| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.1 LAccepted-Finance | L1 | Accepted-Finance Quoting Lowest Rate | |
| 2 | L2₹16.0 L+₹1.9 L (13.8%)Rejected-Finance | L2 | Rejected-Finance Quoting Higher Rate | |
| 3 | L3₹16.7 L+₹2.7 L (19.0%)Rejected-Finance 125 SHIVAJI NAGAR SAVARKUNDLA SAVARKUNDLA GUJARAT 364515 | AMRELI | GUJARAT | 364515 | L3 | Rejected-Finance Quoting Higher Rate |
Tender Value
Refer Docs
EMD Value
₹40,000
Closing Date
15 Jan 2025, 11:00 amClosed
Superintending Engineer,Western El.Circle,PWD
Office of the Superintending Engineer, Western Electrical Circle , PWD, Purta Bhavan, 1st floor, Burdwan-713103
Upgradation of UPS arrangement for SNCU, NICU and PICU at Paediatric Building within the campus of Burdwan Medical College and Hospital, Purba Bardhaman.
2025_WBPWD_797078_1
WBPWD/SEWEC /BED /NIQ-82 /2024-25-3rd Call
Open Tender
ELECTRICAL WORKS ORG
Item Rate
90 days
Purba Bardhaman
Please refer Tender documents.
5 documents required · 5 mandatory
₹40,000
Office of the Superintending Engineer, Western Ele
21 Jan 2025
8 Jan 2025
17 Jan 2025
8 Jan 2025
15 Jan 2025
9 Jan 2025
8 Jan 2025 - 9 Jan 2025
9 Jan 2025
Amount
Supply, Installation, Testing & Commissioning of 15 KVA, 3 Ph, 4 wire, 415 Volt, 50 Hz AC Input and 3 Ph, 4 wire, 415 Volt, 50 Hz / (As per actual site requirement & choice of EIC) Modules comprising of IGBT Microprocessor based DSP controlled PWM technology double conversion true on line UPS System having Isolation Transformer at imput , Input voltage range is 415 volt,+10%-15% AC, Input THD<3% on liner load & THD<5% on non liner load, crest factor 3:1(max), Output voltage 415 V AC,0.8 pf, Efficiency 85%~92%, pure sine wave.The static bypass switch shall automatically transfer the critical load to bypass input supply without interruption after the logic senses one of the following conditions ups overload beyond rating, Battery runtime expired and bypass available for Inverter failure. Fatal error in control system. The static bypass switch shall be equipped with a manual means of transferring the load to bypass and back to inverter. Also UPS should have separate manual bypas switch. DC voltage 216 Volt the UPS sould be connected with battery bank consisting of required no of 12V, total 12480 VAH SMF VRLS battery which can provide minimum back up of 60 minutes on full load with open M.S Rack installation of battery & making necessary connection with suitable size of necy length copper wire, cable etc. & 63 Amp plug top. (Make: AVO / VERTIV / APC & Battery Make- Exide power safe / Amara Raja) Terms & Conditions:-36 months onsite warranty on complete installation inclusive of spare parts, battery etc. from the date of installation.
UPS Technology & Capabilites
i) True online configuration with double conversion
ii) Fully digital control with three Digital Signal Processor including rectifier, Invertor, Charger. Protections Advanced electronic protection for device safety backed with MCBs, Fast acting fuses, High speed pulse blanking.
iii) Input power factor to load>0.99
iv) Main back feed protection
v) Lightning Protection Device
Overload Capacity
110% for 10 minutes, 125% for 1 minutes, 150% for 5 Second. 103% for continious.
UPS Display Panel
The Display panel should capable for display of following measurement/ as per standard availability of specified manufacturer.
i) Input - Voltage/ Frequency/ Current.
ii) By- pass - Voltage/ Frequency.
iii) Output - Voltage/ Frequency/ Current.
iv) Battery - Voltage/ Current/ history data/ residual capacity/ charging status.
v) Load - KVA/ KW/ Percentage
vi) Others standard measurement as per manufacturer standard & IS specification.
B) The display panel should also capable to display following indication
i) DC bus boltage - High/ Low
ii) Inverter - Overload / Short Circuit/ Low
iii) Over Temperature -Battery / By-pass/ Inverter
iv) Fault - Rectifier/ By-pass / Inverter/ Paralleling
v) Fuse failure- Input / Output
vi) Battery - Low/ Overcharged
vii) Mains - On / Fail / High / Low / Single Phasing
Switchgear:
MCB / MCCB for Input, Battery, Output & Manual Bypass Switch.
Alarms
The UPS should generates an audioble alarm for following condition.
Mains failour
Battery Low
UPS Over Load (>_ 110 %)
Fault
Shout Down
Battery Bank / Charger/ Rack
i) Minimum charger rating- 10% of battery AH rating offered
ii) Battery recharge time (after complete discharge) to 90% capacity -8-10 Hrs.
iii) Battery Protection - DC MCCB (Internal/ External)
iv) Battery End Cell Voltage - 1.75 V
v) The UPS battery shall be of Advanced Glass Mat Valve Regulated Sealed Lead Acid Battery Construction type (AGM or VRSLAB) in ABS Flame Retardant (UL94V-O) grade (UL 2436) spill containment casing to meet UL 62368-1/IEC 62133 or equivalent standards type.
vi) Automatic float cum boost charging capability with settable float & boost charging voltage & current levels and boots charger time.
UPS Physical Condition
i) Operating Temperature- 40°C
ii) Humidity: 90% RH (Non Conditioning)
iii) Protection Class - IP-20
iv) Type of Cooling - Forced Air
v) Noice Level - <60db at 1 mtr distance
vi) All the electronic cards inside shall be with conformal coating to protect from harsh / Moist environment.
vii) UPS panel should have Dust filter protection with sensor.
viii) Monitoring Software: UPS Monitoring Software on Windows XP Platform
ix) Communication: RS 232, RS 485, SNMP Provided
x) Remote Monitoring features available.
Certification
ISO 9001: 2015, ISO 14001: 2015, ISO 18001, OHSAS 18001 CE Marking:IEC/EN 62040-1-1, IEC/EN 62040-2(EMC Emission),IEC/EN 62040-3(performance & Design)
Static Bypass Switch :-
i) The static shall consist of fully rated Silicon Controlled Rectifiers (SCRs)
ii) The static bypass switch shall automatically transfer the critical load to bypass input supply without interruption after the logic senses one of the following conditions Inverter overload beyond rating. Battery runtime expired and bypass available. Inverter failure. Fatal error in control system.
iii) The static bypass switch shall be equipped with a manual means of transferring the load to bypass and back to inverter.
iv) Also UPS should have separate manual bypas switch.
Terms & Condition
i) Any Problem must be set right with 24 hrs after reporting.
ii) Two mobile nos of different responsible person must be specified alongwith offer for reporting of problems in future.
Carrying cost of battery and UPS to Burdwan site along with installation, fitting & fixing of accessories etc.
C. CHOWHDURY & CO. (BID ID -5992665)
S. N. ENTERPRISE (BID ID -5994844)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .