Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹7.2 CrAccepted-AOC | ₹7.2 Cr | L-1 | Accepted-AOC Being eligible L1 bidder, work is awarded with the approval of Tender Committee Recommendation for award by the competent authority. |
| 2 | L-2₹7.9 Cr+₹71.7 L (10.00%)Rejected-Finance | ₹7.9 Cr+₹71.7 L (10.00%) | L-2 | Rejected-Finance NOT BEING L-1 BIDDER |
| 3 | L-3₹8.2 Cr+₹1.0 Cr (14.4%)Rejected-Finance | ₹8.2 Cr+₹1.0 Cr (14.4%) | L-3 | Rejected-Finance NOT BEING L-1 BIDDER |
| 4 | L-4₹9.1 Cr+₹1.9 Cr (27.0%)Rejected-Finance 15 402 ASHOKA RATAN SHANKAR NAGAR DISTT RAIPUR CG | RAIGARH | CHHATTISGARH | 492007 | ₹9.1 Cr+₹1.9 Cr (27.0%) | L-4 | Rejected-Finance NOT BEING L-1 BIDDER |
| 5 | L-5₹9.7 Cr+₹2.6 Cr (35.6%)Rejected-Finance C O VOLTAS LIMITED SPARE PARTS DEPOT OLD HUTMENT COLONY NCL NIGAHI SINGRAULI M P 486884 | SINGRAULI | SINGRAULI | MADHYA PRADESH | 486884 | ₹9.7 Cr+₹2.6 Cr (35.6%) | L-5 | Rejected-Finance NOT BEING L-1 BIDDER |
Tender Value
₹9.5 Cr
EMD Value
₹11.9 L
Closing Date
23 May 2024, 5:00 pmClosed
GM(Civil)/HoD, WCL
Office of GM(Civil), 10th Floor, Civil Department, WCL HQ, Nagpur-440001
Planning, Design, Engineering, Construction, Fabrication, Supply, Erection, Trial Run and Commissioning of 2 x 5.00 MVA, 33/6.6 kV Substation including Maintenance on Turnkey Basis at Amalgamated Inder Kamptee Deep OC Project, Nagpur Area, WCL
2024_WCL_306229_1
wcl-hq-gmciv-e01-2024-25
Turnkey
Civil Works - Others
Item Rate
2190 days
WCL Nagpur Area
Please refer tender documents
7 documents required · 7 mandatory
₹11.9 L
Through Video Conferencing as per NIT
5 Nov 2024
3 Apr 2024
24 May 2024
4 Apr 2024
23 May 2024
20 Apr 2024
4 Apr 2024 - 30 Apr 2024
13 Apr 2024
Amount
Survey, Soil Testing and Design Engineering & Cost
Detailed survey & soil investigation of the area within battery limit and submission of report
Design & engineering on Plant and Machineries (Electrical) to be supplied by the Bidder inclusive of Overhead construction cost, Contingencies but excluding GST
Design engineering cost for Civil & Strucrural works
Civil And Strucrural Works excluding GST
Main Sub-station Building (Additional as per the NIT and System Requirement)
Outdoor Steel Structures (As per the NIT and System Requirement)
Foundation of outdoor structures including Transformer foundations(As per the NIT and System Requirement)
Cable Trenches(As per the NIT and System Requirement)
Boundary Wall along with Concertina Coils and gates (As detailed in the NIT)
Surface Dressing (As per the NIT and Site Requirement)
Stone Laying (As per the NIT and Site Requirement)
Anti Weed Treatment (As per the NIT and Site Requirement)
Oil Overflow Chamber with Oil drain pipes (As per the NIT and System Requirement)
Borewell with Casing and gravel packing (As per the NIT and System Requirement)
Security Room (As per the NIT and System Requirement)
RCC Sump, Pump House and Connection arrangements ( As per the NIT and System Requirement)
Shed for Diesel Generator (DG) Set (As per the NIT and System Requirement)
Drain along Boundary Wall (As per the NIT and Site Requirement)
Parking Shed (As per NIT and System Requirement)
Bituminous Road (As per NIT and Site Requirement)
Burnt Oil Chamber (As per NIT and System Requirement)
Pathway (3 Meter Wide) (As per NIT and System Requirement)
Chain Link Fencing (As per NIT and System Requirement)
SUPPLY OF PLANT & MACHINERY, ERECTION, INSTALLATION & COMMISSIONING INCLUDING DLP PERIOD MAINTENANCE FOR A PERIOD OF 60 CALENDAR MONTHS
Isolator, 33kV, 3 poles, 1250 Amps, 25 kA, arrangement for interlocking with vacuum circuit breakers (As per NIT)
Isolator, 33kV, 3 poles, 1250 Amps, 25 kA, arrangement for interlocking with vacuum circuit breakers with earthing switch(As per NIT)
Isolator, 33kV, 3 poles, 1250 Amps, 25 kA, arrangement with earthing switch and DO fuse(As per NIT)
Lightning arrester, station class, 30 kV, 10 kA, suitable for 33 kV supply, effectively earthed (each set consists of 3 Nos.) with counters/surge monitors(As per NIT)
Current transformer (CT), single phase, out door type, 33 kV, 3 cores, CTR as required (each set consists of 3 nos.)(As per NIT)
Potential transformer (PT), outdoor type, 33/√3kV / 110/√3V, 2 cores, 100 VA each for 33 kV, 3 phase system, (each set consists of 3 nos.)(As per NIT)
Earth Fault protection system for NGR consisting of CT , instantaneous earth fault relay etc. incl. NGR complete.(As per NIT)
Vacuum Circuit Breaker, 33kV,1250 A, outdoor type, 750 MVA symmetrical breaking capacity with remote control panel having digital IDMT relay for O/L and E/F protection, ammeter, energymeter, battery charging system, etc.(As per NIT)
Transformer outdoor type conforming to IS:2026 (current) having ON-LOAD tap changer on HV side with all accessories as per IS:3639 (Current) with the rating as given below:-(As per NIT) Rated kVA: 5000 Rated Voltage(primary): 33000V Rated Voltage(secondary): 6600V Connection and vector group: Dy11
6.6 kV, Switch-board, indoor type, 11 panel, with vacuum circuit breakers, 250 MVA symmetrical breaking capacity. (As per NIT)
6.6 kV, Air Break Isolator, gang operated, off load, Outdoor type, 630 Amp along with Earthing switch and lightning arrestor (LA), Station class, for 6.6 kV System(As per NIT)
Station Transformer, Plinth mounted, outdoor type rated as follows:(As per NIT) Rated kVA: 160 Rated Voltage(primary): 33000V Rated Voltage(secondary): 415V
Lighting Transformer, Plinth mounted, outdoor type rated as follows(As per NIT): Rated kVA: 100 Rated Voltage(primary): 33000V Rated Voltage(secondary): 230 V (L-L)
6.6 kV, 650 kVAR Capacitor Bank complete with Automatic Power Factor controller (APFC) panel with automatic on and off switching facility(As per NIT)
415 V, 3Ph - neutral , Power distribution board, Indoor type(As per NIT)
Main Lighting Distribution Board, 230V, Indoor type(As per NIT)
Battery and battery charging (with one stand bye battery charging unit) equipment and control panels etc.(As per NIT)
Insulators,Tubular busbar for 33 kV, Steel hardware, Post Insulator clamps, terminal connectors etc for 33 kV, etc and 33 kV Power receiving arrangement from Double/Four pole structure with the help of ACSR conductor and other necessary structural & hard wares, etc. (As per NIT)
Gang operated AB switch with DO Fuse, Earth Switch and lightning arresters, etc for 6.6 kV out going feeders for double pole structures(As per NIT)
Earthing system including earth pits, required galvanised strips/flats for inter connection etc. complete(As per NIT)
Lightning protection system consisting of spikes, earth pits, galvanised strips /flats, shield conductors etc.(As per NIT)
Luminairies:(As per NIT) Decorative, 1x12 W (min) and 2x12 W (min) LED light fittings
Tubular Galvanised steel poles, 9 m height along with 90 W (min) LED lamps with fittings complete (minimum 15 nos.)(As per NIT)
Lighting masts, 12-15 m height along with required nos. of 200 W (min) LED lamps with fittings complete (minimum 5 nos.)(As per NIT)
120 W (min) LED lamps (complete) fitted on the proposed building(As per NIT)
Accessories such as sub distribution board, junction boxes, individual control cables, PVC conduits/ casings, back up fuses, switches, sockets, ceiling roses, single core PVC cable with copper conductors, flexible wire etc.(As per NIT)
Emergency lighting system suitable for operation on 110 V DC supply in substation building(As per NIT)
Cable and accessories
HT Power cable, 6600 V grade, XLPE, FRLS, Armoured, Copper stranded conductors and 33000 V grade, XLPE, FRLS, SWA, Aluminium Stranded conductor(As per NIT)
LT Power cable, 1100V grade, PVCSWA, FRLS, 10 sq. mm.(minimum), 3/4 core copper stranded conductors (As per NIT)
Outdoor Lighting cable, 1100V, PVCSWA , 2 cores, 10 sq mm (minimum) stranded aluminium conductors (As per NIT)
Control cables, 1100V grade, PVCSWA, for 33kV and 6.6kV side copper conductors of with required number of cores and required sizes(As per NIT)
Wires for internal wiring, PVC insulated copper conductor cable of 1100V grade (As per the requirement) with complete wiring(As per NIT)
Cable trays, cable racks, binding materials, cable glands/lugs, cable jointing kit, bolts, nuts, washers, termination kit etc.(As per NIT)
Fire Fighting System
Fire Fighting equipment system consisting of Nitrogen Injection Fire Protection System (NIFPS) for Main Transformer (for 5.00 MVA, 33kV/6.6kV Main Transformers)(As per NIT)
Fire / Smoke detection alarming system for Substation buildings, etc.(As per NIT)
Fire Control equipment as per IS 3034:1993 Viz. Fire extinguishers, Sand Buckets with stand etc. as per the requirement.(As per NIT)
Diesel & Electrical pump for hydrant type fire fighting, associated electricals, hoses, nozzles, hydrant valves, etc. complete.(As per NIT)
Miscellaneous items
Room air conditioners, 2 t capacity including servo stabilizer(As per NIT)
Exhaust fans, 600 mm & 225 mm sweep(As per NIT)
Ceiling fan, 1200 mm sweep along with electronic regulator (Minimum 5nos.)(As per NIT)
Water purifier with hot & cold water dispenser(As per NIT)
Vacuum cleaner, domestic type(As per NIT)
DG set, 25 kVA,with Power Distribution Board, cable, With Change over switch, etc. complete(As per NIT)
Submersible pump with associated electricals & cables complete(As per NIT)
Miscellaneous Items (Like Rubber mat, hand gloves, earthing rod, paper chart, danger plate, notice board etc. shall be provided as per safety requirement.and other items which is required to complete the work but not mentioned here. Etc.) for the Substation(As per NIT)
Total impact of GST for the purpose of CTC
SRISHTI CONSTRUCTIONS (J.V)
Konstelec Engineers Limited
R.R. ENGINEERS AND SURVEYORS
Universal MEP Projects & Engineering Services Limited
SRISHTI CONSTRUCTIONS (J.V)
Konstelec Engineers Limited
R.R. ENGINEERS AND SURVEYORS
Universal MEP Projects & Engineering Services Limited
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .