Loading…
Loading…
| # | Company | Amount | Status |
|---|---|---|---|
| 1 | ₹7.9 LAdmitted-Finance | ₹7.9 L | Admitted-Finance |
| 2 | ₹8.7 LAdmitted-Finance | ₹8.7 L | Admitted-Finance |
| 3 | ₹15.0 LAdmitted-Finance | ₹15.0 L | Admitted-Finance |
| 4 | ₹15.1 LAdmitted-Finance | ₹15.1 L | Admitted-Finance |
| 5 | ₹15.2 LAdmitted-Finance LANE NO 05 HNO 56 SHIV VIHAR TALAB TILLO JAMMU | ₹15.2 L | Admitted-Finance |
| Sl No | Description | Qty | Unit | J&Sons Construction Pvt Ltd | M/S DAYAL BUILD TECH | RATHER ELECTRICALS AND CONTRACTOR | M/S RAJ ELECTRICAL CONTRACTOR | M/S A A ENTERPRISES | M/S GURUJI ELECTRICAL ENTERPRISES | M/s GCS Associates | JASMEET SINGH | M/S LARVI ENTERPRISE | M/S KUNDAL ELECTRICAL WORKS AND SUPPLIERS | MAHAVEER ENTERPRISES | Noor Hussain and Sons | AQUIB TRADERS | M/S PIONEER ENGINEERS | M/S SALARIA ENTERPRISES | M/S SIGMA CONSTRUCTION |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00220/132/33 KV Grid Stations | |||||||||||||||||||
| 1.01Auto-Transformers/Power Transformers :- A) Checking of Auto starting of fans, External cleaning of radiators,oil pumps, ONAF/OFAF cooling,Cleaning and checking of marshalling boxes of transformer and OLTC, (ii) Tightening of terminations, Checking of OLTC driving mechanism, Electrical checking/ testing of pressure relief device, Buchholz relay, OLTC surge relay/ checking of alarm/ trip and checking/ replacement of the gaskets of the terminal box, Checking / Tightning of earthing connections, Checking of earth resistance of Neutral, Replacement of Silca Gel of breathers and oil toping of transformers and tightning of bushing clamps on HV/IV/LV sides of Auto transformers and 50MVA Power transformers.Checking of space heater and illumination,etc.Required as per schedule of maintenance. | |||||||||||||||||||
| 1.02 | 160 MVA , 220/132 KV | 1 | No. | 21,000 ₹21,000 | 1,65,000 ₹1.6 L | 55,000 ₹55,000 | 27,000 ₹27,000 | 1,50,000 ₹1.5 L | 30,200 ₹30,200 | 30,500 ₹30,500 | 40,000 ₹40,000 | 30,000 ₹30,000 | 30,000 ₹30,000 | 30,000 ₹30,000 | 29,500 ₹29,500 | 30,000 ₹30,000 | 30,000 ₹30,000 | 30,100 ₹30,100 | 1,66,000 ₹1.7 L |
| 1.03 | 50 MVA , 132/33 KV | 1 | No. | 17,000 ₹17,000 | 1,65,000 ₹1.6 L | 52,000 ₹52,000 | 12,700 ₹12,700 | 1,50,000 ₹1.5 L | 15,200 ₹15,200 | 14,500 ₹14,500 | 30,000 ₹30,000 | 28,000 ₹28,000 | 15,000 ₹15,000 | 22,000 ₹22,000 | 15,700 ₹15,700 | 28,000 ₹28,000 | 25,000 ₹25,000 | 15,100 ₹15,100 | 1,66,000 ₹1.7 L |
| 1.04 | 20 MVA , 132/33 KV | 1 | No. | 13,500 ₹13,500 | 1,65,000 ₹1.6 L | 50,000 ₹50,000 | 4,000 ₹4,000 | 1,50,000 ₹1.5 L | 10,000 ₹10,000 | 11,600 ₹11,600 | 30,000 ₹30,000 | 25,000 ₹25,000 | 10,000 ₹10,000 | 18,000 ₹18,000 | 6,000 ₹6,000 | 25,000 ₹25,000 | 20,000 ₹20,000 | 10,000 ₹10,000 | 1,66,000 ₹1.7 L |
| 2.00Routine Maintenance of Auxilliary Transformers including checking of gaskets,checking and tightening of earthing connections,tightening of bushing clamps,replacement of Silica Gel,etc | |||||||||||||||||||
| 2.02 | 250KVA, 33/0.440 KV Auxilliary Transformer | 1 | No. | 4,450 ₹4,450 | 1,50,000 ₹1.5 L | 19,000 ₹19,000 | 2,750 ₹2,750 | 1,50,000 ₹1.5 L | 4,200 ₹4,200 | 3,550 ₹3,550 | 10,000 ₹10,000 | 5,000 ₹5,000 | 4,000 ₹4,000 | 5,500 ₹5,500 | 3,200 ₹3,200 | 5,000 ₹5,000 | 35 ₹35 | 4,100 ₹4,100 | 1,50,000 ₹1.5 L |
| 2.04 | Draning/ De-sludging of oil of transformers | 1 | per Kilo Ltr | 2,250 ₹2,250 | 1,50,000 ₹1.5 L | 500 ₹500 | 850 ₹850 | 1,50,000 ₹1.5 L | 8,000 ₹8,000 | 1,500 ₹1,500 | 5,000 ₹5,000 | 10 ₹10 | 8,000 ₹8,000 | 10,000 ₹10,000 | 1,100 ₹1,100 | 10 ₹10 | 35 ₹35 | 8,100 ₹8,100 | 1,50,000 ₹1.5 L |
| 2.05 | Filling of oil, filtration and dehydration of transformer including carriage of filteration plant to be provided by the Department. | 1 | per Kilo Ltr | 2,350 ₹2,350 | 1,50,000 ₹1.5 L | 500 ₹500 | 1,000 ₹1,000 | 1,50,000 ₹1.5 L | 9,000 ₹9,000 | 2,800 ₹2,800 | 3,000 ₹3,000 | 10 ₹10 | 9,000 ₹9,000 | 15,000 ₹15,000 | 1,200 ₹1,200 | 10 ₹10 | 35 ₹35 | 9,100 ₹9,100 | 1,50,000 ₹1.5 L |
| 2.06 | Reparing of cooling fans of transformers including replacement of damaged winding, bearing etc. | 1 | No. | 3,400 ₹3,400 | 1,50,000 ₹1.5 L | 16,000 ₹16,000 | 2,376 ₹2,376 | 1,50,000 ₹1.5 L | 4,100 ₹4,100 | 4,000 ₹4,000 | 5,000 ₹5,000 | 15,000 ₹15,000 | 4,000 ₹4,000 | 6,000 ₹6,000 | 2,576 ₹2,576 | 15,000 ₹15,000 | 5,000 ₹5,000 | 4,100 ₹4,100 | 1,50,000 ₹1.5 L |
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
30 Apr 2026, 4:00 pmClosed
Executive Engineer, Trans. Line Maintt. Div.-VIII
Executive Engineer, Trans. Line Maintt. Div.-VIII, JKPTCL, Ambedkar Chowk Jammu.
Rate Contract for Preventive/ Routine/ Breakdown maintenance for various 220/132/33 KV Grids and 220 and 132 KV Transmission Lines falling under the jurisdiction of TLMD-VIII, Jammu
2026_PDD_307467_1
TLMD-VIII/J/T/01 of 2026-27 dated 06.04.2026
Open Tender
Electrical and Maintenance Works
1 days
Poonch, Rajouri
Please refer Tender documents.
3 documents required · 3 mandatory
₹2,000
Executive Engineer TLMD-VIII,JKPTCL, JAMMU
₹50,000
Executive Engineer, Trans. Line Maintt. Div.-VIII
21 May 2026
9 Apr 2026
2 May 2026
9 Apr 2026
30 Apr 2026
9 Apr 2026
16 Apr 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
220/132/33 KV Grid Stations | - | - | - | - | - | |
| 1.01 | Auto-Transformers/Power Transformers :-
A) Checking of Auto starting of fans, External cleaning of radiators,oil pumps, ONAF/OFAF cooling,Cleaning and checking of marshalling boxes of transformer and OLTC, (ii) Tightening of terminations, Checking of OLTC driving mechanism, Electrical checking/ testing of pressure relief device, Buchholz relay, OLTC surge relay/ checking of alarm/ trip and checking/ replacement of the gaskets of the terminal box, Checking / Tightning of earthing connections, Checking of earth resistance of Neutral, Replacement of Silca Gel of breathers and oil toping of transformers and tightning of bushing clamps on HV/IV/LV sides of Auto transformers and 50MVA Power transformers.Checking of space heater and illumination,etc.Required as per schedule of maintenance. | - | - | - | - | - |
| 1.02 | 160 MVA , 220/132 KV | - | No. | - | - | item1 |
| 1.03 | 50 MVA , 132/33 KV | - | No. | - | - | item2 |
20 MVA , 132/33 KV | - | No. | - | - | item3 | |
Routine Maintenance of Auxilliary Transformers including checking of gaskets,checking and tightening of earthing connections,tightening of bushing clamps,replacement of Silica Gel,etc | - | - | - | - | - | |
250KVA, 33/0.440 KV Auxilliary Transformer | - | No. | - | - | item4 | |
Draning/ De-sludging of oil of transformers | - | per Kilo Ltr | - | - | item5 | |
Filling of oil, filtration and dehydration of transformer including carriage of filteration plant to be provided by the Department. | - | per Kilo Ltr | - | - | item6 | |
Reparing of cooling fans of transformers including replacement of damaged winding, bearing etc. | - | No. | - | - | item7 |
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.64 MB
BOQ_997471.xls
BOQ • 0.41 MB
SBDNIT01.pdf
Tender Documents • 0.77 MB
Download all tender documents and submit your bid