprise of Copper coil with Aluminium fins and Axial fan with fan Speed Controller. The static pressure of the outdoor unit shall be more than 75 Pa to avoid hot air circulation. The system should give non-stop cooling at 48-52 degrees of outside ambient temperature and provide test certificate. (Make: General/Hitachi / Voltas/ Daikin/ Bluestar) No extra shall be payable for refrigerant gas & transportation/ shifting work.(For HDU 3 & 4)
UVC EMITTER UVC EMITTER (254 nm) for the above AHU's for prevention of fungus in the chilled water cooling coils. The minimum UV intensity in the coils shall be between 600 to 700UW-SEC/CM2 . The unit shall be UL Listed (UL- 1995) (MAKE - Philips/Alfaa / RUKS/Aero Pure)
REFRIGERANT PIPING WITH INSULATION Supply & Laying Hard / Soft drawn Copper Refrigeration pipe line for liquid and suction line suitable for R410 refrigerant & 19 mm thick Nitrile Rubber 'class O' Insulation tube with supports & brackets with 19 mm thick nitrile rubber insulation with Al. Foil covered (make - Accroflex/Suprime/ Armacell) arrangement on walls as per direction of EIC. Liquid Line (1/2")
REFRIGERANT PIPING WITH INSULATION Supply & Laying Hard / Soft drawn Copper Refrigeration pipe ( Make- Nippon/ Hitachi-Ryoku/ Mandev) for liquid and suction line suitable for R410 refrigerant & 19 mm thick Nitrile Rubber 'class O' Insulation tube with supports & brackets with 19 mm thick nitrile rubber insulation with Al. Foil covered (make - Accroflex/Suprime/ Armacell ) arrangement on walls as per direction of EIC. Suction Line (7/8").
DRAIN PIPE Supply and fixing of Drain piping by PVC with 6mm thick nitrile rubber insulation and necessary quantities of supports, flanges, bends, elbows, fittings, nut-bolts, gaskets etc: 32 MM. (Make- Oriplast/ Supreme/Finolex)
DUCT WORK Supply & fixing of Class - VIII grade (120 GSM) supply air duct along with necessary supports, flanges etc. as required and as per IS 655 and IS-277 standards of following gauges.(Make- Tata/Jindal/Sail) 22 SWG
DUCT WORK Supply & fixing of Class - VIII grade (120 GSM) supply air duct along with necessary supports, flanges etc. as required and as per IS 655 and IS-277 standards of following gauges.(Make- Tata/jindal/Sail) 24 SWG
S & F of HEPA Filter with efficiency of 99.99% down to 0.3 microns of size as per actual site requirement to accommodate inside the exhaust air duct. (Make: FMI/ Spectrum /Puromatic )
Supply & Fixing of Aluminium powder coated supply air grilles with volume control damper. (Make - Premire /Systemair / Air Enterprise / Caryaire /Airmaster)
Supply & Fixing of Aluminium powder coated return air grilles without volume control damper. (Make - Premire /Systemair / Air Enterprise / Caryaire / Airmaster)
Supplying, Fixing,testing and commissioning of combination smoke fire dampers (UL 555)of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. (Make - Greenheck/Systemaire/ Airmaster/ Caryaire/ Air enterprises)
Supplying, Fixing,testing and commissioning of Volume Control dampers of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. (Make - GreenheckSystemaire/ Airmaster/ Caryaire/ Air enterprises)
Actuator (Make-Belimo/Honeywell/ Siemens)
Supply & Fixing of Fresh air package with cowl, bird net arragements and volume control damper. (Make - Premire /Systemair / Air Enterprise / Caryaire / Airmaster)
EXHAUST FAN Supply & fixing of Inline Flow fan for exhaust air as per reuirement for successful performance (Make -Nicotra/ Kruger/ Caryaire). 1000 CFM / 60 mm of WG (For HDU 3 & 4)
EXHAUST FAN Supply & fixing of Inline Flow fan for exhaust air as per reuirement for successful performance (Make - Nicotra/ Kruger/ Caryaire). 2000 CFM / 60 mm of WG(For HDU 1 & 2)
DUCT THERMAL INSULATION Supplying and fixing of 19 mm thick duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation. (Make - Armacell / K Flex / Supreme / Aflex)
DUCT THERMAL INSULATION Supplying and fixing of thermal insulation on Room exposed Duct with 50mm thick TF quality expanded polysterene slab incl. checken mase wire & sand cememt pest.
DUCT COVERING Supply & Fixing of IDU & Duct Covered with 3mm Thick ACP Board (Make:Aludecor/Protap Bond/ HexBond/ Alstone) Coplete with linkages, levers, fittings, supports, all accessories any other item required to make the system complete as per direction of E.I.C.
Supply & Installation of Diferential Pressure Gauge to monitor the Negative Pressure . (Make- Danfoss/ Beliimo/Honeywell)
Cost of Allied Putty Civil work. N.B. 1. An Auto CAD GAD of AHU & Duct system should get approved before commencement of the work. 2. System should be fine tuned to make a NEGATIVE PRESSURE arrangment. 3.OEM Certificate for Double Skinned AHU / Evapourator Unit/ Condensing Unit/ Motor/ Fan/ Filters should be submitted.
YOUNG ENGINEERING ENTERPRISE
SKY DECORATIONS PRIVATE LIMITED
stage.html
html • 0.05 MB
technical_665534.pdf
PDF • 0.27 MB
techsummary_665534.pdf
PDF • 0.02 MB
finance_665534.pdf
PDF • 0.27 MB
BOQ Comparative Chart
xlsx • 0.01 MB
finsummary_665534.pdf
PDF • 0.32 MB
FWO.pdf
PDF • 0.24 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .