SUPPLY CUM ERECTION OF ELECTRICAL WORKS AT CISF BARRACK, QUARTER GUARD AND OTHER ALLIED BUILDINGS FOR OSBL FACILITIES ON ITEM RATE BASIS AT TALCHER FERTILIZERS LIMITED, TALCHER, ODISHA
2024_PDIL_806948_1
PNPM/PC-183/E/8006/NCB DATED 11.05.2024
Open Tender
Electrical Works
300 days
Talcher
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹15 L
Yes
PDIL, Noida
26 Aug 2024
11 May 2024
19 Jun 2024
11 May 2024
18 Jun 2024
20 May 2024
17 May 2024
Amount
ELECTRICAL WORKS
DISTRIBUTION BOARD (MPDBs / PDBs / LSDBs / SPDBs / FPB ) Design, Supply, Installation, Testing and Commissioning at site of following weather proof Distribution Board made of CRCA sheet steel IP-55 execution having minimum thickness 2.0 mm suitable for wall / structure mounting, Indoor /Outdoor type and the same shall be suitable for DIN rail mounting MCBs/MCCBs/RCCBs etc. with provision of both (top & bottom) entry with 3nos.LED phase indicating lamps in incomers. Required nos. of suitable Elmex/ phoenix /connectwell terminals, crimping type Cu lugs and double compression rolled aluminum cable glands for Incomer and outgoing cable feeders including power and control cable glanding and terminations, handling, transportation from owner's store/ storage yard to erection site; unpacking, inspection; dressing of foundation as required; on frame works/supports grouted or welded to columns/structures; mounting in position and connecting of loose components and accessories; drilling of gland plates with required holes or enlarging existing holes for cable entries; fixing of cable glands and terminal supplied loose; plugging of all unused cable entries in the board/panels to make the same dust and vermin proof, making good of wall/column broken or chipped by cement plastering; minor repair and touch painting work; operational and functional checking; supply of fixing bolts, nuts and washers and other necessary hardwares and civil masonry materials; all work, labour and materials complete as per drawings & documents, specifications, codes and standards and directions of Engineer-in-Charge. Further please note that termination shall also include drilling, tapping of cable insulation, crimping of lugs to the conductor & connection of the lugs to equipment terminal..If any board is installed in outdoor area PVC shed shall be provided covering the total switchboard and safe staying of one person for maintenance during rainy season.
415V Hose proof and weatherproof industrial type sheet steel enclosed, Extendible type Main Switchboard (MPDB at Vikrampur Guest House) with IP-55 degree of protection having 2 nos. 3200A 4P ACB I/C, 1 No. 3200 A ACB B/C, 1 No. 800 A 4P ACB I/C and Outgoing Feeders as indicated in SLD/ feeder details with ammeter & Voltmeter as per Technical specifications.
415V Hose proof and weatherproof industrial type sheet steel enclosed, Extendible type Power Distribution Board (PDB-1) for CISF Barrack with IP-55 degree of protection having 2 nos. 800A 4PMCCB I/C and Outgoing Feeders as indicated in SLD/ feeder details with ammeter & Voltmeter as per Technical specifications.
415V Hose proof and weatherproof industrial type sheet steel enclosed, Extendible type Power Distribution Board (PDB-2) for BUngalows with IP-55 degree of protection having 2 nos.800A 4P ACB I/C and Outgoing Feeders as indicated in SLD/ feeder details with ammeter & Voltmeter as per Technical specifications.
415V Hose proof and weatherproof industrial type sheet steel enclosed, 12 way Lighting Distribution Board (LSDB) for CISF Barrack with IP-55 degree of protection having 1 no, 63A 4P MCCB, 3 nos 63A DP RCBO in phase and 12 nos.16A DP MCBs outgoing as per Technical specifications , SLD, standards & direction of Engineer in charge including provision for 2 nos earthing with 1x16 sq.mm (Al) unarmoured cable.
415V Hose proof and weatherproof industrial type sheet steel enclosed, 18-way Sub-Power Distribution Board (PDB) for Switch Socket / AC with IP-55 degree of protection having 1 no. 63A 4P MCCB, 63 A DP RCBO in each PHASE and 9 Nos. outgoing 16 A DP MCBs & 9 Nos. outgoing 32A DP MCB as per Technical specifications , SLD, standards & direction of Engineer in charge including provision for 2 nos earthing with 1x16 sq.mm (Al) unarmoured cable.
415V Hose proof and weatherproof industrial type sheet steel enclosed, 21-way Sub-Power Distribution Board (PDB) for Switch Socket / AC with IP-55 degree of protection having 1 no. 63A 4P MCCB, 63 A DP RCBO in each PHASE and 15 Nos. outging 16 A DP MCB & 6 Nos. outgoing 32A DP MCB as per Technical specifications , SLD, standards & direction of Engineer in charge including provision for 2 nos earthing with 1x16 sq.mm (Al) unarmoured cable.
415V Hose proof wall mounted type 24 way MCB prewired Lighting Distribution board having 1 no. 125A 4P MCCB, 63 A DP RCBO in each PHASE and 18 nos 16A DP MCB outgoing feeder and 6 Nos.32A DP MCB outgoing feeder as per Technical specifications , SLD, standards & direction of Engineer in charge including provision for 2 nos earthing with 1x16 sq.mm (Al) unarmoured cable.
Wall mounted Meter Distribution Board complete with 125A Fuse and 125A Isolator, 3 phase, 4 Wire, 415V, house service type (20KW) Digital Energy Meter.
Wall mounted Meter Distribution Board complete with 32A Fuse and 32A Isolator, 1 phase, 2 Wire, 240V, house service type (2KW) Digital Energy Meter.
110 V DC, 2 Wire, Compartmentalized steel enclosed DC Distribution Board (DCDB) . It shall consist of 1 nos. incoming 63 A DP MCCB incomers (with ON & OFF Indication Light) and 14 Nos. 32 A DP MCB as outgoing feeders.
230 V AC, 2 Wire, Compartmentalized steel enclosed AC Distribution Board (ACDB) . It shall consist of 1 nos. incoming 63 A DP MCCB incomers (with ON & OFF Indication Light) and 14 Nos. 32 A DP MCB as outgoing feeders.
LIGHTING
Supply, Installation, Testing and Commissioning of prewired wall/ceiling/false ceiling mounted type following LED lighting fixtures including providing & fixing LED lighting fixtures, electronic drivers,condensers,internal & external reflectors, louvers, etc. Including handling, transportation from owners store to erection site, unpacking, inspection; checking of internal wiring; Erection in position on false ceiling / floor etc ,cable glanding, crimping of lugs and connections at fixtures; supply of all erection materials Including necessary GI hardware, GI clamps, GI brackets, civil masonry materials; all work, labour and materials complete as per drawings, specifications, codes and standards and directions of Engineer in charge. 240VAC 1 phase 45W outdoor light with LED lamp (with short arm) in weatherproof & hose proof light Min IP65/55, fixture complete with driver ,cable glands and other accessories, suitable for 3 X 2.5mm2 (Cu) cable and stopping plug for outdoor area.
Supply, Installation, Testing and Commissioning of prewired wall/ceiling/false ceiling mounted type following LED lighting fixtures including providing & fixing LED lighting fixtures, electronic drivers,condensers,internal & external reflectors, louvers, etc. Including handling, transportation from owners store to erection site, unpacking, inspection; checking of internal wiring; Erection in position on false ceiling / floor etc ,cable glanding, crimping of lugs and connections at fixtures; supply of all erection materials Including necessary GI hardware, GI clamps, GI brackets, civil masonry materials; all work, labour and materials complete as per drawings, specifications, codes and standards and directions of Engineer in charge. 240VAC 1 phase 45 W Street Lighting Fixtures. with LED lamp in weatherproof & hose proof light Min IP55, fixture complete with driver ,cable glands and other accessories, suitable for 3 X 2.5mm2 (Cu) cable and stopping plug for outdoor area.
Supply, Installation, Testing and Commissioning of prewired wall/ceiling/false ceiling mounted type following LED lighting fixtures including providing & fixing LED lighting fixtures, electronic drivers,condensers,internal & external reflectors, louvers, etc. Including handling, transportation from owners store to erection site, unpacking, inspection; checking of internal wiring; Erection in position on false ceiling / floor etc ,cable glanding, crimping of lugs and connections at fixtures; supply of all erection materials Including necessary GI hardware, GI clamps, GI brackets, civil masonry materials; all work, labour and materials complete as per drawings, specifications, codes and standards and directions of Engineer in charge. 240V AC 1 phase 45W outdoor highbay light with LED lamp in weatherproof & hose proof wall / bracket mounted Min IP55, fixture complete with driver, cable glands and other accessories, suitable for 3X2.5 mm2 (Cu) cable and stopping plug for outdoor area.
Supply, Installation, Testing and Commissioning of prewired wall/ceiling/false ceiling mounted type following LED lighting fixtures including providing & fixing LED lighting fixtures, electronic drivers,condensers,internal & external reflectors, louvers, etc. Including handling, transportation from owners store to erection site, unpacking, inspection; checking of internal wiring; Erection in position on false ceiling / floor etc ,cable glanding, crimping of lugs and connections at fixtures; supply of all erection materials Including necessary GI hardware, GI clamps, GI brackets, civil masonry materials; all work, labour and materials complete as per drawings, specifications, codes and standards and directions of Engineer in charge. 240VAC 1 phase Outdoor Type Bollard Light 12W LED in weatherproof & hose proof light Min IP55, fixture complete with driver ,cable glands and other accessories, suitable for 3 X 2.5mm2 (Cu) cable and stopping plug.
Supply, Installation, Testing and Commissioning of prewired wall/ceiling/false ceiling mounted type following LED lighting fixtures including providing & fixing LED lighting fixtures, electronic drivers,condensers,internal & external reflectors, louvers, etc. Including handling, transportation from owners store to erection site, unpacking, inspection; checking of internal wiring; Erection in position on false ceiling / floor etc ,cable glanding, crimping of lugs and connections at fixtures; supply of all erection materials Including necessary GI hardware, GI clamps, GI brackets, civil masonry materials; all work, labour and materials complete as per drawings, specifications, codes and standards and directions of Engineer in charge. High quality LED tube complete with 2X20W tube (T5) eco friendly, having ≥ 2000 lumen output, CCT-6500K, IP-20, luminous efficacy ≥ 100 lm/watt, CRI>80, life ≥ 40000 burning hours, PF>0.95 and THD<10%, no UV radiation etc. suitable for ceiling/ wall mounted
Supply, Installation, Testing and Commissioning of prewired wall/ceiling/false ceiling mounted type following LED lighting fixtures including providing & fixing LED lighting fixtures, electronic drivers,condensers,internal & external reflectors, louvers, etc. Including handling, transportation from owners store to erection site, unpacking, inspection; checking of internal wiring; Erection in position on false ceiling / floor etc ,cable glanding, crimping of lugs and connections at fixtures; supply of all erection materials Including necessary GI hardware, GI clamps, GI brackets, civil masonry materials; all work, labour and materials complete as per drawings, specifications, codes and standards and directions of Engineer in charge. High quality LED tube complete with 1X20W tube (T5) eco friendly, having ≥ 2000 lumen output, CCT-6500K, IP-20, luminous efficacy ≥ 100 lm/watt, CRI>80, life ≥ 40000 burning hours, PF>0.95 and THD<10%, no UV radiation etc. suitable for ceiling/wall mounted
Supply, Installation, Testing and Commissioning of prewired wall/ceiling/false ceiling mounted type following LED lighting fixtures including providing & fixing LED batten lighting fixtures, electronic drivers,condensers,internal & external reflectors, louvers, etc. Including handling, transportation from owners store to erection site, unpacking, inspection; checking of internal wiring; Erection in position on false ceiling / floor etc ,cable glanding, crimping of lugs and connections at fixtures; supply of all erection materials Including necessary GI hardware, GI clamps, GI brackets, civil masonry materials; all work, labour and materials complete as per drawings, specifications, codes and standards and directions of Engineer in charge. High quality LED tube batten complete with 1X20W tube (T5) eco friendly, having ≥ 2000 lumen output, CCT-6500K, IP-55, luminous efficacy ≥ 100 lm/watt, CRI>80, life ≥ 40000 burning hours, PF>0.95 and THD<10%, no UV radiation etc. suitable for ceiling/wall mounted
EARTHING AND LIGHTNING PROTECTION
Supply ,Installation, Testing & Commissioning of 100 NB,3.8 M. Long G.I.pipe Earth Electrode in Earth pit including Earth Bus as per PDS attached with TS Including handling, transportation to Erection site, Excavation of Earth pit in all types of soil, back filling of pit with common salt, charcoal / coke and loose Earth after installation of Electrode there in, removal of surplus Earth away from Erection site, consolidation of loose Earth on back filled pit, making of bricks work, Inspection chamber on back filled pit and cover of RCC ,there of complete with lifting hook, fixing & connecting inside the chamber of G.I. Earth bracket and other accessories of the Earth Electrode, painting of Earth pit No. and Earthing symbol on the cover, supply of salt, charcoal /coke, bricks, sand, cement, stone chips, reinforcement rods, lifting hook, necessary stainless steel hardware, paints etc. all works, labour & materials complete as per Drawings, specifications, code & standards and direction of consultant/owner.
Supply Installation, Testing & Commissioning of GI earth strip / Wire conductors of following sizes as per PDS attached with TS enclosed in ready made concrete trenches or in floor slits, on brick / concrete wall under concrete floors, or paved areas, across pipe joints and valves, directly buried under ground at depth of 500 mm, including handling, transportation to erection site, bending, straightening, cutting to size, welding together of earth strips in overlapping manner, chipping in concrete floors/ paved areas for laying the earth strips under floors/ paved areas and making good by cement plastering concrete after laying of the strips ; clamping and supporting of earth strips laid above ground, connecting the strips/ wire at both ends to equipment or to earth bus / earth plates or to GI brackets fixed inside earth pit chamber, by bolting etc., Hessian tapes, all necessary GI hardware, GI clamps, civil masonry materials, etc. all work, labour as per specifications, codes and standards and directions of owner/consultant. of Hot Dip Galvanized GI earth strips & GI earth wire (with min. coating 610gm/sq.m) of size : 75 mm x 10 mm Note: The conductors shall be laid at a minimum depth of 500 mm from ground level. The excavation for the GI earth conductors/ strips shall not be separately measured and the rates quoted to include the same.
Supply Installation, Testing & Commissioning of GI earth strip / Wire conductors of following sizes as per PDS attached with TS enclosed in ready made concrete trenches or in floor slits, on brick / concrete wall under concrete floors, or paved areas, across pipe joints and valves, directly buried under ground at depth of 500 mm, including handling, transportation to erection site, bending, straightening, cutting to size, welding together of earth strips in overlapping manner, chipping in concrete floors/ paved areas for laying the earth strips under floors/ paved areas and making good by cement plastering concrete after laying of the strips ; clamping and supporting of earth strips laid above ground, connecting the strips/ wire at both ends to equipment or to earth bus / earth plates or to GI brackets fixed inside earth pit chamber, by bolting etc., Hessian tapes, all necessary GI hardware, GI clamps, civil masonry materials, etc. all work, labour as per specifications, codes and standards and directions of owner/consultant. of Hot Dip Galvanized GI earth strips & GI earth wire (with min. coating 610gm/sq.m) of size: - 50 mm x 6 mm Note: The conductors shall be laid at a minimum depth of 500 mm from ground level. The excavation for the GI earth conductors/ strips shall not be separately measured and the rates quoted to include the same.
Supply Installation, Testing & Commissioning of GI earth strip / Wire conductors of following sizes as per PDS attached with TS enclosed in ready made concrete trenches or in floor slits, on brick / concrete wall under concrete floors, or paved areas, across pipe joints and valves, directly buried under ground at depth of 500 mm, including handling, transportation to erection site, bending, straightening, cutting to size, welding together of earth strips in overlapping manner, chipping in concrete floors/ paved areas for laying the earth strips under floors/ paved areas and making good by cement plastering concrete after laying of the strips ; clamping and supporting of earth strips laid above ground, connecting the strips/ wire at both ends to equipment or to earth bus / earth plates or to GI brackets fixed inside earth pit chamber, by bolting etc., Hessian tapes, all necessary GI hardware, GI clamps, civil masonry materials, etc. all work, labour as per specifications, codes and standards and directions of owner/consultant. of Hot Dip Galvanized GI earth strips & GI earth wire (with min. coating 610gm/sq.m) of size: - 35 mm x 6 mm Note: The conductors shall be laid at a minimum depth of 500 mm from ground level. The excavation for the GI earth conductors/ strips shall not be separately measured and the rates quoted to include the same.
Supply Installation, Testing & Commissioning of GI earth strip / Wire conductors of following sizes as per PDS attached with TS enclosed in ready made concrete trenches or in floor slits, on brick / concrete wall under concrete floors, or paved areas, across pipe joints and valves, directly buried under ground at depth of 500 mm, including handling, transportation to erection site, bending, straightening, cutting to size, welding together of earth strips in overlapping manner, chipping in concrete floors/ paved areas for laying the earth strips under floors/ paved areas and making good by cement plastering concrete after laying of the strips ; clamping and supporting of earth strips laid above ground, connecting the strips/ wire at both ends to equipment or to earth bus / earth plates or to GI brackets fixed inside earth pit chamber, by bolting etc., Hessian tapes, all necessary GI hardware, GI clamps, civil masonry materials, etc. all work, labour as per specifications, codes and standards and directions of owner/consultant. of Hot Dip Galvanized GI earth strips & GI earth wire (with min. coating 610gm/sq.m) of size: - 1Cx16 sq.mm Al cable Unarmoured Note: The conductors shall be laid at a minimum depth of 500 mm from ground level. The excavation for the GI earth conductors/ strips shall not be separately measured and the rates quoted to include the same.
Supply Installation, Testing & Commissioning of GI earth strip / Wire conductors of following sizes as per PDS attached with TS enclosed in ready made concrete trenches or in floor slits, on brick / concrete wall under concrete floors, or paved areas, across pipe joints and valves, directly buried under ground at depth of 500 mm, including handling, transportation to erection site, bending, straightening, cutting to size, welding together of earth strips in overlapping manner, chipping in concrete floors/ paved areas for laying the earth strips under floors/ paved areas and making good by cement plastering concrete after laying of the strips ; clamping and supporting of earth strips laid above ground, connecting the strips/ wire at both ends to equipment or to earth bus / earth plates or to GI brackets fixed inside earth pit chamber, by bolting etc., Hessian tapes, all necessary GI hardware, GI clamps, civil masonry materials, etc. all work, labour as per specifications, codes and standards and directions of owner/consultant. of Hot Dip Galvanized GI earth strips & GI earth wire (with min. coating 610gm/sq.m) of size: - 1Cx185 sq.mm Al cable Unarmoured Note: The conductors shall be laid at a minimum depth of 500 mm from ground level. The excavation for the GI earth conductors/ strips shall not be separately measured and the rates quoted to include the same.
Supply Installation, Testing & Commissioning of GI earth strip / Wire conductors of following sizes as per PDS attached with TS enclosed in ready made concrete trenches or in floor slits, on brick / concrete wall under concrete floors, or paved areas, across pipe joints and valves, directly buried under ground at depth of 500 mm, including handling, transportation to erection site, bending, straightening, cutting to size, welding together of earth strips in overlapping manner, chipping in concrete floors/ paved areas for laying the earth strips under floors/ paved areas and making good by cement plastering concrete after laying of the strips ; clamping and supporting of earth strips laid above ground, connecting the strips/ wire at both ends to equipment or to earth bus / earth plates or to GI brackets fixed inside earth pit chamber, by bolting etc., Hessian tapes, all necessary GI hardware, GI clamps, civil masonry materials, etc. all work, labour as per specifications, codes and standards and directions of owner/consultant. of Hot Dip Galvanized GI earth strips & GI earth wire (with min. coating 610gm/sq.m) of size: - 8 SWG Wire Note: The conductors shall be laid at a minimum depth of 500 mm from ground level. The excavation for the GI earth conductors/ strips shall not be separately measured and the rates quoted to include the same.
Supply, Installation & Commissioning of GI Earth Bus bars (size: 390x50x12mm thick) as per PDS attached with TS Including handling, transportation, drilling of necessary holes/enlargement existing holes as required; all associated work for fixing the Bus bars in position e.g. cutting, leveling, aligning, chipping, grouting, welding bolting etc.; making good of broken/chipped portion on walls /columns by cement plastering. Supply of all necessary hardware (GI), paints, civil masonry materials etc. all work, labour complete as per drawings, specifications, codes and standards and directions of consultant /owner. Hot dip galvanized GI earth bus bar of size 390 x 50 x 12 thick (with min. coating 610gm/sq.m of zinc) with fixing materials as per
Supplying and laying of the stainless steel SS-304 air terminations, base plate & clamping of down Conductor complete with base plate, concrete coping fixing accessories and clamping with down Conductor
CABLES (LT)
Supply of 1.1 KV Grade, XLPE Insulated, PVC inner Sheath, Armoured, FRLS PVC outer sheathed cables as specified in Technical Specification Doc. No. PC183-TS-0805. : 3.5 x 300 mm2 (Al)
Supply of 1.1 KV Grade, XLPE Insulated, PVC inner Sheath, Armoured, FRLS PVC outer sheathed cables as specified in Technical Specification Doc. No. PC183-TS-0805. : 3.5 x 120 mm2 (Al)
Supply of 1.1 KV Grade, XLPE Insulated, PVC inner Sheath, Armoured, FRLS PVC outer sheathed cables as specified in Technical Specification Doc. No. PC183-TS-0805. : 3.5 x 150 mm2 (Al)
Supply of 1.1 KV Grade, XLPE Insulated, PVC inner Sheath, Armoured, FRLS PVC outer sheathed cables as specified in Technical Specification Doc. No. PC183-TS-0805. : 3.5 x 50 mm2 (Al)
Supply of 1.1 KV Grade, XLPE Insulated, PVC inner Sheath, Armoured, FRLS PVC outer sheathed cables as specified in Technical Specification Doc. No. PC183-TS-0805. : 3.5 x 25 mm2 (Al)
Supply of 1.1 KV Grade, XLPE Insulated, PVC inner Sheath, Armoured, FRLS PVC outer sheathed cables as specified in Technical Specification Doc. No. PC183-TS-0805. : 3 C x 6 mm2 (Cu)
Supply of 1.1 KV Grade, XLPE Insulated, PVC inner Sheath, Armoured, FRLS PVC outer sheathed cables as specified in Technical Specification Doc. No. PC183-TS-0805. : 3 C x 2.5 mm2 (Cu)
Supply of 1.1 KV Grade, XLPE Insulated, PVC inner Sheath, Armoured, FRLS PVC outer sheathed cables as specified in Technical Specification Doc. No. PC183-TS-0805. : 5 C x 2.5 mm2 (Cu)
Supply of 1.1 KV Grade, XLPE Insulated, PVC inner Sheath, Armoured, FRLS PVC outer sheathed cables as specified in Technical Specification Doc. No. PC183-TS-0805. : 7 C x 2.5 mm2 (Cu)
Supply of 1.1 KV Grade, XLPE Insulated, PVC inner Sheath, Armoured, FRLS PVC outer sheathed cables as specified in Technical Specification Doc. No. PC183-TS-0805. : 10 C x 2.5 mm2 (Cu)
Supply of 1.1 KV Grade, XLPE Insulated, PVC inner Sheath, Armoured, FRLS PVC outer sheathed cables as specified in Technical Specification Doc. No. PC183-TS-0805. : 12 C x 2.5 mm2 (Cu)
Supply of 1.1 KV Grade, XLPE Insulated, PVC inner Sheath, Armoured, FRLS PVC outer sheathed cables as specified in Technical Specification Doc. No. PC183-TS-0805. : 19 C x 2.5 mm2 (Cu)
Horizontal and vertical laying, testing (before and after laying) and commissioning of following LV Power & Control cables in readymade trenches, on pre-fabricated cable trays / racks, on already installed risers, support hangers, saddles / directly buried up to 1000mm depth etc.etc. pulling through pipes on walls / columns, steel structures including transportation of cable drums from storage yard to the site, unrolling the drum, laying the required length of cables including supply and fixing of necessary saddles, saddle bars, cable tags, Al clamps for cables laid vertical on walls / columns / structures, risers with all labour, consumable materials and necessary hardware to make installation complete in all respect as per approved standard drawings and direction of engineer-in-charge. 3.5 x 300 mm2 (Al)
Horizontal and vertical laying, testing (before and after laying) and commissioning of following LV Power & Control cables in readymade trenches, on pre-fabricated cable trays / racks, on already installed risers, support hangers, saddles / directly buried up to 1000mm depth etc.etc. pulling through pipes on walls / columns, steel structures including transportation of cable drums from storage yard to the site, unrolling the drum, laying the required length of cables including supply and fixing of necessary saddles, saddle bars, cable tags, Al clamps for cables laid vertical on walls / columns / structures, risers with all labour, consumable materials and necessary hardware to make installation complete in all respect as per approved standard drawings and direction of engineer-in-charge. 3.5 x 150 mm2 (Al)
Horizontal and vertical laying, testing (before and after laying) and commissioning of following LV Power & Control cables in readymade trenches, on pre-fabricated cable trays / racks, on already installed risers, support hangers, saddles / directly buried up to 1000mm depth etc.etc. pulling through pipes on walls / columns, steel structures including transportation of cable drums from storage yard to the site, unrolling the drum, laying the required length of cables including supply and fixing of necessary saddles, saddle bars, cable tags, Al clamps for cables laid vertical on walls / columns / structures, risers with all labour, consumable materials and necessary hardware to make installation complete in all respect as per approved standard drawings and direction of engineer-in-charge. 3.5 x 120 mm2 (Al)
Horizontal and vertical laying, testing (before and after laying) and commissioning of following LV Power & Control cables in readymade trenches, on pre-fabricated cable trays / racks, on already installed risers, support hangers, saddles / directly buried up to 1000mm depth etc.etc. pulling through pipes on walls / columns, steel structures including transportation of cable drums from storage yard to the site, unrolling the drum, laying the required length of cables including supply and fixing of necessary saddles, saddle bars, cable tags, Al clamps for cables laid vertical on walls / columns / structures, risers with all labour, consumable materials and necessary hardware to make installation complete in all respect as per approved standard drawings and direction of engineer-in-charge. 3.5 x 70 mm2 (Al)
Horizontal and vertical laying, testing (before and after laying) and commissioning of following LV Power & Control cables in readymade trenches, on pre-fabricated cable trays / racks, on already installed risers, support hangers, saddles / directly buried up to 1000mm depth etc.etc. pulling through pipes on walls / columns, steel structures including transportation of cable drums from storage yard to the site, unrolling the drum, laying the required length of cables including supply and fixing of necessary saddles, saddle bars, cable tags, Al clamps for cables laid vertical on walls / columns / structures, risers with all labour, consumable materials and necessary hardware to make installation complete in all respect as per approved standard drawings and direction of engineer-in-charge. 3.5 x 50 mm2 (Al)
Horizontal and vertical laying, testing (before and after laying) and commissioning of following LV Power & Control cables in readymade trenches, on pre-fabricated cable trays / racks, on already installed risers, support hangers, saddles / directly buried up to 1000mm depth etc.etc. pulling through pipes on walls / columns, steel structures including transportation of cable drums from storage yard to the site, unrolling the drum, laying the required length of cables including supply and fixing of necessary saddles, saddle bars, cable tags, Al clamps for cables laid vertical on walls / columns / structures, risers with all labour, consumable materials and necessary hardware to make installation complete in all respect as per approved standard drawings and direction of engineer-in-charge. 3.5 x 35 mm2 (Al)
Horizontal and vertical laying, testing (before and after laying) and commissioning of following LV Power & Control cables in readymade trenches, on pre-fabricated cable trays / racks, on already installed risers, support hangers, saddles / directly buried up to 1000mm depth etc.etc. pulling through pipes on walls / columns, steel structures including transportation of cable drums from storage yard to the site, unrolling the drum, laying the required length of cables including supply and fixing of necessary saddles, saddle bars, cable tags, Al clamps for cables laid vertical on walls / columns / structures, risers with all labour, consumable materials and necessary hardware to make installation complete in all respect as per approved standard drawings and direction of engineer-in-charge. 3.5 x 25 mm2 (Al)
Horizontal and vertical laying, testing (before and after laying) and commissioning of following LV Power & Control cables in readymade trenches, on pre-fabricated cable trays / racks, on already installed risers, support hangers, saddles / directly buried up to 1000mm depth etc.etc. pulling through pipes on walls / columns, steel structures including transportation of cable drums from storage yard to the site, unrolling the drum, laying the required length of cables including supply and fixing of necessary saddles, saddle bars, cable tags, Al clamps for cables laid vertical on walls / columns / structures, risers with all labour, consumable materials and necessary hardware to make installation complete in all respect as per approved standard drawings and direction of engineer-in-charge. 3 C x 6 mm2 (Cu)
Horizontal and vertical laying, testing (before and after laying) and commissioning of following LV Power & Control cables in readymade trenches, on pre-fabricated cable trays / racks, on already installed risers, support hangers, saddles / directly buried up to 1000mm depth etc.etc. pulling through pipes on walls / columns, steel structures including transportation of cable drums from storage yard to the site, unrolling the drum, laying the required length of cables including supply and fixing of necessary saddles, saddle bars, cable tags, Al clamps for cables laid vertical on walls / columns / structures, risers with all labour, consumable materials and necessary hardware to make installation complete in all respect as per approved standard drawings and direction of engineer-in-charge. 3 C x 2.5 mm2 (Cu)
Horizontal and vertical laying, testing (before and after laying) and commissioning of following LV Power & Control cables in readymade trenches, on pre-fabricated cable trays / racks, on already installed risers, support hangers, saddles / directly buried up to 1000mm depth etc.etc. pulling through pipes on walls / columns, steel structures including transportation of cable drums from storage yard to the site, unrolling the drum, laying the required length of cables including supply and fixing of necessary saddles, saddle bars, cable tags, Al clamps for cables laid vertical on walls / columns / structures, risers with all labour, consumable materials and necessary hardware to make installation complete in all respect as per approved standard drawings and direction of engineer-in-charge. 5 C x 2.5 mm2 (Cu)
Horizontal and vertical laying, testing (before and after laying) and commissioning of following LV Power & Control cables in readymade trenches, on pre-fabricated cable trays / racks, on already installed risers, support hangers, saddles / directly buried up to 1000mm depth etc.etc. pulling through pipes on walls / columns, steel structures including transportation of cable drums from storage yard to the site, unrolling the drum, laying the required length of cables including supply and fixing of necessary saddles, saddle bars, cable tags, Al clamps for cables laid vertical on walls / columns / structures, risers with all labour, consumable materials and necessary hardware to make installation complete in all respect as per approved standard drawings and direction of engineer-in-charge. 7 C x 2.5 mm2 (Cu)
Horizontal and vertical laying, testing (before and after laying) and commissioning of following LV Power & Control cables in readymade trenches, on pre-fabricated cable trays / racks, on already installed risers, support hangers, saddles / directly buried up to 1000mm depth etc.etc. pulling through pipes on walls / columns, steel structures including transportation of cable drums from storage yard to the site, unrolling the drum, laying the required length of cables including supply and fixing of necessary saddles, saddle bars, cable tags, Al clamps for cables laid vertical on walls / columns / structures, risers with all labour, consumable materials and necessary hardware to make installation complete in all respect as per approved standard drawings and direction of engineer-in-charge. 10 C x 2.5 mm2 (Cu)
Horizontal and vertical laying, testing (before and after laying) and commissioning of following LV Power & Control cables in readymade trenches, on pre-fabricated cable trays / racks, on already installed risers, support hangers, saddles / directly buried up to 1000mm depth etc.etc. pulling through pipes on walls / columns, steel structures including transportation of cable drums from storage yard to the site, unrolling the drum, laying the required length of cables including supply and fixing of necessary saddles, saddle bars, cable tags, Al clamps for cables laid vertical on walls / columns / structures, risers with all labour, consumable materials and necessary hardware to make installation complete in all respect as per approved standard drawings and direction of engineer-in-charge. 12 C x 2.5 mm2 (Cu)
Horizontal and vertical laying, testing (before and after laying) and commissioning of following LV Power & Control cables in readymade trenches, on pre-fabricated cable trays / racks, on already installed risers, support hangers, saddles / directly buried up to 1000mm depth etc.etc. pulling through pipes on walls / columns, steel structures including transportation of cable drums from storage yard to the site, unrolling the drum, laying the required length of cables including supply and fixing of necessary saddles, saddle bars, cable tags, Al clamps for cables laid vertical on walls / columns / structures, risers with all labour, consumable materials and necessary hardware to make installation complete in all respect as per approved standard drawings and direction of engineer-in-charge. 19 C x 2.5 mm2 (Cu)
Double Compression Cable Glands
1.1 KV Grade, XLPE Insulated, PVC inner Sheath, FRLS PVC outer sheathed cables. 3.5CX400 mm2 (Al)
1.1 KV Grade, XLPE Insulated, PVC inner Sheath, FRLS PVC outer sheathed cables. 3.5 x 300 mm2 (Al)
1.1 KV Grade, XLPE Insulated, PVC inner Sheath, FRLS PVC outer sheathed cables. 3.5 x 150 mm2 (Al)
1.1 KV Grade, XLPE Insulated, PVC inner Sheath, FRLS PVC outer sheathed cables. 3.5 x 120 mm2 (Al)
1.1 KV Grade, XLPE Insulated, PVC inner Sheath, FRLS PVC outer sheathed cables. 3.5 x 70 mm2 (Al)
1.1 KV Grade, XLPE Insulated, PVC inner Sheath, FRLS PVC outer sheathed cables. 3.5 x 50 mm2 (Al)
1.1 KV Grade, XLPE Insulated, PVC inner Sheath, FRLS PVC outer sheathed cables. 3.5 x 35 mm2 (Al)
1.1 KV Grade, XLPE Insulated, PVC inner Sheath, FRLS PVC outer sheathed cables. 3.5 x 25 mm2 (Al)
1.1 KV Grade, XLPE Insulated, PVC inner Sheath, FRLS PVC outer sheathed cables. 3 C x 6 mm2 (Cu)
1.1 KV Grade, XLPE Insulated, PVC inner Sheath, FRLS PVC outer sheathed cables. 3 C x 2.5 mm2 (Cu)
1.1 KV Grade, XLPE Insulated, PVC inner Sheath, FRLS PVC outer sheathed cables. 5 C x 2.5 mm2 (Cu)
1.1 KV Grade, XLPE Insulated, PVC inner Sheath, FRLS PVC outer sheathed cables. 10 C x 2.5 mm2 (Cu)
1.1 KV Grade, XLPE Insulated, PVC inner Sheath, FRLS PVC outer sheathed cables. 12 C x 2.5 mm2 (Cu)
1.1 KV Grade, XLPE Insulated, PVC inner Sheath, FRLS PVC outer sheathed cables. 19 C x 2.5 mm2 (Cu)
TERMINATION OF CABLES
End termination and subsequent testing of XLPE insulated single core/ multi core armoured cables of 1.1KV grade, Al/ Cu cable., excluding supply of termination kits, glands but including lugs , all labour and consumable materials to make installation complete in all respect. Modification in existing switch board for accommodating the proposed cables. The rate shall include drilling, taping of cable insulation, crimping of lugs to the conductor, connection of the lugs to equipment terminal, supply and fixing of supports & clamps for cables, G.I. nuts, screws, bolts, washers and other necessary hardware, PVC tape of required grade for taping, making cable entries dust and vermin proof, earthing etc. as per instruction of manufacturer, approved drawings, specifications and directions of engineer-in-charge. 1.1 KV grade, XLPE Insulated, PVC inner sheath, armoured, FRLS PVC outer, Stranded Cu/ Al Conductor cables as per IS:7098 (Part-1) of size 3.5 x 300 mm2 (Al)
End termination and subsequent testing of XLPE insulated single core/ multi core armoured cables of 1.1KV grade, Al/ Cu cable., excluding supply of termination kits, glands but including lugs , all labour and consumable materials to make installation complete in all respect. Modification in existing switch board for accommodating the proposed cables. The rate shall include drilling, taping of cable insulation, crimping of lugs to the conductor, connection of the lugs to equipment terminal, supply and fixing of supports & clamps for cables, G.I. nuts, screws, bolts, washers and other necessary hardware, PVC tape of required grade for taping, making cable entries dust and vermin proof, earthing etc. as per instruction of manufacturer, approved drawings, specifications and directions of engineer-in-charge. 1.1 KV grade, XLPE Insulated, PVC inner sheath, armoured, FRLS PVC outer, Stranded Cu/ Al Conductor cables as per IS:7098 (Part-1) of size. 3.5 x 150 mm2 (Al)
End termination and subsequent testing of XLPE insulated single core/ multi core armoured cables of 1.1KV grade, Al/ Cu cable., excluding supply of termination kits, glands but including lugs , all labour and consumable materials to make installation complete in all respect. Modification in existing switch board for accommodating the proposed cables. The rate shall include drilling, taping of cable insulation, crimping of lugs to the conductor, connection of the lugs to equipment terminal, supply and fixing of supports & clamps for cables, G.I. nuts, screws, bolts, washers and other necessary hardware, PVC tape of required grade for taping, making cable entries dust and vermin proof, earthing etc. as per instruction of manufacturer, approved drawings, specifications and directions of engineer-in-charge. 1.1 KV grade, XLPE Insulated, PVC inner sheath, armoured, FRLS PVC outer, Stranded Cu/ Al Conductor cables as per IS:7098 (Part-1) of size 3.5 x 120 mm2 (Al)
End termination and subsequent testing of XLPE insulated single core/ multi core armoured cables of 1.1KV grade, Al/ Cu cable., excluding supply of termination kits, glands but including lugs , all labour and consumable materials to make installation complete in all respect. Modification in existing switch board for accommodating the proposed cables. The rate shall include drilling, taping of cable insulation, crimping of lugs to the conductor, connection of the lugs to equipment terminal, supply and fixing of supports & clamps for cables, G.I. nuts, screws, bolts, washers and other necessary hardware, PVC tape of required grade for taping, making cable entries dust and vermin proof, earthing etc. as per instruction of manufacturer, approved drawings, specifications and directions of engineer-in-charge. 1.1 KV grade, XLPE Insulated, PVC inner sheath, armoured, FRLS PVC outer, Stranded Cu/ Al Conductor cables as per IS:7098 (Part-1) of size 3.5 x 70 mm2 (Al)
End termination and subsequent testing of XLPE insulated single core/ multi core armoured cables of 1.1KV grade, Al/ Cu cable., excluding supply of termination kits, glands but including lugs , all labour and consumable materials to make installation complete in all respect. Modification in existing switch board for accommodating the proposed cables. The rate shall include drilling, taping of cable insulation, crimping of lugs to the conductor, connection of the lugs to equipment terminal, supply and fixing of supports & clamps for cables, G.I. nuts, screws, bolts, washers and other necessary hardware, PVC tape of required grade for taping, making cable entries dust and vermin proof, earthing etc. as per instruction of manufacturer, approved drawings, specifications and directions of engineer-in-charge. 1.1 KV grade, XLPE Insulated, PVC inner sheath, armoured, FRLS PVC outer, Stranded Cu/ Al Conductor cables as per IS:7098 (Part-1) of size. 3.5 x 50 mm2 (Al)
End termination and subsequent testing of XLPE insulated single core/ multi core armoured cables of 1.1KV grade, Al/ Cu cable., excluding supply of termination kits, glands but including lugs , all labour and consumable materials to make installation complete in all respect. Modification in existing switch board for accommodating the proposed cables. The rate shall include drilling, taping of cable insulation, crimping of lugs to the conductor, connection of the lugs to equipment terminal, supply and fixing of supports & clamps for cables, G.I. nuts, screws, bolts, washers and other necessary hardware, PVC tape of required grade for taping, making cable entries dust and vermin proof, earthing etc. as per instruction of manufacturer, approved drawings, specifications and directions of engineer-in-charge. 1.1 KV grade, XLPE Insulated, PVC inner sheath, armoured, FRLS PVC outer, Stranded Cu/ Al Conductor cables as per IS:7098 (Part-1) of size 3.5 x 35 mm2 (Al)
End termination and subsequent testing of XLPE insulated single core/ multi core armoured cables of 1.1KV grade, Al/ Cu cable., excluding supply of termination kits, glands but including lugs , all labour and consumable materials to make installation complete in all respect. Modification in existing switch board for accommodating the proposed cables. The rate shall include drilling, taping of cable insulation, crimping of lugs to the conductor, connection of the lugs to equipment terminal, supply and fixing of supports & clamps for cables, G.I. nuts, screws, bolts, washers and other necessary hardware, PVC tape of required grade for taping, making cable entries dust and vermin proof, earthing etc. as per instruction of manufacturer, approved drawings, specifications and directions of engineer-in-charge. 1.1 KV grade, XLPE Insulated, PVC inner sheath, armoured, FRLS PVC outer, Stranded Cu/ Al Conductor cables as per IS:7098 (Part-1) of size 3.5 x 25 mm2 (Al)
End termination and subsequent testing of XLPE insulated single core/ multi core armoured cables of 1.1KV grade, Al/ Cu cable., excluding supply of termination kits, glands but including lugs , all labour and consumable materials to make installation complete in all respect. Modification in existing switch board for accommodating the proposed cables. The rate shall include drilling, taping of cable insulation, crimping of lugs to the conductor, connection of the lugs to equipment terminal, supply and fixing of supports & clamps for cables, G.I. nuts, screws, bolts, washers and other necessary hardware, PVC tape of required grade for taping, making cable entries dust and vermin proof, earthing etc. as per instruction of manufacturer, approved drawings, specifications and directions of engineer-in-charge. 1.1 KV grade, XLPE Insulated, PVC inner sheath, armoured, FRLS PVC outer, Stranded Cu/ Al Conductor cables as per IS:7098 (Part-1) of size. 3 C x 6 mm2 (Cu)
End termination and subsequent testing of XLPE insulated single core/ multi core armoured cables of 1.1KV grade, Al/ Cu cable., excluding supply of termination kits, glands but including lugs , all labour and consumable materials to make installation complete in all respect. Modification in existing switch board for accommodating the proposed cables. The rate shall include drilling, taping of cable insulation, crimping of lugs to the conductor, connection of the lugs to equipment terminal, supply and fixing of supports & clamps for cables, G.I. nuts, screws, bolts, washers and other necessary hardware, PVC tape of required grade for taping, making cable entries dust and vermin proof, earthing etc. as per instruction of manufacturer, approved drawings, specifications and directions of engineer-in-charge. 1.1 KV grade, XLPE Insulated, PVC inner sheath, armoured, FRLS PVC outer, Stranded Cu/ Al Conductor cables as per IS:7098 (Part-1) of size 3 C x 2.5 mm2 (Cu)
End termination and subsequent testing of XLPE insulated single core/ multi core armoured cables of 1.1KV grade, Al/ Cu cable., excluding supply of termination kits, glands but including lugs , all labour and consumable materials to make installation complete in all respect. Modification in existing switch board for accommodating the proposed cables. The rate shall include drilling, taping of cable insulation, crimping of lugs to the conductor, connection of the lugs to equipment terminal, supply and fixing of supports & clamps for cables, G.I. nuts, screws, bolts, washers and other necessary hardware, PVC tape of required grade for taping, making cable entries dust and vermin proof, earthing etc. as per instruction of manufacturer, approved drawings, specifications and directions of engineer-in-charge. 1.1 KV grade, XLPE Insulated, PVC inner sheath, armoured, FRLS PVC outer, Stranded Cu/ Al Conductor cables as per IS:7098 (Part-1) of size 5 C x 2.5 mm2 (Cu)
End termination and subsequent testing of XLPE insulated single core/ multi core armoured cables of 1.1KV grade, Al/ Cu cable., excluding supply of termination kits, glands but including lugs , all labour and consumable materials to make installation complete in all respect. Modification in existing switch board for accommodating the proposed cables. The rate shall include drilling, taping of cable insulation, crimping of lugs to the conductor, connection of the lugs to equipment terminal, supply and fixing of supports & clamps for cables, G.I. nuts, screws, bolts, washers and other necessary hardware, PVC tape of required grade for taping, making cable entries dust and vermin proof, earthing etc. as per instruction of manufacturer, approved drawings, specifications and directions of engineer-in-charge. 1.1 KV grade, XLPE Insulated, PVC inner sheath, armoured, FRLS PVC outer, Stranded Cu/ Al Conductor cables as per IS:7098 (Part-1) of size. 10 C x 2.5 mm2 (Cu)
End termination and subsequent testing of XLPE insulated single core/ multi core armoured cables of 1.1KV grade, Al/ Cu cable., excluding supply of termination kits, glands but including lugs , all labour and consumable materials to make installation complete in all respect. Modification in existing switch board for accommodating the proposed cables. The rate shall include drilling, taping of cable insulation, crimping of lugs to the conductor, connection of the lugs to equipment terminal, supply and fixing of supports & clamps for cables, G.I. nuts, screws, bolts, washers and other necessary hardware, PVC tape of required grade for taping, making cable entries dust and vermin proof, earthing etc. as per instruction of manufacturer, approved drawings, specifications and directions of engineer-in-charge. 1.1 KV grade, XLPE Insulated, PVC inner sheath, armoured, FRLS PVC outer, Stranded Cu/ Al Conductor cables as per IS:7098 (Part-1) of size. 12 C x 2.5 mm2 (Cu)
End termination and subsequent testing of XLPE insulated single core/ multi core armoured cables of 1.1KV grade, Al/ Cu cable., excluding supply of termination kits, glands but including lugs , all labour and consumable materials to make installation complete in all respect. Modification in existing switch board for accommodating the proposed cables. The rate shall include drilling, taping of cable insulation, crimping of lugs to the conductor, connection of the lugs to equipment terminal, supply and fixing of supports & clamps for cables, G.I. nuts, screws, bolts, washers and other necessary hardware, PVC tape of required grade for taping, making cable entries dust and vermin proof, earthing etc. as per instruction of manufacturer, approved drawings, specifications and directions of engineer-in-charge. 1.1 KV grade, XLPE Insulated, PVC inner sheath, armoured, FRLS PVC outer, Stranded Cu/ Al Conductor cables as per IS:7098 (Part-1) of size. 19 C x 2.5 mm2 (Cu)
CABLE ROUTE MARKER
Supply, Grouting and Installation of Cable Route Marker of Round shape made of MS of dia. 200mm with suitable engraving as of HT/ LT / Control / Data Cable jointed with angle of 30X30X5 mm grouted in concrete of size 150mm x 150mm x 500mm.
Hume Pipe
Supply laying of NP2 class 250 mm dia Hume pipe including collars, jointing with stiff mixture of cement mortar in proportion 1:2 including cutting of pipes wherever required
GI Pipe / HDPE Pipe
Supply, laying, installation of medium class GI pipe as per IS:1239 (part-1) of size 50 mm NB
Supply, laying, installation of medium class GI pipe as per IS:1239 (part-1) of size 100 mm NB
Supply, laying, installation of HDPE Pipe of size : 90/75mm, Wall thickness 3.0 +/- 0.2mm, 90mm OD, Homogenous
EXCAVATION AND BACK FILLING
Excavation and back filling of trenches for cables and earth strips etc. following types of soil except rocks for a maximum depth of 1.25 m for cables / 0.6 mtr. for earth strips including shoring, strutting, dewatering, consolidation and disposal of surplus earth upto100 m leads including all labour and materials to complete installation in all respect. Soft soil
Excavation and back filling of trenches for cables and earth strips etc. following types of soil except rocks for a maximum depth of 1.25 m for cables / 0.6 mtr. for earth strips including shoring, strutting, dewatering, consolidation and disposal of surplus earth upto100 m leads including all labour and materials to complete installation in all respect. Back filling with excavated earth in trench including consolidating each deposited layer by ramming, dressing etc.
FINE RIVER SAND
Supply & Spreading of approved fine river sand in cable trenches up to a depth of 250 mm (100 mm below the centre line of cable and 150 mm above cable the centre line of cable) including all labour and materials to make the installation complete in all respect as per approved drawings, specifications and directions of engineer-in-charge.
BRICKS
Supply & Spreading of approved first class bricks of dimension 230mmx115mmx75mm in cable trenches for cable protection including all labour and materials to make installation complete in all respect.
SAFETY EQUIPMENT
Supplying and installing the following including the supply of necessary clamps, raw plugs etc., breaking the walls if required and making good the walls after completion of work, including all materials and labour etc. and as per site instructions. CO2 type fire extinguishers (4.5 Lt capacity) with horn type (with handle) outlet. Make: Ceasefire
Vitreous enamel caution boards (HINDI/ ENGLISH/ODIYA) as per IS 2551 including fixing on the wall with all required hardware etc. complete. 11 V
Vitreous enamel caution boards (HINDI/ ENGLISH/ODIYA) as per IS 2551 including fixing on the wall with all required hardware etc. complete. 440 V
Supply of fire retardant / extinguishing Elect. Insulated Synthetic Mat suitable for all voltages not exceeding 11 KV System (with H.T. Trolley movement) Electrically insulated PVC synthetic sheet along with suitable Resin/ Chemical bound (Hardener)/ Adhesive /Pigment/ PVC Strip etc & having minimum current leakage as per IS with dielectric strength test at 22KV, breakdown strength of 45KV and without adverse effect of mineral oil, high insulation resistance (min. 600 Mega ohm per Km.) including material for water proofing of floor & sealing of all joints having Min. width of 1000 mm ± 20mm. Mats shall conform to BIS: DOC NO. ET-02 (5440) Dt.30/04/04, meet requirements of IS 15652:2006, 5216 (part-1, 2&3), IS 8437, IS 3043 & IEC 479 Pub-1 & tested for Tensile/ Elongation properties, Insulation Resistance, effects of Acid Alkaline Diesel & Transformer Oil, Leakage Current Test, Fire Test etc. 11KV Voltage grade having nominal thickness of 2.5mm ± 10%
Supply of fire retardant / extinguishing Elect. Insulated Synthetic Mat suitable for all voltages not exceeding 11 KV System (with H.T. Trolley movement) Electrically insulated PVC synthetic sheet along with suitable Resin/ Chemical bound (Hardener)/ Adhesive /Pigment/ PVC Strip etc & having minimum current leakage as per IS with dielectric strength test at 22KV, breakdown strength of 45KV and without adverse effect of mineral oil, high insulation resistance (min. 600 Mega ohm per Km.) including material for water proofing of floor & sealing of all joints having Min. width of 1000 mm ± 20mm. Mats shall conform to BIS: DOC NO. ET-02 (5440) Dt.30/04/04, meet requirements of IS 15652:2006, 5216 (part-1, 2&3), IS 8437, IS 3043 & IEC 479 Pub-1 & tested for Tensile/ Elongation properties, Insulation Resistance, effects of Acid Alkaline Diesel & Transformer Oil, Leakage Current Test, Fire Test etc. Up to 3.3KV Voltage grade having nominal thickness of 2.0mm ± 10%
4 Nos. round bottom sand buckets with handle on floor mounted stand. The buckets to be marked "FIRE" in ENGLISH/ HINDI including supply and fixing with necessary clamps, bolts and all other hardware as required.
First aid boxes with necessary medicine on suitable wall mounting stands.
Shock treatment chart conforming to Indian Electricity Rules in Aluminum frame with glass.
Do & Don’t chart as per Indian Electricity Rules in Aluminum frame with glass.
Exit Route / Emergency Exit Route Signage with inbuilt battery backup
STRUCTURAL STEEL
Supply, Fabrication and installation of MS frame supports and brackets base frame, hanger, risers, clamps, etc. for different electrical equipment as and where required. The job will include cutting, drilling, welding, reverting, bolting, grouting etc steel structural with a coat of epoxy primer and two coats of epoxy paint including supply of all consumable necessary hardware, paints etc.of various size of steel structure as required at site.
SPARE: Item wise unit prices of following spares for two years operation and maintenance:
11 V ICOG Breaker Panel :BREAKER 11 kV - Trip bar spring and any other spring used in the circuit breaker mechanism
11 V ICOG Breaker Panel :BREAKER 11 kV - Shunt trip coil
11 V ICOG Breaker Panel :BREAKER 11 kV - Closing coil
11 V ICOG Breaker Panel :BREAKER 11 kV - Secondary Isolating contact blocks
11 V ICOG Breaker Panel :BREAKER 11 kV - Micro Switch for Spring Charging
11 V ICOG Breaker Panel :BREAKER 11 kV - Micro Switch for Service/Test position
11 V ICOG Breaker Panel :BREAKER 11 kV - Rack in/Rack out handle
11 V ICOG Breaker Panel :BREAKER 11 kV - Spring Charging handle
11 V ICOG Breaker Panel :BREAKER 11 kV - Door panel key
11 V ICOG Breaker Panel : CONTROL SWITCHES- Trip-Neutral-Close Control Switch
11 V ICOG Breaker Panel : Push Buttons-Push Button Element of each type
11 V ICOG Breaker Panel : Push Buttons- Push Button Actuator of each type
Indication Lamps (1 no. of each type)
Thermostat
MINIATURE CIRCUIT BREAKER (OF EACH RATING)
METERS: Ammeter
METERS: Voltmeter
LV Switchboards :BREAKERS (3200 A) -Trip bar spring and any other spring used in the circuit breaker mechanism
LV Switchboards :BREAKERS (3200 A) - Cluster Contacts
LV Switchboards :BREAKERS (3200 A) - Arc Chute Assembly
LV Switchboards :BREAKERS (3200 A) - Shunt trip Coil
LV Switchboards :BREAKERS (3200 A) - Closing Coil
LV Switchboards :BREAKERS (3200 A) - Motors for MWS operated breakers
LV Switchboards :BREAKERS (3200 A) - Secondary Isolating Contact Blocks
LV Switchboards :BREAKERS (3200 A) -Shutter Assembly
LV Switchboards :BREAKERS (800 A)- Trip bar spring and any other spring used in the circuit breaker mechanism
LV Switchboards :BREAKERS (800 A)- Cluster Contacts
LV Switchboards :BREAKERS (800 A)- Arc Chute Assembly
LV Switchboards :BREAKERS (800 A)- Shunt trip Coil
LV Switchboards :BREAKERS (800 A)- Closing Coil
LV Switchboards :BREAKERS (800 A)- Motors for MWS operated breakers
LV Switchboards :BREAKERS (800 A)- Secondary Isolating Contact Blocks
LV Switchboards :BREAKERS (800 A)- Shutter Assembly
LV Switchboards :SWITCHES - Trip-Neutral-Close Control Switch
LV Switchboards :SWITCHES - Thermostat
LV Switchboards : INDICATION LAMPS- Indicating Lamp Globes of each colour
LV Switchboards : INDICATION LAMPS- Indication Lamp Fittings
LV Switchboards : INDICATION LAMPS- Indicating Lamp Bulbs
LV Switchboards : METERS - Ammeter (0-3200 A)
LV Switchboards : METERS - Ammeter (0-800 A)
LV Switchboards : METERS - Ammeter (0-250 to 600 A)
LV Switchboards : METERS - Voltmeter
LV Switchboards : CURRENT TRANSFORMERS - Current Transformer 3200/1 A
LV Switchboards : CURRENT TRANSFORMERS - Current Transformer 800/1 A
LV Switchboards : CURRENT TRANSFORMERS - Current Transformer 250-600/1 A
LV Switchboards :MCCB / RCCB/ MCB - 4 P MCCB 250 A
LV Switchboards :MCCB / RCCB/ MCB - 4 P MCCB 125 A
LV Switchboards :MCCB / RCCB/ MCB - 4 P MCCB 63 A
LV Switchboards :MCCB / RCCB/ MCB - DP RCBO 63 A
LV Switchboards :MCCB / RCCB/ MCB - DP MCB, 16 A
LV Switchboards :MCCB / RCCB/ MCB - DP MCB, 32 A
Transformer : Complete set of Gaskets
Transformer : Oil level gauge
Transformer : Complete charge of silica gel with breather
Transformer : Buchhloz relay
Transformer : Analog type OTI
Transformer : Analog type WTI
Transformer : CT for WTI
Transformer : Magnetic oil level gauge
UPS system
Power card of each type
Control card of each type
Indication Lamps of each type and color
TRANSFORMER - Supply, Handling, Installation, Testing and Commissioning of 11kV/0.433kV, 2000KVA, ONAN Distribution Transformer and its accessories excluding Supply, filtration and dehydration of oil/winding, power and control cable termination but including transportation of transformer and its accessories from owner’s stores, dressing of foundation, placing in position on MS base channel/flat, assembly of all accessories supplied loose, topping up with tested oil, all labour and material complete as per drawings/specification and direction of the transformer manufacturer.Transformer efficiency class shall be 2 as per IS 1180.
TRANSFORMER OIL - Supply, Filtration and Dehydration of oil/winding of transformer with streamline filter machine (to be arranged by the Contactor) for bringing the dielectric strength of the oil to the required level as per IS, complete with all labour and material including transportation oil drums from stores.
11 kV PANEL : Supply, Handling, Installation, Testing and Commissioning of Incoming cum Outgoing 11kV 3Ph 50Hz 31.5kA 1250 A VCB Panel complete with metering and protection system free standing floor mounting cubical type as per SLD & Specification Sheet and Technical specification - Electrical System (Doc No. PC183-TS-0805) and SLD No. PC183-7411-0985E including transportation from owner’s stores, dressing of foundation, placing in position on MS base channel/flat, assembly of all accessories supplied loose, all labour and material complete as per drawings/specification and direction of the manufacturer.
PUSH BUTTON : Supply, installation, testing and commissioning of weather proof emergency stop push button (Mushroom type) for transformer with lockable facility in OFF position suitable for outdoor installation with Die cast Aluminium alloy enclosure having rain protection hood fabricated out of 14 SWG Aluminium sheet including shifting of control stations from store to the site of erection, fixing control stations with nuts & bolts, on already erected supports/nearby structure/walls etc. connecting control cable and testing to make the installation complete in all respect as per approved drawings, specifications and direction of engineer-in-charge. Supply of all required hardware for mounting shall be in Contractor’s scope.
CABLES (HT)
Supply of 11 KV (UE) Grade, XLPE Insulated, PVC inner sheathed, Armoured, FRLS PVC outer sheathed cables as specified in Technical Specification. 3C x 400 sq. mm (Al)
Laying (horizontal & vertical), testing and commissioning of 11 KV Grade, XLPE Insulated, PVC inner sheathed, armoured, FRLS PVC outer sheathed cables including its termination in new & readymade trenches, on pre-fabricated/ site-fabricated cable trays/ racks, on already installed risers, support, hangers, saddles / directly buried up to 1000mm depth etc. pulling through pipes on walls/columns, steel structures including transportation of cable drums from storage yard to site, unrolling the drum, including supply & fixing of cable tags, Al clamps with all labour, consumable materials and necessary hardware to make installation complete in all respect as per direction of engineer-in-charge. 3 x400 mm2 (Al)
End termination and subsequent testing of 11KV(UE) Grade, XLPE Insulated, PVC inner sheathed, Armoured, FRLS PVC outer sheathed cables using suitable Heat Shrink Raychem / 3M Termination Kit, including supply of termination kit, glands & lugs & glanding , all labour and consumable materials to make installation complete in all respect. The rate shall include drilling, taping of cable insulation, crimping of lugs to the conductor, connection of the lugs to equipment terminal, supply and fixing of G.I. nuts, screws, bolts, washers and other necessary hardware, PVC tape of required grade for taping, making cable entries dust and vermin proof, earthing etc. as per instruction of manufacturer, approved drawings, specifications and directions of engineer-in-charge. 3C x 400 sq. mm (Al)
Supply & fixing of Heat Shrinkable Raychem make straight through jointing kit suitable for 11 KV grade (UE) XLPE-A-FRLSPVC insulated armoured cables of following sizes including cutting, stripping of cable insulation complete with supply of compression / crimping type ferrules, plastic mould and epoxy resin compound etc., including all labour and materials, as per approved drawings, specifications and directions of Engineer-in-Charge. 3C x 400sq. mm (Al, 11 KV)
PLANT LIGHTING POLES
Supply & fixing of hot dip galvanized MS tubular swaged lighting poles of following types suitable for wind velocity of 150 Km/Hr and along with suitable pole junction box. 5M high ground mounted poles Job shall also inlclude the make of civil foundation for lighting poles.
CABLE TRAYS (PREFABRICATED LADDER TYPE GI CABLE TRAYS) & ACCESSORIES (Supply, installation & fixing of prefabricated ladder GI cable trays and their accessories i.e. supply of all hardware required i.e. J-hooks, GI Nut, Bolt, Washers,coupling plate etc. of width 150 mm, 300 mm, 450 mm & 600 mm as per site requirement for laying of cables with standard rung spacings. Load for support span of 2.5 meter as 30, 60, 75 & 90 (in Kg/Mtr) respectively with concentric static load as 70 Kg at the centre, with materials, labour, tools and tackles, consumables etc. as per drawings, specification and directions of Site Engineer / Engineer-in-Charge.The rates shall be valid for all mounting heights)
Straight Run Cable Trays -600mm wide
Straight Run Cable Trays -300 mm wide
Horizontal Bends- 600mm wide
Horizontal Bends- 300 mm wide
Vertical Inside Bends - 600 mm wide
Vertical Inside Bends - 300 mm wide
LT CABLE STRAIGHT THROUGH JOINT (1.1 KV): Supply and Making of heat shrinkable type straight-through joint for 1.1 KV (E) Voltage Grade Aluminium XLPE insulated, armoured cable, including cutting, stripping of cable insulation complete with supply of compression / crimping type ferrules, plastic mould and epoxy resin compound etc., including all labour and materials, as per approved drawings, specifications and directions of Engineer-in-Charge.
3.5 x 150 mm2 (Al)
3.5 x 120 mm2 (Al)
3.5 x 70 mm2 (Al)
10C x 2.5 sq. mm (Cu)
12C x 2.5 sq. mm (Cu)
HIGH MAST
Erection and commissioning of the high mast with the help of suitable equipment alongwith all its accessories such as head frame, SS wire rope, double drum winch etc. This includes supply of foundation bolts manufactured from special steel along with nuts, washers, anchor plates and templates.
Installation, testing and commissioning of specially designed non-integral flood light luminaries 9 nos. 2X400W, 3 Nos. 1X400W SON T lamps and its control gear boxes. Installation, testing & commissioning of aviation obstruction lights with neon spiral light source (1 no. fitting per mast is necessary).
Installation, testing and commissioning of high powered three phase flameproof power tool for electrical operation of raising and lowering of lantern carriage with its FLP starter, FLP plug, FLP DOUBLE COMPRESSION ROLLED Aluminum cable glands & lugs suitable for 3.5Cx50 Sq. mm (Al) XLPE cable, supporting trolley, torque limiter and fixing chain.
ETHERNET SWITCH and associated Cables
Supply, installation, layig, terminataion,Testing and Commissioning of Following Items to be installed at different Substations
Cyber scured, KEMA certified, IEC 61850Managed Ethernet Switch having 24 Ethernet Ports and 4 Ports for Fiber optic with LIU and Patchcord having 1 GBPS speed(Make Harshman/Etherwan/Rockewell/eq). Job shall also include installation of these ethernet switch in different Substation Panel and I/O Rack cabinets and its connection to I/O Rack via fiber/Cat 6 cable connectionn with required termination in LIU/Patchcord.Necessary Hardware for Installation and coneection shall be considered by the bidder.
Multipair 23 AWG Individually and Overall screened armoured , Fire Resisitance CAT6 Cable
6 Fiber , Loose Tube, Armoured , Fire Resisitance Single mode Fiber Optic Cable
2 Pair 1.5 sqmm Amoured , Fire Resisitance RS485 Modbus Cable
UPS system
Supply, Storage, Installation, Testing and comissioing of Combined Full wave fully contrlolled IGBT 10 KVA AC-DC UPS having dual output of Both AC 230V and DC 110V with ACDB and DCDB. 20 % Spare feeder shall be considered in ACDB and DCDB This shall also comprise of required SMF/VRLA battery bank and other accessories with battery backup of 1 Hourr.This UPS shall be installed at Vikrampur Guest House substation.For detail, Please refer Techncal Specification & SLD.
Supply, Storage, Installation, Testing and comissioing of Combined Full wave fully contrlolled IGBT 10 KVA AC-DC UPS having dual output of Both AC 230V and DC 110V with ACDB and DCDB. 20 % Spare feeder shall be considered in ACDB and DCDB This shall also comprise of required SMF/VRLA battery bank and other accessories with battery backup of 1 Hour.This UPS shall be installe at Trainee hoster MCC room.For detail, Please refer Techncal Specification & SLD.
Supply, Storage, Installation, Testing and comissioing of heavy duty 1.5 Ton 5 Star dual inveter Split AC with stablizer . AC shall be installed at VGH and trainee hoster for cooling of UPS.Necessary cabling MCB box etc. shall be considered (Make: Hitachi, Daikin, O General, Carrier, Voltas)
415 V MV BUS DUCT
Supply, Installation, Testing & Commissioning of 415 V Bus Duct as perspecified in data sheets, Technical Specification - Electrical, Technical Specification Doc. No. PC183-TS-0807, etc. attached with the NIT. 3200 A, 415 V, 50 Hz, 50kA for 1 second, Non-Segregated High Conductivity Aluminium TP+N (100%) Bus Duct of 12.5 Mtr. length (From Transformer Flange Centre Line to Panel Flange Centre Line) including 2 nos. horizontal bends and 3 nos. vertical bends between 11 kV / 0.433 kV, 2 MVA Transformers and PCC(Main MPDB) with associated equipments and all other accessories as per enclosed Main Substation Equipment Layout requirement, Technical Specification - Electrical, Technical Specification Doc. No. PC183-TS-0807, etc. attached with the NIT. Length is minium and shall be as per actual requirement at site
PA system Exchange
Supply Installation, Testing & Commissioning of Digital PA system Central Exchange having required nos. of racks and cards suitable for 45 Nos of Field Call ststaion (FCS), Redundant ampliphier card( Min 250 W), Redundant Power supply(N+N) , Rectifier (N+1),Cyber secured KEMA certified ethernet switch (Min 24 Port+4 nos FO Port), 1 No IP based 16 Keys Master call station(MCS) with redundant supply . Complete system shall be considered with required hardware and software. Exchange shall be floor mounted. Min 6 nOs. PF contacts shall be considered. Input supply shall be 230 V UPS.PA system shall be suitable for hookup and integration with existing system.
FORTUNE ENTERPRISES
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid